Siemens SITRANS F FUH1010, SITRANS F FUH1010BX, SITRANS F FUH1010GX, SITRANS F FUH1010DVX, SITRANS F FUH1010X, SITRANS F FUH1010GCX, SITRANS F FUH1010GCSX, SITRANS F FUH1010SPVX, SITRANS F FUH1010PVX Operating Instructions Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
SITRANS F
SITRANS FUH1010 NEMA 7 Compact
Interface Detector 7ME3601-1, 7ME3601-2
Operating Instructions
Siemens Hardware
6/2014Edition
Answers for industry.
Errata
1010FMA-45
ERRATA
Power Supply Wiring Procedure Update
NOTE: The following applies to System 1010X, 1010BX, 1010DVX, 1010PVX, 1010GX,
1010GCX, 1010GCSX and 1010SPVX Flowmeter installation manuals.
Replace the “Power Connections” description and set up procedure with the following. Note that
paragraph numbers are different for all the above mentioned manuals. The example below is for
the 1010X manual.
NOTE: For flowmeters refer to d
rawings 1010X-7 (1 of 3) & 1010DX-7 (1 of 3) and
for Interface Detectors refer to drawings 1010BX-7 (1 of 3) & 1010BDX-7
(1 of 3).
2.2POWER CONNECTIONS
2.2.1 INPUT POWER CONNECTOR (P8) AND FUSE (F1) LOCATIONS
The standard 1010X flow computer either requires 100/120/200 VAC or one of three 9-36 VDC
power sources for its power input. The power input is protected by a GMA 2A fuse (F1). Please
replace this fuse with the exact type if it becomes necessary to do so.
WARNING
Do not connect AC or
DC power to flowmeter
until the correct type of
input power is determined. See P/N
tables on next page.
Contact with exposed
wiring may lead to fire,
electric shock, or serious personal injury.
Fuse (F1) GMA 2A
Cable
Clamp
AC HOT NEU GND
DC + - GND
WARNING
Connect power per instructions below.
See field manual for complete power
supply wiring procedures.
Terminal
Number
1
2
3
Sample Power Label Located Inside Rear
Housing Cover.
1010X-6SS2
90-230 VAC
(Single Phase)
Hot
Neutral
Ground
1
2
3
This must be
connected to
Earth Ground.
Siemens Hardware
E-1
1010FMA-45Errata
GND
GND
3
2
1
HOT
+
DC
AC
P8
NEU
-
2
3
1
Connector
Mounting
Screws
Stripped Wire
Wire
Clamp
Screws
2.2.2 POWER SUPPLY WIRING
lUsing a 1/16" Hex key, loosen the 1010X Rear Housing Cover locking setscrew.
lUnscrew the Rear Housing Cover and remove.
IMPORTANT: Power Supply label is located inside the Rear Housing cover.
lLocate power supply connector J8. Use the tables below and the part number of your unit to
determine the correct input power source. (See also metal ID label on unit housing.)
*Typical 1010X Part Number Construction:
Root Meter Number
Transducer Support
Relay Support
Numeric Display
Power Supply Option
1010X-T2KNZPL2-S2----Safety Rating Option
Language Option
Meter Part Number *Power Supply P/NUser Supplied Power
Contains S prior to S_Code1010X-6SS290-230 VAC Single Phase
Contains a ZN prior to S_Code1010X-6ZNS29-36 VDC Negative Ground
Contains a ZP prior to S_Code1010X-6ZPS29-36 VDC Positive Ground
Contains a Z at end of P/N1010X-6Z9-36 VDC Floating
lPull wires through flowmeter case conduit cable hole.
lWire input power connector P8 for AC or DC power as shown below. Insert wires into wire
entry holes and secure by tightening wire clamp screws (see note on next page).
NOTE: Loosen Wire
Clamp Screw, insert
stripped end of wire
and then retighten.
NOTE: Power Supply connector wires should be stripped stranded or solid conductors
AWG 12 -18.
