Modulating refrigerant
valves with magnetic
actuator, PS45
Hermetically sealed, for safety refrigerants
MVL661..-..
Use
CE2N4714en
30.05.2011
• One valve type for expansion, hot-gas and suction throttle applications
• Hermetically sealed towards outside
• Selectable standard interface DC 0/2...10 V or DC 0/4...20 mA
• High resolution and control accuracy
• Precise positioning control and position feedback signal
• Short positioning time (< 1 s)
• Closed when deenergized
• Robust and maintenance-free
• Five valve sizes with k
The MVL661..-.. refrigerant valve is designed for modulating control of refrigerant
circuits including chillers and heat pumps. It can be used in expansion, hot-gas and
suction throttle applications as well as with all commonly used safety refrigerants (R22,
R134a, R404A, R407C, R410A, R507, etc.) and R744 (CO
inflammable refrigerants.
values from 0.25 to 12 m³/h
vs
). Not suitable for
2
Building Technologies
Type summary
Type reference DN kvs k
reduced
vs
1)
Δp
max
Q0 E Q0 H Q0 D
[m3/h] [m3/h] [MPa][kW] [kW] [kW]
MVL661.15-0.4 15
MVL661.15-1.0 15
MVL661.20-2.5 20
MVL661.25-6.3 25
MVL661.32-12 32
1)
63% of kvs, refer to "kvs reduction" on page 4
2)
MVL661.32-12.0 is only approved for suction throttle applications
Nominal flow rate of refrigerant through the fully open valve (H
k
vs
0.40 47 9.2 1.7
0.25 29 5.7 1.0
1.0 117 23 4.2
0.63 74 14 2.6
2.5 293 57 10
2.5
1.6 187 37 6.6
6.3 737 144 26
4
12
8
0.2
468 92 17
2)
2)
) at a differential pressure of
100
2)
50
2)
33
100 kPa (1 bar) to VDI 2173
Q
E Refrigeration capacity in expansion applications
0
Q
H Refrigeration capacity in hot-gas bypass applications
0
D Refrigeration capacity in suction throttle applications and Δp = 0.5 bar
Q
0
With R407C at t0 = 0 °C, tc = 40 °C
Q
0
The pressure drop across evaporator and condenser is assumed to be 0.3 bar each, and 1.6 bar
upstream of the evaporator (e.g. spider).
The capacities specified are based on superheating by 6 K and subcooling by 2 K.
The refrigeration capacity for various refrigerants and operating conditions can be
calculated for the 3 types of application using the tables at the end of this data sheet.
For accurate valve sizing, we recommend the valve selection program "Refrigeration
VASP".
Ordering
Example:
Spare parts
Rev. no.
Functio
n / mechanical design
Features and benefits
Valve body and magnetic actuator form one integral unit and cannot be separated.
Product number Stock number Designation
MVL661.15-0.4 MVL661.15-0.4 Refrigerant valve 1
Quantity
If the valve’s electronics become faulty, the entire electronics housing must be replaced
by spare part ASR61, supplied complete with mounting instructions (74 319 0270 0).
See table on page 17.
• 4 selectable standard signals for setpoint and measured value
• DIP switch to reduce the k
value to 63% of the nominal value
vs
• Potentiometer for adjustment of minimum stroke for suction throttle applications
• Automatic stroke calibration
• Forced control input for “Valve closed” or “Valve fully open”
• LED for indicating the operating state
The MVL661..-.. can be driven by Siemens or third-party controllers that deliver
a DC 0/2...10 V or DC 0/4...20 mA output signal.
For optimum control performance, we recommend a 4-wire connection between
controller and valve. When operating on DC voltage, a 4-wire connection is mandatory!
The valve stroke is proportional to the control signal.
