SITOP power supply
Manual
SITOP PSU200M 24 V/5 A 6EP1333 SITOP PSU200M 24 6EP1334 SITOP modular 24 6EP1336 SITOP PSU100M 24 6EP1337-3BA00
04.2018
C98130
Overview
Safety instructions
1
Description, device design, dimension drawing
2
Mounting/removal
3
Mounting position, mounting clearances
4
Installation
5
Technical data
6
Safety, approvals, EMC
7
Ambient conditions
8
Applications
9
Environment
10
Service & Support
11
-3BA10 V/10 A
-3BA10
V/20 A
-3BA00
-A7548-A1-4-7629
V/40 A
Siemens AG Division Process Industries and Drives Postfach 48 48 90026 NÜRNBERG GERMANY
C98130-A7548-A1-4-7629
Copyright © Siemens AG 2018. All rights reserved
Legal information
Warning notice system
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
Qualified Personnel
personnel qualified
Proper use of Siemens products
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
Disclaimer of Liability
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.
The product/system described in this documentation may be operated only by task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems.
Note the following:
documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.
for the specific
04/2018 Subject to change

Overview

The 1-phase/2-phase power supply from the SITOP modular product line is a powerful, stabilized technology power supply for automated machines and systems.
The key benefits of the product include:
Wide-range input, which allows it to be connected to almost any 1-phase/2-phase line supply around the world
Output voltage can be adjusted in the range 24 - 28.8 V
Power boost during operation with 300% rated current for 25 ms
No lateral mounting clearances are required
Ambient temperature -25 (0) … 70 °C
Selectable short-circuit response (constant current or latching shutdown)
A soft characteristic can be selected for a parallel connection (for uniform load distribution
of power supply units of the same type)
Display of the operating state via 3 LEDs
To increase the system availability, these reliable power supplies can be expanded using
SITOP supplementary modules (redundancy module, selectivity module, buffer module, signaling module or signaling contact), as well as SITOP DC-UPS modules.
SITOP modular 1ph/2ph Manual, 04.2018, C98130-A7548-A1-4-7629
3
Overview
Ordering data
Stabilized power supply unit SITOP modular 1ph/2ph
Type
Order number
24 V/10 A output
24 V/20 A output
24 V /40 A output
Validity
NOTICE
The following device options are available:
120-230/230-500 VAC input, 24 V/5 A output 120-230/230-500 VAC input,
120/230 VAC input,
120/230 VAC input,
6EP1333-3BA10
6EP1334-3BA10
6EP1336-3BA00
6EP1337-3BA00
This manual provides information on the following products:
SITOP PSU200M 5 A, SITOP PSU200M 10 A 6EP1333-3BA10, 6EP1334-3BA10 Product State: 3 changes with respect to the previous version (PS: 2):
– Signaling contact: mechanical relay replaced by solid-state relay with modified contact
data PS 2: Contact rating (isolated): 30 V AC/0.5 A; 60 V DC/0.3 A; 30 V DC/1 A PS 3: Contact rating (isolated): 24 V AC/0.1 A; 30 V DC/0.1 A
It is not permissible that the signaling contact is connected on the primary side!
SITOP modular 1ph/2ph
4 Manual, 04.2018, C98130-A7548-A1-4-7629

