Siemens SITOP PSE200U, SITOP SEL1200, SITOP SEL1400 User manual

Brochure
Edition /
SITOP power supply
Electronic protection and fast fault localization in  V DC load circuits
usa.siemens.com/sitop
The SITOP selectivity modules distribute the load current across several 24 V DC load circuits and monitor them reliably for overload and short-circuit conditions. The electronics permit brief current peaks caused, for example, by high inrush currents, but isolate load circuits in the event of an extended overload. This is ensured even on high­resistance lines. In such cases, miniature circuit breakers fail to trip, or trip too late, even if the power supply unit could deliver the required tripping current. The SITOP expansion modules continue to reliably supply 24 V to the load circuits not affected by an overload and can prevent a total system failure. The new SITOP SEL selectivity modules, which have more outputs, an additional tripping characteristic and detailed diagnostics, now offer even more efficient protection for your plant.
Miniature circuit breakers with high current consumption
Miniature circuit breakers are often still used for the selective protection of 24 V DC load circuits. In many cases, however, when interacting with switched-mode power supply units, they do not offer reliable protection. They require several times the rated current in order to trip within a few milliseconds. Because stabilized power supplies limit their output current electronically when there is a critical overload, the tripping current is not always guaranteed. This can cause the 24-V supply to break in and the PLC to go to Stop. Even if the power supply unit could supply the current, immediate tripping is not necessarily assured, because with this high current requirement, the line resistance can no longer be neglected. It prevents the required tripping current from flowing. Therefore fast tripping is only possible up to certain cable lengths and starting from larger cable cross-sections. In addition to the line resistance, the overall circuit design (e.g. contact resistances at terminals) must be taken into consideration when configuring miniature circuit breakers.
SITOP selectivity modules – optimized for switched-mode power supply units
The selectivity modules are specially designed to protect 24 V DC individual load circuits supplied by switched-mode power supplies. Individual setting of the tripping current allows optimum adaptation to the respective load circuit. Engineering effort is minimal since the switch-off characteristic always guarantees reliable tripping – even with high line impedances that limit the short-circuit current.
HMI
Selectivity
Power supply
As an electronic monitor, the SITOP selectivity module switches faulty 24 V DC load circuits off immediately, and continues to supply the other loads without any interruption.
module
24 V DC
Actor/SensorPLC
G_KT01_XX_01567
SITOP PSE200U and SEL1400 – limiting characteristic offers maximum safety
In terms of the tripping characteristic, the new 8-channel SEL1400 modules behave like the tried and tested 4-channel PSE200U modules. They limit the output current to 150% of the set value, corresponding to the overload behavior of the SITOP power supplies of the Advanced and Standard product lines. This means that, even in the case of a short circuit, no overload can occur and consequently no voltage drop at the output of the power supply unit. Even when a power supply without overload reserves is used, the patented SITOP concept ensures reliable protection: The electronics continuously monitor the 24 V DC input voltage. As soon as the 24 V DC threatens to fail, the path with a higher current than the set current is disconnected immediately. All other load circuits continue to be supplied without interruption. Even loads that do not comply with the PLC standard and can only bridge a few milliseconds of undervoltage, continue to operate without any problem.
Tripping characteristics
SITOP SEL1200 – switching characteristic for standard protection
The new SEL1200 8-channel selectivity modules also allow higher, brief overload currents. The higher the current, the faster the output is shut down. It is possible that the power supply is loaded for a few milliseconds with a current significantly higher than that which is set. If the power supply unit only has limited overload reserves, it may result in a momentary drop in the 24 V supply. For loads that comply with the PLC standard, however, this is not critical. For stan­dard applications, the SEL1200 selectivity module therefore offers very efficient protection.
For 24 V loads with a high inrush current, the switching characteristic even offers advantages, since whatever applies at shutdown also applies when switching on. High currents are not limited, but can be permitted for a short time. In addi­tion, two outputs of the SITOP SEL1200 or 1400 selectivity modules can be connected in parallel for a 15 A rated current.
Time in
seconds
100
Normal operation
Switch-off after approx. 5 s
0.1
0.01
10
5
1
Current limitation to 150% for approx. 100 ms, then switching off the faulty output
0
SITOP SEL1400 / PSE200U characteristic: limiting
Shutdown response for current requirement per output
circuit relative to set value (I/I set value = 100%):
Power requirement: Shutdown after:
From 0 A to 100% (set value) No shutdown
From set value to 150%
Above 150%
Above set value with simultaneous collapse of supply voltage below 20 V DC
1)
1)
of set value Current limiting to approx.