Input Power Connector (P8) Wiring
E-2
Errata
Menu Lockout
Switch (S1)
NOTE: The input power connector consists of a removable wire plug and PCB header located on
the 1010X-8 I/O module. Two screws secure the wire plug to the header. The connector assembly
is fully polarized for fast and easy mating. The wire plug accepts stranded or solid conductors of
AWG 12 - 18. To insert a wire into the wire plug, strip back the insulation by 0.31" (8 mm), loosen
the wire clamp screw, insert the stripped wire end and then re-tighten the wire clamp screw.
lPlug input power connector P8 into connector J8 and secure using two captive connector
mounting screws as indicated above.
lSecure power-input cable with cable clamp to prevent wire breakage.
lReplace Rear Housing Cover and tighten setscrew.
lConnect the power cables to the appropriate power source previously selected from the tables
above and power up unit.
lIf unit is operational, turn power off and install transducer cables.
1010FMA-45
2.3THE MENU LOCKOUT SWITCH
System 1010X includes a menu lockout switch to prevent unauthorized access to the Installation
Menu. In addition, a password entry option is available (see Channel Setup). The menu lockout
switch (S1) resides on the I/O module on the right side of I/O wiring terminal block TB1 (see
below). Please switch to the unlocked position before attempting to program the flowmeter. We
recommend that the installation menu remains locked during normal operation. (Refer to appropriate manual section for TB1 and TB2 signal wiring.)
Siemens Hardware
E-3
Errata
1010FMA-61
ERRATA
FUH1010 Interface Detector Compact NEMA 7 Manual Updates
1. FUH1010 Interface Detector NEMA 7 Compact Flow Meter Manual
Troubleshooting Table Update
In the FUH1010 Interface Detector NEMA 7 Compact flow meter manual P/N CQO:1010BXFM-3 Revison
B replace the troubleshooting table in Section 2 - Installation Menu on pages 2-58, 2-59 and 2-60 with
the following:
Error or MessageProbable CauseSolution
Memory Full!
Memory Corrupted!
Chan Not Setup
Clr Active Memory?
Clr Save Data?
<EOT>Response to a request to output
No Sites - Press <ENTER>
Security
RTC ErrorComponent level problem.
Response to an attempt to save site
data when data memory is full.
Memory read error occurred while
accessing the active site data.
Response to an attempt to invoke
an operation that requires a channel to be enabled.
Use this function to restore operation if a severe event (e.g. a violent
power surge) disrupts system
operation.
[Clr Saved Data?] only appears
after pressing <Down Arrow> in
response to [Clr Active Memory?].
Datalogger data to the printer or
the Graphics screen when no
datalogger data exists or at the end
of a transmitted file.
Response while trying to recall/
delete a site setup when no sites
are stored.
Response upon charging previously
entered data when security switch
is in [Disable] position or security
code has been entered.
Delete an obsolete site or clear
Datalogger memory to make
room for the new data.
Refer to F4 reset procedure in
the Operation Instructions
manual.
Enable the channel [ChannelSetupChannel - Enable - Yes].
Note that a channel cannot be
enabled until an “Install” operation is completed.
Refer to F4 reset procedure in
the Operation Instructions
manual.
Answering [Yes] to [Clr Saved
Data?] will erase ALL saved
data. To invoke in RS-232 serial
mode, type @@@ and then
press <ENTER> key.
Set up the Datalogger.
Create a site.
Change switch position to
[Enable].
Enter previously set security
code.
Meter requires service. Request
RMA.
(continued)
Siemens Hardware
E-1
Error or MessageProbable CauseSolution
- - -F - - -Fault Alarm
• Loss of signal signal strength
• Recouple sensors with fresh
couplant.
• Change of Rx signal location (Beam
Blowing)
• Install Sensors in Direct mount
mode.
• Note: If problem persists call
Tech support.
1010FMA-61Errata
Re-space Index
Invalid Setup (use Direct Mode)
The measured liquid sonic velocity
(Vs) is more than +/- 25 % of the average Vs range.
