5.7 Support for SIL-approved devices.................................................................................. 29
6 Appendix30
6.1 Explanations to safety application conditions (SAC)...................................................... 30
10/2017 - A5E40875009-AB EN
www.siemens.com/flow
3
1
INTRODUCTION
1.1 Scope of the document
This document is the safety manual for the SITRANS FX330. Its content applies if the
measurement device is operated in SIL mode or prepared for SIL mode, respectively.
General hint
This vortex flowmeter is a functionally safe flowmeter. It may be deployed within safety critical
systems requiring the safety function (for details refer to
page 8) at a safety integrity level 2, in homogeneous redundant configuration at safety integrity
level 3 (for more information about homogeneous redundancy refer to
10).
In case of a detected potentially hazardous failure, the system performs a safety reaction to
bring the device to a safe state, which is indicated by a failure current on the current output.
Depending on the failure, the device will resume the measuring mode as soon as the root cause
of the failure disappears (transient application dependent failure) or remains in failure mode
(persistent system integrity failure). In the latter case, operator's interaction is required to
restart measuring mode.
SITRANS FX330
Specification of the safety function
Operation modes
on page
on
For safe operation, the operator / integrator must fulfil some conditions. These conditions are
defined as Safety Application Conditions (SAC). For further information refer to
application conditions (SAC)
on page 8.
Safety
INFORMATION!
The data in this supplement only contains the data applicable to the SIL approval. The technical
data for the standard version in the handbook (document [N1]) shall be valid, provided that it is
not rendered invalid or replaced by this supplement. If necessary, parts of [N1] are referenced
herein.
INFORMATION!
Installation, commissioning and maintenance may only be carried out by properly trained and
authorised personnel.
INFORMATION!
Configuration for SIL mode operation needs a login as role "Expert" (for details refer to [N1],
chapter "Security and permissions"]. Nevertheless the operator shall protect the flowmeter
against unauthorised access.
4
www.siemens.com/flow
10/2017 - A5E40875009-AB EN
SITRANS FX330
1.2 Revision history
This safety manual is valid for all versions which are operated in SIL mode, identified by the V
numbers according to the following tables, until its incompatibility with a new version is stated.
INTRODUCTION
1
CodeVG16/
SG16
Functional
safety
relevant
abcde fghijklmnopqrstu
vwx
xxxxx
yz
CodeDescriptionValid flow sensor codes for SIL
device variant
VG16/SG16Prefix to code-
aManufacturer specific-
bGeneral informationC, D
cdeFlange connection, rating and sealing surface-
fMeasuring section-
ghPressure sensor options and gaskets-
iApprovals for hazardous and ordinary locations-
jSignal converter housings1, 2, 4, 5, 7, A, B, D, E
Check in case a firmware is updated or any part of the device is replaced, whether a new safety
manual is available on the manufacturer's internet site.
Release dateElectronic revisionChanges and compatibilityDocumentation
The SITRANS FX330 is a 2-wire vortex flowmeter measuring volume flow rate, temperature and
optionally pressure of liquids, steam and gases. From these data the device calculates
normalised flow rate, mass flow rate, power flowrate, etc.
In SIL mode the SITRANS FX330 measures the volume flow rate and outputs the measurement
via the safe 4…20 mA current output.
For measurement in SIL mode the following conditions apply:
• The 4…20 mA current output provides a safe output exclusively.
• Local display, HART
• The local display and HART
• Parameters can only be changed in non-SIL mode.
• The binary output can also be used in order to provide non-safety related measurement
values.
• The current input can be used for non-safety related functionalities.
SITRANS FX330
®
Interface and the binary output do not provide a safe output.
®
Interface are read-only during SIL mode.
4...20 mA current
Tube→Safe subsystem→Non-safe
1.4 Related documentation
[N1]SITRANS FX330 Operating Instructions
[N2]IEC 61508-1 to 7:2010 Functional safety of electrical / electronic / programmable electronic safety-
related systems
[N3]Siemens Norm SN 29500, Edition 2004-01
output (safe)Current input
↑↓
subsystem
↓
Local display
Binary output
→
HART
→
6
www.siemens.com/flow
10/2017 - A5E40875009-AB EN
SITRANS FX330
INTRODUCTION
1.5 Terms and definitions
TermDescription
DCDiagnostic Coverage of dangerous failures
EUCEquipment Under Control
FirmwareSoftware embedded in the device
FIT
FMEDAFailure Modes, Effects and Diagnostics Analysis
FRTFault Response Time (diagnostic test interval + Fault Reaction Time)
HFTHardware Fault Tolerance
I/OInput / output
λ
DD
λ
DU
λ
SD
λ
SU
MTBFMean Time Between Failures
MTTFMean Time To Failure
MTTRMean Time To Repair
MTRMean Time To Restoration
PFD
AVG
PFHProbability of a dangerous Failure per Hour
PTCProof Test Coverage
SFFSafe Failure Fraction
SILSafety Integrity Level
SISSafety Instrumented Systems
Systematic
Capability
Type A
system
Type B
system
T
Proof
T
Repair
T
Test
1oo11 out of 1 channel architecture (single architecture performs the safety function)
1oo1D1 out of 1 channel architecture with diagnostics
Failure In Time (1x10-9 failures per hour)
Rate for dangerous detected failure
Rate for dangerous undetected failure
Rate for safe detected failure
Rate for safe undetected failure
Average Probability of Failure on Demand
Measure (expressed on a scale of SC 1 to SC 4) of the confidence that the systematic safety integrity of an
element meets the requirements of the specified SIL, in respect of the specified element safety function,
when the element is applied in accordance with the instructions.
