Siemens SQM5 User Manual

SQM5…
Reversing Actuators
ISO 9000 and 14000 REGISTERED FIRM
¤
Technical Instructions
Document No. 155-517P25
July 9, 2007
EA0511R1
Description
Features
SQM5... reversing actuators are used for the positioning of flow control valves, butterfly valves, dampers, or any application requiring rotary motion. The SQM5… actuators accommodate control input signals of 4 to 20 mA, 0 to 135 Ω, 0 to 10 Vdc, 0 to 20 mA, position proportional and floating control. The available output signals include 4 to 20 mA, 0 to 135 Ω, 0 to 10 Vdc, 0 to 20 mA, and 0 to 1000 Ω. SQM5… actuators are available with up to six internal, easily adjustable switches.
A selection of exchangeable circuit boards provide a variety of functions including auto/manual selector switch, manual forward/reverse toggle switch, zero and span adjustment, parallel or master/slave operation, split range control, input signal override, and selectable electronic linearization.
The SQM5… is engineered for precision. It is particularly well suited for applications requiring a high degree of modulating accuracy and repeatability. Drive shaft play is limited to 0.3° with a modulating accuracy of 250 repositions through 90° of travel.
The SQM5… actuator may be mounted in any position. A selection of mounting brackets and shafts provides installation flexibility and allows for the simple replacement of most competitive actuators.
Modulating accuracy of 250 repositions through 90°
Two limit switches, plus up to four internal auxiliary switches
Fully closed “economy position” switch
Drive shaft and cam drum disengagement clutches
Auto/manual switch, manual control forward/reverse toggle switch
UL, CSA approved 24 and 110 Vac versions
CE approved 220 Vac versions
Field reversible clockwise (cw) or counterclockwise (ccw) operation
Various torque ratings and running times available
Selection of field exchangeable single-ended and dual-ended shafts
Mounting brackets to replace competitive actuators
Siemens Building Technologies, Inc.
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007
Features, Continued
Connections for both base and face mounting
Low hysteresis actuator and potentiometer gearing
Externally visible position indication
Selection of input and output signals
Zero and span adjustment
Field exchangeable circuit boards and potentiometers
Electronic damper linearization function
Split range and selectable parallel or master/slave operation
Adjustable input signal override function
Application
SQM5… actuators are uniquely suited for both industrial and commercial applications. The high level of accuracy permits precise modulating control of industrial process and process heating applications, often significantly enhancing performance and product quality.
In commercial and industrial burner applications requiring high turndown and reliable ignition, the auxiliary switches can be applied to create separate positions for burner ignition and low fire. In dual fuel applications, additional switches can be used to create separate high fire, low fire and ignition positions for each fuel. The economy position switch is used to drive the actuator to the full closed position when the burner is off.
In all applications, commissioning is simplified. Shaft and cam drum disengagement clutches allow for the quick manual alignment of the actuator shaft and switch cams. The forward/reverse toggle switch in combination with the auto/manual selector switch provides direct manual control.
Page 2 Siemens Building Technologies, Inc.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007
Table Of Contents

Application Page 2 Product Numbers

Product numbers for pre-assembled UL/CSA/CE-approved actuators, Table 1 Page 4 Product numbers for accessories, Table 2 Page 5 SQM5… Product Number Identification Legend Page 6 Installation and Operating Instructions Shaft Installation Page 7 Rotational Direction Verification Page 8 Actuator Mounting Page 8 Switch Adjustment Page 8 Shaft Adjustment Page 9 Cam Drum Adjustment Page 9

Wiring

Electrical Connection Page 9 Grounding Page 9 Wiring Connections AGA56.1… circuit boards Page 10 AGA56.41/42/43… circuit boards Page 11 AGA56.9… circuit boards Page 13 Commissioning Modulation Adjustment Page 15 Zero Adjustment Page 15 Span Adjustment Page 15 Cover Installation Page 16

Features

SQM5x.xxxxxZx actuators Page 16 SQM5x.xxxxxGx actuators Page 18 SQM5x.xxxxxHx actuators Page 18 SQM5x.xxxxxKx actuators Page 18 SQM5x.xxxxxAx actuators Page 18 Service Guide Reversing Rotational Direction Page 18 Shaft Installation Page 20 Circuit Board Installation Page 20 AGA56.41/42/43… Page 20 AGA56.9A Page 22 AGA56.1A97 Page 24 Potentiometer Removal/Installation Page 25
Specification Data Page 26 Dimensions Page 29
Siemens Building Technologies, Inc. Page 3
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007
Product Numbers
1. Torque will vary with the selection of the shaft. See Specifications.
2. Running time for 135° Æ multiply by 1.5. For 50 Hz Æ multiply by 1.2
3. SQM5x.xxxxxZx models also accept a 0 to 20 mA input signal.
1
Torque
[lb-in] 90°@ 60
90 8 ccw x x SQM50.261R1G3 90 8 cw x x SQM50.261R1G3R 90 8 ccw x SQM50.264R1A SQM50.264R2A 90 8 cw x SQM50.264R1A0R 90 8 ccw x SQM50.264R1A3 90 8 cw x x SQM50.264R1G3R
90 8 ccw x x SQM50.264R1G4 140 12 ccw x x SQM50.361R1G3 140 12 cw x x SQM50.361R1G3R 140 12 ccw x x SQM50.361R1G7 140 12 ccw x x SQM50.364R1G3 140 12 cw x x SQM50.364R1G3R 140 25 ccw x SQM50.461R1A 140 25 ccw x SQM50.461R1A3 140 25 ccw x x SQM50.461R1G3 140 25 cw x x SQM50.461R1G3R 140 25 ccw x x SQM50.461R1H3 140 25 ccw x x x x SQM50.461R1Z3 140 25 ccw x x x x SQM50.461R1Z7 140 25 ccw x SQM50.464R1A SQM50.464R8A 140 25 cw x SQM50.464R1A0R 140 25 ccw x SQM50.464R1A3 140 25 cw x SQM50.464R1A3R 140 25 ccw x x SQM50.464R1G3 SQM50.464R8G3 140 25 cw x x SQM50.464R1G3R SQM50.464R2G3R 140 25 ccw x x SQM50.464R1G7 140 25 cw x x SQM50.464R1G7R 140 25 ccw x x SQM50.464R1H3 SQM50.464R8H3 140 25 ccw x x x x SQM50.464R1Z3 SQM50.464R2Z3 SQM50.464R8Z3 200 25 ccw x SQM53.464R1A 200 25 ccw x SQM53.464R1A3 200 25 ccw x x SQM53.464R1G3 200 25 ccw x x SQM53.464R1G7 200 25 cw x x SQM53.464R1G7R 200 25 ccw x x x x SQM53.464R1Z3 SQM53.464R2Z3 200 25 ccw x x x x SQM53.467R1Z3 200 25 cw x x x x SQM53.467R1Z3R 200 25 ccw x SQM53.467R2A3 310 37 ccw x SQM56.564R1A 310 37 ccw x x SQM56.564R1G4 310 37 ccw x x SQM56.564R1G7 310 37 ccw x x SQM56.564R1H4 310 37 ccw x x x x SQM56.564R1Z3 400 50 ccw x x SQM56.664R1G3 400 50 ccw x x x x SQM56.664R1Z3 400 50 cw x SQM56.667R1A3R 400 50 ccw x x SQM56.667R1G3 400 50 cw x x SQM56.667R1G7R 400 50 ccw x x x x SQM56.667R1Z3
Running
2
Time
Hzsec
Rotation
direction
Table 1. Product Numbers for Pre-assembled Actuators.
