Siemens SITRANS F M MAGFLO MAG 3100 Instructions Manual

s
Introduction
ENGLISH
INSTRUCTIONS
®®
®
SITRANS F M MAGFLO Electromagnetic flowmeter type MAG 3100 with
®®
DEUTSCH
FRANÇAIS
DANSK
PTFE or PFA liner
Siemens Flow Instruments SITRANS F M MAGFLO sensor and a transmitter. These instructions only describe the sensor installation. For further information on the transmitter installation, please refer to the SITRANS F M MAGFLO
Technical Documentation (handbooks, instructions, manuals etc.) on the complete product range SITRANS F can be found on the internet/intranet on the following links:
English: http://www4.ad.siemens.de/WW/view/en/10806951/133300
electromagnetic flowmeters consist of a
handbook.
A5E01019391
Dimensions and
MAG 3100 with PTFE or PFA liner
weight
Nominal
size
[mm] [inch] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [kg]
15 ½ 187 338 59 104 - - 200 200 200 200 6 4 25 1 187 338 59 104 - - 200 200 200 200 6 5 40 197 348 82 124 - - 200 200 200 200 6 8 50 2 205 356 72 139 - - 200 200 200 200 6 9 65 212 363 72 154 200 - 200 200 272 200 6 11
80 3 222 373 72 174 200 - 272 272 272 200 100 4 242 393 85 214 250 - 250 250 310 250 6 16 125 5 255 406 85 239 250 - 250 250 335 250 6 19 150 6 276 427 85 282 300 - 300 300 300 300 6 27 200 8 304 455 137 338 350 350 350 350 350 350 8 40 250 10 332 483 157 393 450 450 450 450 450 450 8 60 300 12 357 508 157 444 500 500 500 500 500 500 8 80 350 14 362 513 270 451 550 550 550 550 550 550 8 110 400 16 387 538 270 502 600 600 600 600 600 600 10 125 450 18 418 569 310 563 600 600 600 600 600 600 10 175 500 20 443 594 350 614 600 625 680 600 730 600 600 24 494 645 430 715 600 750 800 600 860 600
1
) When earthing flanges are used, the thickness of the earthing flange must be added to the built-in length
2
)TE = Type E grounding ring for PTFE only
3
) Weights are approx. and for PN 16 without transmitter
4
) PN 35 DN 500 = 680 mm
5
) PN 35 DN 600 = 750 mm
6
) PN 35 DN 80 = 272 mm
- Not available, D = Outside diameter of flange, see flange tables
A A1BD
1
EN 1092-1-2001
PN PN PN Class Class Class 21 (PN 21)
6, 10, 16 25 40 150 300 Class 35 (PN 35)
1)
L
BS 1560/ANSI 16.5
AS 2129 E T
AS 4087
Class 14 (PN 16)
6)
4)
5)
2)
Weight
E
612
10 200 10 287
3)
SFIDK.PI.024.E4.52
SITRANS F M MAGFLO
®®
®
®®
Electromagnetic flowmeter type MAG 3100 with PTFE or PFA liner
Installation, general
Reading and operating the flowmeter is pos­sible under almost any installation condi­tions because the display can be oriented in relation to the sensor. To ensure optimum flow measurement attention should be paid to the following:
The sensor must always be completely full with liquid.
Therefore avoid:
Installation at the highest point in the pipe system.
Installation in vertical pipes with free out­let.
For partially filled pipes or pipes with down­ward flow and free outlet the flowmeter should be located in a U-tube.
Installation in vertical pipes
Recommended flow direction: upwards. This minimizes the effect on the measurement of any gas/air bubbles in the liquid.
2
SITRANS F M MAGFLO
®®
®
®®
Electromagnetic flowmeter type MAG 3100 with PTFE or PFA liner
Installation, general
(continued)
Installation in horizontal pipes
The sensor must be mounted as shown in the upper figure. Do not mount the sensor as shown in the lower figure. This will position the electrodes at the top where there is possibility for air bubbles and at the bottom where there is possibility for mud, sludge, sand etc. If using empty pipe detection, the sensor can be tilted 45° , as shown in the upper figure.