2/18
Siemens Modulating refrigerant valves with magnetic actuator, PS45 CE2N4714en
Building Technologies 30.05.2011
Operator controls and
indicators in the
electronics housing
1
G0 G Y UMZC
1 Connection terminals
2 LED for indication of operating state
3 Minimal stroke setting potentiometer Rv
4 Autocalibration
2
3
on
1234
5 DIL switches for mode control
Configuration of
DIL switches
-reduction
k
vs
Minimum stroke
setting
Caution
45
4716Z15
Switch Function ON / OFF Description
ON
1
ON
2
ON
3
ON
1)
Factory setting
Positioning signal Y
Positioning range Y and U
Position feedback U
Nominal flow rate k
4
vs
ON Current [mA]
1)
OFF Voltage [V]
ON DC 2…10 V, 4…20 mA
OFF DC 0…10 V, 0…20 mA
ON Current [mA]
OFF Voltage [V]
ON
OFF
For k
63%
100%
reduction (DIL switch 4 in
vs
1)
1)
position ON), the stroke is limited to
63% mechanical stroke. 63% of full
stroke then corresponds to an
input/output signal of 10 V.
If, in addition, the stroke is limited
to 80%, for example, the minimum
stroke is 0.63 x 0.8 = 0.50 of full
stroke.
100 %
80 %
Stroke
In the case of a suction throttle valve, it is
4716D01en
essential that a minimum stroke limit be
maintained to ensure compressor cooling
and efficient oil return. This can be
achieved with a reinjection valve, a bypass
line across the valve, or a guaranteed
minimum opening of the valve. The
0 %
0 %100 %
Y-i np ut
minimum stroke can be defined via the
controller and control signal Y, or it can be
set directly with potentiometer Rv.
The factorysetting is zero (mechanical stop in counterclockwise direction, CCW). The
minimum stroke can be set by turning the potentiometer clockwise (CW) to a maximum
of 80% kvs.
Do not under any circumstances use potentiometer Rv to limit the stroke on
expansion applications. It must be possible to close the valve fully.
1)
3/18
Siemens Modulating refrigerant valves with magnetic actuator, PS45 CE2N4714en
Building Technologies 30.05.2011
Forced control input ZC
No function Fully open Closed
ZC – Function
Signal priority
Calibration
When is a calibration
required?
Indication of operating
state
Connections Transfer
• ZC not connected
• Valve will follow the Y-signal
• Minimum stroke set-ting
function
with potentiometer Rv
possible
G
• ZC connected to G
• Valve will fully open control
path A AB
• ZC connected to G0
• Valve will close control path
GG
A AB
1. Forced control signal ZC
2. Signal input Y and/or minimum stroke setting with potentiometer Rv possible.
The printed circuit board of the MVL661..-.. has a slot to facilitate calibration.
01124
To calibrate, insert a screwdriver in the slot so that the contacts inside are
connected. As a result, the valve will first be fully closed and then fully
opened.
Calibration matches the electronics to the valve mechanism.
During calibration, the green LED flashes for about 10 seconds; refer to
"Indication of operating state" (page 4).
MVL661..-.. refrigerant valves are supplied fully calibrated.
Execute a calibration after replacing the electronics, when the red LED is lit or flashing
or when the valve is leaking (at seat).
LED Indication Function Remarks, troubleshooting
Green Lit
Flashing
Red Lit
Flashing
Both Dark
Control mode Automatic operation; everything o.k.
Calibration in
progress
Calibration error
Internal error
Mains fault Check mains network (outside the frequency or
No power supply
Electronics faulty
Wait until calibration is finished
(green or red LED will be lit)
Recalibrate (operate button in opening 1x)
Replace electronics module
Siemens Modulating refrigerant valves with magnetic actuator, PS45 CE2N4714en
Building Technologies 30.05.2011
Connection type
1)
4-wire connection
3-wire connection
Sizing
Notes
Engineering notes
Always give preference to a 4-wire connection!
SNA P
Product number [VA] [W] [A] max. cable length L [m]
MVL661..-.. 22 12 1.6…4 A 65 110 160
MVL661..-.. 22 12 1.6…4 A 20 35 50
SNA = Nominal apparent power for selecting the transformer
P
med
IF = Required slow fuse
L = Max. cable length; with 4-wire connections, the max. permissible length of the separate 1.5 mm2
1)
All information at AC 24 V
2)
With 4 mm2 electrical wiring reduce wiring cross-section for connection inside valve to 2.5 mm2.