Table of contents

Overview................................................................................................................................................. 3
1 Safety instructions ................................................................................................................................... 7
2 Description, device design, dimension drawing........................................................................................ 9
3 Mounting/removal ................................................................................................................................. 21
4 Mounting position, mounting clearances ................................................................................................ 23
5 Installation ............................................................................................................................................ 33
6 Technical data ...................................................................................................................................... 37
1.1 General safety instructions ....................................................................................................... 7
1.2 Safety instructions for hazardous zones ................................................................................... 7
2.1 Device description ..................................................................................................................... 9
2.2 Connections and terminal designation.................................................................................... 10
2.3 Potentiometer .......................................................................................................................... 12
2.4 Status displays and signaling ................................................................................................. 13
2.5 Change-over switch ................................................................................................................ 14
2.6 Block diagram ......................................................................................................................... 16
2.7 Dimensions and weight ........................................................................................................... 18
4.1 Standard mounting position .................................................................................................... 23
4.2 Other mounting positions ........................................................................................................ 25
4.2.1 6EP1333-3BA10 ..................................................................................................................... 25
4.2.2 6EP1334-3BA10 ..................................................................................................................... 27
4.2.3 6EP1336-3BA00 ..................................................................................................................... 29
4.2.4 6EP1337-3BA00 ..................................................................................................................... 31
5.1 Line-side connection ............................................................................................................... 33
5.2 Output-side connection ........................................................................................................... 35
6.1 Input ........................................................................................................................................ 37
6.2 Output ..................................................................................................................................... 39
6.3 Efficiency ................................................................................................................................. 46
6.4 Closed-loop control ................................................................................................................. 48
6.5 Protection and monitoring ....................................................................................................... 48
6.6 MTBF ...................................................................................................................................... 48
6.7 Mechanical system ................................................................................................................. 49
6.8 Accessories ............................................................................................................................. 49
SITOP modular 1ph/2ph Manual, 04.2018, C98130-A7548-A1-4-7629
5
Table of contents
7 Safety, approvals, EMC ........................................................................................................................ 51
8 Ambient conditions ................................................................................................................................ 55
9 Applications .......................................................................................................................................... 57
10 Environment ......................................................................................................................................... 67
11 Service & Support ................................................................................................................................. 69
6.9 Dimension drawing ................................................................................................................ 50
7.1 Safety ..................................................................................................................................... 51
7.2 Test voltage ............................................................................................................................ 52
7.3 Approvals ............................................................................................................................... 53
7.4 EMC ....................................................................................................................................... 54
9.1 Parallel connection to increase power rating ......................................................................... 57
9.2 Parallel connection for redundancy ....................................................................................... 59
9.3 Series connection for increased voltage ................................................................................ 61
9.4 Overload protection in the 24 V output circuit ........................................................................ 62
9.5 Protection against short-time voltage dips ............................................................................. 63
9.6 Protecting against longer power failures ................................................................................ 64
SITOP modular 1ph/2ph
6 Manual, 04.2018, C98130-A7548-A1-4-7629
1
1.1

General safety instructions

WARNING
Correct handling of the devices
1.2

Safety instructions for hazardous zones

WARNING
WARNING
When operating electrical devices, it is inevitable that certain components will carry dangerous voltages.
Therefore, failure to handle the units properly can result in death or serious physical injury as well as extensive property damage.
Only appropriately qualified personnel may work on or in the vicinity of this equipment.
Perfect, safe, and reliable operation of this equipment is dependent on proper transportation, storage, installation and mounting.
Before installation or maintenance work can begin, the system's main switch must be switched off and measures taken to prevent it being switched on again.
If this instruction is not observed, touching live parts can result in death or serious injury.
The devices comply with ATEX directive 2014/34/EU; EN 60079-0; EN 60079-15.
OPERATE VOLTAGE ADJUSTMENT OR SWITCHES IN NON-HAZARDOUS AREAS ONLY!
EXPLOSION HAZARD – SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2
SITOP modular 1ph/2ph Manual, 04.2018, C98130-A7548-A1-4-7629
7
Safety instructions
1.2 Safety instructions for hazardous zones
SITOP modular 1ph/2ph
8 Manual, 04.2018, C98130-A7548-A1-4-7629
2
2.1

Device description

Line input
DC output
24 - 28.8 V potentiometer
Pilot lamps (24 V OK, OVERLOAD, SHUTDOWN)
A/B selector switch
Voltage selector switch (only for 6EP1333-3BA10 and 6EP1334-3BA10)
DIN rail slider
Natural convection
Clearance above/below
Signaling contact (only for 6EP1333-3BA10 and 6EP1334-3BA10)
SITOP modular is a primary-clocked power supply for connection to a 1-phase/2-phase AC line supply. An electronically regulated DC voltage that can be set via a potentiometer is available at the output of the device. The output of the device is isolated, no-load proof and short-circuit proof. The LED displays indicate the operating state. The integrated signaling contact (for 6EP1336-3BA00 and 6EP1337-3BA00, only when using the supplementary 6EP1961-3BA10 signaling module) can be used to further process the operating state of the device.
Figure 2-1 Design (example, 6EP1334-3BA10 and 6P1337-3BA00)
SITOP modular 1ph/2ph Manual, 04.2018, C98130-A7548-A1-4-7629
9
Description, device design, dimension drawing
2.2
Connections and terminal designation
Connections and terminal designations for 6EP1333-3BA10 and 6EP1334-3BA10
Do not subject the end stop to higher loads

