Document inform ation is subject to change without notice by Siemens Industry, Inc.
Companies, names, and various data used in examples are fictitious unless otherwise
noted. No part of this document may be reproduced or transmitted in any form or by
any means, elect ronic or mechanical, for any purpose, wit hout the express written
permission of Siemens Industry, Inc.
Warning
This equipment generates, uses, and can radiat e radio frequency energy. If equipm ent
is not installed and used in accordance with the instructions manual, it may cause
interference t o radio communications. Equipment has been tested and found to comply
within the limits for a Class B digital device pursuant to Part 15 of the FCC rules. These
limits are designed to provide reasonable protection against such interf erence when
operated in a commercial environment. Operation of this equipment in a residential
area is likely to cause interference. Residential area equipm ent users are required t o
take whatever measures necessary to correct the interference at their own expense.
Service Statement
Control devices are c ombined to make a system. Each control device is mechanical in
nature and all mechanical components must be regularly serviced to optimize their
operation. Siemens Industry, Inc. branch offices and authorized distributors offer
Technical Support Programs that will ensure continuous, trouble-free system
performance.
For further information, contact your nearest Siemens Industry representative.
Copyright Siemens Industry, Inc.
FCC Regulations
The manual for an intentional or unintentional radiator shall caution the user that
changes or modificat ions not expressly approved by the party responsible could void
the user’s authority to operate the equipment.
For a Class B digital device or peripheral, the instructions furnished the user shall
include the following or similar statement, placed in a prom inent location in the text of
the manual:
NOTE: This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to part 15 of the FCC Rules. These limit s are designed to
provide reasonable protection against harmful interference in a residential installation.
This equipment generat es, uses and can radiate radio frequency ener gy and, if not installed and used in accordance with the instructions, may cause harmful interference to
radio communications. However, there is no guarantee that interference will not occur
in a particular inst allation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and on, the
user is encouraged t o try to correct the interference by one or more of the following
measures:
●
Reorient or relocate the receiving antenna.
●
Increase the separ ation between the equipment and receiver.
●
Connect the equipment into an outlet on a circuit different from that to which the
receiver is connect ed.
●
Consult the dealer or an experienced radio/TV technician for help.
2 | 180
Copyright Notice
180
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
To the Reader
Your feedback is important to us. If you have comments about this manual, please
submit them to: SBT_technical.editor.us.sbt@siemens.com
Credits
APOGEE is a registered trademark of Siemens Industry, Inc. Other product or
company names mentioned herein may be the trademarks of their respective owners.
Printed in the USA.
Siemens Industry, Inc.
3 |
Copyright Notice
4 | 180
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
180
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
Table of contents
Ho w to U se this M a nu a l ....................................................................................... 9
Ch a p t e r 1 - U s er In t e r f aces o n S iemens BT 3 00 .....................................................11
Power Ratin gs ........................................................................................................ 172
Interpre ting Serial Nu mbers and Date Cod es .......................................................... 172
Techni cal Data ....................................................................................................... 173
Contro l Board Tech ni ca l Speci fi cati o ns ................................................................... 175
Fieldbus Technical Data ......................................................................................... 176
Accesso ries and Repla ceme nt Parts ....................................................................... 177
7 |
How to Use this Manual
180
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
How to Use this Manual
About This Manual
This manual is written for the owner and user of the BT300 HVAC Variable Speed Drive. It is designed to help you
become familiar with the BT300 HVAC Variable Speed Drive and its applic ations.
This section covers manual organization, docum ent conventions and symbols used in the manual, how to access
help, related publications, and any other inform ation that will help you use this manual.
Document Conventions
The following table list s conventions to help you use this manual in a quick and efficient manner.
ConventionExam ples
Numbered Lists (1, 2, 3…) indicate a
procedure with sequential steps.
Conditions that must be c ompleted or met
before b eginning a task are design ated with a
⊳.
Intermediate results (what wi ll happen
following the execution of a step), are
designated with a ⇨.
Results, which inform the user that a task was
completed successfully, are designated with a
⇨.
Actions that should be performed are specified
in boldfac e fo nt.
Error and s ystem messages are dis played in
Courier New font.
New terms appearing for the first time are
italicized.
1. Turn OFF power to the field panel.
2. Turn ON power to the field panel.
3. Contact the local Siemens Industry representative.
⊳Composer software is properly installed.
⊳A Valid license is available.
2. Open an existing project or create a new one .
⇨The project wi ndow displays.
Type F for Field panels.
Click OK to save changes and close the dialog box.
The message Report Definition successfullyrenamed displays in the status bar.
The field panel continu ously executes a user-defined set
of instructions called the
This symbol signifies Notes. Notes provide additional
informat io n or helpful hi nts .
control program
.
Siemens Industry, Inc.
Cross references to other informa tion are
indicat ed with an arrow and the page number,
enclosed in brac kets: [→ 92]
Placeholders indicate text that can vary based
on your selectio n. Placeholders are specified
by italicized letters, and enclosed with brackets
[ ].
For more information on creating flowcharts, see
Flowcharts [→ 92].
Type A C D H [
username
] [
field panel #]
.
9 |
How to Use this Manual
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
Safety Symbols
The following table lists the safety symbols used in this manual to draw attention to important infor mation.
Table 1: Warning Symbols.
SymbolDescription
DANGER or WARNING: Dangerous voltage is present.
DANGER ou AVERTISSEMENT: Présence de tension dangereuse.
WARNING or CAUTION
AVERTISSEMENT ou ATTENTION
NOTE
REMARQUE
The following table describes the safety notices used in this manual to draw attention to important informat ion.
Table 2: Warning Descriptions.