Approx. 5 seconds
1)
150%
for typ. 100 ms, then
shutdown Immediate shutdown
Switching SITOP SEL1200
Limiting SITOP SEL1400/PSE200U
The higher the current, the faster the trip
250% I-set200%180%150%100%
SITOP SEL1200 characteristic: switching
Shutdown response: The higher the current, the faster the
faulty output is shut down, in line with the limit load
2
integral i
t.
Startup characteristics: Supports loads with high inrush current, whereby the supply voltage can drop to 15 V
G_KT01_XX_01573
Startup characteristics: Load ramp-up to 150% of set value with stable voltage supply of at least 20 V
1)
SITOP PSE200U versions with NEC Class 2: 110%
Advantages of all SITOP selectivity modules
Reliable tripping regardless of cable lengths or cross-sections
Easy configuration thanks to individual setting of maximum output current using potentiometers
Remote reset possible from a central location
Three-color LEDs for fast on-site fault localization
Two possibilities for remote diagnostics: common signaling contact or single-channel signaling
Single-channel evaluation via just one PLC digital input and function block
Simple commissioning thanks to manual switch on/off of load circuits using reset button
Sequential connection delay of individual 24 V DC load circuits reduces total inrush current
Sealable transparent cover protects against maladjustment of tripping currents and sequential delay
Special features of the SITOP SEL1200/SEL1400
SITOP SEL1200: Switching characteristic for standard re-
quirements compliant with PLC standard
SITOP SEL1400: Limiting characteristic for highest
demands on the 24 V protection
Eight load circuits per module, with adjustable output
current range of 2
... 10 A
Two outputs, switchable in parallel (for max. 15 A)
Slim design matching that of the SITOP PSU6200
Single-channel diagnostics via free SIMATIC S7 blocks
with extensive evaluations per output: Actual current, current threshold, reason of the automatic shutdown
Push-in terminals
Special features of the SITOP PSE200U
Limiting characteristic for highest demands on the 24 V
protection
Four load circuits per module, with adjustable output
current range of 0.5
Versions with power limitation of the outputs to 100 VA
according to NEC Class 2
Stepped design corresponding to low-voltage
switchgear, e.g. miniature circuit breakers
Evaluation of individual channels via free of charge
SIMATIC S7 or SIMOTION function blocks or LOGO! software
Library for visualization in SIMATIC PCS 7
Voltage measuring points for output currents
Screw terminals
SITOP selectivity modules – all connections, functions and options at a glance
SITOP SEL1200/SEL1400
selectivity modules
Device identification label (not included in scope of delivery)
Eight outputs with switching (SEL1200) or limiting characteristic (SEL1400)
COM settings: 0: Common signaling 1: Single-channel diagnostics TD1/TD2: Switch-on delay, load-optimized, + 25, + 200 or + 500 ms
Data matrix code
Common signaling contact or single-channel signaling or diagnostics
Remote reset (24 V signal)
Three-color status LED per output:
Green: connected
Orange: manually disconnected
Red: disconnected due
to overload Pushbutton for On/Off/Reset for
each output
Potentiometer for setting the tripping current
0 V supply (only for the electronics, not for the outputs)
24 V DC supply
Sealable transparent cover
... 3 A or 3 ... 10 A
SITOP PSE200U
selectivity module
Four outputs with limiting characteristic
Measuring points for output current by means of voltage:
1V≙1A
Setting Switch-on delay set to 0, 25, 100 ms or load-optimized
Labeling field per output
Sequential switching on reduces burden on the power supply
By switching on the outputs sequentially, the inrush current that the power supply has to provide is considerably reduced. This avoids the danger of a voltage dip which could result in disturbances within the plant. A power supply with a lower rated output current can possibly also be used. The "load­optimized" setting means that the next output is not connected until the previous output current is below the set value. This is a standard response for SITOP SEL, with cumulative delay time; for PSE200U it can be set as an option.