During the Initial Makeup, the system
detects invalid sensor spacing, erroneous liquid/pipe parameters, or
some other factor that prevents it
from completing the Initial Makeup.
• Ensure proper pipe dimensions
and/or Liquid data entries are correct.
• Properly enter correct Sensor
Size into meter [Install Sensor]
menu.
• Confirm sensor spacing is cor-
rect by checking [Install Sensor]
menu spacing parameters.
This may be due to one of the following:
• An out-of-range data entry.
• An invalid condition; (e.g.,
overlapping sensors in Reflect
Mode). If selecting Direct Mode
does not resolve, review all site
setup and sensor installation
choices; particularly data entered for the pipe and liquid.
• In Reflect Mode, the flow
meter detects that the pipe wall
signal may impinge upon the
liquid signal. Use Direct Mode
instead.
E-2
Trigger <ENTER>, <UP Arrow>,
<DOWN Arrow>, or <LEFT Arrow> to abort install routine. Continue programming other site data
in anticipation of resolving the difficulty later. Call technical support
for help if necessary.
(continued)
Errata
Error or MessageProbable CauseSolution
Low Signal - Press <ENTER>
During the Initial Makeup the flow
meter decides that a level of the receive signal is insufficient for proper
operation.
Some reasons for low signal are:
• Invoking [Install Complete?] on
an empty pipe.
• Coupling compound insufficient,
not applied or evaporated. Reapply couplant.
• A disconnected or broken sen-
sor cable.
• The pipe needs to be condi-
tioned at the mounting location.
• Flush out large air bubbles.
• The sensor cables are defec-
tive or not connected to the correct channel.
1010FMA-61
Detection Fault
If it appears that the flow meter can
not complete an Initial Makeup this
means that the pipe and/or liquid conditions do not permit a recieve signal
that meets the flow detection standards.
The system will not operate.
• The Set Empty routine per-
formed when pipe was NOT actually empty.
• If you locate and correct the im-
proper condition immediately trigger <ENTER> to resume the installation procedure. Otherwise,
trigger the <Left Arrow> to abort
the installation and conduct a thorough investigation.
Attempt to improve operating conditions by reinstalling the sensors
at a different spacing offset, or
even at a different location on the
pipe.
Switching from Reflect to Direct
Mount may solve the problem.
However, operation may not be
possible if there is poor liquid, pipe
wall sonic conductivity or extreme
liquid aeration.
Siemens Hardware
E-3
1010FMA-61Errata
2. DIN Pipe Table Note
In Section 2, add the following note right after paragraph 2.2.1 How to Select a Pipe Class:
NOTE:
The DN sizes listed in the [Select Pipe Size] menu option list are referenced to DIN Table
2448. After selecting pipe size, check pipe OD and wall thickness for correct dimensions.
3. Empty Pipe Set Procedure Update
In Section 2, paragraph 2.4.10 Empty Pipe Set Menu replace the introductory paragraphs and
warning with the following:
The flow meter performs the MTYmatic routine automatically during its Initial Make-up to establish a standard setting for the Empty Pipe alarm. This process is normally sufficient for setting
this parameter. The [Empty Pipe Set] option list allows you to re-invoke MTYmatic, use an
Actual MTY routine (if application conditions allow you to empty and refill the pipe) or use the
Set Empty routine to set the empty pipe threshold by direct numeric entry.
How To Use the Actual MTY Command
If application conditions allow you to empty and refill the pipe, then you may choose to perform
the Actual Empty procedure; however, it is not required to do so.
WARNING: NEVER perform the Actual MTY procedure if the pipe can not be emptied.
E-4
IMPORTANT NOTICE
Controlotron is now part of:
Siemens Industry, Inc.
Industry Automation division
CoC Ultrasonic Flow
Hauppauge, NY 11788 USA
SITRANS FUH1010BX
INTERFACE DETECTOR
This equipment contains components that are
susceptible to electrostatic discharge (ESD).
Please observe ESD control measures during
the handling and connection process.