Warni ng Ty peDesc ription
DANGER
WARNING
CAUTION
NOTICE
NOTENotes provide additional information o r helpful hints.
Serious injury, death, or severe equipme nt damag e is imminent if a p rocedur e or
instruction is not followed as specified.
Le non respect d'une procédure o u instruction peut provoquer ins tantanément des
blessur es graves, voir mortelles , ou endom mager l'é quipement
Serious injury, death, or severe equipme nt damag e could occur if a p rocedure or
instruction is not followed as specified.
Le non respect d'une procédure ou instruction peut prov oquer des blessures graves
voir mortelles ou e nd ommager l'équipe ment.
Minor or moderate injury m ay occur if a procedure or instruction is not followed as
specified.
Le non respect d'une procédure o u instruction peut provoquer des bless ures
mineures ou modérés.
Equipm ent damag e or unwan ted operation may occur if a procedur e or instruction is
not foll owed as s pecified.
Le non res pect d'u ne procédure ou instructi on peut end ommager l 'équipement ou
entraîner un fonc tionnement intempestif.
Les remarques fournissent des informations supplémentaires ou des conseils utiles.
Getting Help
For more information about BT300 products, contact your local Siemens Industry representative.
10 | 180
Chapter 1
-
User Interfaces on Siemens BT300
Drive Keypad
180
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
Chapter 1 - User Interfaces on Siemens BT300
This chapter presents the different user interf aces on Siemens BT300:
●Keypad
●Siemens NET
●Fieldbus
Drive Keypad
The control keypad with graphical interface is the interface between the Siemens BT300 HV AC Drive and the user.
With the control keypad it is possible to control the speed of a motor, to supervise the state of the equipment and
to set the variable frequency driver's parameters .
Keypad Buttons
The keypad features nine buttons used to configure and control the drive.
● This button (back/ reset) allows you to move backwards in the menu, backup a step when using a wizard,
exit the edit mode, or reset a fault (when held for approximately one sec ond).
● or These buttons allow you to scroll up (or down) in the menu or increase (or decrease) a param eter
value when editing.
Siemens Industry, Inc.
Figure 1: Keypad Buttons.
11 |
Chapter 1
-
User Interfaces on Siemens BT300
Drive Keypad
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
● or These buttons allow you to move the cursor left (or right) when editing a paramet er value.
● This button allows you to move to the next step when using a wizard, select an item in the menu, or
select a setting for a parameter when editing.
● This button allows you t o quickly access the Control Page and to easily c hange between the Hand
(Keypad) or Auto mode of operation. If an Electronic Bypass is present, this button provides access to the
drive-off bypass functions.
● This button allows you to start the drive in Keypad (Hand) mode of operation.
● This button allows you to stop the drive in Keypad (Hand) mode of operation. This button can also be
used as an emergency stop (unless limited by the Keypad St op Button [P3.2.3]).
Keypad Display
The keypad display indicates the status of the motor and the drive and any irregularities in m otor or drive functions.
On the display, you can view information about the present locat ion in the menu structure and the item displayed.
See
Chapter 4
for a comprehensive view of the menu structure.
Several pieces of inf ormation are available on the display at any given moment. Five status fields are provided
across the top of the display, as well as the location/parameter selected. Group information is also available.
These fields are:
●Status 1: Indicates the drive’s run status.
●Status 2: Indicates the drive’s run direction.
●Status 3: Indicates if the drive is READY to run,NOT READY to run, in FAULT, or in BYPASS (if Electronic
Bypass is enabled).
●Status 4: Indicates if the drive is in ALARM.
●Status 5: Indicates the current control place, such as I/O, FB, KEYPAD, PC, or OFF (if Electronic Bypass is
enabled).
●Location: Indicates the Menu name, Sub-menu name, or parameter name that is currently selected.
12 | 180
Figure 2: Keypad Display.
Chapter 1
-
User Interfaces on Siemens BT300
Drive Keypad
180
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
●ID: Indicates the parameter ID (if applicable) for the parameter select ed.
NOTE:
NOTES:
●Tree: Indicates the menu, sub-menu, or parameter tree structure number.
This field always shows standard English digits regardless of the language selected
by Language Selections (P6.1).
●Group: Indicates the group, sub-group, or parameter name that is in the list. The highlight represent s the
selected item.
●Count: Indicates the count of items listed in the group or sub-group.
The data on the control keypad are arranged in menus and sub-menus. Use the UP and DOWN arrows to
move between the menus. Enter the group/item by pressing the button and return to the previous level by
pressing the Back/Reset button.
Using the Keypad
This section covers the editing of parameter v alues, resetting of faults, accessing the control page, obtaining help
related to paramet ers, and configuring the items for the Favor ites menu.
Editing Values
1. Some parameters c annot be changed when the drive is in the Run stat e.
2. Some paramet ers require a power cycle to implement changes.
Change the value of a param eter by using the following procedure:
1. Locate the paramet er. See
2. Highlight the parameter and complete one of the following:
Press the button to enter the parameter choice menu, which contains Edit, Help, and Add To (or
Remove From ) Favorites. Highlight Edit and press the button a second time.
Press the button to enter directly into the parameter editing mode.
3. Set the new value using the or buttons.
Chapter 4
for parameter details.
NOTE:
You can move from digit-to-digit using the or buttons if the value is
Siemens Industry, Inc.
numerical.
13 |
Chapter 1
-
User Interfaces on Siemens BT300
Drive Keypad
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
4. Confirm the change with the button or ignor e the change by returning to the previous level with the
NOTE:
NOTE:
button.
5. To exit a parameter, press the button.
Resetting a Fault
When a fault has occurred, there are four ways to reset the fault:
Remove the external control signal before resetting the fault to prev ent unintentional
restart of the drive.
