Construction Details Features 2
Features 3
Specification 8
Sentron® SMP Switchboards
Construction Details
Simplified system design.
A typical SMP switchboard consist of
a floor mounted, wall supported service section, and a distribution section.
The wireway can also be added where
required by the local utility or if additional cable termination space is required.
Wireways are modular to allow
flexibility.
The wireway is available in 2 depths to
suit customer needs. Wireway has split
front doors as standard with optional
hinged doors. The lug pads are standard
NEMA hole pattern and accept up to 5
mechanical lugs or 6 compression lugs.
90oC rated wireway.
The termination temperature for main
incoming cables can be sized at 90oC
for bussed pull sections.
Service Entrance Sections house a
variety of equipment.
b
Service Entrance Sections.
Service sections can be fed directly from
overhead by cable.
Service entrance sections equipped
for bottom feed will accept cable from
underground directly into the service
section.
b
Utility Metering
In addition to the main device, the
service section contains utility metering
provisions. “Cold” metering provisions
(CT’s on the load side of the main
device) are furnished. The CT’s are
provided by the utility company. The
compartment will be built to utility
company standards, with hinged doors
and provisions for utility metering
equipment.
Distribution Sections have ample
wiring room and front accessibility.
Generous top or bottom gutters have
been created by locating the bus-link in
the top or bottom of the distribution
section, so there’s ample room to run
cables into the distribution section and
make connections.
Standard bolted covers allow complete
access to load conductors. Future
flexibility comes standard in the
Siemens SMP switchboard. The
distribution section can accommodate
any combination of panel mounted
devices, including MCCBs and fusible
disconnect switches.
Operating temperatures are in
accordance with CSA Standards
Bus bars are available in standard
tin-finished aluminum or optional
silver-finished copper. Standard bus is
sized on the basis of heat rise criteria,
in accordance with CSA C22.2 #31. All
bus bars are sized to limit heat rise to
65°C above an ambient temperature of
40°C.
Construction
Bus-Link Connections are accessible
from the front.
The Bus-Link can be bolted from the
front of the switchboard. Each bus-link
is attached by grade five bolts to assure
solid joints between sections, and to
maintain full bus ampacity through the
joint.
To make installation and servicing of the
bus-link easier, all phase and neutral
busses are stacked one above the other.
Cable Terminals
Screw mechanical connectors (lugs) are
provided as standard equipment.
b
User Metering
The service section provides space for
the Siemens Digital Meter with remote
display, and it’s associated components.
b
Main protective device
The MCCB is mounted individually
so that it can be located quickly in an
emergency. SMP switchboards will
accommodate different types of main
circuit breakers. Selection depends on
the characteristics of your individual
electrical system.
2
Sentron® SMP Switchboards
Power and Distribution
SMP Switchboard Introduction
Whether the design is for a 240V AC, 400 ampere
system; a 600V AC, 1200 A ampere system; or
something in between, Siemens Sentron Switchboards
should be considered. Every aspect of design has
been aimed at improving layout convenience, reducing
installation costs, and minimizing the impact and
cost of system changes. These switchboards provide
the space saving construction and service flexibility
necessary in systems for light industrial plants, retail
strip malls, and commercial buildings.
Service entrance sections of the SMP accepts a wide
range of Sentron Molded Case Circuit Breakers as
main disconnect devices.
The SMP switchboard is designed for special
configurations. It can be equipped with incoming and
outgoing cable/conduit connections, supplied with
metering and other special features.
The distribution sections of all Sentron Switchboards
are designed with improved wiring space and
greater accessibility. They’re also designed for easier
installation and maintenance. Conveniently located
bus-link without compromising useful wiring gutter
space, and standard bolted gutter covers offer
complete access to load conductors. Front accessibility
to bus and protective devices makes adding or
replacing circuit breakers or switches quick and easy.
SMP Switchboard Features and Ratingsb
Main bus rated up to 1200 ampere.
b
Rear of all sections aligned so that
switchboard can be floor mounted and
secured against the wall.
22.5” in MUD Section, or
60” in Distribution Section
Siemens Digital Metering with Remote Display
SEM3 Embedded Metering
SPD Units
Sill Channels (1.5”)
Lifting Hooks
Main and Distribution Section Dimensions (Table 2)
Switchboard Type Access
SMPFront90” (2286)38” (965)12.75” (324)
Dimensions - Inches (mm)
H
WD
General
a
Only available as a Wireway.
3
Sentron® SMP Switchboards
Power and Distribution
Protective Devices - Molded Case Circuit Breakers
Standard
Breakers are designed for commercial, industrial, institutional and other
heavy duty applications. They are rated up to 600V AC and 250V DC. Their
interrupting ratings are higher than normal duty breakers.