Measuring abrasive liquids and liquids containing particles
Recommended installation is in a vertical/ inclined pipe to minimize the wear and de­posits in the sensor.
Inlet and outlet conditions
To achieve accurate flow measurement it is essential to have straight lengths of inlet and outlet pipes and a certain distance between pumps and valves. It is also important to centre the flowmeter in relation to pipe flanges and gaskets.
Pressure drop
The flowmeter can be installed between two reducers (e.g. DIN 28545). At 8° the follow­ing pressure drop curve applies. The curves are applicable to water.
Example:
A flow velocity of 3 m/s (V) in a sensor with a diameter reduction from DN 100 to DN 80
= 0.8) gives a pressure drop of 2.9
(d
1/d2
mbar.
3
SITRANS F M MAGFLO
®®
®
®®
Electromagnetic flowmeter type MAG 3100 with PTFE or PFA liner
Installation, general
For PTFE liner
For PFA liner
The sensor is equipped with a liner of PTFE teflon. At delivery the sensor is mounted with wooden blanks to hold the liner in place during transportation and storage. These blanks should remain on the sensor until installation. Without the blanks the liner will creep back towards its original shape and installation will be more difficult to carry out.
The sensor should max. be left a few hours without the blanks.
Immediately before installation, remove the blanks.
The sensor is equipped with a liner of PFA. At delivery the sensor is mounted with blanks to protect the liner during transportation and storage. These blanks should remain on the sensor until installation.
Potential equalization
Before installation, remove the blanks without using sharp objects which can damage the liner.
Electrically conductive piping
Potential equalization with an electrically con­ductive pipe. Use an earth straps on one side.
Non-conductive piping
Here an earthing flange is used, placed bet­ween flowmeter and the adjacent pipe flange. Earthing flange type E for PTFE. For PFA flat rings must be used.
4
SITRANS F M MAGFLO
®®
®
®®
Electromagnetic flowmeter type MAG 3100 with PTFE or PFA liner
Cathodic protected piping
Earting flanges
For PTFE liner
Special attention must be given to systems with cathodic protection.
By compact mounting:
The transmitter must be supplied through an isolation transformer. The terminal "PE" must never be connected.
By remote mounting:
The screen must only be connected at the sensor end via a 1.5 μF condensator. The screen must never be connected at both ends.
By isolated sensor:
If above mentioned connections are unac­ceptable, the sensor must be isolated from the pipe work.
Where necessary on non conductive pipes, mount earthing flanges type E. For potential equalization one earthing flange is sufficient even for bidirectional flow. With unidirectional flow the earthing flange should be mounted on the inlet side.
In special cases with abrasive flow the earthing flanges will also work as inlet protection.
High temperature sensors are delivered with two factory mounted earthing flanges. No fur­ther action need to be taken for potential equali­sation.
For PFA liner
Earthing flanges must be connected to the meter body with the enclosed earthing straps.
Where necessary on non conductive pipes, mount flat earthing rings.
For potential equalization one earthing ring is sufficient even for bidirectional flow. With uni­directional flow the earthing ring should be mounted on the inlet side.
In special cases with abrasive flow the earthing ring will also work as inlet protection.
Earthing rings must be connected to the meter body with the enclosed earthing straps.