= Typical power consumption
copper positioning signal wire is 200 m
IF Wire cross-section [mm2]
MED
1.5 2.5 4.0 2)
For straightforward valve sizing, refer to the tables for the relevant application (from
page 13).
For accurate valve sizing, we recommend to make use of the valve sizing software
"Refrigeration VASP", available from your local Siemens office.
The refrigeration capacity Q
is calculated by multiplying the mass flow by the specific
0
enthalpy differential found in the h, log p-chart for the relevant refrigerant. To help
determine the refrigeration capacity more easily, a selection chart is provided for each
application (page 9 and following). With direct or indirect hot-gas bypass applications,
the enthalpy differential of Q
(the condenser capacity) must also be taken into account
c
when calculating the refrigeration capacity.
If the evaporating and / or condensing temperatures are between the values shown in
the tables, the refrigeration capacity can be determined with reasonable accuracy by
linear interpolation (refer to the application examples on page 9 and following).
At the operating conditions given in the tables, the permissible differential pressure
(25 bar) across the valve is within the admissible range for these valves.
Δp
max
If the evaporating temperature is raised by 1 K, the refrigeration capacity increases by
about 3%. If, by contrast, subcooling is increased by 1 K, the refrigeration capacity
increases by about 1 to 2% (this applies only to subcooling down to approximately
8 K).
Depending on the application, additional installation instructions may need to be
observed and appropriate safety devices (e.g. pressostats, full motor protection, etc.)
fitted.
Warning
To prevent damage to the seal inside the valve insert, the plant must be vented on the
low-pressure side following a pressure test (valve port AB), or the valve must be fully
open during the pressure test and during venting (power supply connected and
positioning signal at maximum or forced opening by G → ZC).
Expansion application
To prevent formation of flash gas on expansion applications, the velocity of the
refrigerant in the fluid pipe may not exceed 1 m/s. To assure this, the diameter of the
fluid pipe must be greater than the nominal size of the valve, using reducing pieces for
making the connections to the valve.
5/18
Siemens Modulating refrigerant valves with magnetic actuator, PS45 CE2N4714en
Building Technologies 30.05.2011
a) The differential pressure over reduction must be less than half the differential
pressure Δp
.
FL
b) The inlet path between diameter reduction and expansion valve inlet
Must straight for at least 600 mm
May not contain any valves
A filter / dryer must be mounted upstream of the expansion valve.
The valve is not explosion-proof.
It is not approved for use with ammonia (NH3, R717).
Mounting notes
The valve should be mounted and commissioned by qualified staff. The same applies
to the replacement electronics and the configuration of the controller (e.g. SAPHIR or
PolyCool).
•The refrigerant valves can be mounted in any orientation, but
90°
90°
upright mounting is preferable.
•Arrange the pipework in such a way that the valve is not
located at a low point in the plant where oil can collect.
•The pipes should be fitted in such a way that the alignment
does not distort the valve connections. Fix the valve body so
4716Z16
00441
that that it cannot vibrate. Vibration can lead to burst
connection pipes.
•Before soldering the pipes, ensure that the direction of flow
through the valve is correct.
•The pipes must be soldered with care. To avoid dirt and the
formation of scale (oxide), inert gas is recommended for
soldering.
•The flame should be large enough to ensure that the junction
heats up quickly and the valve does not get too hot.
• The flame should be directed away from the valve.
• During soldering, cool the valve with a wet cloth, for example,
to ensure that it does not become too hot.
•Port B must be sealed off when a 2-port valve (AB A) is
used.
•The valve body and the connected pipework should be
lagged.
•The actuator must not be lagged.
6/18
Siemens Modulating refrigerant valves with magnetic actuator, PS45 CE2N4714en
Building Technologies 30.05.2011
Loading...
+ 12 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.