2.2 Connections and terminal designation

The line input terminals can be used to establish the connection to the supply voltage. The output terminals Installation (Page 33)).
are used to connect to the loads to be supplied (see also Section
Line input L1, N (L2), PE
Output +
Output –
Signaling contact 13, 14
*1)
Figure 2-2 Terminal data for 6EP1333-3BA10 and 6EP1334-3BA10
One screw terminal each
2 screw terminals
2 screw terminals
One screw terminal each
SITOP modular 1ph/2ph
10 Manual, 04.2018, C98130-A7548-A1-4-7629
Description, device design, dimension drawing
Connections and terminal designations for 6EP1336-3BA00 and 6EP1337-3BA00
Do not subject the end stop to higher loads
Do not subject the end stop to higher loads
2.2 Connections and terminal designation
Line input L1, N (L2), PE, Jump 120 V AC
Output +
Output –
*1)
Figure 2-3 Terminal data for 6EP1336-3BA00
One screw terminal each
2 screw terminals
2 screw terminals
*1)
Figure 2-4 Terminal data for 6EP1337-3BA00
SITOP modular 1ph/2ph Manual, 04.2018, C98130-A7548-A1-4-7629
11
Description, device design, dimension drawing
2.3
Potentiometer
NOTICE
Thermal overload possible
Note
It is only permissible to use an insulated screwdriver when actuating the potentiometer.

2.3 Potentiometer

The potentiometer on the front of the device is used to set the output voltage. The output voltage is set to 24 V in the factory, and can be adjusted in the range 24 - 28.8 V; for example, to compensate voltage drops across long supply lines to the connected load.
Figure 2-5 Potentiometer (example of 6EP1337-3BA00)
When adjusting the output voltage to > 24 V, the output current must be derated by 4 %/V, or the permissible ambient temperature must be taken into account with 3 °C/V.
For notes on actuating the potentiometer (screwdriver, torque), see Figure 2-2 Terminal data for 6EP1333-3BA10 and 6EP1334-3BA10 (Page 10), Figure 2-3 Terminal data for 6EP1336­3BA00 (Page 11) and Figure 2-4 Terminal data for 6EP1337-3BA00 (Page 11).
SITOP modular 1ph/2ph
12 Manual, 04.2018, C98130-A7548-A1-4-7629
Description, device design, dimension drawing
2.4
Status displays and signaling
6EP1333-3BA10 (24 V/5 A) 6EP1334-3BA10 (24 V/10 A)
6EP1336-3BA00 (24 V/20 A) 6EP1337-3BA00 (24 V/40 A)
Red LED for latching shutdown in "shut down" mode
24 V O.K
Signaling
6EP1333-3BA10 (24 V/5 A) 6EP1334-3BA10 (24 V/10 A) 6EP1336-3BA00 (24 V/20 A)
6EP1337-3BA00 (24 V/40 A)
tary signaling module 6EP1961-3BA10 is used)

2.4 Status displays and signaling

Status indicator Green LED for 24 V O.K.
Yellow LED for overload in "constant current" mode
Signaling contact 13, 14
Figure 2-6 Status indicators and signals (example of 6EP1337-3BA00)
Relay contact (NO contact, contact rating (isolated) 24 V AC/0.1 A; 30 V DC/0.1 A) for
Remote switch off when using the signaling module (6EP1961-3BA10)
Green LED ④ lights up
Yellow LED ④ lights up
Red LED ④ lights up
Green LED ④ off
Normal operation, output voltage > 20 V ±0.5 V
Overload (U
Latching shutdown or remote switch-off for 6EP1336-3BA00 and 6EP1337-3BA00 (only when the supplemen-
No supply voltage
SITOP modular 1ph/2ph Manual, 04.2018, C98130-A7548-A1-4-7629
< 20 V ± 0.5 V)
out
13
Description, device design, dimension drawing
2.5
Change-over switch
Switch
ON
OFF
A
Parallel operation:
attained.
Single operation:
B
Latching shutdown:
OFF.
Constant current:

2.5 Change-over switch

Figure 2-7 A/B selector switch
The two switches A and B are used to influence the output characteristic:
influences the output characteristic in the load range
influences the output characteristic in the overload range
'Soft' characteristic curve (see, e.g. 6EP1333-3BA10 parallel operation output char­acteristic (Page 43)) for the parallel operation of two or more devices: The output voltage falls with increasing output current (namely, also for the overcurrent pulse!). This means that for full output current the high­est output voltage can normally no longer be
If the output current rises above the rated value and above the current limit, the device reduces the output voltage (see, e.g. 6EP1333-3BA10 latching shutdown output characteristic (Page 44 falls below 20 V, the device shuts down latch­ing, the red LED lights up. This limit voltage of 20 V is independent of the set output voltage. The 'Short-time overload current' feature is not available in this operating mode. To also permit charging of large capacitances in this operating mode at the output, a shutdown is performed during the first 10 s after power on or remote switch on in conjunction with the non-latching signaling module. During these first 10 s, the device responds for overload as if the switch is
)). If the output voltage
Figure 6-10
Figure 6-14
Delivery state
'Hard' characteristic curve (see, e.g. Figure 6-3 6EP1333-3BA10 single operation output char­acteristic (Page 41)) for normal operation (sin­gle operation): The output voltage is independent of the output current.
Delivery state
If the output current rises above the rated value and above the current limit, the device reduces the output voltage. The yellow LED lights up if the output voltage falls below 20 V.
SITOP modular 1ph/2ph
14 Manual, 04.2018, C98130-A7548-A1-4-7629
Conditioned when delivered: A - OFF; B - OFF
Description, device design, dimension drawing
2.5 Change-over switch
Selector switch for the input voltage range for 6EP1333-3BA10 (24 V/5 A) and 6EP1334­3BA10 (24 V/10 A)
Figure 2-8 Voltage selector switch (example, 6EP1334-3BA10)
The selector switch as delivered is in the 230 V position. It must be moved to the appropriate position for operation in the 120 V range. The selector switch can only be actuated in the de­energized state.
To switch the input voltage range for 6EP1336-3BA00 (24 V/20 A) and 6EP1337-3BA00 (24 V/40 A) to 120 V, a wire jumper must be connected to the input terminal, Jump 120 V AC. This must be dimensioned as for the power supply cable with regard to cross-section and insulation. The length must not exceed 100 mm.
Figure 2-9 Wire jumper (example, 6EP1437-3BA00)
SITOP modular 1ph/2ph Manual, 04.2018, C98130-A7548-A1-4-7629
15
Description, device design, dimension drawing
2.6
Block diagram

2.6 Block diagram

Figure 2-10 Block diagram for 6EP1333-3BA10 and 6EP1334-3BA10
SITOP modular 1ph/2ph
16 Manual, 04.2018, C98130-A7548-A1-4-7629
Description, device design, dimension drawing
2.6 Block diagram
Figure 2-11 Block diagram for 6EP1336-3BA00 and 6EP1337-3BA00
SITOP modular 1ph/2ph Manual, 04.2018, C98130-A7548-A1-4-7629
17
Description, device design, dimension drawing
2.7
Dimensions and weight

2.7 Dimensions and weight

Figure 2-12 Dimension drawing, 6EP1333-3BA10 and 6EP1334-3BA10 (example, 6EP1334-3BA10)
Figure 2-13 Dimension drawing for 6EP1336-3BA00
SITOP modular 1ph/2ph
18 Manual, 04.2018, C98130-A7548-A1-4-7629
Description, device design, dimension drawing
6EP1333-3BA10 (24 V/5 A)
6EP1334-3BA10 (24 V/10 A)
6EP1336-3BA00 (24 V/20 A)
6EP1337-3BA00 (24 V/40 A)
mm
Weight
Approx. 0.6 kg
Approx. 0.8 kg
Approx. 2.2 kg
Approx. 2.9 kg
2.7 Dimensions and weight
Figure 2-14 Dimension drawing for 6EP1337-3BA00
Dimensions (W × H × D) in
70 × 125 × 120,5 70 × 125 × 120,5 160 × 125 × 120,5 240 × 125 × 120,5
SITOP modular 1ph/2ph Manual, 04.2018, C98130-A7548-A1-4-7629
19
Description, device design, dimension drawing
2.7 Dimensions and weight
SITOP modular 1ph/2ph
20 Manual, 04.2018, C98130-A7548-A1-4-7629
3
WARNING
Installing the device in a housing or a control cabinet
Mounting
Removing
The SITOP modular power supply is a built-in device. It must be installed in a housing or control cabinet, to which only qualified personnel have access.
The device can be mounted in a control cabinet on standard mounting rails (see Chapter Mechanical system (Page 49))
To mount the device, position it with the mounting rail guide at the upper edge of the standard mounting rail and press down to lock it into place. If this is too difficult, press slider
at the same time, as described under "Removal".
To remove, pull up the slider using a screwdriver and disengage the device at the bottom edge of the standard mounting rail. Then you can remove the device from the upper edge of the standard mounting rail.
Figure 3-1 Removal (example, 6EP1334-3BA10)
SITOP modular 1ph/2ph Manual, 04.2018, C98130-A7548-A1-4-7629
21