Digital Damping Procedure Update for Gas & Liquid Flowmeters
INTRODUCTION
The following Digital Damping procedure updates are for SITRANS F gas and liquid clamp-on
flowmeters.Replace the Digital Damping Control: (Hot Key 1 and 2) procedure in the “Detection Modes”
section (sub-paragraph: Command Modes) in the appropriate gas and liquid STIRANS F flowmeter
manuals.
FUG1010 Gas Clamp-on Flowmeter Manuals
Digital Damping Control: (Hot Key 1 and 2)
The FUG1010 permits user modification of the digital averaging used by the signal processing routines.
In general, the default damping values selected by the FUG1010 will provide optimal performance over
a wide range of transit time applications. However, in extreme cases of unstable flow, pulsating flow,
low signal levels or high electronic noise it may be necessary to override these default settings to
permit uninterrupted and reliable flow measurement.
Test Facilities Graph Screen
The FUG1010 Graph Screen includes the capability to access a set of command codes, which enable
a user to override a number of default meter settings. The most important parameter is the digitaldamping control, which can be accessed by pressing number <1> or <2> on the keypad while in the
Signal Graph Screen mode.
[MinDamp] Command
Pressing the <1> key will cause [MinDamp #] to appear on the command line at the lower left-hand
corner of the screen. The number listed to the right of the command code represents the exponent in
the FUG1010 exponential averaging routine, where the larger the number the greater the digital averaging.
Pressing the <+> key will increase the damping value. Likewise, pressing the <-> key will decrease
the damping value. To exit this mode, press the <0> key on the keypad.
[MaxDamp] Command
Pressing the <2> key will bring up the [MaxDamp] command. The function of this parameter is similar
to the [MinDamp] command described above; however, the two parameters interact in the following
manner. The MinDamp value must not exceed the MaxDamp value, therefore increasing the MinDamp
value above the previous MaxDamp value will set both parameters to the same value. In most cases,
it is preferred that both damping parameters be set to the same value, however, in cases where rapid
response to changes in gas sound velocity for flow rate is required, the two values may be set differently.
In this situation the meter will use the MaxDamp value when conditions are stable, but then switch to
a faster damping value (limited by MinDamp) when a significant change in sound velocity or flow rate
is perceived. To exit this mode, press the <0> key on the keypad.
Siemens Hardware
A-1
Manual Addendum
1010FMA-58
To access the Digital Damping Control using the Test Facilities Graph Screen, proceed as follows:
1. To use the Test Facilities Graph Screen you must have a working site.
2. To activate the Test Facilities Graph Screen:
zIn the main menu, scroll to the [Diagnostic Data] menu and select [Test Facilities].
zScroll down to [Graph], press the <Right Arrow> and highlight [Yes]. Press <ENT> to select.
zThe Test Facilities Graphic Screen will appear on the meter display as shown below.
Setting the Digital Damping Factor to a value HIGHER than the default value of 4 may be necessary
in cases where the signal to noise ratio (SN) is found to be unacceptably low (<15:1), but only if the
noise is determined to be asynchronous (i.e., not associated with the transmit or flowmeter timing
circuitry) as shown in the signal example above, where the baseline noise has a higher frequency
than the true gas signal.
The following application conditions may require a higher Digital Damping Factor:
zClose proximity to pressure control valves which may generate in-band acoustic noise
zVery low acoustic signal levels (ALC < 40%)
zHigh electronic noise from variable frequency drives or other external equipment.
A-2
Manual Addendum
To INCREASE the Digital Damping:
1. Press the <1> key while viewing the Test Facilities Graph Screen as shown above. The damping
control [MinDamp #] should appear on the command line at the lower left-hand corner of the
screen.
Note: The number listed to the right of the command code on the screen represents the
exponent in the exponential averaging routine, where the larger the number represents
the greater the digital averaging. Setting this exponent higher than 7 is generally not
recommended.