High Interrupting
Breakers are designed for heavy duty applications where the interrupting
requirements exceed the ratings of heavy duty breakers. They are rated up to
600V AC.
Current Limiting
Molded case breakers incorporate the exclusive I-T-E blow-apart interruption
principle. They meet the CSA requirements for current-limiting breakers.
Current-limiting circuit breakers can limit the let-through I
the I2t of one-half cycle wave of the symmetrical prospective current without
any fusible elements when operating within their current-limiting range.
Space includes housing frame plate with blank cover
plate. Provision includes all necessary mounting hardware, less circuit breaker, and includes housing frame
cover plate with breaker handle opening.
1 to 6 poles may be mounted in 3.75” (95) of unit space
Accessories such as shunt trips on three pole breakers
require 6.25” (159) of unit space.
Ground fault is not available on branch Sensitrip breakers.
e
Also 10kA at 600Y/347 Volts.
f
Refer to Table 5 for layout dimensions.
5
Sentron® SMP Switchboards
)
)
)
)
)
)
)
)
)
)
)
)
)
)
)
(
)
Power and Distribution
Protective Devices - Fusible Disconnects
Fuse Selection
The Proper Fuse Type for the Application
is Selected Using the Following
Parameters:
b Voltage Requirements
b Conductor Ampacity
b Horsepower Requirements
b Maximum Available RMS Fault Current
b CSA Fuse Class
Branch Switch Gutter Dimensions
For 38W Distribution Section (Table 8)
7.5"(191
7.5"(191
7.5"(191
10.0"(254
10.0"(254
10.0" (254)
8.0"(203
9.25"(235
30/30A VK Switch
60/60A VK Switch
100/100A VK Switch
200/200A VK Switch
30/30A VB Switch
60/60A VB Switch
100/100A VB Switch
200/200A VB Switch
400A thru 600A
VB Switch
6.25"(159
6.25"(159
7.5"(191
7.5"(191
7.5"(191
7.5"
10.0"(254
15.0"(381
10.0" (254)5.0"(127
Branch Switches 600V Maximum (Table 11)
Rating Max Fusing Mounting
Ampere Voltage Height 38”W
191
30/30A & 60/60A (VK)
10 0/100A (VK)200/200A (VK)30/30A & 60/60A (VB) 600V Class J 7.5” (190)100/100A (VB) 600V Class J 7.5” (190) 200A (VB) 600V Class J 10.0” (254)400A & 600A (VB) 60 0V Class J15.0” (381)
30 (1)—#14–#4 AWG (Cu or Al)
60 (1)—#14–#4 AWG (Cu or Al)
100 (1)—#10–#1/0 AWG (Cu or Al)
200 (1)—#6 AWG-350kcmil (Cu or Al)
40 0 (1)—#1/0 AWG-750 MCM OR
(2)—#1/0 AWG-250 MCM (Cu or Al)
60 0 (1)—#1/0 AWG-750 MCM OR
(2)—#1/0 AWG-250 MCM (Cu or Al)
Switch Interrupting Ratings
Interrupting Rating
Switch
Type
(kA)
240V 480V 600V
VB20 010 010 0
VK20 020 020 0
Gutters (Table 12)
End Gutters Side Gutters
Ampere Minimum - Minimum Rating Inches (mm)Inches (mm)
400 12” (305) 7.9” (201)
600 12” (305) 7.9” (201)
Switch Accessories (Table 13)
Fuse Pullers (VK)
30 or 60 Amp FP2
100 Amp FP3
200 Amp FP4
Cat. No.
CSA Fuse Classes (Table 14)
Class Amperes Volts (AC) I2t, Ip (Let-Thru) Circuits
H Standard Code 1-600A 250 and 600V — Less than
or less — 10,000A available
a
K
Fast Acting 1-600A 250 and 600V — Feeder circuits
(One time) or less
JFast Acting 1-600A 600V or less Ip and I2t-Low Feeder circuits
and Time Delay (motor load small %) Motor circuits
RK1Fast Acting 1/10-600A 600V or less I2t-Slightly > J Feeder circuits
and Time Delay 250V or less Ip-Slightly > J Motor circuits
RK5Fast Acting 1/10-600A 600V or less I2t- > RK-1 Feeder circuits
and Time Delay 250V or less Ip- > RK-1 Motor circuits
C Moderate 2-600A 600V or less I2t- < RK-5 Motor circuits
(FORM II)
Delay Ip- < RK-5
TFast Acting 1-600A 300 and 600V I2t-Low Non-motor loads
or less Ip-Low
LFast Acting 601-5000A 600V or less I2t-Low Feeder circuits
and Time Delay motor loads Motor circuits
a
Fuse clips do not prohibit the use of Class H type fuse
in switch.