"Non-complex" system (all failure modes are well defined). For more data, refer to subsection 7.4.3.1.2 of
IEC 61508-2.
"Complex" system (all failure modes are not well defined). For more data, refer to subsection 7.4.3.1.2 of
IEC 61508-2.
Proof Test Interval
Time to Repair
Internal Diagnostics Test Interval
1
10/2017 - A5E40875009-AB EN
www.siemens.com/flow
7
2
SPECIFICATION OF THE SAFETY FUNCTION
2.1 Preconditions
The device must be operated within the process and ambient conditions specified in the
handbook ([N1]) of the device.
The following chapter defines additional conditions, which have to be obeyed for safety
applications.
2.2 Safety application conditions (SAC)
INFORMATION!
This chapter defines the conditions which must be met by the operator to ensure safe operation.
Further explanations can be found in appendix I. The safety application condition is valid, while
the related explanation might be incomplete.
2.2.1 General
SAC1: System changes
The flowmeter can be deployed as device with safety responsibility. Non specified changes are
not allowed. Especially after maintenance measures, carrier and operator must ensure that no
hazardous states came up, and that all safety application conditions are still met.
SITRANS FX330
2.2.2 Installation
SAC2: Mounting and connecting
[N1] defines requirements regarding installation and electrical connections of the device. These
requirements are safety critical and must be strictly observed.
2.2.3 Functional safe configuration
SAC3: SIL mode
The flowmeter is functionally safe only if configured for operation in SIL mode.
SAC4: Parameter input
Parameters are changed under responsibility of the operator.
2.2.4 Maintenance
SAC5: Maintenance mode
If maintenance mode (for definition refer to
operated under responsibility of the operator.
SAC6: Resetting the fail-safe flag
Resetting the fail-safe flag is done under responsibility of the operator. He is responsible for the
correct execution of appropriate tests and the evaluation of test results.
Operation modes
on page 10) is entered, the device is
SAC7: Firmware update
Firmware may be updated by authorised personnel only.
8
www.siemens.com/flow
10/2017 - A5E40875009-AB EN
SITRANS FX330
SAC8: Inspection intervals
The definition of the maximum proof test intervals (for details refer to
proof test
responsible for adjusting the proof test intervals if the deployment conditions deviate from the
reference conditions.
SAC9: Modification
The flowmeter must not be manipulated.
SAC10: Repair
Repair of the flowmeter must only be done by manufacturer’s personnel or personnel authorised
by the manufacturer. Exceptions regarding replacement with spare parts are shown in chapter
"Service" in [N1]. In all other cases, send the flowmeter to the manufacturer for repair (for
instructions refer to chapter "Returning the device to the manufacturer" in [N1]).
2.2.5 Operation
SAC11: Operational limits
The operational limits as shown in [N1] in the chapter "Technical data" must be observed. To
prevent unintentional trigger of the safety reaction, a permanent operation near the operational
limits should be avoided.
SPECIFICATION OF THE SAFETY FUNCTION
Operation modes and
on page 19) are calculated for operation under reference conditions. The operator is
2
SAC12: Supervision of failure current
If a safety critical failure has been detected, the device outputs a failure current on the current
output (4...20 mA). The operator must supervise both failure currents
(<3.6mA and >21mA).
In case of the occurrence of any failure current the operator has to ensure that the safety loop
reacts according to relevant application specific norms (e.g. the safety loop must be prevented
from automatically resuming operation after failure notification disappears).
2.2.6 Homogeneous redundancy
SAC13:
The logic subsystem must compare the current values transmitted by the two flowmeters (or
one dual version respectively) permanently. In case of a difference greater than 4% of the
measurement range over a time interval greater than 30 seconds, the devices must be regarded
as non-safe, or defect respectively.
SAC14:
The two flowmeters (or one dual version respectively) must be operated independently. Any
hazardous re-activeness from the logic subsystem (for details refer to
10)
on the two measurement devices must be excluded. This means at least:
• Current loops are independently driven.
• Current loops are installed in a way that failures affecting both lines at a time (common
cause) can be avoided.
• The logic subsystem must provide an appropriate low failure rate.
Operation modes
on page
10/2017 - A5E40875009-AB EN
www.siemens.com/flow
9
2
SPECIFICATION OF THE SAFETY FUNCTION
2.3 Operation modes
SIL mode
In SIL mode, the device executes the safety function and will react safely if an error is detected
which prevents the correct execution of the safety function. In this mode, the device is
functionally safe and the safety relevant key figures like hazard rate, FRT etc. can be guaranteed.
Non-SIL mode
In non-SIL mode, the device operates as a standard device. Its behaviour is state-of-the-art, its
specific functionality depends on the individual, customised parameter settings.
Maintenance mode
Maintenance mode is intended to boot a potentially defect device in order to test it in its normal
operational environment. During this time, operation is done under responsibility of the
operator. To avoid improvident and unintentional entering of the maintenance mode the operator
is requested to enter the password for "Expert" level access.
SITRANS FX330
By entering the (correct) password, the operator acknowledges the above regulation regarding
responsibility, also regarding safety responsibility if the device is operated in SIL mode.