Fast, channel-exact diagnostics
The single-channel signaling of the PSE200U and the single-channel diagnostics of the SEL1200/1400 are efficient status signals to the PLC via only one digital input. A serial code is evaluated via a free-of-charge SIMATIC S7 function block. SITOP PSU200U reports the status of the outputs via 4 channel bits, each of which are separated by a pause bit:
2750 ms
Max. total current without sequential switching on
Max. total current with sequential switching on
Output current
Activation Output 1 Output 2 Output 3 Output 4
Total current without sequential switching on Total current current with sequential switching on Output current of the outputs
Time t
G_KT01_XX_01574
SITOP PSE200U: Current measurement with voltmeter
The SITOP PSE200U selectivity module has a measuring point (MP) for each output, via which the current value at any moment is output. Because one volt corresponds to one ampere, simple voltage measurement is possible for determining the current without having to disconnect the cable. The 24 V supply to the load circuit is not interrupted and the plant remains fully operational.
Signal output
OUT 1 OUT 2 OUT 3 OUT 4
SITOP PSE200U
Start sign
1011
1 digital input
In addition, SITOP SEL1200 and SEL1400 offer extensive evaluation options:
Output current from each of the 8 outputs
Set current threshold
Reason for automatic disconnection:
– Overload up to 150% for more than 5 s – Overload in excess of 150% total current (> 63 A, > 30 s) – Overcurrent (I > I setting) and undervoltage (< 20 V) – Input voltage too low (< 15 V) / too high (> 30 V) – Overtemperature
SITOP SEL type: manufacturing date, article number
The values are encrypted in a telegram with 32 bits that are transmitted as Manchester code:
3450 ms
1000
1
Bit 1Bit 2Bit 3Bit 31Bit
...
1 digital input
32
SEL1200/
Signal output
SITOP
1400
Start sign
By means of WinCC faceplates the states and values of each output of the SITOP SEL1200 or SEL1400 can be easily visualized:
G_KT01_XX_01571
G_KT01_XX_01572
Technical specifications
SITOP SEL1200 SITOP SEL1400
Article number
6EP4438-7FB00-3DX0 6EP4438-7EB00-3DX0
... with NEC Class 2
Input
Rated voltage V
in rated
24 V DC
Voltage range 22 ... 30 V DC
Input current Max. 63 A
Output
Rated voltage V
Typ. Uin – 0.2 V
out rated
Number of outputs 8 8
Rated current I per output
up to +60 °C
out rated
10 A 10 A
Setting range per output 2 ... 10 A 2 ... 10 A
Tripping characteristic Switching – for standard protection devices Current-limiting – for increased requirements
regarding protection
Set time delay Load-optimized (as soon as the previous output is less than the set rated value again),
+ 25 ms, + 200 ms, + 500 ms
Efficiency at V
out rated
, I
Typ. 97%
out rated
Protection and monitoring
Status displays Three-color LED per output:
green – connected, yellow – manually disconnected, red – disconnected due to overload
Signal output Diagnostics interface for common signaling or single-channel diagnostics.
Evaluation of the single-channel diagnostics via SIMATIC S7 function block
Diagnostics Common signaling: Disconnection of at least one output
Single-channel diagnostics: Current, set current threshold, status (on/off), where applicable, reason for disconnection per output
Protection class Class III
Degree of protection (EN 60 529) IP20
Certifications CE, UL, cURus, CB, cCSAus Class I Div 2; available soon: IECEx, GL, ABS, ATEX
Connections
Input +24 V
2 push-in for 0.5 ... 16 mm
2
(load and electronics supply)
Input 0 V (electronics supply) 2 push-in for 0.5 ... 4 mm
Outputs 1 push-in each for 0.5 ... 4 mm
Signal output 2 push-in for 0.5 ... 1.5 mm
Remote reset 1 push-in for 0.5 ... 1.5 mm
2
2
2
2
General data
Emitted interference EN 61000-6-3, EN 55022 Class B
Noise immunity EN 61000-6-2
Ambient temperature range -25 ... +60 °C (-25 ... +85 °C transport/storage)
Mounting DIN rail EN 60715 35 x 7.5/15
Dimensions
45 x 135 x 125 45 x 135 x 125
(width × height × depth) in mm
Weight Approx. 300 g Approx. 440 g
Accessories Reference identification labels 15 mm × 10 mm, 160 units. Article No.: 6ES7193-6LF30-0AW0
Technical specifications
SITOP PSE200U with common signaling contact SITOP PSE200U with single-channel signaling
Article number ... with NEC Class 2
6EP1961-2BA11 6EP1961-2BA51
6EP1961-2BA21 6EP1961-2BA31
6EP1961-2BA61
6EP1961-2BA41
Input
Rated voltage V
in rated
24 V DC
Voltage range 22 ... 30 V DC
Input current 40 A max.