Refer to Siemens for single phase and DC horsepower
requirements.
Ratings are based on UL test procedure.
Connector range applies to VB Switches only.
5
Not suitable for use in distribution space in main section.
6
Sentron® SMP Switchboards
Power and Distribution
Special Construction, Additions and Accessories
When required, special constructions
or additions to standard Switchboards
may be specified for all factory-assembled Power and Distribution
Switchboards. Listed below are those
available for Type SMP Switchboards.
1. Enclosure Type
38” Enclosure Types
Type 1
Type 2 (dripproof & sprinklerproof)
Optional: Dripshield
2. Wireway Options
24”W x 90”H x 12.75” Dp
24”W x 90”H x 25.5” Dp
Hinged Door
Door Covers
Hinged Door
Door Covers
3. Painted Finish
Touch-Up Paint (ASA61, Light Grey)
12 oz. aerosol can, Cat. # TUP-61
4. Miscellaneous Accessories
Nameplate - laminated and engraved
5. Bus-Link (One Set Per Panel)
Ampere Unit Space Occupied in MUD -
Rating Inches (mm)
400-1200 Consult Factory
6. Grounding of SMP Switchboard
Non-Insulated Equipment Ground Bus
Including Ground Lug
Continuous Solid Copper Ground
(optional)
7. Main Bus
Standard Main bus and Neutral bus are
tin plated aluminum or silver finished
copper (option).
8. Lugs
For Main Device and Neutral
For Main Breakers please see SpeedFax
section #6
Neutral - please consult factory
9.SPD Modules
Sentron TPS3 05
100KA
150KA
200KA
250KA
300KA
Options: Surge Counter
Remote Monitor
10. Circuit Breaker Accessories
Handle Blocking Device
Blocks handle in either the “ON” or
“OFF” position. Available for:
Breaker TypeCat. Number
BL, BLH, HBL, BQ,
BQH, HBQ
All BQD, GBBQDHBD
All QRHPLQR
All BQD, NGB, NGB2,
HGB2, LGB2
All EDE2HBL
All FDFD6HB1
All JD, LDJD6HBL
All MD, ND, PDMN6BL
Padlocking Device — Padlocks in
“OFF” position. Available for:
Breaker TypeCat. Number
BQ, BQH, BL, BLH, HBL ECQLD3
One Pole BL, BLF, BE,
BAF
Two-Pole BL, BLF, BEECPLD2
All QRHPLQR
All BQD, NGB, NGB2,
HGB2, LGB2
All EDED2HPL
All FDFD6PL1
All JD, LDJD6HPL
All MD, ND, PD, RDMN6PLD
Handle Extensions - For replacement
(one extension shipped with breaker)
The switchboard enclosure shall be of
bolted construction:
Type 1 indoor.
Type 1 with dripshield (optional).
Type 2.
Switchboard shall be bolted together to
form one metal enclosed rigid switchboard.
Switchboard shall include all protective
devices and equipment as listed on
drawings with necessary interconnections,
instrumentation and control wiring.
All groups of control wires leaving the
switchboard shall be provided with terminal
blocks with suitable numbering strips.
The switchboard shall have space or
provisions for future expansion as noted on
the plans. Switchboard shall be constructed
and certified in accordance with CSA
22.2.31 standards and shall be Siemens
type (SMP) or approved equal. Individual
sections shall be front accessible, not less
than 12.75” (324) deep, and the rear of all
sections shall align.
Distribution sections shall be designed to
accommodate the intermixing of Molded
Case Breakers and Fusible Disconnects in
the same distribution interior.
C. Bus Requirements
The bus shall be tin-finished aluminum
silver-finished copper (option) of
sufficient size to limit the temperature
rise to 65°C. The bus shall be braced for
50,000 or 65,000 (option) amperes
symmetrical and supported to withstand
mechanical forces exerted during short
circuit conditions when directly connected
to a power source having the indicated
available short circuit current.
D. Incoming Service
Overhead or Underground Service:
Cable Entry
This section shall be bussed and
sealable per local utility requirements.
Screw-type mechanical lugs,
compression lugs to terminate,
aluminum, copper cable, shall be
__________ kcmil, and ___ cables per
phase. Main breaker standard aluminum
mechanical lugs suitable for aluminum or
copper. (No wireway)
E. Metering Service Section
The service section shall be designed
for the system parameters indicated in
section “A” above. The metering service
section shall have a Utility Metering
compartment per utility requirements.
