Siemens SMP Switchboards User Manual

SMP Switchboards
Selection and application guide
www.siemens.ca/powerdistribution
Switchboards
Contents
Sentron SMP Switchboards
Type SMP
Sentron® SMP Switchboards
Construction Details
Simplified system design.
A typical SMP switchboard consist of a floor mounted, wall supported ser­vice section, and a distribution section. The wireway can also be added where required by the local utility or if addition­al cable termination space is required.
Wireways are modular to allow flexibility.
The wireway is available in 2 depths to suit customer needs. Wireway has split front doors as standard with optional hinged doors. The lug pads are standard NEMA hole pattern and accept up to 5 mechanical lugs or 6 compression lugs.
90oC rated wireway.
The termination temperature for main incoming cables can be sized at 90oC for bussed pull sections.
Service Entrance Sections house a variety of equipment.
b
Service Entrance Sections.
Service sections can be fed directly from overhead by cable.
Service entrance sections equipped for bottom feed will accept cable from underground directly into the service section.
b
Utility Metering In addition to the main device, the service section contains utility metering provisions. “Cold” metering provisions (CT’s on the load side of the main device) are furnished. The CT’s are provided by the utility company. The compartment will be built to utility company standards, with hinged doors and provisions for utility metering equipment.
Distribution Sections have ample wiring room and front accessibility.
Generous top or bottom gutters have been created by locating the bus-link in the top or bottom of the distribution section, so there’s ample room to run cables into the distribution section and make connections.
Standard bolted covers allow complete access to load conductors. Future flexibility comes standard in the Siemens SMP switchboard. The distribution section can accommodate any combination of panel mounted devices, including MCCBs and fusible disconnect switches.
Operating temperatures are in accordance with CSA Standards
Bus bars are available in standard tin-finished aluminum or optional silver-finished copper. Standard bus is sized on the basis of heat rise criteria, in accordance with CSA C22.2 #31. All bus bars are sized to limit heat rise to 65°C above an ambient temperature of 40°C.
Construction
Bus-Link Connections are accessible from the front.
The Bus-Link can be bolted from the front of the switchboard. Each bus-link is attached by grade five bolts to assure solid joints between sections, and to maintain full bus ampacity through the joint.
To make installation and servicing of the bus-link easier, all phase and neutral busses are stacked one above the other.
Cable Terminals
Screw mechanical connectors (lugs) are provided as standard equipment.
b
User Metering The service section provides space for the Siemens Digital Meter with remote display, and it’s associated components.
b
Main protective device The MCCB is mounted individually so that it can be located quickly in an emergency. SMP switchboards will accommodate different types of main circuit breakers. Selection depends on the characteristics of your individual electrical system.
2
Sentron® SMP Switchboards
Power and Distribution
SMP Switchboard Introduction
Whether the design is for a 240V AC, 400 ampere system; a 600V AC, 1200 A ampere system; or something in between, Siemens Sentron Switchboards should be considered. Every aspect of design has been aimed at improving layout convenience, reducing installation costs, and minimizing the impact and cost of system changes. These switchboards provide the space saving construction and service flexibility necessary in systems for light industrial plants, retail strip malls, and commercial buildings.
Service entrance sections of the SMP accepts a wide range of Sentron Molded Case Circuit Breakers as main disconnect devices.
The SMP switchboard is designed for special configurations. It can be equipped with incoming and outgoing cable/conduit connections, supplied with metering and other special features.
The distribution sections of all Sentron Switchboards are designed with improved wiring space and greater accessibility. They’re also designed for easier installation and maintenance. Conveniently located bus-link without compromising useful wiring gutter space, and standard bolted gutter covers offer complete access to load conductors. Front accessibility to bus and protective devices makes adding or replacing circuit breakers or switches quick and easy.
SMP Switchboard Features and Ratings b
Main bus rated up to 1200 ampere.
b
Rear of all sections aligned so that switchboard can be floor mounted and secured against the wall.
b
Front connected and front accessible.
b
Main devices – individually mounted.