Input Control Signals
Line
Voltage
4-20 mA
Ω
0-135
3
110 V 220 V 24 V
0-10 Vdc
Product Number
Page 4 Siemens Building Technologies, Inc.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007
Table 2. Product Numbers for Accessories.
Electronic Circuit Boards
AGA56.1A97 24-250 Vac (A) board for SQM5x.xxxxxAx AGA56.9A87 24 Vac (Z) board for SQM5x.xxxxxZx AGA56.9A17 110 Vac (Z) board for SQM5x.xxxxxZx AGA56.9A27 220 Vac (Z) board for SQM5x.xxxxxZx AGA56.41A87 24 Vac (G) board for SQM5x.xxxxxGx AGA56.41A17 110 Vac (G) board for SQM5x.xxxxxGx AGA56.41A27 220 Vac (G) board for SQM5x.xxxxxGx AGA56.42A87 24 Vac (H) board for SQM5x.xxxxxHx AGA56.42A17 110 Vac (H) board for SQM5x.xxxxxHx AGA56.42A27 220 Vac (H) board for SQM5x.xxxxxHx AGA56.43A87 24 Vac (K) board for SQM5x.xxxxxKx AGA56.43A17 110 Vac (K) board for SQM5x.xxxxxKx AGA56.43A27 220 Vac (K) board for SQM5x.xxxxxKx
See Product Number Identification Legend, Figure 1.
Mounting Brackets & Adapters
AGA57.3 for replacement of Honeywell MOD III, IV
actuators
AGA57.4 for replacement of Honeywell M640/740/940 and
Barber Colman EA20/40/50/60 actuators. Directly adaptable to Eclipse butterfly valves.
ASK33.9 mounting kit for direct attachment to Siemens
VKF41... butterfly valve. (Shaft AGA58.1 required)
Shafts
AGA58.1 10 mm round with key. Gear end only. AGA58.2 12 mm round with key. Gear end only. AGA58.3 9 mm square. Dual-ended. AGA58.4 3/8 inch square. Dual-ended. AGA58.7 14 mm round with key. Gear end only. For exact shaft sizes, see Dimensions.
Crank Arm, Push Rods
338 031 Crank arm kit. Includes two crank arms for connecting the AGA58.4 shaft to a 1/2-inch damper shaft with two ball joints. (Does not include push rod.)
338 041 5/16" damper push rod, 12 inches long. 338 042 5/16" damper push rod, 15 inches long. 338 043 5/16" damper push rod, 18 inches long. 338 044 5/16" damper push rod, 24 inches long. 338 045 5/16" damper push rod, 36 inches long. 338 046 5/16" damper push rod, 48 inches long.
Potentiometers
ASZ12.803 and ASZ12.30 1000Ω, 90° ASZ12.833 and ASZ12.33 1000Ω, 135° ASZ22.803 and ASZ22.30 1000/1000Ω double potentiometer, 90° ASZ22.833 and ASZ22.33 1000/1000Ω double potentiometer, 135° ASZ16.703 135Ω, 90° (wire wound) ASZ16.733 135Ω, 135° (wire wound) ASZ66.733 135Ω/135Ω, double potentiometer 135° (wire wound)
Additional potentiometer models available. See Siemens technical data sheet 7921.
Siemens Building Technologies, Inc. Page 5
Technical Instructions SQM5… Reversing Actuators
y
f
(
)
(SQ
G
SZ…)
A
(1000 O
G
)
Clockwi
Fi
6
)
Document No. 155-517P25 July 9, 2007
Product Number Identification Legend
For actuator identification only. To select product numbers for ordering, see Table 1.
Actuator famil
Torque in-lb @ 60 (50) Hz.
Running time for 90°
Number of SPDT switches
Shaft selection
Approvals
Operating voltage (Vac @50-60 Hz)
Internal circuit board
Potentiometer
90 for 8 (10) sec. running time
0
140 for 12 (15), 25 (30), 37 (45) sec.
0
200 for 25 (30) sec.
3
310 for 37 (45) sec.
6
400 for 50 (60), 75 (90)sec.
6
Not all actuator running tim es are available in each torque. Refer to table 1
60 Hz.
8 sec.
2
12 sec.
3
25 sec.
4
37 sec.
5
50 sec.
6
2 limit and 4 auxiliary switches
6
no sha
0
round 10 mm, single ended (for use with VKF41... butterfly valves)
1
square 3/8 inch, dual ended
4
round 14 mm, single ended
7
UL recognized, CSA certified
R
110-120 Vac
1
220-240 Vac
2
24 Vac
8
AGA56.1A97 (position proportional control) AGA56.41A... (4 to 20 mA input)
G
AGA56.42A... (0 to 135 Ohm input)
H
AGA56.43A... (0 to 10 Vdc input)
K
AGA56.9... (all inputs/outputs, linearization, split ranging, override and pre-set positioning)
Z
ASZ12.30 (1000 ohm, 90°)
3
ASZ12.33 (1000 Ohm, 135°)
4
ASZ22.30 (1000/1000 Ohm, 90°)
7
ASZ22.33 (1000/1000 Ohm, 135°)
8
ASZ16.703 (135 Ohm, 90°)
B
ASZ16.733 (135 Ohm, 135°)
C
ASZ66.733 (135/135 Ohm, 135°)
L
Figure 1. SQM5… Product Number Identification Legend.
SQM50 .4 8 0 R 1 Z 3 R
50 Hz.
10 sec.
2
15 sec.
3
30 sec.
4
45 sec.
5
60 sec.
6
t
shaft must be ordered separately
M5x.xxxxx
hm required when using SQM5x.xxxxx
, H, K , Z
x actuators require potentiomet er A
, H, K, Z
x actuators
Rotational Direction
R
se (when facing gear end. See
(Product numbers ending without R are ccw)
gure
.
Page 6 Siemens Building Technologies, Inc.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007
Installation and Operation Instructions
SQM5… actuators are sometimes shipped without the shaft installed. To install the selected shaft:
1. Loosen the two screws on the actuator cover corners. See Figure 2.
2. Lift the screws and raise the cover. See Figure 3.
Shaft Installation
EA0564R1
Figure 2.
EA0568R1
Figure 3.
3. Each shaft is supplied with two washers and a “C” clip. See Figure 4. Using spreading pliers, remove the “C” clip and the washers from the shaft.
KEY END
INSERT END
SHAFT KEY
WASHERS ON
BOTH SIDES
OF THE BEARING
EA0559R1
C-CLIP
Figure 4.