●If fieldbus communication is in use, command t he Reset Fault object.
●If a digital input is program med for Fault Reset Close (P3. 5.1.9) or Fault Reset Open (P3.5.1.10), toggle the
digital input.
The default setting for Fault Reset Close (P3.5.1.9) is Digital Input 6 (DigIN SlotA.6).
●Press and hold the butt on on the keypad for one second.
●Enter the Diagnostics (M4) menu, enter Reset Faults (P4.2) parameter, and select Reset F aults.
See
Chapter 6
for further informat ion on fault diagnostics.
Control Places
A
control place
is the source of control where the drive can be started and stopped. Every control plac e has its
own parameter for selecting the frequency reference source. In Hand, the control place is the keypad (by default).
The auto control place is determined by the setting in Auto Control Place (P1.15 or P3.2.1). The selected control
place is displayed on the keypad in the area marked Status 5 (see
Figure 2
).
Auto Control Place
I/O A, I/O B, and fieldbus can be used as auto control places.
●I/O A and fieldbus have the lowest priority and can be chosen with Auto Control Place (P3.2.1).
●I/O B can bypass the auto cont rol place selected using a digital input. The digital input is selected with I/O B
Control Force (P3.5.1.5).
●The keypad is always used as a control place while in Hand Control.
Selection of Hand from Auto
1. From any screen in the menu structure, press the button.
2. Use the or buttons to highlight Hand and press the button.
3. When Activate displays, press the button to confirm.
14 | 180
Chapter 1
-
User Interfaces on Siemens BT300
NET (Software Tool)
180
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
Selecting Auto from Hand
1. From any screen in the menu structure, press the button.
2. Use the or buttons to highlight Auto and press the button.
3. When Activate displays, press the button to confirm.
Accessing the Co ntrol Page
The Control Page enables easy operation and monitoring of the most essential values . It contains the setpoint (in
hertz) and four additional pieces of information (output frequency, energy counter, motor current, and motor power)
that you can charge.
1. From any screen in the menu structure, press the button.
2. Use the or buttons to highlight Control Page and press the button.
3. When Activate displays, press the button to confirm.
Help
The graphical keypad features instant help, and information displays for various items.
All parameters offer an instant help display. Select Help and press the button.
Text information is also available for faults, alarms and the Start-up Wizar d.
Addin g an Item to Favorites
At times, you may need to r efer to certain parameter values or other items. Inst ead of locating them one-by-one in
the menu structure, you can add them to a folder called Favorites, where they can easily be reached.
To remove an item from Favorites, see Favorites (M7) [➙ 163] in
Chapter 4
.
NET (Software Tool)
NET is a personal computer tool used for commissioning and maint aining the BT300 HVAC Drive. Contact your
local Siemens Representative to obtain a copy of the Siemens NET Tool.
The tool includes the following features:
●Parameterizat ion, monitoring, drive information, data logging, and so on.
●Integrated soft ware download tool--Siemens LoadT ool.
Portuguese, Romanian, Russian, Slovak, Spanis h, Swedish, and Turkish.
●Connection can be made using the USB/RS-422 cable (Part Number BT300-CABLE) or any standard
Category 5 Ethernet cable.
●USB/RS-422 drivers are automatically inst alled during the Siemens NET installat ion.
●When the connect ion is made, Siemens NET automatically finds the connected drive.
Siemens Industry, Inc.
15 |
Chapt
er 1-User Interfaces on Siemens BT300
Fieldbus
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
NOTE:
See the software’s Help menu for more information on using Siemens NET.
Fieldbus
The BT300 HVAC Drive has both RS-485 communication and Ethernet protocols built into the core product; there
are no special order requirem ents for obtaining t he desired protocols. The RS-485 protocols are: APOGEE-P1,
BACnet MS/TP, Johnson N2, and Modbus RTU. The Ethernet protocols are: BACnet IP and Modbus TCP.
The built-in RS-485 protocols are documented in section
documented in the
Ethernet
section in Chapter 4.
RS-485
in Chapter 4. The built-in Ethernet prot ocols are
16 | 180
Chapter 2
-
Control Board Terminal Connections
Fieldbus
180
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
Chapter 2 - Control Board Terminal Connections
The control board terminals are located on the control module. The control module is identical for all sizes of the
BT300 HVAC Drive. It c ontains the keypad, terminals, and the control processor of t he drive.
Connect the control wiring to the BT300 control terminals per the site-specific drawings.
Siemens Industry, Inc.
Figure 3: Slot A Terminal Connections.
Figure 4: Slot B Terminal Connections.
17 |
Chapter 2
-
Control Board Terminal Connections
Analog Input Terminal Connections
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
Figure 5: I/O-Related DIP Switches.
Analog Input Terminal Connections
The BT300 HVAC Drive cons ists of two analog inputs built on Slot A. When using analog input s, the DIP switches
must be correctly set and the analog inputs correctly configured before enabling them.
When using an analog input for speed reference, the signal is automatically sc aled f or Minimum Frequency (P3.3.1)
to Maximum Frequency (P3.3.2) in accordance with the signal range (for example, on a 0 to 10 Vdc signal, 0V
represents Minimum Frequency and 10V represents Maximum Frequency). This scaling can be modified. See the
analog input parameters listed in
Analo g Input 1
By default, Analog Input 1 is configured for a 0 to 10 Vdc signal source. The wiring is shown below. See Figure 5
for the location of the AI1 DIP switch. The DIP sw itch is set to the U (volt age) position at the factory. AI1 Signal
Range (P3.5.2.3) is used for programming the signal range of the analog input. Possible settings are 0 to 10 Vdc/0
to 20 mA or 2 to 10 Vdc/4 to 20 mA.
Chapter 3
.