Molded Case Breaker: 400-1200 amps.
b
Branch Devices – panel mounted. Molded Case Breaker: 15–1200 amps fixed. Quick-Make Quick-Break Fusible Switch: 30 - 600A
600 Volts AC Maximum 1200 Ampere Mains 1200 Ampere Maximum Branch CSA Short Circuit Rating — 65,000A IR Maximum
CSA Certified To: CAN/CSA-22.2 No. 31-14
CSA File #LR 153416 (013076)
SMP Specifications (Table 1)
SMP Switchboard
Enclosure Type
Dimensions Main or Distribution Wireway
Volts 600V Max
Amperes 400-1200A
Bus Type
Bus Bracing
Interrupting Capacity
Entry Cable only (top or bottom)
Main Device
Branch Devices (Unit Space)
Metering Devices
Other Options
Type 1 Type 2 (dripproof & sprinklerproof) Optional: Dripshield
38” W x 90” H x 12.75” Dp 24” W x 90” H x 12.75” Dp or 25.5” Dp
Aluminum (tin plated) Copper (silver finished) optional
50 KA 65 KA (optional)
50 KA 65 KA (optional)
MCCB 400-1200A
b
80% Rated
b
100% Rated (option)
52.5” in Main with Distribution Section, or
22.5” in MUD Section, or 60” in Distribution Section
Siemens Digital Metering with Remote Display SEM3 Embedded Metering
SPD Units Sill Channels (1.5”) Lifting Hooks
Main and Distribution Section Dimensions (Table 2)
Switchboard Type Access
SMP Front 90” (2286) 38” (965) 12.75” (324)
Dimensions - Inches (mm)
H
W D
General
a
Only available as a Wireway.
3
Sentron® SMP Switchboards
Power and Distribution
Protective Devices - Molded Case Circuit Breakers
Standard
Breakers are designed for commercial, industrial, institutional and other heavy duty applications. They are rated up to 600V AC and 250V DC. Their interrupting ratings are higher than normal duty breakers.
High Interrupting Breakers are designed for heavy duty applications where the interrupting requirements exceed the ratings of heavy duty breakers. They are rated up to 600V AC.
Current Limiting Molded case breakers incorporate the exclusive I-T-E blow-apart interruption principle. They meet the CSA requirements for current-limiting breakers. Current-limiting circuit breakers can limit the let-through I the I2t of one-half cycle wave of the symmetrical prospective current without any fusible elements when operating within their current-limiting range.
Main Breaker Selection (Table 3)
Maximum Interrupting Rating (kA)
Amperage Rating
400
600
800
1200
Breaker Type Trip Type
JXD6
JD6 65 35 25 200, 225, 250, 300, 350, 400
HJD6 100 65 35 200, 225, 250, 30 0, 350, 400
HHJD6 200 100 50 200, 225, 250, 300, 350, 400
CJD6
SJD6
SHJD6 10 0 65 35 200, 300, 40 0
SCJD6 200 150 10 0 200, 300, 40 0
LXD6
LD6 65 35 25 250, 300, 350, 400, 450, 500, 600
HLD6 100 65 35 250, 300, 350, 400, 450, 500, 600
HHLD6 200 100 50 250, 300, 350, 400, 450, 500, 600
CLD6
SLD6
SHLD6 10 0 65 35 300, 400, 50 0, 600
SCLD6 200 150 10 0 300, 400, 50 0, 600
MXD6
MD6 65 50 25 500, 600, 700, 800
HMD6 100 65 50 500, 600, 700, 800
CMD6
SMD6
SHMD6 10 0 65 50 600, 700, 800
SCMD6 20 0 100 65 600, 700, 800
NXD6
ND6 65 50 25 800, 900, 1000, 1200
HND6 100 65 50 800, 900, 1000, 1200
CND6 200 10 0 65 800, 900, 1000, 1200