4. Insert the “insert end” of the shaft into the “gear end” of the actuator.
5. Push the shaft until the “insert end” reaches just short of the brass bushing at the other end of the actuator.
6. Put one of the washers on the insert end of the shaft. See Figure 5.
WASHERS
EA0569R1
Figure 5.
7. Line up the “shaft key” with the key slot on the “gear end” of the actuator and slide the shaft until the “insert end” is completely through the brass bushing.
8. Place the second washer onto the “insert end” of the shaft. Using spreading pliers, install the “C” clip.
Siemens Building Technologies, Inc. Page 7
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007
Rotational Direction Verification
Actuator model numbers that end with “R” are factory configured for clockwise (cw), minimum to maximum rotation when facing the gear end of the actuator, or counterclockwise (ccw) rotation when facing the other end of the actuator. The gear end of the actuator is the side opposite of the visual position indicator.
To field reverse the direction of rotation, see Service Guide, “Reversing Rotational Direction”.
Actuator Mounting
ACTUATOR POSITION INDICATING POINTER
CAM DRUM
RELEASE BUTTON
GEAR END
SQM5… actuators can be mounted in any orientation using the four 1/4"-20 UNC tapped holes located on the bottom corners of the actuator base. Optional base mounting brackets are available. See Table 2. SQM5… actuators can also be face mounted using self tapping screws in combination with the various holes on the face of the actuator gear end.
ACTUATOR
POSITION SCALE
SWITCH CAM I
SET AT MAXIMUM
SWITCH CAM II
SET AT ZERO ("ECONOMY")
50
10
0
30
10 30
10
0
50
0
70
SINGLE SWITCH
CAM POINTER
DOUBLE SWITCH CAM POINTER
SWITCH CAM III
SET AT MINIMUM
50
30
10
0
0
CAM DRUM
ASZ... (1000 Ohm)
FEEDBACK POTENTIOMETER
50
30
10
0
0
DIAL POINTER
ACTUATOR POSITION
INDICATING DIAL
EA0561R3
Figure 6. Component Identification on the Cam Drum Side of the SQM5… Actuator.
Switch Adjustment
See Figure 6.
All SQM5…actuators are factory wired with Switch I (maximum), Switch II (fully closed “economy position”) and Switch III (minimum). The individual switch cams I, II, and III are factory set to 90°, 0° and 10° respectively.
NOTE: The single switch cam pointers are used together with the black scales when
configured for counterclockwise (ccw) operation.
The double switch cam pointers are used together with the red scales when
configured for clockwise (cw) operation.
The individual switch cams can be adjusted by hand or with the use of the tool
attached to the outside of the hinged switch terminal protection lid.
Page 8 Siemens Building Technologies, Inc.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007
Switch Adjustment, Continued
NOTE: If a potentiometer is installed, the adjustable range of the switches depends
on the range of the potentiometer. SQM5x.xxxxxAx actuators may be adjusted between 0° and 160°. SQM5x.xxxxxx3 actuators have a 90° potentiometer and the switches must be adjusted only between 0 and 90°. SQM5x.xxxxxx4 actuators have a 135° potentiometer and the switches must be adjusted only between 0 and 135°.
Shaft Adjustment
See Figure 6.
Cam Drum Adjustment
See Figure 6. Position Indicating Dial
Adjustment
Wiring
Electrical Connection
The actuator shaft can be disengaged by pressing the silver shaft release button. The button is located above the grounding screw, under the hinged terminal protection cover, and to the right of the auto/manual switch. After pressing the shaft release button in and slightly upward, the shaft can be manually rotated. After the shaft has been manually aligned to the closed position, re-engage the shaft by pushing the shaft release button downwards.
Once the shaft has been set, the cam drum must be manually aligned by pressing and holding the black cam drum release button (see Figure 6). Rotate the cam drum until the “0” mark on the actuator position scale (left scale on the cam drum) is aligned with the gray actuator position indicating pointer.
The actual position of the SQM5… actuator is indicated by the gray actuator position indicating pointer (see Figure 6). The position is also displayed by the indicating dial through the housing’s window. Ensure that the actuator position indicating dial is aligned with the actuator position scale. If necessary, rotate the dial in the clockwise direction.
CAUTION:
Turning the dial in the counterclockwise direction may loosen the potentiometer locking screw.
SQM5… actuators are equipped with two removable conduit connection plates located on the upper corner of the gear housing. Each plate is provided with two threaded connections for 1/2" NPSM conduit connectors. The use of flexible stranded wire is recommended.
Grounding
CAUTION:
To avoid electro-magnetic interference, the SQM5… actuators must be grounded.
The ground terminal is located to the right of the auto/manual switch. Disconnect the circuit board wire marked 51 during high voltage testing.
Reconnect it to the grounding terminal after the test.
Siemens Building Technologies, Inc. Page 9
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007
Wiring Connections
NOTE: SQM5… actuators require a single source, single phase power supply. Wiring connections vary depending on which AGA56…. circuit board is installed.
AGA56.1… circuit boards.
See Figures 7 and 8.
Manual Operation
1. Set the AUTO/MAN switch in the MAN position.
2. Connect ground to the screw located below the shaft release button.
3. Connect neutral to the double terminal block, located on the left side of the gray switch housing.
4. Only terminal "L" must be to enable manual operation. The actuator can now be driven to the maximum position (switch cam I) or the fully closed "economy position" (switch cam II) by using the toggle switch located to the left of the AUTO/MAN switch.
Automatic Operation
1. Set the AUTO/MAN switch in the AUTO position.
2. Connect ground to the screw located below the shaft release button.
3. Connect neutral to the double terminal block located on the left side of the gray
switch housing.
4. Connect line voltage to terminal A to drive the actuator in the opening direction.
5. Connect line voltage to terminal Z to drive the actuator in the closing direction.
CAUTION:
Do not power terminals A and Z simultaneously. Actuator damage will occur.
A
L
Z
AGA56.1A97
51
EA0555R3
N
shown in auto position
M
MAN AUTO
1213
12
I
11 21
II
12 22 13 23
21 12
wire leads
III
3
actuator switch
Maximum/High fire
I
II
"Economy"/Fully closed
III
Minimum/Low fire Auxilliary
IV...VI
4
IV
14
24
5
V
25
15
6
VI
26
16
c
b
a
ASZ...
(1000 Ohm)
Figure 7. Basic Functional Diagram of AGA56.1…
Page 10 Siemens Building Technologies, Inc.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007
Wiring, Continued
AGA56.41/42/43…
Circuit Boards. See Figures 9 and 10.
AZ L
AZ L
MAN.
0
AUTO.
AGA56.1A97
EA0554R3
Figure 8. AGA56.1A97 Terminal/Auto-Manual Board.
Manual Operation
1. Set the AUTO/MAN switch in the MAN position.
2. Connect ground to the screw located below the shaft release button.
3. Connect neutral to terminal N.
4. Only terminal "L" must be powered to enable manual operation. The actuator can now be driven to the maximum (high fire) position (switch cam I) or the fully closed "economy position" (switch cam II) by using the toggle switch located to the left of the AUTO/MAN switch.
