Technical Instruction
Document No. CM1N4845E-P2
Rev. 4, February, 200
VVP45… and VXP45… Series
Two-port and Three-port Seat Valves
ANSI Class 250 Short-stroke Valves
Two-port Seat Valve
VVP45…
Description
Features
Two-port seat valves of the VVP45… range with two-port connection
Three-port seat valves of the VXP45… range with three-port connection
•
Nominal pressure, ANSI Class 250
•
Bronze valve bod y
•
1/2-inch, 3/4-inch and 1-inch diameters
Three-port Seat Valve
VXP45…
Application
Product Numbers
•
Externally threaded connections G 1/2-inch, G 3/4-inch and G 1-inch
•
Nominal stroke 5.5 mm
•
Manual adjusting knob
•
Can be fitted with SSB… or SSC… electric actuators
•
In ventilating and air conditioning applications to control, for water side, terminal
units in closed circuits, such as induction and fan coil units, small unit heaters and
small water-cooled units. For use in:
−
Two-pipe systems with one heat exchanger for heating and cooling
−
Four-pipe systems with two separate heat exchangers for heating and cooling
•
In heating applications to control heating zones in closed circuits, such as:
−
Self-contained heating systems
−
Apartments
−
Individual rooms
See Table 1.
Siemens Building Technologies, Inc.

Technical Instructions VVP45… and VXP45... Series Two-port and Three-port Seat Valves
Document Number CM1N4845E-P25 ANSI Class 250
Rev. 4, February, 2002
Fluids
Hot water: to maximum 230°F (110°C), short-term to maximum 248°F (120°C)
Chilled water: over 36°F (2°C)
Water-glycol solutions
Operating Pressure
Maximum 1600 kPa (16 bar) and ANSI Class 250
Table 1. Product Numbers.
Connectio
ISO Thread
GPM
Straight
through
VVP45…
(2-port)
∆
(ps
p
s
GPM
Bypass
Line Size
mm
(inch)
10 (.394) G 1/2-inch
1.1
1.8
2.8
4.4
7.0
15 (.5906) G 3/4-inch
20 (.7874
G 1-inch 17.6
∆
p = >29 psi increases risk of noise and seat-plug erosion
∆
p
s
∆
p
max
11.0
= Close-off pressure
= Maximum permissible differential pressure across closed valve with actuator
VVP45.10-0.25
VVP45.10-0.4
VVP45.10-0.63
VVP45.10-1
VVP45.10-1.6
VVP45.15-2.5
VVP45.20-4
87
0.79
1.23
1.90
3.08
4.93
58
58
7.71
12.33
Cv = Nominal flow at pressure drop of 1 psi
Ordering
When ordering, give quantity, product number and name of valve.
VXP45…
(3-port)
VXP45.10-0.25
VXP45.10-0.4
VXP45.10-0.63
VXP45.10-1
VXP45.10-1.6
VXP45.15-2.5
VXP45.20-4
p
∆
max
psi
Actuator
Positioning
Force
45lbf 67 lb
SSB SSC
29
Equipment
Combinations
Page 2
Siemens Building Technologies, Inc.
Example:
1 VXP45.10-1 three-port valve
Valves, actuators and screwed fittings are packed separately.
Valves V…45.10-0.25 to V…45.25-6.3 are operated with SSB actuators (see data shee
CA1N4891.1E-P25 and CA1N4891.2E-P25) or SSC actuators. Valves V…P45.25-10,
V…45.32-16 and V…P45.40-25 are only operated with SSC actuators.
Actuator
SSB61...
SSB81...
SSC61...
SSC81...
Operating
Voltage
24 Vac 0 to 10 Vdc
3-Point 150
0 to 10 Vdc
3-Point 150
Control Run Time
(Seconds
75 45 lbf 27.7
30 67 lbf 110
Positioning
Force
GPM