Analo g Input 2
By default, Analog Input 2 is configured for a 4 to 20 mA signal source. The wiring is shown below. See Figure 5
for the location of the AI2 DIP switch. The DIP switch is set to the I (current) position at the factory. AI2 Signal
18 | 180
Figure 6: Analog Input 1 Terminal Connections.
Chapter 2
-
Control Board Terminal Connections
Digital Input T
erminal Connections
180
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
Range (P3. 5.2.9) is used for programming the signal range of the analog input . Possible settings are 0 to 10 Vdc/0
to 20 mA or 2 to 10 Vdc/4 to 20 mA.
Figure 7: Analog Input 2 Terminal Connections.
Digital Input Terminal Connections
The BT300 HVAC Drive consists of six digital inputs built on Slot A. When using digital input s, the DIP switch must
be correctly set and digit al inputs correctly configured before enabling them.
Digital Inputs 1 through 6
See Figure 5 for the location of the DIO DIP switch. The DIP switch is set to the GND (Grounded) position at the
factory.
Analog Output Terminal Connections
The BT300 HVAC consists of one analog output built on Slot A. When us ing the analog output, the DI P switch
must be correctly set and the analog output correct ly configured.
Analog Output 1
By default, Analog Output 1 is configured for a 4 to 20 mA signal. The wiring is shown below. See Figure 5 for the
location of the AO1 DIP switch. The DIP switch is set to the I (current) position at the factory.
Siemens Industry, Inc.
Figure 8: Digital Input Terminal Connections.
Figure 9: Analog Output 1 Terminal Connections.
19 |
Chapter 2
-
Control Board Terminal Connections
Digital Output Terminal Connections
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
Digital Output Terminal Connections
The BT300 HVAC Drive consists of three digit al (relay) outputs built on Slot B. See Figure 5 for the location of the
DIO DIP switch. When using the digital outputs, the DIP switch must be correctly set and digital outputs correctly
configured.
Figure 10: Digital Output Terminal Connections.
20 | 180
Chapter 3
-
Start-up Information
Procedure and Checklist
180
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
Chapter 3 - Start-up Information
Procedure and Checklist
To provide the most reliable drive available, and to avoid any extra costs related to loss or reduction of warranty
coverage, a factory-certified specialist should complete the startup procedures covered in the
and Checklist
(125-1006).
Commissioning Flowchart
Table 3: Commissioning Flowchart.
There are several pre-chec ks that s hould be complet ed prior to powering up and commissioning th e
BT300 HVAC Drive. See
This step should be completed on all drives at start-up to ensure a good, known starting point. Select:
User Settings (M6) > Parameter Backup (M6.5) > Restore Factory Defaults (P6.5.1).
This step should be completed on all drives at start-up. This will be automatically s tarted at the end of
the Factory Reset. Select: Quick Setup > Star tu p Wizard (P1.19), if necessary.
the BT300 Startup Procedure and Checklist
Startup Procedure
(125-1006) for more details.
If any other wizards are needed, select one of the following:
Quick Setup > PID M in i-Wizard (M1.17) > Quick Setup/Mul t i-Pump Wizard (M1.20)
Quick Setup > St artup Wiza rd (M1.19) > Quick Setup/Fire Mode Wizard (M1.20)
Quick Setup > Bypass Wizard (M1.21)
Any other application-specific settings should be completed at this time.
Even if enabled during the Startup Wizard, the Auto-R eset sh ould be c onfigure d for the site’s
requirements. There are several parameters to configure in this menu. Review all paramet ers.
Select: Pa ramet ers (M3) > Automatic Reset (M3.10)
This forces the Mo nitor, Favorites, and User Level menus only. This prevents un authorized
parameterization through the keypad.
Select: User Levels (M8) > Acce ss Code (P8.2) . Set to desired access code ( such as 4521).
User Levels (M8)/User Level (P8.1). Set to Monitoring.
To return to edit menus, select: User Lev els (M8) > Us er Level (P8.1), and set to Normal. Enter the
Acces s code whe n prompted.
Siemens Industry, Inc.
21 |
Chapter 3
-
Start-up Information
Wizards
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
Wizards
Wizards are available in t he Quick Set up (M1) menu. The wizards assist you with various start-up and
commissioning functions. There are five wizards available in the BT300 HVAC Drive that prompt for essential
information needed for the following:
●Start-up Wizard - Easy commissioning of the drive.
●PID Mini-Wizar d - Proper configuration of internal PID Loop Controller 1.
●Multi-Pump Wizard - Proper configuration of the Multi-pump application.
●Fire-Mode Wizar d - Proper configuration of the Fire-mode.
●Bypass Wizard - Proper configuration of the bypass options (if connected).
Startup Wi za rd (P1.19)
The Startup Wizard prompts you for the essent ial information needed by the driv e so that it can start controlling the
output as desired. Once power is connected to the BT300 HVAC Drive, the Startup Wizard should run
automatically. If it is not running, it can be activated in the Quick Set up (M1) menu or by completing Restore
Factory Def aults (P6.5.1)
The following steps are required to successf ully complete the Startup Wizard:
StepParameter/Q uestionSettings
1Language Selections (P6.1)
2Daylight Saving (P5.5.5)
3Time (P5.5.2)
4Year (P5.5.4)
5Date (P5.5.3)
6Startup Wizard?Specify if the Startup Wizard should be activated: Yes , No
Select the icon for the languag e you want applied to the keypad. This
varies depending upon th e language packag e install ed.
Select the Daylight Sav ing Rul e
1 = Off
2 = EU
3 = US
4 = Russia
Specify the curre nt time of day in the following format: hh:mm:ss where
h = hour, m = minute, s = seconds.