SND6
SHND6 100 65 50 800, 1000, 1200
SCND6 200 10 0 65 800, 1000, 1200
Thermal Magnetic
Electronic (Solid State)
Thermal Magnetic
Electronic (Solid State)
Thermal Magnetic
Electronic (Solid State)
Thermal Magnetic
Electronic (Solid State)
240V 480V 600V
65 35 25 200, 225, 250, 300, 350, 400
200 150 10 0 200, 225, 250, 300, 350, 40 0
65 35 25 200, 300, 400
65 35 25 450, 500, 600
200 150 10 0 450, 500, 600
65 35 25 300, 400, 500, 600
65 50 25 500, 600, 700, 800
200 100 65 500, 600, 700, 800
65 50 25 600, 700, 800
65 50 25 800, 900, 1000, 1200
65 50 25 800, 1000, 1200
2
t to a value less than
Available Trip Values
Selection
Branch Breaker Gutter Dimensions
For 38”W Distribution Section (Table 5)
3.75” (95)
3.75” (95)
3.75” (95)
3.75” (95)
5” (127)
8.75” (222)
8.75” (222)
6.25” (159)
10" (254)
12” (305)
8.75" (222)
13.98” (355)
11.62” (295)
10” (254)
7.61”(193)
8.75” (222)
8.25” (210)
10.90” (276)
11.76” (299)
7.92” (201)
8” (203)
13.42” (341)
12” (305)
15.5” (393)
13” (330)
12” (305)
13” (330)
14.0” (356)
A A
B B
C C
D D
E E
F
G
H
J
K
L
M
N
O
P
Q
R
F
G
H
K
L
5” (127)
5” (127)
8.75” (222)
6.25” (159)
3.75” (95)
5”
(127)
4
Sentron® SMP Switchboards
Power and Distribution
Branch Circuit Breaker Selectiona (Table 4)
Breaker Frame Rating
100
125
150
225
250
400
600
800
1200
Trip Type Breaker Type Poles Trip Amperage
Thermal Magnetic
Ground Fault Circuit Interrupter
Arc Fault Circuit Interrupter
BL BLH HBL 1, 2, 3 15, 20, 25, 30, 40, 50, 60, 70, 80, 90, 100 3.75" (95)
e
BQD6 BLE (GFCI) 1, 2 15, 20, 30, 40, 50, 60 3.75" (95)
BLF (GFCI) 1, 2 15, 20, 30, 40, 50, 60 3.75" (95) BLHF (GFCI) 1, 2 15, 20, 30, 40, 50, 60 3.75" (95) BAF (AFCI) 1 15, 20 3.75" (95)A 14" (356) 10 / / BAFH (AFCI) 1 15, 20 3.75" (95)A 14" (356) 22 / /
1, 2, 3 1, 2, 3
1, 2, 3 15, 20, 30, 40, 50, 60, 70 3.75" (95)
ED2 1, 2, 3 15, 20, 30, 40, 50, 60, 70, 80, 90, 100 3.75" (95) ED4 1, 2, 3 15, 20, 30, 40, 50, 60, 70, 80, 90, 100, 110, 125 3.75" (95) ED6 1, 2, 3 15, 20, 30, 40, 50, 60, 70, 80, 90, 100, 110, 125 3.75" (95)
HED4 1, 2, 3 15, 20, 30, 40, 50, 60, 70, 80, 90, 100, 110, 125 3.75" (95) Thermal Magnetic
CED6 2, 3 15, 20, 30, 40, 50, 60, 70, 80, 90, 100, 110, 125 3.75" (95)3.75" (95)E 7.61" (193) 200 200 100
HEB 2, 3 15, 20, 30, 40, 50, 60, 70, 80, 90, 100, 110, 125 3.75" (95)
NGB 1, 2, 3 15, 20, 25, 30, 40, 50 ,60, 70, 80, 90, 100, 110, 125 3.75" (95)
NGB2 1, 2, 3 15, 20, 25, 30, 40, 50 ,60, 70, 80, 90, 100, 110, 125 3.75" (95)
HGB2 1, 2, 3 15, 20, 25, 30, 40, 50 ,60, 70, 80, 90, 100, 110, 125 3.75" (95)
LGB2 1, 2, 3 15, 20, 25, 30, 40, 50 ,60, 70, 80, 90, 100, 110, 125 3.75" (95)
(Solid State)
LDG 3 60, 100, 150 5" (127) H 10.9" (276) 200 100 18
NDG 3 60, 100, 150 5" (127) H 10.9" (276) 65 35 18
Electronic
QR2 2, 3 100, 110, 125, 150, 175, 200, 225 5" (127) 5" (127) F 8.75" (222) 10 / / Thermal Magnetic
QRH2 2, 3 100, 110, 125, 150, 175, 200, 225 5" (127) 5" (127) F 8.75" (222) 25 / /
HQR2 2, 3 100, 110, 125, 150, 175, 200, 225 5" (127) 5" (127) F 8.75" (222) 65 / /
