Siemens SIPROTEC 7SD80 User Manual

SIPROTEC
Preface
Contents
Line Differential Protection 7SD80
V4.6
Manual
Literature
Glossary
Index
E50417-G1140-C474-A1
Note
For safety purposes, please note instructions and warnings in the Preface.

Disclaimer of Liability

We have checked the contents of this manual against the hardware and software described. However, deviations from the description cannot be completely ruled out, so that no liability can be accepted for any errors or omissions contained in the information given.
The information given in this document is reviewed regularly and any necessary corrections will be included in subsequent editions.

Copyright

Copyright © Siemens AG 2011. All rights reserved. Dissemination or reproduction of this document, or evaluation and
communication of its contents, is not authorized except where ex­pressly permitted. Violations are liable for damages. All rights re­served, particularly for the purposes of patent application or trade­mark registration.
We appreciate any suggested improvements. We reserve the right to make technical improvements without
notice. Document version V04.00.03 Release date 09.2011

Registered Trademarks

SIPROTEC, SINAUT , SICAM and DIGSI are registered trademarks of Siemens AG. Other designations in this manual might be trade­marks whose use by third parties for their own purposes would in­fringe the rights of the owner.
Siemens Aktiengesellschaft Order no.: E50417-G1140-C474-A1

Preface

Purpose of this Manual

This manual describes the functions, operation, installation, and placing into service of device 7SD80. In par­ticular:
• Information regarding the configuration of the scope of the device and a description of the device functions and settings Chapter 2;
• Instructions for Installation and Commissioning Chapter 3;
• Compilation of the Technical Data Chapter 4;
• As well as a compilation of the most significant data for advanced users Appendix A.
General information with regard to design, configuration, and operation of SIPROTEC 4 devices are set out in the SIPROTEC 4 System Description /1/.

T arget Audience

Protection engineers, commissioning engineers, personnel concerned with adjustment, checking, and service of selective protective equipment, automatic and control facilities, and personnel of electrical facilities and power plants.

Applicability of this Manual

This manual applies to: SIPROTEC 4 Line Differential Protection 7SD80; firmware version V4.6.

Indication of Conformity

This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Council Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage Directive 2006/95 EC). This conformity is proved by tests conducted by Siemens AG in accordance with the Council Directive in agreement with the generic standards EN 61000-6-2 and EN 61000-6-4 for EMC directive, and with the standard EN 60255-27 for the low-voltage directive. The device has been designed and produced for industrial use. The product conforms with the international standards of the series IEC 60255 and the German standard VDE 0435.
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
3
Preface
Additional St andards IEEE C37.90 (see Chapter 4 "Technical Data")
This product is UL certified according to the Technical Data. file E194016
UL certification according to standard UL 508 for the devices 7SD803x and 7SD807x has been applied for.

Additional Support

Should further information on the System SIPROTEC 4 be desired or should particular problems arise which are not covered sufficiently for the purchaser's purpose, the matter should be referred to the local Siemens rep­resentative.
Our Customer Support Center provides a 24-hour service. Telephone: +49 (180) 524-7000 Fax: +49 (180) 524-2471 e-mail: support.energy@siemens.com

Training Courses

Inquiries regarding individual training courses should be addressed to our Training Center: Siemens AG Siemens Power Academy Humboldt Street 59 90459 Nuremberg Telefon: +49 (911) 433-7415 Fax: +49 (911) 433-7929 Internet: www.siemens.com/energy/power-academy e-mail: power-academy.energy@siemens.com
4
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual

Safety Information

This manual does not constitute a complete index of all required safety measures for operation of the equip­ment (module, device), as special operational conditions may require additional measures. However, it com­prises important information that should be noted for purposes of personal safety as well as avoiding material damage. Information that is highlighted by means of a warning triangle and according to the degree of danger, is illustrated as follows.
DANGER!
Danger indicates that death, severe personal injury or substantial material damage will result if proper precau­tions are not taken.
WARNING!
indicates that death, severe personal injury or substantial property damage may result if proper precautions are not taken.
Caution!
indicates that minor personal injury or property damage may result if proper precautions are not taken. This particularly applies to damage to or within the device itself and consequential damage thereof.
Preface
Note
indicates information on the device, handling of the device, or the respective part of the instruction manual which is important to be noted.
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
5
Preface
WARNING!
Qualified Personnel
Commissioning and operation of the equipment (module, device) as set out in this manual may only be carried out by qualified personnel. Qualified personnel in terms of the technical safety information as set out in this manual are persons who are authorized to commission, activate, to ground and to designate devices, systems and electrical circuits in accordance with the safety standards.
Use as prescribed The operational equipment (device, module) may only be used for such applications as set out in the catalog
and the technical description, and only in combination with third-party equipment recommended or approved by Siemens.
The successful and safe operation of the device is dependent on proper handling, storage, installation, opera­tion, and maintenance.
When operating an electrical equipment, certain parts of the device are inevitably subject to dangerous voltage. Severe personal injury or property damage may result if the device is not handled properly.
Before any connections are made, the device must be grounded to the ground terminal. All circuit components connected to the voltage supply may be subject to dangerous voltage. Dangerous voltage may be present in the device even after the power supply voltage has been removed (ca-
pacitors can still be charged). Operational equipment with exposed current transformer circuits may not be operated. The limit values as specified in this manual or in the operating instructions may not be exceeded. This aspect
must also be observed during testing and commissioning.
6
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual

T ypographic and Symbol Conventions

The following text formats are used when literal information from the device or to the device appear in the text flow:
Parameter Names
Designators of configuration or function parameters which may appear word-for-word in the display of the device or on the screen of a personal computer (with operation software DIGSI), are marked in bold letters in monospace type style. The same goes for the titles of menus.
1234A
Parameter addresses have the same character style as parameter names. Parameter addresses contain the suffix A in the overview tables if the parameter can only be set in DIGSI via the option Display additional set- tings.
Parameter Options
Possible settings of text parameters, which may appear word-for-word in the display of the device or on the screen of a personal computer (with operation software DIGSI), are additionally written in italics. This also applies to header bars for selection menus.
„Messages“
Designators for information, which may be output by the relay or required from other devices or from the switch gear, are marked in a monospace type style in quotation marks.
Preface
Deviations may be permitted in drawings and tables when the type of designator can be obviously derived from the illustration.
The following symbols are used in drawings:
Device-internal logical input signal
Device-internal logical output signal
Internal input signal of an analog quantity External binary input signal with number (binary input,
input indication) External binary input signal with number
(example of a value indication) External binary output signal with number (device indication) used as
input signal
Example of a parameter switch designated FUNCTION with address 1234 and the possible settings ON and OFF
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
7
Preface
Besides these, graphical symbols are used according to IEC 60617-12 and IEC 60617-13 or symbols derived from these standards. Some of the most frequently used are listed below:
Analog input variable
AND operation of input variables
OR operation of input variables
Exclusive OR (antivalence): output is active if only one of the inputs is active
Coincidence: output is active if both inputs are active or inactive at the same time
Dynamic input signals (edge-triggered) above with positive, below with negative edge
Formation of one analog output signal from a number of analog input signals
Threshold element with setting address and parameter names
Timer (pickup delay T adjustable) with setting address and parameter names
Timer (dropout delay T not adjustable)
Edge-triggered time element with action time T
Static memory (SR flipflop) with setting input (S), resetting input (R), output (Q) and inverted output (Q
), setting input dominant
Static memory (RS-flipflop) with resetting input (R) setting input (S), output (Q) and inverted output (Q
), resetting input dominant
8
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual

Contents

1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
1.1 Overall Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
1.2 Application Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
1.3 Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
2 Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
2.1.1 Functional Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
2.1.1.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
2.1.1.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
2.1.1.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
2.1.2 Device, General Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
2.1.2.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
2.1.2.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
2.1.2.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
2.1.2.4 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
2.1.3 General Power System Data (Power System Data 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
2.1.3.1 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
2.1.3.2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
2.1.4 Oscillographic Fault Records. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
2.1.4.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
2.1.4.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
2.1.4.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2
2.1.4.4 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
2.1.5 Change Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
2.1.5.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
2.1.5.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
2.1.5.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 3
2.1.5.4 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
2.1.6 General Protection Data (Power System Data 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
2.1.6.1 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
2.1.6.2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 7
2.1.6.3 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
2.1.7 EN100-Modul 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
2.1.7.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
2.1.7.2 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
2.1.8 Protection Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
2.1.8.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
2.1.8.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
2.1.8.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1
2.1.8.4 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
9
Contents
2.2 Phase Comparison Protection and Ground Differential Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . .52
2.2.1 Differential Topol ogy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
2.2.1.1 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
2.2.1.2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
2.2.1.3 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
2.2.2 Phase Comparison Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
2.2.2.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
2.2.2.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
2.2.3 Ground Current Differential Protection in Grounded Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
2.2.3.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
2.2.3.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
2.2.4 Ground Fault Differential Protection in Resonant-grounded/Isolated Systems. . . . . . . . . . . . . . . .63
2.2.4.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
2.2.4.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66
2.2.5 Differential Protection Pickup Logic and Tripping Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
2.2.5.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
2.2.6 87 Differential Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
2.2.6.1 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
2.2.6.2 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
2.2.7 Differential Protection Test and Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
2.2.7.1 Differential Protection Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
2.2.7.2 Differential Protection Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
2.3 Breaker Intertrip and Remote Tripping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
2.3.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
2.3.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
2.3.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
2.3.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
2.4 Backup Overcurrent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78
2.4.1 Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78
2.4.2 Non-directional Overcurrent Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78
2.4.3 Directional Overcurrent Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83
2.4.4 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89
2.4.5 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93
2.4.6 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96
2.5 Inrush Restraint. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .98
2.5.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .98
2.5.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99
2.5.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100
2.5.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100
2.6 Circuit-Breaker Failure Protection 50BF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .101
2.6.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .101
2.6.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108
2.6.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
2.6.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
10
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Contents
2.7 Thermal Overload Protection 49 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .112
2.7.1 Method of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .112
2.7.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .113
2.7.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .115
2.7.4 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .115
2.8 Undervoltage and Overvoltage Protection 27/59 (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .116
2.8.1 Overvoltage Protection (ANSI 59) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .116
2.8.2 Undervoltage Protection (ANSI 27) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .121
2.8.3 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124
2.8.4 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .128
2.8.5 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130
2.9 Frequency Protection 81 (Optional). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .133
2.9.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .133
2.9.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .136
2.9.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137
2.9.4 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .138
2.10 Direct Local Trip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .139
2.10.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .139
2.10.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .140
2.10.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .140
2.10.4 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .140
2.11 Automatic Reclosure Function 79 (Optional). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .141
2.11.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .141
2.11.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .148
2.11.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .152
2.11.4 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .154
2.12 Circuit-Breaker Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .155
2.12.1 CB Close Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .155
2.12.2 Circuit-Breaker Position Detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .158
2.12.3 Circuit-Breaker Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .159
2.12.4 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .160
2.13 Direct Remote Trip and Transmission of Binary Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .161
2.13.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .161
2.13.2 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .162
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
11
Contents
2.14 Monitoring Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
2.14.1 Measurement Supervision. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .163
2.14.1.1 Hardware Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .163
2.14.1.2 Software Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .165
2.14.1.3 External Transformer Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .165
2.14.1.4 Fault Responses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
2.14.1.5 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
2.14.1.6 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
2.14.1.7 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .178
2.14.2 74TC Trip Circuit Supervision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
2.14.2.1 Method of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .179
2.14.2.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
2.14.2.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
2.14.2.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .182
2.15 Flexible Protection Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .183
2.15.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .183
2.15.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .187
2.15.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .191
2.15.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .193
2.16 Function Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
2.16.1 Pickup Logic for the Entire Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .194
2.16.2 Overall Tripping Logic of the Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
12
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Contents
2.17 Additional Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .199
2.17.1 Indications Processing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .199
2.17.1.1 LEDs and Binary Outputs (Output Relays). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .199
2.17.1.2 Information via Display Fi e ld or PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .200
2.17.1.3 Information to a Control Center . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .201
2.17.2 Statistics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .201
2.17.2.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202
2.17.2.2 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202
2.17.3 Measurement During Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .203
2.17.3.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .203
2.17.3.2 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .205