Specify the current year in the following format: yyyy where
yyyy = 4-digit year.
Specify the current date in the following format: dd.mm where
dd = 2-digit day, mm = 2-di gi t month.
If the option Yes is selected for Startup Wizard (recommended), you will be prompted for the following values:
StepParameter/Q uestionSettings
7
8Motor Nom Voltg (P3.1.1.1)Defines nominal motor vol tage from motor na meplate d ata.
9Motor Nom Freq (P3.1.1.2)Defines nominal motor fr equency from motor nameplate data.
22 | 180
Fan o r Pump
(Applica tion Type)
Pump
Automatically sets the followi ng:
Acce l Time 1 (P1.13) = 30
Decel Time 1 (P1.14) = 30
Start Function (P3.2.4) = Ramping
Stop Function (P3.2.5) = Ramping
Fan
Automatically sets the followi ng:
Acce l Time 1 (P1.13) = 120
Decel Time 1 (P1.14) = 12 0
Start Function (P3.2.4) = Flying Start
Stop Function (P3.2.5) = Coast to Stop
Chapter 3
-
Start-up Information
Wizards
80
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
StepParameter/QuestionSettings
10Motor Nom Speed (P3.1.1.3)Defines nominal motor spe ed f rom mot or namepl ate data.
11Motor Nom Currnt (P3.1.1.4)Defines nominal motor current from motor nameplat e data.
12
13Motor Nom Power (P3.1.1.6)Defines nominal motor power from motor nameplate data.
14Min Frequency (P3.3.1)Minimum allowed frequency ref erence.
15Max Frequ e nc y (P3.3.2)Maximum allowed frequency reference.
16I/O Ctrl Ref (P3.3.3)
17Accel Time (P3.4.2)
18Decel Time (P3.4.3)
19Ctrl Place Auto (P3.2.1)
20Automatic Reset (P3.10.1)Determines if the Automatic Reset feature can be used.
21Start Function (P3.2.4)
22Stop Function (P3.2.5)
23Motor Switch (P3.1.2.2)
24Bypass Wizard (P1.21)
Motor Cos Phi (P3.1.1.5)
(Power Factor)
Defines nominal motor Cos Phi (power factor ) from m otor nameplate
data.
Selects location of frequency setpoint source when in I/O A control. In
the following list of possible settings, the main setpoint is selected:
1= Preset Freq 0
2 = Keypad Reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID 1 Reference
8 = Motor Potentiometer
Defines the time required to increase output frequency from 0 to Max
Frequency (P3.3.1).
Defines the time required to decrease output frequency from Max
Frequency (P3.3.1) to 0 frequency.
Start/Stop commands are given differ ently dependin g upon the control
place. This parameter defines whether the Start/Stop command is
controlled by digital inputs as defined in Control Signal 1 A (P3.5.1.1)
and Control Signal 2 A (P3.5.1.2) in accordance with the I/O A
Start/Stop Logic (P3.2.6) or if the Start/Stop com mand is controlled by
the Fieldbus that is in use.
Settings:
0 = I/O Control (control is from the physical I/O, PID control, or time
channels)
1 = Fieldbus (control is from the configured fieldbus found in Ethernet
or RS-485 settings).
Defines the start function of the drive.
0 = Ramping Start
1 = Flying Start
Defines the stop function of the drive.
0 = Coast to Stop
1 = Ramping Stop
Prevents the driv e from trip ping when a motor swit ch is located
between the drive and motor.
0 = No
1 = Yes
Enable parameter for the Bypass Wizard. This wizard can be act ivated
during the Startup W izard.
The Startup Wizar d is now complete.
Siemens Industry, Inc.
23 | 1
Chapter 3
-
Start-up Information
Wizards
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
PID Mini-Wizard (P1.17)
The PID Mini-Wizard is activated in the Quick Setup (M1) menu. This wizard will assist with configuring the drive
for use with the PID Controller 1 in a “one-feedback/one-setpoint” mode. The control place will be I/O A and the
default process unit is %.
The following steps ar e required to successfully c omplete the PID Mini-Wizard:
StepParameter/QuestionSettings
1
If a process unit other t han % is selected, the following questions display. Otherwise, the wiz ard jumps directly to
Step 5:
StepParameter/QuestionSettings
2
3
4
5
If one of the analog input signals is selected, Step 6 displays. Otherwise, the wizard jumps directly to Step 7.
StepParameter/QuestionSettings
6
7
8
Process unit selection (P3.12.1.4)Several selections, see P3.12.1.4.
Process Unit Min (P3.12.1.5)Varies
Process Unit Max (P3.12.1.6)Varies
Process Unit Decimals (P3.12.1.7)Range: 0 to 4
Feedba ck 1 Source Selection (P3.12.3.3)Several selections, see P3.12.3.3.
Analog Input Signal Ran ge
Error Inversion (P3.12.1.8)
Setpoint Source Selection (P3.12.2.4)Several selections, see P3.12.3.4.
0 to 10V/0 to 20 mA
2 to 10V/4 to 20 mA
Reverse Acting
Direct Actin g
If one of the analog input signals is selected, Step 9 displays. If the either of the options Keypad SP1 or Keypad
SP2 is selected, then Step 10 displays. Otherwise, the wizard jumps directly to Step 11.
StepParameter/QuestionSettings
9
10
11
Analog Input Signal Ran ge
Keyp ad SP 1 (P3.12.2.1) or Keypad SP2
(P3.12.2.2)
Sleep Function?
0 to 10V/0 to 20 mA
2 to 10V/4 to 20 mA
Varies
No
Yes
If the option Yes is selected for Sleep Function, you will be prompt ed for the sleep function settings:
StepParameter/QuestionSettings
12
13
14
Sleep Frequency Lim it 1 (P3.13.2.7)Varies
Sleep Delay 1 (P3.12.2.8)Varies
Wake-up Level 1 (P3.12.2.9)Varies
The PID Mini-Wizard is now com plete.