HQR2H 2, 3 100, 110, 125, 150, 175, 200, 225 5" (127) 5" (127) F 8.75" (222) 100 / /
Thermal Magnetic
Electronic (Solid State)
FXD6, FD6 2, 3 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 5" (127) 5" (127) G 8.25" (210) 65 35 22
HFD6 2, 3 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 5" (127) 5" (127) G 8.25" (210) 100 65 25
CFD6 2, 3 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 5" (127) J 11.76" (299) 200 200 100
NFG 3 100, 150, 250 5" (127) H 10.9" (276) 65 35 18
LFG 3 100, 150, 250 5" (127) H 10.9" (276) 200 100 25
JXD6, JD6 2, 3 200, 225, 250, 300, 350, 400 8.75" (222) 8.75" (222) K 7.92" (201) 65 35 25 Thermal Magnetic
HJD6 2, 3 200, 225, 250, 300, 350, 400 8.75" (222) 8.75" (222) K 7.92" (201) 100 65 35
HHJD6 2, 3 200, 225, 250, 300, 350, 400 8.75" (222) 8.75" (222) K 7.92" (201) 200 100 50
CJD6 2, 3 200, 225, 250, 300, 350, 400 8.75" (222) N 12" (305) 200 150 100
SJD6 3 200, 300, 400 8.75" (222) M 13.42" (341) 65 35 25
Electronic (Solid State)
SHJD6 3 200, 300, 400 8.75" (222) M 13.42" (341) 100 65 35
SCJD6 3 200, 300, 400 8.75" (222) N 12" (305) 200 150 100
NJG 3 250, 400 6.25" (159) 6.25" (159) L 8" (203) 65 35 25
LJG 3 250, 400 6.25" (159) 6.25" (159) L 8" (203) 200 100 25
LXD6 2, 3 450, 500, 600 8.75" (222) M 13.42" (341) 65 35 25
Thermal Magnetic
LD6 2, 3 250, 300, 350, 400, 450, 500, 600 8.75" (222) M 13.42" (341) 65 35 25
HLD6 2, 3 250, 300, 350, 400, 450, 500, 600 8.75" (222) M 13.42" (341) 100 65 35
HHLD6 2, 3 250, 300, 350, 400, 450, 500, 600 8.75" (222) M 13.42" (341) 200 100 50
CLD6 2, 3 450, 500, 600 8.75" (222) N 12" (305) 200 150 100
Electronic (Solid State)
SLD6 3 300, 400, 500, 600 8.75" (222) M 13.42" (341) 65 35 25
SHLD6 3 300, 400, 500, 600 8.75" (222) M 13.42" (341) 100 65 35
SCLD6 3 300, 400, 500, 600 8.75" (222) N 12" (305) 200 150 100
MXD6 2, 3 500, 600, 700, 800 10" (254) P 13" (330) 65 50 25 Thermal Magnetic
MD6 2, 3 500, 600, 700, 800 10" (254) P 13" (330) 65 50 25
HMD6 2, 3 500, 600, 700, 800 10" (254) P 13" (330) 100 65 50
CMD6 2, 3 500, 600, 700, 800 10" (254) P 13" (330) 200 100 65
Electronic (Solid State)
SMD6 3 600, 700, 800 10" (254) Q 12" (305) 65 50 25
SHMD6 3 600, 700, 800 10" (254) Q 12" (305) 100 65 50
SCMD6 3 600, 700, 800 10" (254) Q 12" (305) 200 100 65
NXD6 2, 3 800, 900, 1000, 1200 10" (254) P 13" (330) 65 50 25 Thermal Magnetic
ND6 2, 3 800, 900, 1000, 1200 10" (254) P 13" (330) 65 50 25
HND6 2, 3 800, 900, 1000, 1200 10" (254) P 13" (330) 100 65 50
CND6 2, 3 800, 900, 1000, 1200 10" (254) P 13" (330) 200 100 65
SND6 3 800, 1000, 1200 10" (254) Q 12" (305) 65 50 25 Electronic
(Solid State)
SHND6 3 800, 1000, 1200 10" (254) Q 12" (305) 100 65 50
SCND6 3 800, 1000, 1200 10" (254) Q 12" (305) 200 100 65
15, 20, 25, 30, 40, 50, 60, 70, 80, 90, 100 15, 20, 25, 30, 40, 50, 60, 70, 80, 90, 100
Selection
Mounting Height Inches (mm) Max IC Rating (kA)
Single Twin Gutter
— —
3.75" (95)
3.75" (95)
3.75" (95)
3.75" (95)
3.75" (95)
3.75" (95)
A
14" (356)
A
14" (356)1022//
A 14" (356) 65 / /