Output
Rated voltage V
Number of outputs 4 4 4
Rated current I per output
Typ. Uin – 0.2 V
out rated
up to +60 °C
out rated
3 A 10 A 3 A 10 A
4
Setting range per output 0.5 ... 3 A 3 ... 10 A 0.5 ... 3 A 3 ... 10 A
Tripping characteristic Current-limiting – for increased requirements regarding protection
Set time delay 0 ms, 25 ms or 100 ms (identical between outputs) or load-optimized
(as soon as the previous output is less than the set rated value)
, I
Efficiency at V
out rated
97% 99% 97% 99%
out rated
Protection and monitoring
Status displays Three-color LED per output: green for output connected, yellow for output manually disconnected,
red for output disconnected due to overload/short-circuit
Signal output Common signaling contact, changeover contact,
contact rating 24 V/0.5 A
Single-channel signaling: cyclic signaling for channel-specific evaluation using SIMATIC S7 function block
Diagnostics Disconnection of at least one output.
The current per output can be measured via voltage
measuringpoints(1V≙1A)
Status (on/off) of each of the 4 outputs. The current per output can be measured via voltage
measuringpoints(1V≙1A)
Protection class Class III
Degree of protection (EN 60 529) IP20
Certifications UR (UL 2367), cURus (UL 508, CSA C22.2 No. 107.1) cCSAus (Class I Div 2), ATEX (EN 60079-0, -15), GL, ABS,
6EP1961-2BA51/6EP1961-2BA61: NEC Class 2
Connections
Input +24 V
2 screw terminals for 0.5 ... 10 mm
2
(load and electronics supply)
Input 0 V (electronics supply) 2 screw terminals for 0.5 ... 4 mm
Outputs 1 to 4 1 screw terminal each for 0.5 ... 4 mm
Signal output 3 screw terminals for 0.5 ... 4 mm
Remote reset 1 screw terminal for 0.5 ... 4 mm
2
2
2
2
1 screw terminal for 0.5 ... 4 mm
2
General data
Emitted interference EN 61000-6-3, EN 55022 Class B
Noise immunity EN 61000-6-2
Ambient temperature range 0 ... +60 °C (-25 ... +85 °C transport/storage)
Mounting DIN rail EN 60715 35 x 7.5/15
Dimensions
72 × 80 × 72 72 × 80 × 72 72 × 80 × 72 72 × 80 × 72
(width × height × depth) in mm
Weight Approx. 170 g Approx. 220 g Approx. 170 g
Approx. 220 g
Accessories Device identification label 20 mm x 7 mm, 340 units Article No.: 3RT1900-1SB20
Get more information:
More on the SITOP selectivity modules:
www.siemens.com/sitop-select
Using the TIA Selection Tool to select the appropriate power supply, including add-on module:
www.siemens.com/tia-selection-tool
Operating instructions as download: www.siemens.com/sitop/manuals
CAx data (D, D, circuit diagram macro) as download:
www.siemens.com/sitop-cax
Find your personal contact partners at:
www.siemens.com/automation/partner
Security information
Siemens provides products and solutions with industrial security functions that support the secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when
Published by Siemens Industry, Inc. 
Digital Industries Process Automation  Triangle Parkway Norcross, GA 
Subject to change without prior notice Order No. PSBR-AH- Article No. ZB-AH-BA All rights reserved Printed in USA ©  Siemens Industry, Inc.
The technical data presented in this document is based on an actual case or on as-designed parameters, and therefore should not be relied upon for any specific application and does not constitute a performance guarantee for any projects. Actual results are dependent on variable conditions. Accordingly, Siemens does not make representations, warranties, or assurances as to the accuracy, currency or completeness of the content contained herein. If requested, we will provide specific technical data or specifications with respect to any customer’s particular applications. Our company is constantly involved in engineering and development. For that reason, we reserve the right to modify, at any time, the technology and product specifications contained herein.
appropriate security measures (e.g. firewalls and/or network segmentation) are in place.
For additional information on industrial security measures that may be implemented, please visit
https://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed under
https://www.siemens.com/industrialsecurity.
usa.siemens.com/sitop