5
SITRANS F M MAGFLO
®®
®
®®
Electromagnetic flowmeter type MAG 3100 with PTFE or PFA liner
Effect of temperature and material on working pressure
Metric (Pressures in bar)
PN rated flanges Material Flange Temperature group rating 20 50 100 150 180
1C1 PN 6 6.0 6.0 6.0 5.8 5.6 (A105) PN10 10.0 10.0 10.0 9.7 9.4
PN16 16.0 16.0 16.0 15.6 15.1 PN 25 25.0 25.0 25.0 24.4 23.7
PN 40 40.0 40.0 40.0 39.1 37.9 2C1 PN 6 5.5 5.3 4.5 4.1 3.8 (304) PN 10 9.1 8.8 7.5 6.8 6.3
PN 16 14.7 14.2 12.1 11.0 10.2
PN 25 23.0 22.1 18.9 17.2 16.0
PN 40 36.8 35.4 30.3 27.5 25.5 2C2 PN 6 5.5 5.3 4.6 4.2 3.9 (316) PN 10 9.1 8.9 7.8 7.1 6.6
PN 16 14.7 14.3 12.5 11.4 10.6
PN 25 23.0 22.3 19.5 17.8 16.5
PN 40 36.8 35.6 31.3 28.5 26.4
ANSI flanges Material Flange Temperature group rating 20 38 93 149 180
1.1 Cl. 150 19.7 19.7 17.9 15.9 14.7 (A105) Cl. 300 51.0 51.0 46.6 45.2 44.4
2.1 Cl. 150 19.0 19.0 15.9 14.1 13.6 (F304) Cl. 300 49.7 49.7 41.4 37.2 35.5
2.2 Cl. 150 19.0 19.0 16.2 14.8 14.1 (F316) Cl. 300 49.7 49.7 42.8 38.6 36.9
°°
° C
°°
°°
° C
°°
Imperial (Pressures in Psi)
PN rated flanges Material Flange Temperature group rating 5 122 212 302 356
ASTM PN 6 87 87 87 84 81 A105 PN 10 145 145 145 141 136
PN 16 232 232 232 226 219 PN 25 363 363 363 354 344
PN 40 580 580 580 567 550 ASTM PN 6 80 77 65 59 55 A240 PN 10 132 128 109 99 91 304 PN 16 213 206 175 160 148
PN 25 334 320 274 249 232
PN 40 534 513 439 399 370 ASTM PN 6 80 77 67 61 57 A240 PN 10 132 129 113 103 96 316 PN 16 213 207 181 165 154
PN 25 334 323 283 258 239
PN 40 534 516 454 413 383
ANSI flanges Material Flange Temperature group rating 5 100 200 300 356
ASTM Cl. 150 285 285 260 230 213 A105 Cl. 300 740 740 675 655 644 ASTM Cl. 150 275 275 230 205 197 A240 Cl. 300 720 720 600 540 515 F304 ASTM Cl. 150 275 275 235 215 204 A240 Cl. 300 720 720 620 560 535 F316
°°
° F
°°
°°
° F
°°
The above tables show the effect that an increase of temperature or change of material have on the maximum working pressure of the flange. The values are independent of nominal size. For intermediate temperatures use value from nearest higher temperature.
Example
For a PN 16 flange in 2C2 (316) material at 80 degrees the maximum working pressure should be taken as 12.5 bar.
Installation
Tightening
The sensor must be mounted between two flanges. Gaskets are only necessary when the flowmeter is installed with earthing flanges as the liner replaces gaskets.
Standard bolts must be well lubricated and tightened evenly around the gasket. Leakage/ damage to the flowmeter or piping may arise if bolts are overtightened.