As the maintenance mode is intended for testing, the operator shall provide additional measures
to secure the safety of the overall system. Therefore, the operator shall install additional
measures to provide safety of the overall system.
10
www.siemens.com/flow
10/2017 - A5E40875009-AB EN
SITRANS FX330
Homogeneous redundancy
The degree of a functional safe device is determined by the accomplished qualitative safety
integrity level and the quantitative hazard rate determined by the failure rate of the deployed
hardware.
If two or more identically constructed devices are used in parallel (device A is of the same type as
device A’ like the "Dual Version"), the hazard rate for the combination (here: sensor subsystem)
can be reduced.
A precondition for this is a logic subsystem comparing the output of devices A and A’: The
complete sensor subsystem fails if at least one of the two devices fails (availability is reduced to
50% of the value of a single device A!).
SPECIFICATION OF THE SAFETY FUNCTION
2
Figure 2-1: Homogeneous redundancy
1 Sensor subsystem
2 Measurement device A
3 Measurement device A'
4 Logic subsystem
2.4 Definition
The flowmeter provides a safety function according to the international standard IEC 61508 [N2].
It is defined as follows:
Output of the volume flow rate at the 4...20 mA current output with a maximum delay of
Output of the volume flow rate at the 4...20 mA current output with a maximum delay of
Output of the volume flow rate at the 4...20 mA current output with a maximum delay of Output of the volume flow rate at the 4...20 mA current output with a maximum delay of
30 seconds and a measurement accuracy better than 4%.
30 seconds and a measurement accuracy better than 4%.
30 seconds and a measurement accuracy better than 4%.30 seconds and a measurement accuracy better than 4%.
Remarks
• The function is always and only executed in SIL mode.
• The measurement uncertainty of the flowmeter in safe operation equals to those
operation
curre
• Concerning random errors in the device, the safety tolerance must be considered. The safety
tolerance is the tolerable error before setting the safe state of the device. A random fault can
cause an error of up to 2% of the present measurement value or output current
si
as described in [N1]. It consists of the uncertainty of measurement function
nt output.
gnaled. For further information refer to
Measuring accuracy
in non-SIL
and
before it is
on page 28.
10/2017 - A5E40875009-AB EN
www.siemens.com/flow
11
2
SPECIFICATION OF THE SAFETY FUNCTION
2.5 Safety reaction and safe state
As soon as a failure is detected, the vortex flowmeter reacts safely, by setting the current output
to the low or high failure current (safety reaction). As an additional feature, temporary and
persistent failures can be distinguished:
• A failure current of approximately 3.5 mA is output in case of a transient failure.
• A failure current of approximately 3.35 mA or below, is output in case that a persistent failure
is assumed. A device with a persistent failure will not boot into SIL mode without operator’s
interaction (for details refer to
Troubleshooting
Remarks
• The decision whether a failure is transient or persistent will be made within 30 seconds after
its detection.
• A too low volume flow (below the lower sensor limit) is classified as a typical transient
application dependent failure.
• Some failures will prevent the output of the lower failure current. In such cases, the device
tries to output the high failure current (> 21 mA).
• The fault response time is 30 seconds. Any output older than 30 seconds is correct if the
safety reaction is not triggered due to a safety critical device failure.
on page 23).
SITRANS FX330
12
www.siemens.com/flow
10/2017 - A5E40875009-AB EN
SITRANS FX330
3.1 Preparation for SIL mode operation
For execution of the safety function, the device must be unlocked for SIL mode operation and
configured for SIL mode.
Devices, which have been ordered as SIL devices, have been unlocked for SIL mode by factory
setting. Devices, which have not been ordered as SIL devices, must be unlocked with a key code.
Please contact the manufacturer for registration and individual 4-digit key code.
The preparation for SIL mode is done in three steps:
Unlocking of the SIL mode by entering the SIL mode key code (Not applicable for devices or-
1.
dered as SIL devices (for details refer to
2. Se
tup the device for SIL mode operation (for details refer to
eration
3. Ver
by se
on page 14).
ification of the actual configuration and subsequent confirmation of successful verifica
tting the SIL jumper (for details refer to
Entering the SIL mode key
Parametrisation for SIL mode op-
Verification of configuration
OPERATION
on page 13).
on page 14).
3
tion
3.1.1 Entering the SIL mode key
This step has only to be performed once before the first configuration for SIL mode operation. It
is only applicable for devices, which have not been ordered as SIL devices. For basic principles of
local display operation and menu structure overview refer to [N1].
INFORMATION!
For entering the SIL mode key code it is required to gain
refer to [N1], chapter "Security and permissions").
MenuTo doKeys
Enter menu1 x →
A Quick SetupGo to "C Setup"2 x ↓
C ProcessGo to "C6 Device"1 x →, 5 x ↓
C6 DeviceGo to "C6.2 Security"1 x →, 1 x ↓
C6.2 SecurityGo to "C6.2.4 Unlock SIL"1 x →, 3 x ↓
C6.2.4 Unlock SILEnter menu and unlock SIL by entering the four digits of the
password, confirm with enter key
After entering the SIL mode key code and confirming with enter key, return to measuring mode.
INFORMATION!
Before switching to SIL mode the customer has to ensure the proper condition of the device. In
case of any doubt, a Proof Test may be performed. Previous hours of operation have to be taken
into account for failure rate calculation.