2, Pressing the <+> key will increase the MinDamp Factor by one unit for each key press. To exit this
mode, press the <0> key on the keypad.
1010FMA-58
The above example shows that increasing the Digital Damping reduces asynchronous noise.
Setting the Digital Damping factor to a value LOWER than the default value of 4 may be justified in
cases where pulsating flow is present (such as from a reciprocating compressor) or for the purpose
of diagnosing transient signal behavior. A pulsating flow condition that generates more than +/- 45
degrees of phase jitter will generally cause signal correlation problems when any digital averaging is
used. In this case it may be necessary to completely eliminate the digital averaging by reducing the
Digital Damping Factor to 0. In such a case it may also be necessary to install a narrow band tuned
amplifier (Input Module) if too much asynchronous noise exists.
To DECREASE the Digital Damping:
1. Press the <2> key while viewing the Test Facilities Graph Screen. The damping control [MaxDamp
#] should appear on the command line at the lower left-hand corner of the screen.
2. Pressing the <-> key will decrease the MaxDamp Factor by one unit for each key press. To exit this
mode, press the <0> key on the keypad.
Siemens Hardware
A-3
Manual Addendum
Liquid Clamp-on Flowmeter Manuals
Replace the Digital Damping Control: (Hot Key 1 and 2) procedure in the “Detection Modes” section
(sub-paragraph: Command Modes) in the following flowmeter manuals:
FUS1010 IP 65 (NEMA 4X) Clamp-On Flowmeter manual (CQO:1010NFM-3)
FUE1010 IP 65 (NEMA 4X) Clamp-On Flowmeter manual (CQO:1010ENFM-3)
FUH1010 IP 65 (NEMA 4X) Clamp-On Flowmeter manual (CQO:1010DVNFM-3)
FUH1010 IP 65 (NEMA 4X) Clamp-On Flowmeter manual (CQO:1010PVNFM-3)
FUP1010 IP 40 (NEMA 1) Clamp-On Portable Flowmeter manual (CQO:1010PFM-3)
FUE1010 IP 40 (NEMA 1) Clamp-On Portable Flowmeter manual (CQO:1010EPFM-3)
Digital Damping Control: (Hot Key 1 and 2)
The meter permits user modification of the digital averaging used by the signal processing routines. In
general, the default damping values selected by the METER will provide optimal performance over a
wide range of transit time applications. However, in extreme cases of unstable flow, pulsating flow, low
signal levels or high electronic noise it may be necessary to override these default settings to permit
uninterrupted and reliable flow measurement.
1010FMA-58
Test Facilities Graph Screen
The Graph Screen includes the capability to access a set of command codes, which enable a user to
override a number of default meter settings. The most important parameter is the digital dampingcontrol, which can be accessed by pressing number <1> or <2> on the keypad while in the Signal
Graph Screen mode.
[MinDamp] Command
Pressing the <1> key will cause [MinDamp #] to appear on the command line at the lower left-hand
corner of the screen. The number listed to the right of the command code represents the exponent in
the meter exponential averaging routine, where the larger the number the greater the digital averaging.
Pressing the <+> key will increase the damping value. Likewise, pressing the <-> key will decrease
the damping value. To exit this mode, press the <0> key on the keypad.
[MaxDamp] Command
Pressing the <2> key will bring up the [MaxDamp] command. The function of this parameter is similar
to the [MinDamp] command described above; however, the two parameters interact in the following
manner. The MinDamp value must not exceed the MaxDamp value, therefore increasing the MinDamp
value above the previous MaxDamp value will set both parameters to the same value. In most cases,
it is preferred that both damping parameters be set to the same value, however, in cases where rapid
response to changes in liquid sound velocity for flow rate is required, the two values may be set
differently. In this situation the meter will use the MaxDamp value when conditions are stable, but then
switch to a faster damping value (limited by MinDamp) when a significant change in sound velocity or
flow rate is perceived. To exit this mode, press the <0> key on the keypad.