Automatic Operation
1. Set the AUTO/MAN switch in the AUTO position.
2. Connect ground to the screw located below the shaft release button.
3. Connect neutral to terminal N.
4. Connect line voltage at all times to terminal L to provide power to the electronic
circuit board.
5. Connect line voltage to terminal LR to provide power when modulating. Connect
line voltage to Terminal LR only after removing power on terminals A and Z (otherwise actuator damage may result).
6. Connect line voltage to terminal A to drive the actuator to the maximum (high fire
purge) position. Once the maximum position is reached, terminal 11 (on switch I) will be energized to provide position feedback.
7. Connect power to terminal ZL to drive the actuator to the minimum (low-fire)
position. Once the minimum position is reached, terminal 23 (on switch III) will be energized to provide position feedback. Adjustment of switch III will determine the low-fire stop position. Switch III (low fire) must be set at a higher position than switch II (fully closed). Terminal ZL may be energized only after removing power from terminals A, Z, 13, and LR.
8. Connect line voltage to terminal Z to drive the actuator to the fully closed/economy
position (switch II).
9. Connect the input control signal wires to the appropriate terminals. See Figure 9.
CAUTION:
Do not power terminals A and Z simultaneously. Actuator damage will occur.
Siemens Building Technologies, Inc. Page 11
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007
Wiring, Continued
EA0556R5
51
N
EA0553R4
N
shown in auto position
M
OPE MAX MIN
MAX
MIN
AGA56.41A...
A
Z
L
ZL
13
MAN AUTO
1 2 13 3
123
I II III
11 21
12 22 13 23
21 12
wire leads
Figure 9. Basic Functional Diagram of AGA56.4…
Y- Y+
"G" Board 4 to 20mA
13ZL
LRNL
MAN.
0
AUTO.
LR
actuator switch
Maximum/High fire
I
II
"Economy"/Fully closed
III
Minimum/Low fire Auxilliary
IV...VI
4
IV
14
24
ZA
AGA56.4...
REG
MAX
MIN
MIN
MAX
Y
for ccw
blue
5
V
25
15
6
VI
26
16
rotation
black
brown
c
b
a
OPE MAX MIN ZALR13NZL L
MAX
MIN
AGA56.42A...
EA0552R4
OPE MAX
MIN
MAX
MIN
ASZ... (1000 Ohm)
YM U
0
"H" Board 0 to 135 ohm
Y+
Y-
U
M
Y
M
Y
MAN.
AUTO.
AGA56.41... ("G" board 4...20 mA)
(+2 V)
B
W
R
AGA56.42...
135 Ohm
("H" board 0-135 Ohm)
0...2 V
AGA56.43... ("K" board 0...10 V)
OPE MAX MIN
AGA56.43A...
EA0578R4
YM
M
MAX
MIN
"K" Board 0 to 10V
3
Y
Pos L ZA
L
0
N
LR13NZL A Z L
MAN.
AUTO.
L
Z
Figure 10. AGA56.41/42/43… Terminal and Trim Potentiometer Boards.
Page 12 Siemens Building Technologies, Inc.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007
AGA56.9… Circuit Boards
See Figures 11 and 12.
Manual Operation
1. Set the AUTO/MAN switch in the MAN position.
2. Connect ground to the screw located below the shaft release button.
3. Connect neutral to terminal N.
4. Only terminal "L" must be powered to enable manual operation. The actuator can now be driven to the maximum (high fire) position (switch cam I) or the fully closed "economy position" (switch cam II) by using the toggle switch located to the left of the AUTO/MAN switch.
Automatic Operation
1. Set the AUTO/MAN switch in the AUTO position.
2. Connect ground to the screw located below the shaft release button.
3. Connect neutral to terminal N.
4. Connect line voltage at all times to terminal L to provide power to the electronic
circuit board.
5. Connect line voltage to terminal L1 to provide power when modulating. Connect line
voltage to terminal L1 only after removing power on terminals A and Z (otherwise actuator damage may result).
6. Connect line voltage to terminal A to drive the actuator to the maximum (high fire
purge) position. Once the maximum position is reached, terminal 11 (on switch I) will be energized to provide position feedback.
7. Connect power to terminal ZL to drive the actuator to the minimum (low-fire)
position. Once the minimum position is reached, terminal 23 (on switch III) will be energized to provide position feedback. Adjustment of switch III will determine the low-fire stop position. Switch III (low fire) must be set at a higher position than switch II (fully closed). Terminal ZL may be energized only after removing power from terminals A, Z, 13, and LR.
8. Connect line voltage to terminal Z to drive the actuator to the fully closed/economy
position (switch II).
9. Connect the input control signal wires to the appropriate terminals. See Figure 11.
CAUTION:
Do not power terminals A and Z simultaneously. Actuator damage will occur.
Siemens Building Technologies, Inc. Page 13
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007
Wiring, Continued
A
1 2 13 3
123
I
11 21
51
EA0557R6
N
shown in auto position
N
M
Z
L
MAN AUTO
II
12 22 13 23
21 12
wire leads
ZL
III
1
L
actuator switch
I
II
III
IV...VI
45
IV V
141524 25
P
AGA56.9...
POS
POS
0...3
Y
POS
REG
MAX
MIN
MIN MAX
Maximum/High fire "Economy"/Fully closed Minimum/Low fire Auxilliary
0...3
Y
6
VI
26
16
OPE MAX MIN
1 2
1 2
20 mA
25% 50%
SHIFT
18 mA
16 mA
14 mA
0 or 12 mA
10 mA
8 mA
ZF =
6 mA
4 mA
75%
MAX
0...3
Y
ZF
M
U
4
M
0
Y
M
3
Y
M
1
Y
M
Y2
U
3
U
2
U
1
M
4...20 mA
(+2 V)
B
135 Ohm
W
0...2 V
R
4...20 mA
0...10 V
0...20 mA
4...20 mA
0...20 mA
0...10 V
common
LIN
MAX 75% 50% 25% MIN
J1
LIN
MIN
MIN
MAX
0...3
Y
J2
for ccw
rotation
black
blue
brown
c
b
a
ASZ... (1000 Ohm)
EA0558R3
Figure 11. Basic Functional Diagram of AGA56.9…
MU
4
ZF
M
Y1Y2Y
Y
0
U
MUU
1
3
23
1
LZAL
MAN.
0
AUTO.
ZLNP
1
OPE MAX
MIN
MAX POS MIN
3-POSITION
SWITCH
1 2
J2
U1...U3
2
LIN
J1
JUMPERS
POT. METERS
AGA56.9A...
Figure 12. AGA56.9… Terminal and Trim Potentiometer/Jumper Board.
Page 14 Siemens Building Technologies, Inc.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007
Modulation Adjustment
See Figures 10 and 12.
The blue trim potentiometers allow the adjustment of the minimum (zero) and maximum (span) positions. The factory setting of the MIN trim potentiometer is rotated fully counter clockwise. The factory setting of the MAX trim potentiometer is rotated fully clockwise.
Zero Adjustment
Span Adjustment
90 deg.