“
Expert” access level before (for details
1 x →, ****, 1 x ^
10/2017 - A5E40875009-AB EN
www.siemens.com/flow
13
3
OPERATION
3.1.2 Parametrisation for SIL mode operation
Display indicationTo doKeys
SITRANS FX330
Go to SIL measurement page (After
unlocking the SIL mode, a SIL
measurement page will be available)
Press > button to enter SIL setupEnter SIL configuration menu1 x →
A Quick SetupChange parameters in "Quick Setup" or
"Save Configuration?" (only displayed, if
any parameter has been changed)
Switch to SIL mode?Confirm switching to SIL mode with
If last question was confirmed with
"YES": "Password?"
Wait for reboot
"Setup" as described in [N1]
Leave Quick Setup" or "Setup"1 x ^
Confirm settings with "YES" or cancel all
changes with "NO"
"YES" or cancel with "NO"
Enter password for "Expert" (refer to
[N1], chapter "Security and
permissions")
(0...3) x ↑
-
YES / NO ^
YES / NO ^
**** ^
If question "Switch to SIL mode?" has been confirmed with "YES", the operator will be requested
to enter the password for the access level "Expert" (refer to [N1], chapter "Security and
permissions") and the system will reboot automatically. If question "Switch to SIL mode?" has
been refused with "NO", the device will stay in non-SIL mode. Nevertheless, the changed
parameters are stored persistently.
By displaying "Press key for verification" the device shows preparedness for verification of the
SIL configuration.
3.1.3 Verification of configuration
During configuration verification, the device will output the complete range between 4 and 20 mA
in 2 mA steps and the failure currents <3.6 and >21 mA. Each value will be held for approx.
2 seconds (after the output of >21 mA, the next output will be <3.6 mA again).
The test is performed in an endless loop which can be terminated by setting the SIL jumper or by
refusing the SIL mode request (for details refer to
on page 15).
mode
Required equipment
• Calibrated current meter
Execution of the verification
The parameter verification is performed as follows:
• Integrate a calibrated current meter into the current loop.
• The device will perform an automatic restart.
• Confirm request "Press key for verification" by pressing any key.
• Check carefully, whether the device shows <3.6, 4 mA, 6 mA…20, >21 mA in a loop.
• Confirm request "Set SIL jumper or press key to cancel" by setting the SIL jumper or refuse
switch to SIL mode by pressing any key
Reconfiguration of a device operated in SIL
14
www.siemens.com/flow
10/2017 - A5E40875009-AB EN
SITRANS FX330
Setting of the SIL jumper
• Remove the display while device is powered (for details refer to [N1], chapter "Turning the
• Set the jumper to SIL position as shown in the figures below.
• Reattach the display.
dis
play").
OPERATION
3
Figure 3-1: Jumper position
1 Non-SIL position
2 SIL position
After setting the jumper to the SIL position, the flowmeter will perform an automatic reboot and
start operation in SIL mode. The operation in SIL mode is indicated by a small SIL logo.
Figure 3-2: Indication of SIL mode
1 SIL logo for indication of SIL mode
3.2 Reconfiguration of a device operated in SIL mode
The device must be set to non-SIL mode first, before any parameter can be changed, as changing
of parameters is prohibited in SIL mode.
Follow the steps shown in the next chapter and then reconfigure the device.
10/2017 - A5E40875009-AB EN
www.siemens.com/flow
15
3
OPERATION
3.3 Switch to non-SIL mode
In order to switch the device from SIL mode to non-SIL mode the following steps have to be
performed.
• Remove the display (for details refer to [N1], chapter "Turning the display").
• Set the jumper to non-SIL position (for details refer to
page 13).
• Reattach the display.
• The flowmeter will perform an automatic reset.
• Confirm request "Press key for verification" by pressing any key.
• Refuse request "Set SIL jumper or press key to cancel" by pressing any key.
• Enter password for access level "Expert".
The device will now perform an automatic reboot and start operation in non-SIL mode.
3.4 Error conditions
In principle, the error conditions for non-SIL mode and SIL mode are the same (refer to chapter
"Status messages and diagnostic information" in N1]).
SITRANS FX330
Preparation for SIL mode operation
on
In SIL mode, the following special conditions apply additionally:
• Safety critical failures will always result in an output of a failure current.
• The failure current is the only safety relevant signal. Regarding the safe state of the device,
all other interfaces must be ignored (Example: a failure current indicates a safety critical
®
defect, even if the HART
• Due to power considerations, the lower failure current is the pre-defined failure current. The
related user’s configuration in non-SIL mode is ignored in SIL mode. High failure current will
only be set if the lower failure current cannot be output for any reasons.
• The events shown in the following table are SIL specific, i. e. they will occur only if the device
is operated in SIL mode.
Status type Event groupDescriptionActions to eliminate the event
FElectronicsEmergency off
interface is still online).
triggered
Restart the device according to given procedure
(for details refer to
on page 23).
Resetting the fail-safe flags
16
www.siemens.com/flow
10/2017 - A5E40875009-AB EN
SITRANS FX330
3.5 Parameter types
In SIL mode the device parameters are distinguished in three parameter types. Two types affect
safety:
• Safety critical data:
Safety critical data: These parameters have a fixed setting and cannot be changed but read
Safety critical data:Safety critical data:
only. They are marked with a padlock symbol.