A 14" (356) 65 / 10 A 14" (356) 10 / /
A 14" (356) 10 / / A 14" (356) 22 / /
D 10" (254) 10 / /
D 10" (254) 65 18 /
D 10" (254) 100 18 18
D 10" (254) 100 65 30
C 11.62 (295) 100 65 25
B 13.98" (355) 100 25 14
B 13.98" (355) 100 25 14
B 13.98" (355) 100 35 22
B 13.98" (355) 100 65 25
f
240V 480V 600V
/ /
a
Space includes housing frame plate with blank cover plate. Provision includes all necessary mounting hard­ware, less circuit breaker, and includes housing frame cover plate with breaker handle opening.
1 to 6 poles may be mounted in 3.75” (95) of unit space
Accessories such as shunt trips on three pole breakers require 6.25” (159) of unit space.
Ground fault is not available on branch Sensitrip breakers.
e
Also 10kA at 600Y/347 Volts.
f
Refer to Table 5 for layout dimensions.
5
Sentron® SMP Switchboards
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
(
)
Power and Distribution
Protective Devices - Fusible Disconnects
Fuse Selection
The Proper Fuse Type for the Application is Selected Using the Following Parameters:
b Voltage Requirements b Conductor Ampacity b Horsepower Requirements b Maximum Available RMS Fault Current b CSA Fuse Class
Branch Switch Gutter Dimensions For 38W Distribution Section (Table 8)
7.5"(191
7.5"(191
7.5"(191
10.0"(254
10.0"(254
10.0" (254)
8.0"(203
9.25"(235
30/30A VK Switch
60/60A VK Switch
100/100A VK Switch
200/200A VK Switch
30/30A VB Switch
60/60A VB Switch
100/100A VB Switch
200/200A VB Switch
400A thru 600A
VB Switch
6.25"(159
6.25"(159
7.5"(191
7.5"(191
7.5"(191
7.5"
10.0"(254
15.0"(381
10.0" (254)5.0"(127
Branch Switches 600V Maximum (Table 11)
Rating Max Fusing Mounting Ampere Voltage Height 38”W
191
30/30A & 60/60A (VK)
10 0/100A (VK) 200/200A (VK) 30/30A & 60/60A (VB) 600V Class J 7.5” (190) 100/100A (VB) 600V Class J 7.5” (190) 200A (VB) 600V Class J 10.0” (254) 400A & 600A (VB) 60 0V Class J 15.0” (381)
Maximum VB HP Ratings (Table 6)
Volts
Amp 3 Phase Single Phase
Rating 240 480 600 240 30 7.5 15 20 3 60 15 30 50 10 100 30 60 50 15 200 60 125 50 – 400 50 50 50 – 600 50 50 50
Maximum VK HP Ratings (Table 9)
Volts
Amp 3 Phase Single Phase
Rating 240 480 600 240 30 7.5 15 20 3 60 1.5 30 50 10 100 30 50 75 15 200 60 125 150 15
e
600V Class J 6.25” (159)
e
60 0V Class J 7.5” (190)
e
600V Class J 10.0” (254)
Selection
Branch Switch Connectors (Table 10)
Switch Ampere Rating Wire and Cable Range
30 (1)—#14–#4 AWG (Cu or Al) 60 (1)—#14–#4 AWG (Cu or Al) 100 (1)—#10–#1/0 AWG (Cu or Al)
200 (1)—#6 AWG-350kcmil (Cu or Al) 40 0 (1)—#1/0 AWG-750 MCM OR (2)—#1/0 AWG-250 MCM (Cu or Al) 60 0 (1)—#1/0 AWG-750 MCM OR (2)—#1/0 AWG-250 MCM (Cu or Al)
Switch Interrupting Ratings
Interrupting Rating
Switch Type
(kA)
240V 480V 600V
VB 20 0 10 0 10 0
VK 20 0 20 0 20 0
Gutters (Table 12)
End Gutters Side Gutters Ampere Minimum - Minimum ­Rating Inches (mm) Inches (mm)
400 12” (305) 7.9” (201)
600 12” (305) 7.9” (201)
Switch Accessories (Table 13)
Fuse Pullers (VK)
30 or 60 Amp FP2
100 Amp FP3
200 Amp FP4
Cat. No.