EA0562R1
Set the OPE/MAX/MIN slide switch to MIN. The blue MIN trim potentiometer can now be gently adjusted to the required minimum position. Return the OPE/MAX/MIN slide switch to OPE for operation.
NOTE: Do not set switch cam I higher than: 90° when using feedback potentiometers ASZxx.30
135° when using feedback potentiometers ASZxx.33 Set the OPE/MAX/MIN slide switch to MAX. The blue MAX trim potentiometer can now
be gently adjusted to the required maximum position. Return the OPE/MAX/MIN slide switch to OPE for operation.
Example of limit switch I and III
and trim potentiometer settings
Switch I setting
MAX trim potentiometer setting
MIN trim potentiometer setting
Switch III setting
0 deg.
Figure 13. Switch cam and Trim
Potentiometer Setting.
NOTE: The actual minimum and maximum
modulating range is determined either by the setting of the MIN and MAX trim potentiometers or the setting of switch cam III (Minimum) and switch cam I (Maximum). The actuator can never modulate outside of the range set by switch cam I and III. If the MIN and MAX trim potentiometers are set outside the setting range of switch cams I and III, then the switch cam settings determine the modulating range. If a soft stop is desired, the modulating range can be defined by the trim potentiometers if the MIN and MAX trim potentiometers are set inside the setting range of switch cams I and III. See the example in Figure 13.
Siemens Building Technologies, Inc. Page 15
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007
Cover Installation
1. Lift the two screws on the cover corners and slide the cover end into the grooves at the gear end of the actuator. See Figure 14.
2. Press the cover into place and then press the screws inward and tighten. See Figure 15.
Features of SQM5x.xxxxxZx Actuators
Multiple Input Signals
Multiple Output Signals
EA0567R1
Figure 14.
EA0563R1
Figure 15.
SQM5xx.xxxxxZx actuators contain the AGA56.9A… multi function circuit board. This circuit board provides the following features:
The AGA56.9A… circuit board accepts the following input signals:
Line voltage
Power to A drives the actuator open to the setting of switch cam I (Maximum).
Power to ZL drives the actuator closed to the setting of switch cam III (Minimum).
Power to Z drives the actuator closed to the setting of switch cam II (Economy).
4 to 20 mA (Signal to Y3, common to M)
0 to 135 Ω (Slide wire signal to Y0, potentiometer connected to M and U4)
0 to 10 Vdc (Signal to Y1, common to M)
0 to 20 mA (Signal to Y2, common to M)
The AGA56.9A… circuit board provides the following output signals:
4 to 20 mA (Signal from U3, common to M)
0 to 10Vdc (Signal from U1, common to M)
0 to 20mA (Signal from U2, common to M)
Double potentiometers ASZ22… provide additional output signals.
Page 16 Siemens Building Technologies, Inc.
SQM5… Reversing Actuators Technical Instructions
.3
Document No. 155-517P25 July 9, 2007
Electronic Linearization Function
Butterfly valves have non-linear flow characteristics. Near the fully closed position, a small change in the valve’s position will produce a very large change in flow. Near the fully open position, a large position change will produce a relatively small change in flow.
The linearization function is intended to minimize the initial steep flow curve characteristics of a typical butterfly valve. The linearization function is enabled when Jumper J1 is in position 1 (upper position). Consequently, the actuator will make smaller rotational movements when subjected to lower input signals and larger rotational movements when subjected to higher input signals.
For example (based on a 90° modulating range), a change in input signal from 4 to 8 mA will cause a rotational movement of 11.25°. An equal change from 16 to 20 mA will cause a rotational movement of 45°. Thus, with the linearization function enabled, the change in flow is closely proportional to the change in input signal.
The linearization function is disabled when Jumper J1 is in position 2 (lower position). When disabled, the rotational movement of the shaft is proportional to the input signal.
Input Signal Override
Parallel Operation
Master/Slave Operation
Split Ranging
Line voltage to terminal P will drive the actuator to a pre-set adjustable position, overriding all modulating input signals. Use the potentiometer marked POS to adjust the override position to any setting within the setting range of switch cams I and III.
NOTE: The input signal override can also be used for the ignition position of burners if
different from the low fire position.
Set Jumper J2 in position 1 (upper position) to configure the actuator for parallel operation. Input signals Y0, Y1, Y2 or Y3 are directly shunted to output signals U1, U2 and U3. All output signals are available regardless of which input signal is applied.
Set J2 in position 2 (lower position) to configure the actuator for master/slave operation. The output signals U1, U2 and U3 reflect actual shaft position.
AGA56.9… circuit boards have a modulating signal shift feature which can be used for split ranging. If no signal is present on Y0, Y1, Y2 or Y3, the actuator will modulate through the full rotational range in response to a 12 to 20 mA signal applied at ZF. If a maximum signal is present on Y0, Y1, Y2, or Y3, then the actuator will modulate through the full rotational range in response to a 4 to 12 mA signal applied at ZF. (Maximum signal can be easily achieved by bridging terminals U4 and Y0.) See Figure 16.
NOTE: It is possible to configure the actuator for split range operation 12 to 4 mA and
20 to 12 mA. Consult your authorized Siemens Building Technologies combustion products sales representative for details.
MAX
75%
50%
25%
MIN
EA0560R1
20 mA
25% 50% 75% MAXMIN
14 mA
12 mA 10 mA
8 mA 6 mA 4 mA
Y
0..
16 mA
18 mA
Figure 16. Split Ranging.
Siemens Building Technologies, Inc. Page 17
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007
Features of SQM5x.xxxxxGx, SQM5x.xxxxx SQM5x.xxxxx
Hx, Kx
Actuators
Input Signals
Output Signals
Features of SQM5x.xxxxx Actuators
Input Signals
Ax
SQM5x.xxxxxGx actuators contain the AGA56.41A… circuit board with terminals Y- and Y+ for 4 to 20 mA modulating input.
SQM5x.xxxxxHx actuators contain the AGA56.42A… circuit board with terminals Y, M and U for 0 to 135 Ω modulating input.
SQM5x.xxxxxKx actuators contain the AGA56.43A… circuit board with terminals Y and M for 0 to 10 Vdc modulating input.
The AGA56.4xA… circuit boards accept the following additional input signal: Line voltage
Power to A drives the actuator open to the setting of switch cam I (Maximum).
Power to Z drives the actuator closed to the setting of switch cam II (Economy).
Power to ZL drives the actuator closed to the setting of switch cam III (Minimum).
The AGA56.4xA… circuit boards do not provide output signals. Install a double potentiometer ASZ22…to obtain a 0 to 1000 Ω actuator position output signal.
The AGA56.1A97… circuit boards accept the following additional input signal:
Line voltage
Power to A drives the actuator open to the setting of switch cam I (Maximum).
Power to Z drives the actuator closed to the setting of switch cam II (Economy).
Power to switch III, terminal 3 drives the actuator to the setting of switch cam III
(Minimum).
Output Signals
Service Guide
Reversing Rotational Direction
The AGA56.1A97 circuit board provides no output signals. Install an ASZ… potentiometer to obtain an actuator position output signal.