ParameterFixed settingDescription
OPERATION
3
Current Out. Meas.Volume FlowIndex of the device variable which is mapped to the current
4mA Trimming0.004 [A]The externally measured analogue level during trimming
20mA Trimming0.020 [A]The externally measured analogue level during trimming
High Error Current0.0215 [A]High failure current.
Low Error Current0.0035 [A]Low failure current.
Analog Lower Endpoint
Value (no menu entry
available)
Lower Ext. Range0.004 [A]The minimum value that the analogue channel is capable of or
Analog Upper Endpoint
Value (no menu entry
available)
Upper Ext. Range0.02 [A]The maximum value that the analogue channel is capable of
Error FunctionALARMSELECTION LOWStates whether the alarm is indicated with high or low signal
Current Loop ModeONA switch for enabling/disabling loop current signalling.
k-Factor / Offset0.0Offset value to adapt k-factor.
k-Factor Linear. /
Function
Up. Pip. Dist. Cor. /
Function
Temp. Comp. / FunctionONSetup of k-factor temperature compensation.
Lin. Thermal Exp. 1/K0.0000175 [per Kelvin]Coefficient of linear thermal expansion (bluff body).
Min/Max Oper. Dens. /
Function
Sensor Overrange0Is used to determine the high flow cutoff factor.
Vortex Algorithm / Filter
Mode
Vortex Algorithm / Min.
Amplitude
Gain CA0Piezo configuration.
VA Piezo Test Mode (no
menu entry available)
Distortion Reduction /
Function
0.004 [A]Corresponds to 0% range and therefore to the "Lower Range
0.02 [A]Corresponds to 100% range and therefore to the "Upper
OFFSwitches the k-factor linearisation on/off.
OFFSetup of k-factor upstream compensation.
OFFSwitch for use of upper and lower densities for calculation of
FULL AUTO SETTINGSFilter configuration:
0.01 [V]Indicator for valid measurement of vortex frequency.
PIEZO TESTMODE OFFPiezo configuration.
ONAmplitude correction.
output.
(user calibration) of the "Analog Lower Endpoint Value".
(user calibration) of the "Analog Upper Endpoint Value".
Value" of the range conversion.
is limited to.
Range Value" of the range conversion.
or is limited to.
level or not at all.
®
ON: HART
sensor limits.
"FULL_AUTO_SETTINGS" means that all settings are derived
from Pickup configuration.
Vortex Filter / Filter TypeFILTER TYPE NONEOutput filter type for vortex.
Vortex Filter / Filter
Length
Vortex Filter / Smoothing
Factor
Vortex Algorithm / Min.
SNR
Time Constant2.0 [s]Time constant (for filter).
Low Flow Cutoff0.0 [cubic meters per
Minimum hold time
transient error (no menu
entry available)
Vortex Algorithm
Extended Sensor Limits
• Safety relevant data:
Safety relevant data: These parameters can be changed under responsibility of the operator.
Safety relevant data:Safety relevant data:
204011Amplitude correction P-factor.
2141041197Amplitude correction filter factor.
25Output filter length.
0.05Output filter smoothing factor.
50.0Indicator for valid measurement of vortex frequency.
second]
5000 [ms]Minimum hold time of the failure current in case of transient
OFFExtended sensor limits
Low flow cutoff (When the flow rate drops below low flow
cutoff , the current output is 4 mA)
errors.
Misconfiguration via erroneous setting is detected by the parameter verification procedure
which is executed automatically if the device is setup for SIL mode and parameters have been
changed (for details refer to
Preparation for SIL mode operation
on page 13).
Access levelParameterSetting / Description
Expert"Lower Range Value" of
Expert"Upper Range Value" of
Servicek-FactorRepresents the relation between vortex frequency and flow
ExpertDensity (operating)Used to determine the flow sensor limits.
ExpertTemperature (operating)Used for correction of the k-factor.
ExpertFluidDetermines signal processing and on-screen menu of the
ServiceNominal DiameterUsed to determine the flow sensor limits.
• Non-SIL data:
Non-SIL data: These parameters do not have any influence on the safety function and may be
Non-SIL data:Non-SIL data:
the current output
the current output
For further information refer to
on page 14.
velocity.
local display.
Verification of configuration
changed as in non-SIL mode.
The parametrisation in SIL mode works as described in chapter "Operation" in [N1] for the most
parameters. However, there are some parameters which have an influence on functional safety
if set incorrectly.
For every safety affecting parameter, two values, potentially equal ones, exist in the device: one
is used for non-SIL, the other for SIL operation. Depending on the device’s state, either the one
parameter set or the other is shown or can be edited. As soon as the SIL mode is requested, the
SIL mode parameters become active.
18
www.siemens.com/flow
10/2017 - A5E40875009-AB EN
SITRANS FX330
4.1 Maintenance
You must follow the maintenance instructions given in the handbook [N1].
4.2 Availability of services
The manufacturer offers a range of services to support the customer after expiration of the
warranty. These include repair, maintenance, technical support and training.
INFORMATION!
For more precise information, please contact your local sales office.
4.3 Operation modes and proof test
Continuous and high demand mode
If the flowmeter is operated in continuous or high demand mode within the specified
environmental limits, the device needs no proof test during its useful lifetime (for details refer to
Useful lifetime
respectively.
on page 29). Observe SAC 11 regarding useful lifetime and constant failure rates,
SERVICE
4
Low demand mode
The flowmeter includes a comprehensive set of online diagnostic tests which are executed fast
and frequently, resulting in a very low mean down time. Assuming reasonable low repair and
restoration times as well, the device fulfils SIL2 compatible PFD values as well during the whole
useful life time without additional proof tests.