User metering as indicated below and
as shown on plans.
Main (service) section:
Siemens Digital metering with
remote display
_______ current transformer(s)
_______ /5 or suitable rating
SEM3 Embedded Metering
Ground fault Protection (3-Phase, 4-Wire):
Furnish and install on the service
equipment and/or switchboard a Ground
Fault protection system and indication
equipment as specified herein and as
shown on drawings in accordance with
CEC Section 14-102.
All new Ground Fault Protection and
Indication equipment shall be factory
installed, wired and tested by the
switchboard manufacturer.
F. Switchboard SMP Guide Specification
The complete switchboard shall be finished
with light grey, ASA-61 paint.
Each switchboard main section shall have a
metal nameplate permanently affixed to it,
listing the following information:
b Name of manufacturer
b System voltage
b Ampacity
b Type
b Manufacturer’s shop order number and
date
b Each section of switchboard shall bear a
CSA certification mark and a short circuit
rating label.
The switchboard shall be per the
arrangement below.
F1. Switchboard Type Panel-Mounted,
Front Accessible.
Switchboard shall be of Siemens SMP
type, or approved equal. Individual sections
shall be front accessible, floor mounted
rear supported, not less than 12.75” (324)
deep, and rear, of all sections shall align.
Incoming line termination, main device
connection and all bolts used to join
current-carrying parts shall be installed so
as to permit servicing from the front only
so that no rear access is required. The
branch devices shall be front removable
and panel mounted with line and load side
connections front accessible.
G. Main Protective Devices
The main protective device, to be installed
in the main device section, shall be as
indicated below:
G1. Molded Case Circuit Breaker
Molded case circuit breaker shall be of the
quick-make, quick-break, trip-free,
Sensitrip III) type.
It shall be _______ frame (3-pole)
(240V) (600V) breaker with a trip
current rating of:
400A, 600A, 800A, 1000A
1200 A
a
of an interrupting capacity
a
,
Specification
of not less than _______ amperes RMS
symmetrical at the system voltage.
The following accessory options are to be
included:
Shunt trip
Ground fault relay
Long time (Sensitrip III only)
Long time delay (Sensitrip III only)
Short time (Sensitrip III only)
Short time delay (Sensitrip III only)
Integral ground fault (Sensitrip III only)
Other_______ (list)
H. Branch Protective Devices
(Select as necessary)
All molded case circuit breakers, and
fusible disconnect units used as a
protective device in a branch circuit will
meet the requirements of the appropriate
paragraph below
H1. Molded Case Circuit Breaker
Molded case circuit breakers shall be
of quick-make, quick-break, trip-free
(thermal magnetic type) (current limiting)
(solid state) with frame, trip and voltage
rating, either 2-pole or 3-pole, as
indicated on the plans. All breakers shall
have an interrupting capacity of not less
than _______ amperes RMS symmetrical
at the system voltage. All breakers shall
be removable from the front of the
switchboard without distributing adjacent
units. The switchboard shall have space or
provisions for future units shown on the
plans.
H2. Current Limiting Circuit Breaker
Current limiting circuit breakers shall
provide inverse time delay, instantaneous
circuit protection, and also limit the letthrough I2t to a value less than I2t of
one-half cycle wave of the symmetrical
prospective current without any fusible
elements. Breakers shall have an
interrupting capacity of not less than
_______ ampere RMS symmetrical at the
system voltage.
H3. Fusible Disconnect
Fusible disconnects shall be quick-make,
quick-break units utilizing the double-break
principle of circuit rupturing to minimize
arcing and pitting and shall conform to the
ratings shown on the plans.
Each disconnect shall have an individual
door over the front, equipped with a
voidable interlock that prevents the door
from being opened when the switch is
in the ON position unless the interlock
is purposely defeated by activation of
the voiding mechanism. All disconnects
shall have externally operated handles.
Disconnects shall be equipped with
Class J (standard), Class R rejection
type, Class L (standard), Class T fuse
holders as indicated on the plans suitable
for application on system with _______
amperes symmetrical available fault
current.
a
Ground fault protection required, per CEC section 14-102 when “the current is O 1000A at 60 0 volts.”
8
Siemens Canada Limited
Low Voltage & Products
1577 North Service Road East
Oakville, ON L6H 0H6
Canada
Customer Interaction Centre
Tel: 1 (888) 303-3353
cic.ca@siemens.com
Order number: SI-LP-1668
www.siemens.ca/powerdistribution
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.