Siemens SITOP PSE200U, SITOP SEL1200, SITOP SEL1400 User manual

Brochure
Edition /
SITOP power supply
Electronic protection and fast fault localization in  V DC load circuits
usa.siemens.com/sitop
The SITOP selectivity modules distribute the load current across several 24 V DC load circuits and monitor them reliably for overload and short-circuit conditions. The electronics permit brief current peaks caused, for example, by high inrush currents, but isolate load circuits in the event of an extended overload. This is ensured even on high­resistance lines. In such cases, miniature circuit breakers fail to trip, or trip too late, even if the power supply unit could deliver the required tripping current. The SITOP expansion modules continue to reliably supply 24 V to the load circuits not affected by an overload and can prevent a total system failure. The new SITOP SEL selectivity modules, which have more outputs, an additional tripping characteristic and detailed diagnostics, now offer even more efficient protection for your plant.
Miniature circuit breakers with high current consumption
Miniature circuit breakers are often still used for the selective protection of 24 V DC load circuits. In many cases, however, when interacting with switched-mode power supply units, they do not offer reliable protection. They require several times the rated current in order to trip within a few milliseconds. Because stabilized power supplies limit their output current electronically when there is a critical overload, the tripping current is not always guaranteed. This can cause the 24-V supply to break in and the PLC to go to Stop. Even if the power supply unit could supply the current, immediate tripping is not necessarily assured, because with this high current requirement, the line resistance can no longer be neglected. It prevents the required tripping current from flowing. Therefore fast tripping is only possible up to certain cable lengths and starting from larger cable cross-sections. In addition to the line resistance, the overall circuit design (e.g. contact resistances at terminals) must be taken into consideration when configuring miniature circuit breakers.
SITOP selectivity modules – optimized for switched-mode power supply units
The selectivity modules are specially designed to protect 24 V DC individual load circuits supplied by switched-mode power supplies. Individual setting of the tripping current allows optimum adaptation to the respective load circuit. Engineering effort is minimal since the switch-off characteristic always guarantees reliable tripping – even with high line impedances that limit the short-circuit current.
HMI
Selectivity
Power supply
As an electronic monitor, the SITOP selectivity module switches faulty 24 V DC load circuits off immediately, and continues to supply the other loads without any interruption.
module
24 V DC
Actor/SensorPLC
G_KT01_XX_01567
SITOP PSE200U and SEL1400 – limiting characteristic offers maximum safety
In terms of the tripping characteristic, the new 8-channel SEL1400 modules behave like the tried and tested 4-channel PSE200U modules. They limit the output current to 150% of the set value, corresponding to the overload behavior of the SITOP power supplies of the Advanced and Standard product lines. This means that, even in the case of a short circuit, no overload can occur and consequently no voltage drop at the output of the power supply unit. Even when a power supply without overload reserves is used, the patented SITOP concept ensures reliable protection: The electronics continuously monitor the 24 V DC input voltage. As soon as the 24 V DC threatens to fail, the path with a higher current than the set current is disconnected immediately. All other load circuits continue to be supplied without interruption. Even loads that do not comply with the PLC standard and can only bridge a few milliseconds of undervoltage, continue to operate without any problem.
Tripping characteristics
SITOP SEL1200 – switching characteristic for standard protection
The new SEL1200 8-channel selectivity modules also allow higher, brief overload currents. The higher the current, the faster the output is shut down. It is possible that the power supply is loaded for a few milliseconds with a current significantly higher than that which is set. If the power supply unit only has limited overload reserves, it may result in a momentary drop in the 24 V supply. For loads that comply with the PLC standard, however, this is not critical. For stan­dard applications, the SEL1200 selectivity module therefore offers very efficient protection.
For 24 V loads with a high inrush current, the switching characteristic even offers advantages, since whatever applies at shutdown also applies when switching on. High currents are not limited, but can be permitted for a short time. In addi­tion, two outputs of the SITOP SEL1200 or 1400 selectivity modules can be connected in parallel for a 15 A rated current.
Time in
seconds
100
Normal operation
Switch-off after approx. 5 s
0.1
0.01
10
5
1
Current limitation to 150% for approx. 100 ms, then switching off the faulty output
0
SITOP SEL1400 / PSE200U characteristic: limiting
Shutdown response for current requirement per output
circuit relative to set value (I/I set value = 100%):
Power requirement: Shutdown after:
From 0 A to 100% (set value) No shutdown
From set value to 150%
Above 150%
Above set value with simultaneous collapse of supply voltage below 20 V DC
1)
1)
of set value Current limiting to approx.
Approx. 5 seconds
1)
150%
for typ. 100 ms, then
shutdown Immediate shutdown
Switching SITOP SEL1200
Limiting SITOP SEL1400/PSE200U
The higher the current, the faster the trip
250% I-set200%180%150%100%
SITOP SEL1200 characteristic: switching
Shutdown response: The higher the current, the faster the
faulty output is shut down, in line with the limit load
2
integral i
t.
Startup characteristics: Supports loads with high inrush current, whereby the supply voltage can drop to 15 V
G_KT01_XX_01573
Startup characteristics: Load ramp-up to 150% of set value with stable voltage supply of at least 20 V
1)
SITOP PSE200U versions with NEC Class 2: 110%
Loading...
+ 5 hidden pages