6
®®
®
SITRANS F M MAGFLO
®®
Electromagnetic flowmeter type MAG 3100 with PTFE or PFA liner
Maximum allowable torques
(to meet PED)
Nominal Maximum torque
size EN 1092-1 EN 1092-1 EN 1092-1 EN 1092-1 EN 1092-1 ANSI B16.5 ANSI B16.5 AS 2129 JIS JIS
PN 6 PN 10 PN 16 PN 25 PN 40 Class 150 Class 300 Table E K10 K20 mm Inch Nm F/Lbs Nm F/Lbs Nm F/Lbs Nm F/Lbs Nm F/Lbs Nm F/Lbs Nm F/Lbs Nm F/Lbs Nm F/Lbs Nm F/Lbs 1”N/AN/AN/AN/AN/AN/AN/AN/A107N/AN/A32648686 251"N/AN/AN/AN/AN/AN/AN/AN/A161275 759716121612 40 1½” N/A N/A N/A N/A N/A N/A N/A N/A 34 25 9 7 18 13 17 13 20 15 20 15 50 2" N/A N/A N/A N/A N/A N/A N/A N/A 46 34 20 14 11 8 20 15 27 20 13 10 65 2½” 10 7 N/A N/A 25 18 N/A N/A 34 25 25 18 16 12 21 16 36 27 18 13 80 3" 25 18 N/A N/A 25 18 N/A N/A 42 31 34 25 24 18 32 23 21 16 28 21 100 4" 25 18 N/A N/A 25 18 N/A N/A 72 53 26 19 34 25 24 18 26 19 37 27 125 5" 25 18 N/A N/A 32 24 N/A N/A 114 84 42 31 42 31 33 24 43 32 59 44 150 6" 25 18 N/A N/A 50 37 N/A N/A 144 106 57 42 35 26 40 30 76 56 40 30 200 8" 25 18 50 37 52 38 105 77 185 137 88 65 57 42 61 45 46 34 62 45 250 10" 25 18 50 37 88 65 160 118 300 221 99 73 57 42 62 46 72 53 113 83 300 12" 50 37 60 44 117 86 170 125 320 236 132 97 86 63 78 58 56 41 96 71 350 14" 50 37 60 44 120 89 240 177 450 332 225 166 N/A N/A 147 109 72 53 147 108 400 16" 50 37 88 65 170 125 330 244 650 480 210 155 N/A N/A 168 124 115 85 175 129 450 18" 56 41 92 68 170 125 320 236 570 421 220 162 N/A N/A 164 121 109 80 184 135 500 20" 53 39 103 76 230 170 390 288 740 546 200 148 N/A N/A 194 143 127 93 211 155 600 24" 81 60 161 119 350 258 560 413 1220 900 280 207 N/A N/A 306 225 150 111 255 188
Torque calculations
Manufacturer’s design and safety statement
All values are theoretical and are calculated making the following assumptions:
1. All bolts are new and material selection is according to EN 1515-1 table 2.
2. The standard flange gasket material to be used between the flowmeter and mating flanges should not exceed 75 shore A durometer.
3. All bolts are galvanized and adequately lubricated.
4. The values are calculated for use with carbon steel flanges.
5. Flowmeter and mating flanges are correctly aligned.
1. Responsibility for the choice of lining and electrode materials with regard to their abrasion and corrosion resistance lies with the purchaser; the effect of any change in process medium during the operating life of the flowmeter should be taken into account. Incorrect selection
of lining and/or electrode materials could lead to a failure of the flowmeter.
2. It is the responsibility of the user to ensure that stresses and loading caused by earthquakes, traffic, high winds and fire damage are taken into account during installation, when appropriate. These forces are not taken into account during flowmeter design.
3. It is the responsibility of the user to ensure that the flowmeter is installed such that it does not act as a focus for pipeline stresses. External loadings are not taken into account during flowmeter design.
4. During operation do not exceed the pressure and/or temperature ratings indicated on the data label or in the installation instructions.
5. It is the responsibility of the user to ensure that all installations include over pressure protection, means for draining/venting, and that adequate protection is provided to minimise any risk of contact with hot surfaces.
6. Under the Pressure Equipment Directive this product is a pressure accessory, and not approved for use as a safety accessory, as defined by the Pressure Equipment Directive.
emoval of the terminal box except by Siemens Flow Instruments or their approved agents
7. R
will invalidate the PED conformity of the product.
In accordance with the Pressure Equipment Directive (97/23/EC)
7
s
INSTRUCTIONS
DEUTSCH
®®
®
SITRANS F M MAGFLO Magnetisch induktiver Durchflussmesser Typ MAG 3100 mit PTFE- oder PFA- Auskleidung
®®
Einführung
Abmessungen und Gewichte
Siemens Flow Instruments SITRANS F M MAGFLO
magnetisch-induktive Durchflussmesser bestehen aus einem Messaufnehmer und einem Messumformer. Diese Instruktion beschreibt nur die Montage des Messaufnehmers. Für weitere Informationen über die Montage des Messumformers, siehe bitte das SITRANS F M MAGFLO
Produkthandbuch.