WARNING:
Disconnect the power supply to the actuator before performing any service functions.
1. Disconnect the wires marked 21 and 12, and reverse.
2. Adjust all switch cams to the desired settings (see Figure 6):
For CCW rotation use the black cam drum scales and the single switch cam pointers.
For CW rotation, use the red cam drum scales and the double switch cam pointers.
NOTE: Press and hold the black cam drum release button to rotate the cam drum.
This will give easy access to the switch cams and a better view of the cam drum scales.
If no potentiometer ASZ… is installed, the reversing procedure is complete. If a potentiometer ASZ… is installed, complete Steps 3 through 9.
Page 18 Siemens Building Technologies, Inc.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007
Reversing Rotational Direction, Continued
BLUE
BROWN
BLACK
BLUE
POSITION
INDICATION
min.
max.
POINTER
BLACK
BROWN
POSITION
min.
max.
INDICATION
POINTER
EA1210R1
EA1199R1
GEAR WITH MARK "1" FOR
COUNTERCLOCKWISE ROTATION
POTENTIOMETER GEAR
ALIGNMENT POINTER
POTENTIOMETER GEAR
ATTACHMENT SCREW
EA0517R1
Figure 17a. Reversing Rotational Direction on the ASZ Potentiometer (Gear Models).
min.
max.
EA1209R1
EA1200R1
BLACK
BROWN
BLUE
BLACK
BLUE
BROWN
min.
max.
POSITION
INDICATION
POINTER
min.
max.
Counterclockwise
Figure 17. Reversing Rotational Direction on the ASZ Potentiometer.
BOARD
ALIGNMENT
1
POTENTIOMETER
SCREW
TERMINAL
BLOCK
BROWN
BLACK
BLUE
POTENTIOMETER GEAR
ALIGNMENT POINTER
EA0518R1
GEAR WITH MARK "0"
FOR CLOCKWISE
ROTATION
POTENTIOMETER GEAR
ATTACHMENT SCREW
3. Disconnect the blue and brown wires from the terminal block located on the ASZ… potentiometer circuit board and reverse. The black wire remains connected to the middle terminal. See Figures 17 and 17a.
min.
max.
Clockwise
0
POTENTIOMETER
min.
max.
POSITION
INDICATION
POINTER
min.
max.
BOARD
ALIGNMENT
SCREW
TERMINAL
BLOCK
BLUE
BLACK
BROWN
4. Remove the white plastic actuator position-indicating dial by gently pulling while rotating in the clockwise direction. See Figure 6.
5. The actuator position indicating pointer, located near the actuator gear end of the cam drum, must point to the “0” mark on the actuator position scale (scale on the cam drum nearest to the actuator gear end). Press and hold the black cam drum release button while manually rotating the cam drum.
6. Loosen the black potentiometer cam attachment screw approximately one turn. Gently wedge a small screwdriver between the potentiometer and the gray plastic housing. Gently twist the screwdriver until the potentiometer releases from the cam drum shaft.
7. Change potentiometer end position:
Manually rotate the potentiometer position indication pointer exactly to the other
end mark (see Figure 17).
Gear models (see Figure 17a):
For clockwise rotation, manually rotate the potentiometer gear until the white line next to the “0” mark on the potentiometer gear face is exactly in alignment with the potentiometer gear alignment pointer. For counterclockwise rotation, manually rotate the potentiometer gear until the white line next to the “1” mark on the potentiometer gear face is exactly in alignment with the potentiometer gear alignment pointer
Siemens Building Technologies, Inc. Page 19
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007
Reversing Rotational Direction, Continued
8. Firmly tighten the black potentiometer cam attachment screw while manually holding the potentiometer position indication pointer in alignment. Check the alignment again.
9. Re-install the white actuator-indicating dial by gently pressing it onto the potentiometer cam attachment screw. Align scale position “0” on the actuator position indicating dial with the dial pointer by rotating the dial in the clockwise direction to avoid loosening the potentiometer cam attachment screw.
Shaft Installation
Preparation Before Circuit Board Installation
See Installation and Operation Instructions.
WARNING:
Disconnect the power supply to the actuator before replacing the circuit boards.
The black circuit board mounting bracket, installed on the inside base of the SQM5… actuator has four vertical, slotted circuit board supports. Remove the terminal section and circuit board(s) from the mounting bracket.
The actuator motor capacitor is attached to the lower section of the gray plastic switch housing using snap-on holding clips. Gently pull the capacitor forward until it unclips and temporarily place it on top of the gear housing. See Figure 18.
CAUTION:
Do not disconnect any capacitor wiring.
EA0570R1
Figure 18.
CAPACITOR
AGA56.41/42/43 Circuit Board Installation
1. Remove the AGA56.41/42/43… circuit board from the packaging. The circuit board is shipped as one board.
TERMINAL
SECTION
2. Separate the board at the perforation by holding the circuit board at both ends and gently bending the board until it separates.
3. Move the terminal section containing the auto/manual switch to the opposite end of the base circuit board.
4. From the switch housing side of the actuator, guide the base circuit board into the bottom of the circuit board mounting bracket. See Figure 19.
EA0574R1
BASE
CIRCUIT
BOARD
Figure 19.
Page 20 Siemens Building Technologies, Inc.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007
AGA56.41/42/43 Circuit Board Installation, Continued
5. Re-install the actuator motor capacitor. See Figure 20.
6. Gently guide the terminal section into the support slots and slide the terminal board downward until both supports snap into place. Ensure that the four brown wires and the flat white connector cable which connect the two circuit boards are positioned correctly in their respective corners allowing the board to freely slide into place without pinching either wire. See Figure 21.
7. Connect the bundled blue, black and brown potentiometer wires to the terminal block located on the ASZ… potentiometer circuit board. See Potentiometer Installation.
EA0575R1
Figure 20.
TERMINAL
SECTION
CAPACITOR
EA0576R1
Figure 21.
Siemens Building Technologies, Inc. Page 21
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007
AGA56.41/42/43 Circuit Board Installation, Continued
8. Make the following connections to the actuator: See Figure 22.
a. Connect the wire, marked “1” from
the circuit board to switch I, terminal 1.
b. Connect the wire, marked “2” from
11
12
13
14
15
16
17
18
27
28
7
8
VII
VIII
24
25
26
4
5
6
IV
V
VI
211222
23
3
II
III
I
13
the circuit board to switch II, terminal 2.
c. Connect the wire, marked “3” from
the circuit board to switch III, terminal 3.
d. Connect the wire, marked “13”
from the circuit board to switch III,
N
TERMINAL
BLOCK
3
2
1
terminal 13.
e. Connect the blue neutral wire
marked “N” to the double terminal block located on the outer end of the switch housing
f. Connect the grounding wire
marked "51" to the ground terminal located to the right of the auto/manual switch.
EA0577R2
Figure 22.
MAN.
0
AUTO
N
51
AGA56.9A… Circuit Board Installation
1. Remove the ASZ... potentiometer if already installed on the SQM5... actuator. See Potentiometer Removal/Installation Instructions.