Proof test
Proof tests are required in case of:
• Deployment under extreme conditions beyond the device's specificatio
nmental conditions might increase the failure rate. To keep undetected failures sm
enviro
uch deployment requires more frequent proof tests. For details refer to
s
pag
e 29, operational limits as set forth in SAC 11 must not be exceeded.
• Achieving the required PFD
over time.
AVG
n. In this case,
Useful lifetime
all
on
WARNING!
SIS engineers must calculate the interval of proof tests based on the required PFD
For this purpose, the following tests can be performed. The diagnostic coverage of all tests
together is nearly as good as the tests and procedures in the factory which were executed during
or at the end of the production cycle. Only flow sensor calibration is missed here which requires
a reference meter.
AVG
.
10/2017 - A5E40875009-AB EN
www.siemens.com/flow
19
4
SERVICE
SITRANS FX330
Proof test coverage
StepMeasureProof Test Coverage
1Current output check according to routine in chapter
"Verification of configuration".
2Test with simulated vortex frequencies.96%
12%
Calibration verification (optional)
A proof test coverage of > 97% can be reached with a calibration verification. If appropriate
facilities are not available, please contact the manufacturer for calibration verification.
Test with simulated vortex frequencies (step 2)
Required equipment
• Power supply 14…30 VDC
• Calibrated frequency generator, accuracy << 1%, two channels 180° phase shifted, 100 mVpp
amplitude (step 2)
• Calibrated current meter (steps 1 and 2)
Execution of frequency simulation for the proof test
To setup the device for proof testing, the following steps have to be performed:
• Set the device to non-SIL mode (for details refer to
Switch to non-SIL mode
• Unfix the electronics housing by loosening the 4 cylinder screws 1 and take off the
electronics housing carefully.
on page 16).
20
Figure 4-1: Unfixing of the electronics housing
1 Cylinder screws
2 Washers
3 Gasket
www.siemens.com/flow
10/2017 - A5E40875009-AB EN
SITRANS FX330
• Integrate a current meter into the current loop.
• Disconnect the 3-pole plug and connect a frequency generator as illustrated below.
Figure 4-2: Connection of frequency generator
1 Frequency f1
2 Grounding
3 Frequency f2, phase-shifted by 180° compared to f1
The 2-pole and 5-pole plugs must remain connected!
The 2-pole and 5-pole plugs must remain connected!
The 2-pole and 5-pole plugs must remain connected!The 2-pole and 5-pole plugs must remain connected!
SERVICE
4
• Set start frequencies f1 and f2 to almost 0 Hz.
• Connect the flowmeter with the power supply.
• Boot the device.
• Confirm request "Press key for verification" by pressing any key.
• Login as "Expert".
• After reboot of the device activate proof test as follows:
Menu/displayTo doKeys
Enter menu1 x →
A Quick SetupGo to "C Setup"2 x ↓
C SetupGo to "C6 Device"1 x →, 5 x ↓
C6 DeviceGo to "C6.8 Proof Test"1 x →, 6 x ↓
C6.8 Proof TestEnter "Proof Test"1 x →
"Unsaved
parameters will be
lost!"
"Run Proof Test?"Confirm start of proof test with "YES" or cancel with "NO"YES / NO ^
Confirm warning with enter1 x ^
If question "Confirm start of proof test?" has been confirmed with "YES", the device is prepared
for proof test and displays "Proof Test is running…".
10/2017 - A5E40875009-AB EN
www.siemens.com/flow
21
4
SERVICE
SITRANS FX330
• Increase frequencies stepwise. The loop current must follow according to the following table:
Frequency [Hz]Nominal current [mA]Acceptable current range
[mA]
3554.03.96...4.04
8178.58.41...8.58
122912.512.38...12.63
163616.516.30...16.63
200020.019.81...20.21
• Continue only if test is successful. Stop if any current is out of the accepted limits!
• To finish or cancel the proof test press "Enter". The device will display "Device will be reset
now!" and perform an automatic reboot after pressing the "Enter" key once again.
• Re-attach the electronics housing: Carefully place the electronics housing with the gasket 3
on the device as shown in the figure "Unfixing of the electronics housing".
Pay attention not to pinch the cable! Fasten the cylinder screws 1 including the washers 2
with a bolting torque of 8 Nm.
INFORMATION!
A current value below or above the acceptable limits is an indicator for wear out of the
electronics. Please refer to chapters "Maintenance" and "Availability of service".
INFORMATION!
The frequency test does not consider the sensor element, configuration and drift errors.
22
www.siemens.com/flow
10/2017 - A5E40875009-AB EN
SITRANS FX330
4.4 Resetting the fail-safe flags
Rebooting of a device operated in SIL mode with a detected safety critical failure is inhibited. In
this case, the following message is shown on the display:
The test is performed under full responsibility of the operator! The device will operate in SIL
mode to allow extensive testing, but the SIL tag is not shown in the header bar on the display
(because the device is actually non-safe!)
(because the device is actually non-safe!). Consequently, additional measures should be
(because the device is actually non-safe!)(because the device is actually non-safe!)
installed to prevent the overall system from safety critical failures. The flowmeter might be
defect persistently!