Technische Unterlagen (Handbücher, Instruktionen, Betriebsanleitung usw.) des kompletten Warenangebotes von SITRANS F sind auf dem Internet/Intranet unter folgenden Links verfügbar
Deutsch:
http://www4.ad.siemens.de/WW/view/de/10806951/133300
MAG 3100 mit PTFE- oder PFA-Auskleidung
A5E01019391
Nominelle
Nennweite
[mm] [inch] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [kg]
15 ½ 187 338 59 104 - - 200 200 200 200 6 4 25 1 187 338 59 104 - - 200 200 200 200 6 5 40 197 348 82 124 - - 200 200 200 200 6 8 50 2 205 356 72 139 - - 200 200 200 200 6 9 65 212 363 72 154 200 - 200 200 272 200 6 11
80 3 222 373 72 174 200 - 272 272 272 2006)612 100 4 242 393 85 214 250 - 250 250 310 250 6 16 125 5 255 406 85 239 250 - 250 250 335 250 6 19 150 6 276 427 85 282 300 - 300 300 300 300 6 27 200 8 304 455 137 338 350 350 350 350 350 350 8 40 250 10 332 483 157 393 450 450 450 450 450 450 8 60 300 12 357 508 157 444 500 500 500 500 500 500 8 80 350 14 362 513 270 451 550 550 550 550 550 550 8 110 400 16 387 538 270 502 600 600 600 600 600 600 10 125 450 18 418 569 310 563 600 600 600 600 600 600 10 175 500 20 443 594 350 614 600 625 680 600 730 6004) 10 200 600 24 494 645 430 715 600 750 800 600 860 6005) 10 287
1
) Beim Ensatz von Erdungsflanschen muss die Wandstärke zur Gesamtlänge hinzugerechnet werden
2
)TE = Typ E Erdungsflansch
3
) Die Gewichtsangaben sind Näherungswerte und gelten für PN 16 Flanschausführungen ohne Messumformer
4
) PN 35 DN 500 = 680 mm
5
) PN 35 DN 600 = 750 mm
6
) PN 35 DN 80 = 272 mm
- Nicht verfügbar, D = Außendurchmesser des Flansches
A A1BD
1
EN 1092-1-2001
PN PN PN Class Class Class 21 (PN 21)
6, 10, 16 25 40 150 300 Class 35 (PN 35)
1)
L
BS 1560/ANSI 16.5
AS 2129 E T
AS 4087
Class 14 (PN 16)
E
2)
Gewicht
3)
SFIDK.PI.024.E4.52
SITRANS F M MAGFLO
®®
®
®®
Magnetisch induktiver Durchflussmesser Typ PTFE- oder PFA-Auskleidung
Einbau, allgemein
Der Durchflussmesser kann in jeder Ein­baulage abgelesen werden, da die Anzeige drehbar ist und in jeder beliebigen Position im Verhältnis zum Messaufnehmer einge­baut werden kann. Die endgültige Position sollte vor der Montage festgelegt werden. Um optimale Messergebnisse zu sichern, sind folgende Hinweise zu beachten:
Der Messaufnehmer muss immer vollstän­dig gefüllt sein.
Vermeiden Sie:
Einbau an höchster Stelle des Rohrsys­tems
Einbau in einer senkrechten Rohrleitung mit freiem Ablauf.
Ist eine nur teilweise gefüllte Rohrleitung oder der freie Ablauf nicht zu vermeiden, sollte der Durchflussmesser gedükert wer­den.
Einbau in einer senkrechten Rohrleitung
Empfohlene Strömungsrichtung: von unten nach oben. Dadurch werden ungenaue Messergebnisse, verursacht durch Gas- bzw. Luftblasen im Medium, vermieden.
9
Loading...
+ 19 hidden pages