Siemens sqm50 Installation Instructions Manual

Installation Instructions
Document No. 129-399
January 18, 2008
SQM5… Reversing Actuator with Line Voltage Input Signal
Product Description
Product Numbers
SQM5x.xxxRxAx for line voltage input signals Actuator Torque: SQM50.2… 90 in/lb SQM50.3… 90 in/lb SQM50.4… 140 in/lb SQM53.4… 200 in/lb SQM56.5… 310 in/lb SQM56.6… 400 in/lb SQM… motors allow torque on either end of the
AGA58.3 and AGA58.4 shafts. NOTE: For detailed information, see Technical
Instructions 155-517P25.
Max Shaft Torque: AGA58.1 200 in/lb AGA58.3 220 in/lb AGA58.4 270 in/lb AGA58.7 400 in/lb
Caution Notation
CAUTION:
Equipment damage may occur if procedures are not followed as specified.
Installation
Cover Removal
Use a Phillips screwdriver to loosen the two screws on the actuator cover corners. See Figure 1.
EA0564R1
Figure 1. Figure 2.
EA0568R1
Rotational Direction Verification
Actuator model numbers that end with “R” are factory configured for clockwise (cw), minimum to maximum rotation when facing the gear end of the actuator, or counterclockwise (ccw) rotation when facing the other end of the actuator. The gear end of the actuator is the side opposite of the visual position indicator
Actuator Mounting
SQM5… actuators can be mounted in any orientation. Optional base mounting brackets are available.
SQM5… actuators can also be face-mounted using self-tapping screws in combination with the various holes on the face of the actuator gear end.
Switch Adjustment
SQM5…actuators are factory-wired with Switch I (maximum), Switch II (fully closed/economy position) and Switch III (minimum/low-fire). The individual switch cams I, II, and III are factory set to 90°, 0° and 10°, respectively. See Figures 3 and 4.
Lift the screws and raise the cover. See Figure 2.
Item Number 129-399, Rev. BA Page 1 of 4
Document No. 129-399 Installation Instructions January 18, 2008
EA0561R3
ACTUATOR
POSITION SCALE
ACTUATOR POSITION INDICATING POINTER
CAM DRUM
RELEASE BUTTON
GEAR END
SWITCH CAM I
SET AT MAXIMUM
SWITCH CAM II
SET AT ZERO ("ECONOMY")
50
10
0
30
10 30
10
0
50
0
70
SINGLE SWITCH
CAM POINTER
DOUBLE SWITCH CAM POINTER
SWITCH CAM III
SET AT MINIMUM
Figure 3. Component Identification on the Cam Drum Side of the SQM5…Actuator.
NOTE: The single switch cam pointers are used
together with the black scales when configured for ccw operation.
The double switch cam pointers are used
together with the red scales when configured for cw operation.
The individual switch cams can be
adjusted by hand or with the use of the tool attached to the outside of the hinged switch terminal protection lid.
SQM5x.xxxRxA actuators without
potentiometer must be adjusted only between 0° and 160°.
If a potentiometer is installed, the
adjustable range of the switches depends on the range of the potentiometer.
SQM5x.xxxRxA3 actuators have a 90°
potentiometer and the switches must be adjusted between 0° and 90°.
SQM5x.xxxRxA4 actuators have a 135°
potentiometer and the switches must be adjusted between 0° and 135°.
ACTUATOR POSITION
CAM DRUM
ASZ... (1000 Ohm)
FEEDBACK POTENTIOMETER
50
30
10
0
0
50
30
10
0
0
DIAL POINTER
INDICATING DIAL
Shaft Adjustment
The actuator shaft can be disengaged by pressing the silver shaft release button. The button is located above the grounding screw, under the hinged terminal protection cover, and to the right of the auto/manual switch. After pressing the shaft release button in and slightly upward, the shaft can be manually rotated. After the shaft has been manually aligned to the closed position, re-engage the shaft by pushing the shaft release button downwards.
Cam Drum Adjustment
Once the shaft has been set, the cam drum must be manually aligned by pressing and holding the black cam drum release button (see Figure 3). Rotate the cam drum until the “0” mark on the actuator position scale (left scale on the cam drum) is aligned with the gray actuator position indicating pointer.
Position Indicating Dial Adjustment
The actual position of the SQM5… actuator is indicated by the gray actuator position indicating pointer (see by the indicating dial through the housing’s window. Ensure that the actuator position indicating dial is aligned with the actuator position scale. If necessary, rotate the dial in the clockwise direction.
Figure 3). The position is also displayed
Page 2 of 4 Siemens Building Technologies, Inc.
Loading...
+ 2 hidden pages