CSA Fuse Classes (Table 14)
Class Amperes Volts (AC) I2t, Ip (Let-Thru) Circuits
H Standard Code 1-600A 250 and 600V Less than
or less 10,000A available
a
K
Fast Acting 1-600A 250 and 600V Feeder circuits
(One time) or less
J Fast Acting 1-600A 600V or less Ip and I2t-Low Feeder circuits
and Time Delay (motor load small %) Motor circuits
RK1 Fast Acting 1/10-600A 600V or less I2t-Slightly > J Feeder circuits
and Time Delay 250V or less Ip-Slightly > J Motor circuits
RK5 Fast Acting 1/10-600A 600V or less I2t- > RK-1 Feeder circuits
and Time Delay 250V or less Ip- > RK-1 Motor circuits
C Moderate 2-600A 600V or less I2t- < RK-5 Motor circuits
(FORM II)
Delay Ip- < RK-5
T Fast Acting 1-600A 300 and 600V I2t-Low Non-motor loads
or less Ip-Low
L Fast Acting 601-5000A 600V or less I2t-Low Feeder circuits
and Time Delay motor loads Motor circuits
a
Fuse clips do not prohibit the use of Class H type fuse
in switch.
Refer to Siemens for single phase and DC horsepower
requirements.
Ratings are based on UL test procedure.
Connector range applies to VB Switches only.
5
Not suitable for use in distribution space in main section.
6
Sentron® SMP Switchboards
Power and Distribution
Special Construction, Additions and Accessories
When required, special constructions or additions to standard Switchboards may be specified for all factory- assembled Power and Distribution Switchboards. Listed below are those available for Type SMP Switchboards.
1. Enclosure Type
38” Enclosure Types
Type 1
Type 2 (dripproof & sprinklerproof)
Optional: Dripshield
2. Wireway Options
24”W x 90”H x 12.75” Dp
24”W x 90”H x 25.5” Dp
Hinged Door Door Covers Hinged Door Door Covers
3. Painted Finish
Touch-Up Paint (ASA61, Light Grey)
12 oz. aerosol can, Cat. # TUP-61
4. Miscellaneous Accessories
Nameplate - laminated and engraved
5. Bus-Link (One Set Per Panel)
Ampere Unit Space Occupied in MUD -
Rating Inches (mm)
400-1200 Consult Factory
6. Grounding of SMP Switchboard
Non-Insulated Equipment Ground Bus
Including Ground Lug Continuous Solid Copper Ground (optional)
7. Main Bus
Standard Main bus and Neutral bus are
tin plated aluminum or silver finished copper (option).