24 | 180
Chapter 3
-
Start-up Information
Wizards
180
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
Multi-Pump Wiza rd (P1. 18 )
NOTE:
The Multi-Pump Wizard is activated in the Quick Setup (M1) menu. This wizard assists with configuring the drive for
use with PID Controller 1, and then asks the most important questions for setting up a multi-pump system.
The following steps are required to successf ully complete the Multi-Pump Wizard:
StepParameter/QuestionSettings
1 – 14
15
16
17
If the Auto-change function is enabled, the following will display. Otherwis e, the wizard jumps directly to St ep 21:
StepParameter/QuestionSettings
18
19
20
21
22
Same as PID Mini-Wizard
Numb er of Motors (P3.14.1)1 to 4
Interlock Function (P3.14.2)
Auto-change (P3.14.4)
Include FC (P3.14.3)
Auto-c hange Inter v a l (P3.14.5)0.0 to 3000.0 h
Auto-change Fr equency Limit (P3.14.6)0.0 to 60.0 Hz
Bandwidth (P3.14.8)0 to 100%
Bandwidth Delay (P3.14.9)0 to 3600 s
Not Used
Enabled
Disabled
Enabled
Disabled
Enabled
After this, the keypad displays the digital input and relay output configuration done by the application. It is
recommended that these values are written down for fut ure reference.
The Multi-Pump Wizard is now complete.
Fire Mode Wizard (P1.20)
The Fire Mode feature of the drive is designed t o place the drive in a mode that ignores all commands from the
keypad, fieldbuses, and the personal com puter tool. In addition, the driv e will ignore all alarms and faults of the
drive and continue providing frequency to the attached motor. This is designed for instances when the destruction of
equipment is better than loss of life. The Fire Mode feature can be operated so that the PID loop is still in control of
the attached motor. The Fire Mode Wizard allows for easy commissioning of the Fire Mode function.
The Fire Mode Wizard is activated in the Quick Setup (M1) menu. The wizard assists with configuring the drive for
use with the Fire Mode feature.
The warranty is void if t he Fire Mode function is activ ated. Test Mode can be used to
test the Fire Mode function without voiding the warranty. Read important information
about the password and warranty issues in Chapter 4 before you proc eed.
Test Mode can be used to test the Fire Mode function without voiding the warranty.
The Fire Mode Wizard can be initiated by choos ing Activate for Fire Mode Wizard (P 1.20) in the Quick Setup (M1)
Menu.
The following steps are required to successf ully complete the Fire-Mode Wizard:
Siemens Industry, Inc.
25 |
Chapter 3
-
Start-up Information
Wizards
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
StepParameter/QuestionSettings
1
Fire Mo de F requency Sourc e (P3.16.5)Several selections; see P3.16.5.
If Fire Mode Frequency is selected, the following will display. Otherwise, the wizard jumps directly to Step 3:
StepParameter/QuestionSettings
2
3
4
5
6
Fire Mo de Fr e q ue nc y (P3.16.4)Range: 0 to Maximum Frequency (P1.9)
Signal Activation?
Fire Mo de A ctivation Open (P3.16.2)
Or
Fire Mo de A ctivation Clos e (P3.16.3)
Fire Mo de R ev erse (P3.16.6)
Fire Mo de Passwor d (P3.16.1)
Open Contact
Closed Contact
Choose the digital input to activate Fire Mode.
Choose the digital input to activate the reverse command in
Fire Mode.
DigIN Slot0.1 = FORWARD
DigIN Slot0.2 = REVERSE
Choose the password to enable the Fire Mode Function.:
1234 = Tes t M od e
1002 = En ab le Fire Mode
The Fire Mode Wizar d is now complete.
Bypass Wizard (P1.21)
The Bypass Wizard is activated in the Quick Setup (M1) menu. The wizard assists with configuring the drive for use
with the Conventional or Electronic Bypass options. If the Electronic Bypass option is selected, additional f eatures
can be enabled, if desired. The standard I/O is re-mapped for use with the Electronic Bypass option. Additional
parameters are available when the Electronic Bypass option is enabled.
The following steps are required to successf ully complete the Bypass Wizard:
StepParameter/QuestionSettings
1
Select the Bypass (P3.17.4) mode
Electronic
Conventional
Disabled
If Conventional is selected, the following changes occur automatically, the wizard completes, and the message:
Bypass Wizard is now complete. Press OK to continue. displays.
●Control Signal 2 A (P3.5.1.2) is set to DigIN Slot0.1 to disable the reverse command on Digital Input 2.
●Run Interlock 2 (P3.5.1.13) is set to DigIN SlotA.2 to enable the run int erlock on Digital Input 2. The status of
the Output Contactor (M2) is factory-wired to digit al input 2.
●Preset Freq Sel0 (P3.5.1.15) is set to DigIN Slot0.1 to disable the Preset Frequency Selection 0 on Digit al Input
4.
●Overload (P3.5.1.53) is set to DigIN SlotA.5 to enable the overload on Digital Input 5. The stat us of the
Overload is factory -wired to Digital Input 5.
If Electronic is selected, the following change occ urs automatically:
Overload (P3.5.1.53) is set to DigIN SlotA.5 to enable the overload on Digital Input 5. The status of the Overload is
factory-wir ed to Digital Input 5.
The wizard continues with the following steps:
26 | 180
Chapter 3
-
Start-up Information
Wizards
180
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
StepParameter/QuestionSettings
2
Bypass Delay (P3.18.1) Time
3
Essential Services* (P3.18.5)
Defines the amount of time between the un it being
placed into Bypass mode and the M1 contact or closin g.