2. Remove the AGA56.9A… circuit boards from the packaging. The three separate AGA56.9A circuit boards are shipped in a circuit board mounting bracket.
3. Remove the two upright circuit boards from the mounting bracket by gently pulling aside the vertical supports and sliding the boards upward. Remove the base circuit board from the bottom of the mounting bracket. Discard the shipping mounting bracket.
Page 22 Siemens Building Technologies, Inc.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007
AGA56.9A… Circuit Board Installation, Continued
4. Guide the base circuit board from the
switch housing side of the actuator into the bottom of the circuit board mounting bracket. See Figure 23.
5. Re-install the actuator motor capacitor.
See Figure 24.
6. Gently guide the terminal board into the
support slots and slide the terminal board downward until both supports snap into place. See Figure 25.
7. See Figure 26 and make the following
EA0571R1
Figure 23.
BASE
CIRCUIT
BOARD
connections to the actuator: a. Connect the wire, marked “1” from
the circuit board to switch I, terminal 1.
b. Connect the wire, marked “2” from
the circuit board to switch II, terminal 2. Connect the white wire, marked “3” from the circuit board to switch III, terminal 3.
c. Connect the wire, marked “13” from
the circuit board to switch III, terminal 13.
d. Connect the neutral wire, marked
“N” to the double terminal block located on the outer end of the switch housing.
e. Connect the grounding wire marked
"51" to the ground terminal located to the right of the auto/manual switch.
EA0572R1
CAPACITOR
Figure 24.
TERMINAL
SECTION
EA0573R1
Figure 25.
Siemens Building Technologies, Inc. Page 23
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007
AGA56.9A… Circuit Board Installation, Continued
8. Gently guide the L-shaped circuit board containing the three blue trim potentiometers into the vertical support slots located on the cam drum side of the actuator. See Figure 27.
18
27
28
7
8
VII
VIII
24
25
26
4
5
6
IV
V
VI
211222
23
3
I
II
III
13
11
12
13
14
15
16
17
9. Slide the circuit board downward until both supports snap into place. Install the ASZ… potentiometer. (See
Potentiometer Removal/Installation Instructions.)
N
3
2
1
10. Connect the bundled blue, black and brown potentiometer wires to the terminal block located on the ASZ… potentiometer circuit board.
MAN.
0
AUTO
AGA56.1A97 Circuit Board Installation
N
EA0565R2
51
Figure 26.
L-SHAPED
CIRCUIT
BOARD
EA0566R1
Figure 27.
1. Install the AGA56.1A97 circuit board into the two slotted circuit board supports located on the switch housing side of the actuator.
2. Gently guide the AGA56.1A97 circuit board into the support slots and slide the board downward until both supports snap into place.
3. Make the following connections to the actuator: a. Connect the wire, marked “1” from the circuit board to switch I, terminal 1. b. Connect the wire, marked “2” from the circuit board to switch II, terminal 2. c. Connect the wire, marked “13” from the circuit board to switch III, terminal 13.
Page 24 Siemens Building Technologies, Inc.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007
Potentiometer Removal
9. Remove the white plastic actuator position-indicating dial by gently pulling while rotating in the clockwise direction. See Figure 6.
10. Disconnect the blue, black and brown wire from the potentiometer terminal block. See Figure 17.
11. Remove the silver potentiometer alignment screw.
12. Loosen the black potentiometer cam attachment screw approximately one turn.
13. Gently wedge a small screwdriver between the potentiometer and the gray plastic housing.
14. Carefully twist the screwdriver until the potentiometer releases from the cam drum shaft. Remove the ASZ… potentiometer.
Potentiometer Installation
1. Install the new ASZ… potentiometer by gently sliding the bushing over the cam drum shaft.
2. Align the potentiometer alignment screw hole with the hole in the gray plastic housing and install the potentiometer alignment screw. See Figures 17 and 17a.
3. The actuator position indicating pointer, located near the actuator gear end of the cam drum, must point to the “0” mark on the actuator position scale. See Figure 6. The scale is located on the cam drum nearest to the actuator gear end. Press and hold the black cam drum release button while manually rotating the cam drum.
4. If installing a potentiometer without gear, manually rotate the potentiometer pointer until the pointer is exactly in the “min” position. See Figure 17. Firmly tighten the black potentiometer cam attachment screw while manually holding the potentiometer pointer in alignment. Check the alignment again.
5. If installing a gear model potentiometer, manually rotate the potentiometer gear until the white line next to the “0” or “1” mark on the potentiometer gear face is exactly in alignment with the potentiometer gear alignment pointer. See Figure 17a. For counterclockwise (ccw) operation the line beside the “1” mark must exactly align with potentiometer gear alignment pointer. For clockwise (cw) operation the line beside the “0” mark must exactly align with potentiometer gear alignment pointer. Firmly tighten the black potentiometer cam attachment screw while manually holding the potentiometer gear in alignment. Check the alignment again.
6. Connect the bundled blue, black and brown potentiometer wires to the terminal block located on the ASZ… potentiometer board. See Potentiometer Installation and Figures 17 and 17a.
7. Re-install the white actuator-indicating dial by gently pressing it onto the potentiometer cam attachment screw. Align scale position “0” on the actuator position indicating dial with the dial pointer by rotating the dial in the clockwise direction to avoid loosening the potentiometer gear attachment screw. See Figure 6.
Siemens Building Technologies, Inc. Page 25
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007
Specifications
SQM5... Reversing Actuator
SQM5... Reversing actuator
Agency approvals UL, CSA, CE Operating voltage 24 Vac +10%-15%
110 Vac-15% to 120 Vac +10% 220 Vac-15% to 240 Vac +10%
Operating frequency 50 to 60 Hz Power consumption 20 VA Type of motor Reversing synchronous motor Duty cycle 100% Torque See Table 1. Maximum shaft torque AGA58.1 90 lb-in AGA58.2 200 lb-in AGA58.3 220 lb-in AGA58.4 270 lb-in AGA58.7 400 lb-in Timings See Table 1. Rotational range of operation SQM5x.xxxxxA models 0° to 160° SQM5x.xxxxxx3 models 0° to 90° SQM5x.xxxxxx4 models 0° to 135° SQMSx.xxxxxx6 models 0° to 160° Direction of rotation Reversible Shaft Selectable. See Table 2.
Custom versions on request Shaft disengagement Independent, cam and drive shaft Number of auxiliary switches
4 switches (standard, maximum 6) Limit switches 2 switches (standard) Electrical rating of auxiliary switches 7.5 (3) A, 250 Vac Mounting position Optional Ambient operating temperature -5°F to 140°F (-20°C to 60°C) Shipping temperature -58°F to 140°F (-50°C to 60°C) NEMA ratings NEMA 1, 2, 3, 3R, 3S, 5, 12, and 13 Connections
Switches Spade connectors Boards Screwed and spade connectors
Dimensions See Figures 28 through 31. Weight 7.3 lb (3.3 kg) Housing Aluminum pressure die casting Enclosure (cover) Lexan Motor Lock resistant Disengagements Manual for drive and cam shaft
Page 26 Siemens Building Technologies, Inc.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007
Specifications
SQM5... Reversing Actuator, Continued
Circuit Boards
Conduit connection Two removable inserts with two 1/2-inch NPSM threads. Each insert allows insertion of entire cable tree for easy servicing
Gears and bearings Maintenance-free Mounting Four 1/4"-20 UNC screws in bottom
Face mounting at gear side also possible
Adaptation to other actuator brands Screw pattern and shaft height Adaptation with AGA57... adapters See Table 2.