8. Lugs
For Main Device and Neutral
For Main Breakers please see SpeedFax
section #6
Neutral - please consult factory
9.SPD Modules
Sentron TPS3 05
100KA
150KA
200KA
250KA
300KA
Options: Surge Counter Remote Monitor
10. Circuit Breaker Accessories Handle Blocking Device Blocks handle in either the “ON” or “OFF” position. Available for:
Breaker Type Cat. Number
BL, BLH, HBL, BQ, BQH, HBQ
All BQD, GB BQDHBD
All QR HPLQR
All BQD, NGB, NGB2, HGB2, LGB2
All ED E2HBL
All FD FD6HB1
All JD, LD JD6HBL
All MD, ND, PD MN6BL
Padlocking Device — Padlocks in “OFF” position. Available for:
Breaker Type Cat. Number
BQ, BQH, BL, BLH, HBL ECQLD3
One Pole BL, BLF, BE, BAF
Two-Pole BL, BLF, BE ECPLD2
All QR HPLQR
All BQD, NGB, NGB2, HGB2, LGB2
All ED ED2HPL
All FD FD6PL1
All JD, LD JD6HPL
All MD, ND, PD, RD MN6PLD
Handle Extensions - For replacement (one extension shipped with breaker)
Breaker Type Cat. Number
All MD, ND, PD EX11
Ground Fault Sensing Relay Kit Equipment Protection (30 mA)
For Use with Number Catalogue Number Breaker Types of Poles Description
ED4, ED6, HED4 1, 2, 3
Shunt Trip on Main or Branch
Description Cat. Number
BL, BQD6 (branch only) ED2, ED4, HED4 (branch only) All others through 1200A
ECQL1
BQDHBD
ECPLD1
BQDPLD
See breaker section of this catalogue.
See breaker portion of this catalogue
Selection
VK Switch For Use With FPP6 Panelboards
30/30 VK23611JP 6.25 (159)
60/60 VK23622JP 6.25 (159)
100/100 VK33633JP 7.5 (90)
200/200 VK73644JP 10 (254)
VB Switch For Use With VB6 Panelboards
30/30 V7E3611JP 7.5(190)
60/60 V7E3622JP 75(190)
100/100 V7E3633JP 7.5(190)
200 V7F3604JP 10(254)
400 V7H3605JP 15(381)
600 V7H3606JP 15(381)
7
Sentron® SMP Switchboards
A. Scope
Furnish and install, as shown on the plans, a secondary distribution switchboard, as specified herein, for the system indicated below:
 120/208V  3-phase  3-wire  347/600V  4-wire  600V
B. Configuration
The switchboard enclosure shall be of bolted construction:
Type 1 indoor. Type 1 with dripshield (optional). Type 2.
Switchboard shall be bolted together to form one metal enclosed rigid switchboard. Switchboard shall include all protective devices and equipment as listed on drawings with necessary interconnections, instrumentation and control wiring. All groups of control wires leaving the switchboard shall be provided with terminal blocks with suitable numbering strips. The switchboard shall have space or provisions for future expansion as noted on the plans. Switchboard shall be constructed and certified in accordance with CSA
22.2.31 standards and shall be Siemens type (SMP) or approved equal. Individual sections shall be front accessible, not less than 12.75” (324) deep, and the rear of all sections shall align. Distribution sections shall be designed to accommodate the intermixing of Molded Case Breakers and Fusible Disconnects in the same distribution interior.
C. Bus Requirements
The bus shall be tin-finished aluminum silver-finished copper (option) of
sufficient size to limit the temperature rise to 65°C. The bus shall be braced for 50,000 or 65,000 (option) amperes symmetrical and supported to withstand mechanical forces exerted during short circuit conditions when directly connected to a power source having the indicated available short circuit current.
D. Incoming Service
Overhead or Underground Service: Cable Entry This section shall be bussed and sealable per local utility requirements. Screw-type mechanical lugs, compression lugs to terminate, aluminum, copper cable, shall be __________ kcmil, and ___ cables per phase. Main breaker standard aluminum mechanical lugs suitable for aluminum or copper. (No wireway)
E. Metering Service Section
The service section shall be designed for the system parameters indicated in section “A” above. The metering service section shall have a Utility Metering compartment per utility requirements.