Range: 1 to 30 s
Enabled
Disabled
If Enabled is selected for Essential Services, Step 4 displays. Other wise, the wizard jumps directly to Step 5.
If Enabled is selected for Remote Bypass, Step 6 displays. Otherwise, the wizard jumps directly to Step 7.
StepParameter/QuestionSettings
6
Command Source (P3.5.1.1)
7
Interlock* (P3.2.11)
Fieldbus CTRL
I/O Control
Enabled
Disabled
If Enabled is selected for Interlock, Step 8 displays. Otherwise, the wizard jumps directly to Step 9.
StepParameter/QuestionSettings
8
Interlock Delay (P3.2.12)Range: 0 to 120 s
9
Auto Bypass* (P3.18.2)
Enabled
Disabled
If Enabled is selected for Auto By pass, Step 10 displays. Otherwise, the wizard jumps directly to Step 11.
StepParameter/QuestionSettings
10
Auto Bypass Delay (P3.18.4)Range: 0 to 30 s
11
Fault Se lec tion (P3.18.3)
* Feature of the Electronic Bypass Option. For more details, see
Select faults to enable auto Bypass:
Any Fault
Undervoltage
Overvoltage
Overcurrent
AI Low
Unit Temperature
Motor Overtemp
External Fault
Underload Fault
BT300 Bypass Operator’s Manual
(DPD01391)
The Bypass Wizar d is now complete. The following message displays: Bypass Wizard is now complete.
Press OK to continue.
If Disabled is selected, no changes occur and the wizard completes T he following message displays: Bypass
Wizard is now complete. Press OK to continue.
For more information on the bypass options, see the
Instruct ions
(DPD01375) and the
BT300 Variable Frequency Drive Bypass Operator’s Manual
BT300 Variable Frequency Dr ive Bypass Installation
(DPD01391).
Siemens Industry, Inc.
27 |
Chapter 4
-
Parameters and Menu S tructure
Wizards
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
Chapter 4 - Parameters and Menu Structure
All information and param eters are organized in a menu struc ture:
Quick Setup (M1)
All basic pa ra me ter s
required to quickly setup
the BT300 VFD for
operation and all av ailable
wizards.
Monitor (M2)
Acces s to the Multimonitor display an d
parameters used f or
monitoring.
Parameters (M3)
Parameters used for
basic and advanced
configu ration
requirements.
P1.17 PID Mi ni-Wizard
P1.18 Mult i-Pump Wiz ar dM4.2 Reset Faults
P1.19 Star tu p WizardM4.3 Fault History
P1.20 Fir e Mode Wiz ardM4.4 Total Counters
P1.21 By pass WizardM4.5 Trip Counters
M2.1 Mult im o nit orM4.6 Sof tware Info
M2.2 Basic
M2.3 Timer FunctionsM5.2 Sl ot C
M2.4 PID Controll er 1M5.3 Slot D
M2.5 PID Controll er 2M5.4 Slot E
M2.6 Mult i-PumpM5.5 Real T ime Clock
M2.8 Fieldbus DataM5.6 Power Unit Settings
M2.9 Tem p. I nputsM5.7 Keyp ad
M3.1 Motor SettingsM5.8 RS-485
M3.2 Start/Stop SetupM5.8.1 Common Settings
M3.3 ReferencesM5.8.3 BAC net MSTP
M3.4 Ra mps and BrakesM5.8.3 Modbus RTU
M3.5 I/O C onfigM5.8.3 N2
M3.5.1 Digital InputsM5.8.3 P1
M3.5.2 Analog InputsM5.9 Ethernet
M3.5.3 Digital OutputsM5.9.1 Common Settings
M3.5.4 Analog OutputsM5.9.2 Modbus TCP
M3.6 Fieldbus DataMapM5.9. 3 BACnet IP
M3.7 Pro hibit Freq
M3.8 Limit SupervM6.5 Parameter B ackup
M3.9 Protec tionsM6 .6 Parameter Co mpare
M3.10 Automatic ResetM6.7 Drive Name
M3.11 Timer Function
M3.12 PID Control ler 1
M3.13 PID Control ler 2
M3.14 Multi-Pump
M3.16 Fire ModeP8.2 Access Code
M3.17 Appl. Setttings
M3.18 Bypass
21
Diagnostics (M4)
Diagnostics information such
as active faults, fault history
and counters.
I/O and Hardware (M5)
Parameters for status of I/O,
real time clock, keypad, and
fieldbus configuration.
User Settings (M6)
User information such as
keypad language selection,
paramet er backup/restor e, an d
drive nam e.
Favorites (M7)
List of user-defined para m eter
list.
User Levels (M8)
Restricts the visibility of
parameters
Displayed based on value of Protocol (P5.8.1.1)
2
Displayed based on value of Bypass (P3.17.4)
M4.1 Active Fa ults
M5.1 Basic IO
1
1
1
1
M6.1 Language S election
P8.1 User Level
28 | 180
Chapter 4
-
Parameters an
d Menu Structure
Quick Setup (M1)
180
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
Quick Setup (M1)
The Quick Setup param eter group is a collection of parameters that are the most commonly us ed during installation
and commissioning. They are collected in the first parameter group so that they can be found quickly and easily.
However, they can be also be reached and edited in the actual parameter gr oups. Changing a parameter value in
the Quick Setup group als o changes the value of this parameter in its actual group.
The Quick Setup param eters are presented in the following table:
Table 4: Quick Setup Parameters.