AGA56.1A97 Switch circuit board Operating voltage Voltage independent Operating frequency 50 to 60 Hz
AGA56.1A97
AGA56.41A…
AGA56.42A…
Auto/manual switch 2-position switch Manual toggle switch 3-position switch Ambient operating temperature -5°F to 140°F (-20°C to 60°C) Shipping temperature -58°F to 140°F (-50°C to 60°C) Weight 0.22 lb (0.1 kg) AGA56.41A… Electronic circuit boards Single potentiometer
ASZ... (1000 ohm) is required Operating voltage 24 Vac +10%-15% 110 Vac -15% to 120 Vac +10% 220 Vac -15% to 240 Vac +10% Operating frequency 50 to 60 Hz Ambient operating temperature -5°F to 140°F (-20°C to 60°C) Shipping temperature -58°F to 140°F (-50°C to 60°C) Input signal 4 to 20 mA Impedance Current input ≤300 Ω Zero adjustment MIN: 0 to 75% Span adjustment MAX: min 100% Auto/manual switch 2-position switch Manual toggle switch 3-position switch Weight 0.7 lb (0.33 kg) AGA56.42A… Electronic circuit boards Same specifications as AGA56.41A
except Input signal 0 to 135 ohm Impedance Current input ≤300 Ω Voltage input ≥100K Ω
Siemens Building Technologies, Inc. Page 27
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007
Specifications, continued
AGA56.43A…
AGA56.9A
ASZ... Potentiometers
AGA56.43A… Electronic circuit boards Same specifications as AGA56.41A
except: Input signal 0 to 10 Vdc Impedance Voltage input ≥100K Ω
AGA56.9A… Multi function electronic Single potentiometer circuit boards ASZ... (1000 ohm) is required
Operating voltage 24 Vac +10%-15% 110 Vac -15% to 120 Vac +10% 220 Vac -15% to 240 Vac +10%
Operating frequency 50 to 60 Hz Input signals 4 to 20 mA
0 to 20 mA 0 to 10 Vdc 0 to 135 ohm Impedance
Current input ≤300 Ω Voltage input ≥100K Ω Output signals 4 to 20 mA
0 to 20 mA 0 to 10 Vdc
Max output load Current output <600 ohm Voltage output > 1.5K ohm Zero adjustment MIN: 0 to 75% Span adjustment MAX: min-100% Split ranging (SHIFT) 4 to 20 mA on terminal ZF Input signal override (POS) Line voltage (... Vac) on terminal P
adjust with POS potentiometer Ambient operating temperature -5°F to 140°F (-20°C to 60°C) Shipping temperature -58°F to 140°F (-50°C to 60°C) Auto/manual switch 2-position switch Manual toggle switch 3-position switch Weight 0.7 lb (0.33 kg) ASZ... Potentiometers Versions Single and double potentiometer Resistor values See Table 2 and Data Sheet 7921. Hysteresis < 0.3% related to drive shaft
Page 28 Siemens Building Technologies, Inc.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007
Dimensions
The first dimension given is measured in inches. Millimeters are shown in parentheses.
5-1/4 (133)
2-5/8
(67)
EA0522R1
1/16
(1)
ALLOW 3.5" SPACE FOR
COVER REMOVAL
4-7/16
(113)
1/4"-20
UNC
7-1/16
(180)
7-1/16
(180)
1-3/16
(30)
3/8
(10)
3-1/8
(80)
5/8
(16)
1/8
(3.5)
5-3/16
(132)
Pg 13.5 / 1/2"
NPSM
1-7/16
(36)
1-3/16
(30)
1/4 (6)
M 8
6-7/16
EA0542R2
5/16 (8.5)
(164)
5/16 (7.5)
Figure 28. SQM5x.xxxRxx Dimensions.
Siemens Building Technologies, Inc. Page 29
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007
Dimensions, Continued
6-7/16
11/16
(18)
(164)
4-1/16
(103.3)
9/16
(14.5)
5-5/16
(135)
4-3/4
(120.65)
4-7/16
(113)
1/8
(3)
EA0519R2
7/16 (11)
3-1/8
(80)
2-3/8 (60.4)
AGA57.3
4-7/16
(113)
C
L
4 X 1/4
(7)
Figure 29. Mounting Bracket AGA57.3.
7-5/16
(185)
5/16
(7.94)
1-3/8
(35)
(57.15)
5/16
(8.73)
2-1/4
(7.94)
5/16
(8.73)
5/16
6-7/16
(164)
AGA57.4
C
L
1-9/16
(40)
3-1/8
(80)
4 X 1/4
(7)
4-7/8
(123.8)
2-1/2
(63.5)
3-1/8
(80)
(101.5)
4-7/16
(113)
4
5/16
(7.94)
EA0520R2
1/2
(12.5)
13/16
(20.3)
1-5/8
(42)
2-3/8
(60.64)
1-1/2 (38.1)
1/8
(3)
2
(50.8)
1-11/16
(43)
4545
13/16 (20.3)
All non-sized holes
O 5/16 (7.62)
Figure 30. AGA57.4 Mounting Bracket.
Page 30 Siemens Building Technologies, Inc.
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007
Dimensions, Continued
0.31 (8)
7.09
(180)
AGA58.1
AGA58.2
1
(25.5)
0.79 (20)
1
(25.5)
0.79 (20)
GEAR SIDE
0.35 (9)
0.44
(11.2)
0.35 (9)
0.52
(13.2)
0.39 (10)
0.47 (12)
0.12 (3)
0.12 (3)
0.35 (9)
0.375 (9.5)
M5 x 9
8-32 UNC
28 x 0.56
(14.2)
0.35 (9)
0.27
(6.9)
0.42
(10.6)
0.05
(1.3)
0.81
(20.5)
0.67 (17)
AGA58.3
AGA58.4
AGA58.7
0.85
(21.5)
0.78
(19.8)
(10.6)
0.42
0.05 (1.3)
1.71
(43.5)
1.10 (28)
0.43 (11)
0.27
(6.9)
M5 x 9
8-32 UNC
28 x 0.56
(14.2)
0.20 (5)
0.60
(15.1)
0.35 (9)
0.375 (9.5)
0.55 (14)
0.20 (5)
EA0543R1
Figure 31. Shaft Dimensions.
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Other product or company names mentioned herein may be the trademarks of their respective owners. © 2007 Siemens Building Technologies, Inc.
Siemens Building Technologies, Inc.
1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 U.S.A.
Your feedback is important to us. If you have comments about this document, please send them to SBT_technical.editor.us.sbt@siemens.com
Document No.155-517P25
Country of Origin: US
Page 31
Loading...