INFORMATION!
In case of any doubt, call the service department of the manufacturer and leave the device in the
current safe state!
SERVICE
SIL locked!
SIL locked!
SIL locked!SIL locked!
Press key to start test
Press key to start test
Press key to start testPress key to start test
but the SIL tag is not shown in the header bar on the display
but the SIL tag is not shown in the header bar on the display but the SIL tag is not shown in the header bar on the display
4
Menu/displayTo doKeys
SIL locked!
Press key to start
test
Password?Enter the 4 digit "Expert" password.**** ^
Clear fail safe
flag?
Password?Enter the 4 digit "Expert" password.**** ^
Wait for reboot--
4.5 Troubleshooting
INFORMATION!
•
Modifications to SIL capable devices by the user are not permitted.
•
Only authorised personnel from the manufacturer shall repair the device.
Failures that are critical to functional safety must be reported to technical support of the
manufacturer. If you find a problem, please contact your local representative. If the device must
be returned to the manufacturer, refer to "Returning the device to the manufacturer" in [N1].
Start maintenance mode under full responsibility of the
operator for testing purposes.
Test device.
Enter and leave menu when finished.
Clear if the device is intact without doubt; do not clear
otherwise!
Attention: Entering "YES" will cause the flowmeter to boot to
Attention: Entering "YES" will cause the flowmeter to boot to
Attention: Entering "YES" will cause the flowmeter to boot to Attention: Entering "YES" will cause the flowmeter to boot to
SIL operation next time!
SIL operation next time!
SIL operation next time!SIL operation next time!
Any key.
1 x →, 1 x ^
YES / NO ^
10/2017 - A5E40875009-AB EN
www.siemens.com/flow
23
5
TECHNICAL DATA
5.1 General notes
SITRANS FX330
• The safety relevant key indicators (for details refer to
27) are related to the safety function (for details refer to
• Commissioning and use of the device presupposes agreement with its design and
performance characteristics. This includes ambient and process conditions (refer to
handbook [N1]).
• The values shown in the table for the safety relevant key indicators have been determined for
an environmental temperature of +40°C / +104°F and below. For higher temperatures refer to
Useful lifetime
• Failure rates are assumed to be constant during the useful lifetime (for details refer to
lifetime
• Failure rates do not include mechanical wear of the sensor and bluff body. The operator is
responsible for observing the specification for intended use (refer to chapter "Intended use"
in [N1], respectively for adequate inspections if the device is deployed out of specification and
damages caused by the process need to be assumed.
• Installation of the device must be in accordance with the instructions and the requirements of
the application.
• All components that are not necessary to execute the safety function and cannot influence the
safety function are not included in the calculation of the failure rates.
• External power failure rates are not included in the calculation of the failure rates.
• The FMEDA of the device was calculated with the exida tool FMEDA v7.1.17. The tool uses the
latest values from the database SN 29500 [N3].
on page 29).
on page 29.
Safety relevant key indicators
Operation modes
on page 10).
on page
Useful
24
www.siemens.com/flow
10/2017 - A5E40875009-AB EN
SITRANS FX330
5.2 SIL certificate
TECHNICAL DATA
5
10/2017 - A5E40875009-AB EN
www.siemens.com/flow
25
5
TECHNICAL DATA
5.3 Declaration
SITRANS FX330
26
www.siemens.com/flow
10/2017 - A5E40875009-AB EN
SITRANS FX330
5.4 Safety relevant key indicators
All values shown in the following table are related to reference conditions according to [N3]:
1 The PFH values for the dual version, or other device configurations deployed in homogeneous
redundant configuration (for details refer to
SACs 13 and 14 are fulfilled.
2 If deployed within specified environment conditions (for details refer to
page 29).
3 For reference conditions, but with an extended temperature range up to +40°C / +104°F.
4 Value depends on the depth of the proof test (for details refer to
on page 19).
test
5 This is the part of the process safety time which must be reserved for the safety reaction of
the flowmeter or for the delay of its safety function respectively.
6 Assuming MTTR = MTR = 8 hours.
7 Related to hardware components relevant for safe operation.
10/2017 - A5E40875009-AB EN
Operation modes
www.siemens.com/flow
on page 10) is applicable only, if
Useful lifetime
on
Operation modes and proof
27
5
TECHNICAL DATA
5.5 Measuring accuracy
The flowmeter measures with the same accuracy in both operation modes, in the non-SIL mode
as well as in the SIL mode, as long as the device is intact.
But diagnostic measures need a reasonable gap between the states intact and defect for
availability reasons. Therefore, a safety engineer integrating the flowmeter into the overall
system must take the higher measurement inaccuracy into consideration.
The following figure illustrates the logical coherences.
y
4%
0.75%
SITRANS FX330
- 0.75%
- 4%
Figure 5-1: Measuring accuracy vs. flow
x: Flow
y: Measuring accuracy
1 Bounds for non-SIL, device intact (designed, tested)
2 SIL bounds (supervised)
3 Actual inaccuracy, noise etc.
x
28
www.siemens.com/flow
10/2017 - A5E40875009-AB EN
SITRANS FX330
5.6 Useful lifetime
The established failure rates of electronic components apply within the useful lifetime according
to IEC 61508-2, section 7.4.9.5 note 3.
The useful lifetime can only be extended under responsibility of the plant operator regarding
special operation conditions and the employment of suitable intervals for testing and
maintenance.