A-4
Manual Addendum
To access the Digital Damping Control using the Test Facilities Graph Screen, proceed as follows:
1. To use the Test Facilities Graph Screen you must have a working site.
2. To activate the Test Facilities Graph Screen:
zIn the main menu, scroll to the [Diagnostic Data] menu and select [Test Facilities].
zScroll down to [Graph], press the <Right Arrow> and highlight [Yes]. Press <ENT> to select.
zThe Test Facilities Graphic Screen will appear on the meter display as shown below.
1482.1
1010FMA-58
Setting the Digital Damping Factor to a value HIGHER than the default value of 4 may be necessary in
cases where the signal to noise ratio (SN) is found to be unacceptably low (<15:1), but only if the noise
is determined to be asynchronous (i.e., not associated with the transmit or flowmeter timing circuitry)
as shown in the signal example above, where the baseline noise has a higher frequency than the true
liquid signal.
The following application conditions may require a higher Digital Damping Factor:
zClose proximity to pressure control valves which may generate in-band acoustic noise
zHigh un-dissolved gas solids content in liquid.
zHigh electronic noise from variable frequency drives or other external equipment.
Siemens Hardware
A-5
Manual Addendum
1010FMA-58
To INCREASE the Digital Damping:
1. Press the <1> key while viewing the Test Facilities Graph Screen as shown above. The damping
control [MinDamp #] should appear on the command line at the lower left-hand corner of the
screen.
Note: The number listed to the right of the command code on the screen represents the
exponent in the exponential averaging routine, where the larger the number represents
the greater the digital averaging. Setting this exponent higher than 7 is generally not
recommended.
2. Pressing the <+> key will increase the MinDamp Factor by one unit for each key press. To exit this
mode, press the <0> key on the keypad.
1482.1
The above example shows that increasing the Digital Damping reduces asynchronous noise.
Setting the Digital Damping factor to a value LOWER than the default value of 4 may be justified in
cases where pulsating flow is present (such as from a reciprocating pump) or for the purpose of
diagnosing transient signal behavior. A pulsating flow condition that generates more than +/- 45 degrees
of phase jitter will generally cause signal correlation problems when any digital averaging is used. In
this case it may be necessary to completely eliminate the digital averaging by reducing the Digital
Damping Factor to 0.
To DECREASE the Digital Damping:
1. Press the <2> key while viewing the Test Facilities Graph Screen. The damping control [MaxDamp
#] should appear on the command line at the lower left-hand corner of the screen.
2. Pressing the <-> key will decrease the MaxDamp Factor by one unit for each key press. To exit this
mode, press the <0> key on the keypad.
5.11The Dual Channel Menu Chart ...................................................................... 5-9
The Meter Type Menu .................................................................................... 5-9
The Meter Facilities Menu ............................................................................ 5-9
The Dual Channel Menu .............................................................................. 5-10
APPENDICES
Appendix A - Engineering Drawings ....................................................................................A-1
Index
Pipe Table
Siemens Hardware
vii
1010BXFM-3Section 1
1.INTRODUCTION
Congratulations on your purchase of the System 1010BX Interface Detector. The System 1010BX
is a compact NEMA-7/EExd-rated explosion-proof Interface Detector. Intended for dedicated
applications, this versatile meter is easy to set up and operate. The 1010BX represents the
state-of-the-art in computerized instrumentation. We are confident that in a very short time,
you will appreciate its unrivaled performance and features; especially Controlotron’s ground
breaking enhanced transit-time Digitally Coded MultiPulse™ technology and the on-line automatic and interactive site setup help facility.
This section explains how to install the System 1010BX Interface Detector with a minimum of
effort. It also will illustrate how to use the Installation Menu to set up the system and explain
the basic connections to and from the instrument. For additional information on connections,
see the drawings at the end of manual.
1.1IMPORTANT SAFETY CONSIDERATIONS
The System 1010BX Interface Detector operates from either an external AC or DC power
source. Please observe all the electrical safety codes, etc., that apply to your application. We
recommend that only experienced personnel with knowledge of local electrical codes and safety
operating procedures perform the installation and wiring. It is solely the user’s responsibility
to operate this equipment safely. Controlotron cannot accept responsibility for any damage
that may occur due to failure to observe any local safety rules.
