![](/html/06/06a3/06a3ebaca9657a407f54f9d0647f688da721a41fc09c8c58e7681fc8715e954c/bg1.png)
Technical Specification Sheet
Dimensions in Inches (cm)
Split-Core Current Transformers
Small, Medium and Large Sizes
Description
Siemens Split-Core Current Transformers (CTs)
provide linear output voltage that is directly
proportional to the input current. These transformers
are safely and easily installed over existing electrical
power lines without disconnecting the lines or
interrupting service.
Siemens energy monitoring components are used for a
variety of applications including building automation,
tenant submetering, performance verification, energy
management, and new technology assessment. These
devices are targeted for use with the Siemens MD
Series Power Meters.
Features
• Available wit h three window sizes:
Small: 0.75” (1.9 cm)
Medium: 1.25" (3.2 cm)
Large: 2.0" (5.1 cm)
• Available in six current ranges:
Model Current Range
50A, Small 5 to 65A AC
100A, Small 2 to 130A AC
CT Size Part Number
Small
Medium
Large
Table 1. CT Dimensions.
SCT-SCS-0050-U
SCT-SCS-0100-U
SCT-SCM-0100-U
SCT-SCM-0200-U
SCT-SCM-0400-U
SCT-SCM-0600-U
SCT-SCL-0600-U
SCT-SCL-1000-U
Document No. 149-406
August 27, 2014
2.0
2.1
5.0
0.6
(1.6)
1.00
(2.5)
1.2
(3.1)
(5.1)
3.25
(8.3)
4.8
(12.1)
(5.4)
3.35
(8.5)
(12.7)
0.75
(1.9)
1.25
(3.2)
2.0
(5.1)
0.75
(1.9)
1.25
(3.2)
2.0
(5.1)
100A, Medium 5 to 130A AC
200A, Medium 4 to 260A AC
400A, Medium 8 to 520A AC
600A, Medium 12 to 780A AC
600A, Large 30 to 780A AC
1000A, Large 20 to 1300A AC
• Output: 333 mV at rated current
Siemens Industry, Inc.
Page 1 of 2
![](/html/06/06a3/06a3ebaca9657a407f54f9d0647f688da721a41fc09c8c58e7681fc8715e954c/bg2.png)
Your feedback is important to us. If you have
Specifications
Electrical Output Signal 333 mV at rated current
Wire Colors White = (+) Hi, positive
Black = (-) Low, neg ative
Frequency Range 50 Hz to 400 Hz
Phasing Orientation Arrow points towards load
Ratio Error <1% at rated current (typical)
Phase Error <2° at rated current (typical)
Mechanical Case Material Epoxy encapsulated housing
Leads 8 feet (2.7 m), twisted pair, 20 AWG
Operating temperature Maximum 105°F (220°C)
Weight SCS 4.8 oz (136 g)
SCM 12.0 oz (340 g)
SCL 26.0 oz (748 g)
Safety Working Voltage 600 Vac, Category III
Dielectric Strength 5000 Vac around case
600 Vac rated leads
Certifications ETL certified to UL Standard 61010-1
cETL certified to CAN/CSA Standard
C22.2 No. 61010-1
CE Conformity CE Low Voltage Directive 2006/95/EC
Ordering Information
Part Number Description
Small Split-Core CT; 0.75” (19 mm) Opening; 50A
Small Split-Core CT; 0.75” (19 mm) Opening; 100A
Medium Split-Core CT; 1.25” (32 mm) Opening; 100A
Medium Split-Core CT; 1.25 (32 mm) Opening; 200A
Medium Split-Core CT; 1.25" (32 mm) Opening; 400A
Medium Split-Core CT; 1.25” (32 mm) Opening; 600A
Large Split-Core CT; 2.00” (51 mm) Opening; 600A
Large Split-Core CT; 2.00” (51 mm) Opening; 1000A
1) Included in MD Model Power Meter Kits numbers MD-xxx-3-CTSC-400A.
2) Included in MD Model Power Meter Kits numbers MD-xxx-3-CTSC-600A.
Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as
design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners.
© 2014 Siemens Industry, Inc.
Building Technologies Division
1000 Deerfield Parkway
Buffalo Grove, IL 60089-4513
USA
+1-847-215-1000
comments about this document, please send them to
sbt_technical.editor.us.sbt@siemens.com
.
Printed in the USA
Page 2 of 2