User metering as indicated below and as shown on plans. Main (service) section: Siemens Digital metering with remote display _______ current transformer(s) _______ /5 or suitable rating SEM3 Embedded Metering Ground fault Protection (3-Phase, 4-Wire): Furnish and install on the service equipment and/or switchboard a Ground Fault protection system and indication equipment as specified herein and as shown on drawings in accordance with CEC Section 14-102. All new Ground Fault Protection and Indication equipment shall be factory installed, wired and tested by the switchboard manufacturer.
F. Switchboard SMP Guide Specification
The complete switchboard shall be finished with light grey, ASA-61 paint. Each switchboard main section shall have a metal nameplate permanently affixed to it, listing the following information:
b Name of manufacturer b System voltage b Ampacity b Type b Manufacturer’s shop order number and
date b Each section of switchboard shall bear a CSA certification mark and a short circuit rating label. The switchboard shall be per the arrangement below.
F1. Switchboard Type Panel-Mounted, Front Accessible.
Switchboard shall be of Siemens SMP type, or approved equal. Individual sections shall be front accessible, floor mounted rear supported, not less than 12.75” (324) deep, and rear, of all sections shall align. Incoming line termination, main device connection and all bolts used to join current-carrying parts shall be installed so as to permit servicing from the front only so that no rear access is required. The branch devices shall be front removable and panel mounted with line and load side connections front accessible.
G. Main Protective Devices
The main protective device, to be installed in the main device section, shall be as indicated below:
G1. Molded Case Circuit Breaker
Molded case circuit breaker shall be of the quick-make, quick-break, trip-free,
(standard) (High Interrupting) (Current Limiting)  (solid state
Sensitrip III) type. It shall be _______ frame (3-pole) (240V) (600V) breaker with a trip current rating of:
400A, 600A, 800A, 1000A 1200 A
a
of an interrupting capacity
a
,
Specification
of not less than _______ amperes RMS symmetrical at the system voltage. The following accessory options are to be included:
 Shunt trip  Ground fault relay  Long time (Sensitrip III only)  Long time delay (Sensitrip III only)  Short time (Sensitrip III only)  Short time delay (Sensitrip III only)  Integral ground fault (Sensitrip III only)  Other_______ (list)
H. Branch Protective Devices (Select as necessary)
All molded case circuit breakers, and fusible disconnect units used as a protective device in a branch circuit will meet the requirements of the appropriate paragraph below
H1. Molded Case Circuit Breaker
Molded case circuit breakers shall be of quick-make, quick-break, trip-free (thermal magnetic type) (current limiting) (solid state) with frame, trip and voltage rating, either 2-pole or 3-pole, as indicated on the plans. All breakers shall have an interrupting capacity of not less than _______ amperes RMS symmetrical at the system voltage. All breakers shall be removable from the front of the switchboard without distributing adjacent units. The switchboard shall have space or provisions for future units shown on the plans.
H2. Current Limiting Circuit Breaker
Current limiting circuit breakers shall provide inverse time delay, instantaneous circuit protection, and also limit the let­through I2t to a value less than I2t of one-half cycle wave of the symmetrical prospective current without any fusible elements. Breakers shall have an interrupting capacity of not less than _______ ampere RMS symmetrical at the system voltage.
H3. Fusible Disconnect
Fusible disconnects shall be quick-make, quick-break units utilizing the double-break principle of circuit rupturing to minimize arcing and pitting and shall conform to the ratings shown on the plans. Each disconnect shall have an individual door over the front, equipped with a voidable interlock that prevents the door from being opened when the switch is in the ON position unless the interlock is purposely defeated by activation of the voiding mechanism. All disconnects shall have externally operated handles. Disconnects shall be equipped with Class J (standard), Class R rejection type, Class L (standard), Class T fuse holders as indicated on the plans suitable for application on system with _______ amperes symmetrical available fault current.
a
Ground fault protection required, per CEC section 14-102 when “the current is O 1000A at 60 0 volts.”
8
Siemens Canada Limited
Low Voltage & Products 1577 North Service Road East Oakville, ON L6H 0H6 Canada
Customer Interaction Centre
Tel: 1 (888) 303-3353 cic.ca@siemens.com
Order number: SI-LP-1668
www.siemens.ca/powerdistribution
Loading...