If this equipment is used for a hazardous application (high line pressure, hostile liquid characteristics, perilous atmosphere, etc.), the end-user must ensure that only properly trained personnel are involved in its installation and operation.
Please do not let the size of the Installation Menu intimidate you. Almost all menu cells already contain default parameters. To begin operation, you only need to access the menu cells
that control a required parameter, such as the pipe outer diameter. You will see that by accepting most defaults, you can set up the meter in about five minutes.
1.2INTERFACE DETECTOR INSTALLATION STEPS
The following are typical steps to complete the installation procedure.
zCollect the site data (pipe and liquid data, part numbers, etc.).
zChoose a mounting location for the Interface Detector and transducers.
zMount the Interface Detector at the selected location.
zPrepare pipe for transducer mounting.
zAccess the Installation Menu and create a site (see paragraph 1.16.1).
zEnter pipe parameters (see paragraph 2.2).
zInvoke transducer install procedure (see paragraph 2.4).
zMount transducers on pipe and connect to Interface Detector (see Section 3).
zComplete transducer install menu operation (see paragraph 2.4).
Siemens Hardware
1-1
1010BXFM-3Section 1
1.3SYSTEM HARDWARE DESCRIPTION
System 1010BX is housed inside a cylindrical explosion-proof NEMA-7 aluminum, epoxy painted
case. The main metering compartment front and rear sections are sealed with an O-Ring with
separate threaded covers. The front section houses the main electronics and the optional
Magnetic Touch-Panel User Interface with a 2x16 character LCD Alphanumeric Display viewable through a tempered glass window. The rear section contains terminal blocks for the fused
power input and data I/O wiring. The primary instrumentation output is an isolated 4-20 mA
current loop. The meter includes a conventional RS-232 I/O port.
The main metering compartment is connected to the secondary housing by an aluminum pipe
that provides a pass-through for flow transducer and temperature sensor cabling. The secondary housing provides screw-on wire clamp terminals for flow and temperature sensors. To
maintain the NEMA-7 explosion-proof rating, all cabling and the transducer physical and electrical design must be in compliance with hazardous area specifications.
SPECIFICATIONS
Temperature:Operating TemperatureOperational and StorageElectronics: 14ºF to 122ºF (-10ºC to 50ºC)
LCD display: 14ºF to 122ºF (-10ºC to 50ºC)
Storage Temperature
Electronics: -4ºF to 140ºF (-20ºC to 60ºC)
*T ransducers temperature ratings depend on the individual
transducer type(s).
Power Consumption110/220 VAC, less than 10 watts.
G-Force RatingInstrument survives 3’ drop onto 1” plywood (standard indus-
trial drop test). Mechanical design supports operation in a high
vibration environment.
For Hazardous Area UseExplosion-proof case designed for installation in Division 1/Zone
1 hazardous environments when installed per our instructions.
Agency approvals: CE (for EM) and FM/CENELEC pending. International approvals pending.
Provisions for User Menu AccessMagnetic triggers (4-Arrows + Enter).
RS-232 interface for menu access and Datalogger dump.
OptionsStainless Steel Case
Dial-up Modem
One RTD temperature sensing channel (measures clamp-on
liquid temperature
Blind System (programming vial serial link only)
1.4STANDARD FEATURES
zSame features as the 1010 family of NEMA 4X flow computers except constructed in a
compact NEMA-7 explosion-proof housing.
zFlexible Setup options using either Magnetic Wand or a PC connected to RS-232 port.
zIntegral 2x16 Character LCD panel display shows real-time data and Installation Menu
for Magnetic Wand programming.
zFlexible mounting - either on pipe or located up to 300 feet (100m) from the transducers.
For distances greater then 300 feet, please contact Controlotron Customer Service.
1-2
Loading...
+ 196 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.