TECHNICAL DATA
5
As a consequence for the safety function, the total failure rate, and consequently λ
must not
DU
be assumed as constant at the end of the life time. The following table provides an overview
about the downgrade of lifetime, depending on electronic temperature which is the most lifetime
reducing factor.
Non-Ex/Ex i [IS]
ProfileTemperature
[°C / °F]
140 / 104
260 / 140
380 / 176
λ
DU
[/h]
4.64 * 10
9.79 * 10
2.13 * 10
Reduction of
Reliability to
[%]
Exp. Lifetime 1
[years]
Recommended
Proof Test
Interval 2
[years]
-8
-8
-7
4766
2232
11.512
Ex d/Ex t/Ex nA [XP/DIP/NI]
ProfileTemperature
[°C / °F]
140 / 104
260 / 140
380 / 176
λ
DU
[/h]
4.72 * 10
9.98 * 10
2.17 * 10
Reduction of
Reliability to
[%]
Exp. Lifetime 1
[years]
Recommended
Proof Test
Interval 2
[years]
-8
-8
-7
4766
2232
11.512
1 The expected lifetime is defined here as time interval wherein less than 15% of all devices
failed.
2 For low demand applications for a tolerated residual failure probability of 0.0003 per demand.
5.7 Support for SIL-approved devices
All instruments which are unlocked for the use in a SIL mode are registered by the
manufacturer.
In case that modifications at the supplied flowmeter will be necessary which are relevant to the
safety function of the device, the manufacturer will inform the customer immediately.
10/2017 - A5E40875009-AB EN
www.siemens.com/flow
29
6
APPENDIX
6.1 Explanations to safety application conditions (SAC)
SITRANS FX330
For some SACs (for details refer to
explanations are given below:
Safety application conditions (SAC)
on page 8) additional
SAC1: System changes
Every state of the system which does not meet its specification might be hazardous, because
those states were not completely analyzed. Hazardous states can be reached by
- the use of failed, but not as "failed" marked parts, or not tested parts,
- changing the wiring, especially the use of the serial interfaces in combination with a service
computer ("notebook") during operation with safety responsibility.
Most measures within the communication network are harmless, but not all. In any case, the
related safety application conditions must be observed.
SAC2: Mounting and connecting
Incorrect installation will have an effect on measurement and on the measuring accuracy in
general. Therefore, the correct execution of the safety function cannot be guaranteed if the
installation conditions are not met.
SAC3: SIL mode
The device can be operated in SIL mode, providing the safety function or in non-SIL mode. In
non-SIL mode, the key figures given in this manual (for details refer to
indicators
measures are disabled for performance reasons and the safety reaction is switched off.
on page 27) are not valid. During operation in non-SIL mode, some diagnostic
Safety relevant key
SAC4: Parameter input
The internal check functions can only detect range failures or incompatibilities in the whole data
set. They cannot decide whether the data is configured as intended.
The actual parameter setting must be executed carefully.
SAC5: Maintenance mode
The maintenance mode is intended to test a device which has already potentially failed. To
provide full test capability, the safe output (4..20 mA current output) is not blocked.
Consequently, the operator must implement other measures temporarily to keep the overall
system in a safe state.
SAC6: Resetting the fail-safe flag
When the safety reaction is triggered because a hazardous failure has been detected, a flag is
saved in persistent memory to prevent the device from starting safe operation after a reset.
The device must be completely tested (for details refer to
page 19). The fail-safe flag shall be reset only, if the operator is sure that the device is still intact
(for details refer to
safe operation as soon as the fail-safe flag is reset.
The NAMUR diagnostic information must not be used to decide whether the device is intact or
not. Reason is that this information is not safe, as the "latest" diagnostic message(s) may get lost
due to a device failure.
Resetting the fail-safe flags
on page 23). Note that the device will (re-)start
Operation modes and proof test
on
30
www.siemens.com/flow
10/2017 - A5E40875009-AB EN
SITRANS FX330
SAC7: Firmware update
Firmware update requires special tooling and can be provided by the authorised personnel of the
manufacturer only.
SAC8: Inspection intervals
Many external events, e.g. environment temperature, may cause the device to age faster than
expected. This has an effect on the failure rate which is assumed as constant over the lifetime at
reference conditions.
APPENDIX
6
For recommendations regarding the calculation of the proof test intervals refer to
modes and proof test
on page 19 and refer to
Useful lifetime
on page 29.
Operation
SAC9: Modification
A modification may have unexpected influence on the safety function. Such effects must be
analysed. This can only be done by deep knowledge of the internal construction of the device.
SAC10: Repair
Repair of the device exceeding the defined exceptions need more tooling, test and calibration
facilities than available in the field.
SAC12: Supervision of failure current
The preferred failure current is low as it is a state with the lowest energy consumption.
Nevertheless, a failure might prohibit the output of the lower failure current. In that case the
output will be switched to the high failure current.
The failure current (low/high) is configurable but the configuration is only effective in non-SIL
mode. Consequently, a device evaluating the current output must react on both failure currents,
not only on the configured one.
10/2017 - A5E40875009-AB EN
www.siemens.com/flow
31
For more information
www.siemens.com/flow
www.siemens.com/processautomation
Siemens AG
Process Industries and Drives
Process Automation
76181 Karlsruhe
Germany
Product
Information
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.