StructureParameterUnitIDDescription
P1.1Motor Nom VoltgV110
P1.2Motor Nom FreqHz111
P1.3Motor Nom Speedrpm112
P1.4Motor Nom CurrntA113
P1.5Motor Cos Phi120
P1.6Motor Nom Powerhp116
P1.7Current LimitA107
P1.8Min FrequencyHz101
P1.9Max Frequ enc yHz102
P1.10I/O A Ctrl Ref117
P1.11Preset Fr eq 1Hz105
P1.12Preset Fr eq 2Hz106
P1.13Accel Tim e 1s103
P1.14D ecel Time 1s104
Defines nominal motor vol tage from motor na meplate d ata.
Also see
Defines nominal motor fr equency from motor nameplate data.
Also see
Defines nominal motor spe ed f rom mot or namepl ate data.
Also see
Defines nominal motor current fr om motor nameplate data.
Also see
Defines nominal motor Cos Phi (power factor) from m otor nameplate data.
Also see
Defines nominal motor power from motor nameplate data.
Also see
Defines maximum current limit for mot or. Sugges ted to use Motor Nominal
Current (P1.4) multipli ed by motor service factor from motor nameplate data.
Also see
Sets minimum moto r frequenc y at which motor wil l run irrespective of
frequency setpoint.
Also see
Sets maximum motor frequency at which motor will run irrespective of
frequency setpoint.
Also see
Selects location of frequency setpoint source when in I/O A control. In the
following list of possible settings, the main setpoint is selected:
1= Preset Freq 0
2 = Keypad Reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID 1 Reference
8 = Motor Potentiometer
Also see
Used according to state of digital i nput defined for Preset Frequency
Selection 1 (P3.5.1.16). Decodin g mode chosen with Preset Frequency M ode
(P3.3.10). Also see
Used acc ording to state of digi tal inputs Preset Frequency Selection 2
(P3.5.1.17). Decoding mode chosen with Preset Frequency Mode (P3.3.10).
Also see
Time allowed for motor to acc elerate fro m a standstill (0) up to Maximum
Frequency (P1.9).
This parameter can also be found in Menu Str ucture P3.4.2
Time allowed for motor to decelerate from Maximum Frequency (P1.9) to a
standstill (0). Also see
Menu Structure P3.1.1.1
Menu Structure P3.1.1.2.
Menu Structure P3.1.1.3
Menu Structure P3.1.1.4
Menu Structure P3.1.1.5
Menu Structure P3.1.1.6.
Menu Structure P3.1.1.7.
Menu Structure P3.3.1.
Menu Structure P3.3.2.
Menu Structure P3.3.3.
Menu Struc ture P3.3.12
Menu Structure P3.3.13
Menu Structure P3.4.3
.
.
.
.
.
.
.
Siemens Industry, Inc.
29 |
Chapter 4
-
Parameters and Menu S tructure
Monitor Menu (M2)
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2017-09-28
StructureParameterUnitIDDescription
P1.15Ct rl. Place A uto172
P1.16Automatic Reset731
P1.17PI D Mi ni-Wizar d1803
P1.18MultiPump Wizard
P1.19Startup Wizard1171
P1.20Fir e Mode Wizard1672Enable parameter for the F ire Mode Wizard.
P1.21Bypass Wizard1823
Start/Stop commands are given differently depending upon the control place.
This parameter defines w hether the Start/Stop command is controlled by
digital inputs as defined i n Control Signal 1 A (P3.5.1.1) and Con trol Sig nal 2
A (P3.5.1.2) in accordance with the I/O A Start/Stop Logic (P3.2.6) or if the
Start/Stop command is controlled by the Fieldbus that is in use.
Settings:
0 = I/O Control (control is from the physical I/O, PID control, or time channels)
1 = Fieldbus (control is from the configured fieldbus found in Ethernet or RS485 settings)
Also see
Enable parameter for the A utomatic Reset function of the drive. This feature
is config ured in the Parameters (M3) … Automatic Reset (M3.10) menu.
Also see
Enable parameter for the PID Mini-Wizard. This wizard as sists w ith the
configu ration of the PID Controller 1 using a single feedback and single
setpoint.
Enable parameter for the Multi-Pu mp Wizard . This wizard assis ts with the
configuration of the Multi-Pump function of the drive. The PID Mini Wiz ard will
precede this wizard.
Enable parameter for the Startup Wizard. This wizard assist with the essential
information required for drive operation.
This wizard is automatically e nabled after Restore Factory Defaults (P6.5.1) is
activated.
Enable parameter for the Bypas s Wizard. This wizard c an be act ivated during
the Startup Wizard.
Menu Structure P3.2.1
Menu Structure P3.10.1
.
.
Monitor Menu (M2)
The Siemens BT300 HVAC Drive allows you to monitor actual values, parameters, and signals as well as status
and measurements. Some of the monitored values are customizable.
Table 5: Monitor Menu.
Menu and Parameter GroupDescription
Multimonitor (M2.1)Display of 9 monitored values.
Basic (M2.2)Display of basic drive mo nitorin g parameters.
Timer Functions (M2.3)Display of timer function specific monitoring par ameters.
PID Controller 1 (M2.4)Display of PID Controller 1 specific monitoring parameters.
PID Controller 2 (M2.5)Display of PID Controller 2 specific monitoring parameters.
Multi-Pump (M2.6)Display of Multi-Pump specific monitoring parameters.
Fieldbus Data (M2.8)Display of Mappe d Fieldbus Data monitorin g parameters.
Temp. Inputs (M2.9)Display of connected temperature inputs.
Multimo nitor (M2.1)
On the Multi-Monitor page, you can collect nine values to monitor. The display fields can be changed by selecting
the display field to be changed with the and arrow buttons, and then pressing the button. Scroll
30 | 180
Loading...
+ 150 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.