2.17.4 Differential Protection Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .206
2.17.4.1 Measured Values of the Differential Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .206
2.17.4.2 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .206
2.17.5 Constellation Measured Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .206
2.17.5.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .206
2.17.6 Min/Max Measurement Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .207
2.17.6.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .207
2.17.6.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .207
2.17.6.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .208
2.17.6.4 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .208
2.17.7 Demand Measurement Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .210
2.17.7.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .210
2.17.7.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .210
2.17.7.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .210
2.17.7.4 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .211
2.17.8 Set Points (Measured Values) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .212
2.17.8.1 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .212
2.17.8.2 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .212
2.17.9 Energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .213
2.17.9.1 Energy Metering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .213
2.17.9.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .213
2.17.9.3 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .213
2.18 Breaker Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .214
2.18.1 Control Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .214
2.18.1.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .214
2.18.1.2 Information List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .215
2.18.2 Command Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .216
2.18.2.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . .216
2.18.3 Command Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .217
2.18.3.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .217
2.18.4 Switchgear Interlocking Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .218
2.18.4.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .218
2.18.5 Command Logging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .228
2.18.5.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .228
2.19 Notes on Device Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .229
2.19.1 Different operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .229
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
13
Contents
3 Mounting and Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
3.1 Mounting and Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .232
3.1.1 Configuration Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .232
3.1.2 Hardware Modifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
3.1.2.1 Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
3.1.2.2 Connections of the Current Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .241
3.1.2.3 Connections of the Voltage Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .243
3.1.2.4 Interface Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .244
3.1.2.5 Reassembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .247
3.1.3 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .248
3.1.3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
3.1.3.2 Panel Flush Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
3.1.3.3 Cubicle Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .250
3.1.3.4 Panel Surface Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .251
3.2 Checking Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .252
3.2.1 Checking the Data Connections of the Interfaces. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .252
3.2.2 Checking the Protection Data Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .255
3.2.3 Checking the System Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
3.3 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .258
3.3.1 Test Mode and Transmission Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .259
3.3.2 Checking Time Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .259
3.3.3 Testing the System Interface (at Port B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .260
3.3.4 Configuring Communication Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .262
3.3.5 Checking the Status of Binary Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265
3.3.6 Checking the Protection Data Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .268
3.3.7 Tests for Circuit-Breaker Failure Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270
3.3.8 Checking the Instrument Transformer Connections of One Line End. . . . . . . . . . . . . . . . . . . . . .272
3.3.9 Checking the Instrument Transformer Connections of Two Line Ends . . . . . . . . . . . . . . . . . . . . . 277
3.3.10 Checking the Pilot Protection for Internal and External Remote Tripping . . . . . . . . . . . . . . . . . . .277
3.3.11 Testing User-defined Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .277
3.3.12 Trip and Close Test with the Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .278
3.3.13 Switching Check for the Configured Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .278
3.3.14 Triggering Oscillographic Recording for Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279
3.4 Final Preparation of the Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .280
4 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .281
4.1 General Device Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282
4.1.1 Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282
4.1.2 Auxiliary Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
4.1.3 Binary Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 84
4.1.4 Communication Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .285
4.1.5 Electrical Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .288
4.1.6 Mechanical Stress Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .290
4.1.7 Climatic Stress Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 290
4.1.8 Service Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .291
4.1.9 Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .291
4.1.10 UL certification conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .292
14
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Contents
4.2 Protection interfaces and Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .293
4.3 87 Differential Protection Phase Comparison Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .296
4.4 Ground Fault Differential Protection in Grounded Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .299
4.5 Ground Fault Differential Protection in Resonant-grounded / Isolated Systems . . . . . . . . . . . . . . . . .300
4.6 Breaker Intertrip and Remote Tripping- Direct Local Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .301
4.7 Time Overcurrent Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .302
4.8 Inrush Current Restraint Breaker Intertrip and Remote Tripping. . . . . . . . . . . . . . . . . . . . . . . . . . . . .309
4.9 Circuit-Breaker Failure Protection (Optional). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .310
4.10 Thermal Overload Protection 49 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .311
4.11 Voltage Protection (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .313
4.12 Frequency Protection (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .316
4.13 Automatic Reclosing (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .317
4.14 Transmission of Binary Information and Commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .318
4.15 Monitoring Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .319
4.16 Flexible Protection Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .321
4.17 User-defined Functions (CFC). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .324
4.18 Additional Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .328
4.19 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .330
4.19.1 Panel Flush Mounting and Cabinet Flush Mounting (H ousing Size 1/6) . . . . . . . . . . . . . . . . . . . .330
4.19.2 Panel Surface Mounting (Housing Size 1/6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .331
4.19.3 Bottom View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .332
A Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .333
A.1 Ordering Information and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .334
A.1.1 Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
A.1.1.1 7SD80 V4.6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .334
A.1.2 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .337
A.2 Terminal Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .339
A.2.1 7SD80 — Housing for Panel Flush Mounting and Cabinet Flush Mounting and
for Panel Surface Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .339
A.3 Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .345
A.4 Current Transformer Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .348
A.4.1 Current Transformer Ratio: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .348
A.4.2 Overcurrent Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .348
A.4.3 Class Conversion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .349
A.4.4 Core Balance Current Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .349
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .349
Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .349
Class Accuracy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .350
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
15
Contents
A.5 Default Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .351
A.5.1 LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .351
A.5.2 Binary Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .351
A.5.3 Binary Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .352
A.5.4 Function Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .352
A.5.5 Default Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353
A.5.6 Pre-defined CFC Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356
A.6 Protocol-dependent Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357
A.7 Functional Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .358
A.8 Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .360
A.9 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .371
A.10 Group Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 393
A.11 Measured Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .394
Literature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .399
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .401
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 413
16
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual

Introduction 1

This chapter introduces the SIPROTEC 4 7SD80 and gives an overview of the device's application, properties and functions.
1.1 Overall Operation 18
1.2 Application Scope 21
1.3 Characteristics 23
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
17
Introduction

1.1 Overall Operation

1.1 Overall Operation
The digital SIPROTEC 7SD80 overcurrent protection is equipped with a powerful microprocessor. It allows all tasks to be processed digitally, from the acquisition of measured quantities to sending commands to circuit breakers. Figure 1-1 shows the basic structure of the 7SD80 device.

Analog Inputs

The measuring inputs (MI) convert the currents and voltages coming from the instrument transformers and adapt them to the level appropriate for the internal processing of the device. The device provides 4 current transformers and - depending on the model - additionally 3 voltage transformers. Three current inputs serve for the input of the phase currents, another current input (I
I
(current transformer starpoint) or for a separate ground current transformer (for sensitive ground fault detec-
N
tion I
and directional determination of ground faults) - depending on the model.
Ns
) may be used for measuring the ground fault current
N
18
Figure 1-1 Hardware structure of the 7SD80 differential protection
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
There is one voltage input available for each phase-to-ground voltage. The differential protection does not need measuring voltages due to its functional principle. Directional overcurrent protection, however, requires the phase-to-ground voltage V displaying voltages and power values and also measuring the line voltage for automatic reclosing. The analog quantities are forwarded to the input amplifier group (IA).
The input amplifier group IA provides high-resistance termination for the analog input quantities. It consists of filters that are optimized for measured value processing with regard to bandwidth and processing speed.
The analog-to-digital (AD) element consists of an analog-to-digital (A/D) converter and memory components for data transmission to the microcomputer system.

Microcomputer System

Apart from processing the measured values, the microcomputer system µC also executes the actual protection and control functions. They especially consist of:
• Filtering and preparation of the measured quantities
• Continuous monitoring of the measured quantities
• Monitoring of the pickup conditions for the individual protection functions
• Interrogation of limit values and time sequences
• Control of signals for the logic functions
• Decision on trip and close commands
• Recording of messages, fault data and fault values for analysis
• Administration of the operating system and its functions, e.g. data storage, realtime clock, communication, interfaces, etc.
• Formation of the local differential protection values (phasor analysis and charge current computation) and creation of the transmission protocol
• Decoding the received transmission protocol, synchronization of differential protection values and totaling the differential currents and charge currents
• Monitoring the communication with the device of the remote en d
Introduction
1.1 Overall Operation
, VB and VC to be connected. Additionally, voltages can be connected that allow
A
The information is provided via output amplifier OA.

Binary Inputs and Outputs

Binary inputs and outputs to and from the computer system are relayed via the input/output modules. The com­puter system obtains information from the system (e.g. remote resetting) or from other devices (e.g. blocking commands). Outputs are, in particular, commands to the switchgear units and annunciations for remote signal­ing of important events and statuses.
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
19
Introduction
1.1 Overall Operation

Front Elements

Information such as messages related to events, states, measured values and the functional status of the device are visualized by light-emitting diodes (LEDs) and a display screen (LCD) on the front panel.
Integrated control and numeric keys in conjunction with the LCD enable communication with the remote device. These elements enable the user to retrieve all device information such as configuration and setting parameters, operational indications and fault indications or measured values and to edit setting parameters.
In addition, control of circuit breakers and other equipment is possible from the front panel of the device.

Interfaces

Communication with a PC can be implemented via the USB DIGSI interface using the DIGSI software allowing the user to conveniently handle all device functions.
Port A can be used as protection interface to communicate with another 7SD80 device via an optical fiber cable.
If you are using a copper link to create a connection to the other 7SD80 device, use the voltage terminals D1 and D2 as protection interface.
The protection data interfaces are used to transfer the data of the measured quantities from each end of the protected zone to the opposite end. Further information such as closing of the local circuit breaker or other ex­ternally injected trip commands can be transmitted to the opposite end via the protection interface.
In addition to the device communication via DIGSI, port B can also be used to transmit all device data to a central evaluator or a control center. This interface may be provided with various protocols and physical trans­mission schemes to suit the particular application.

Power Supply

The functional units described are supplied by a power supply (PS) with the adequate power in the different voltage levels. Transient voltage dips may occur if the auxiliary voltage supply system becomes short-circuited. Usually, they are bridged by a capacitor storage (see also the Section 4, Technical Data).
A buffer battery is located behind the lower front cover.
20
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
1.2 Application Scope
The digital Line Differential Protection SIPROTEC 4 7SD80 is a selective short-circuit protection for overhead lines and cables with single- and multi-ended infeeds in radial, ring or any type of meshed systems of any trans­mission level. The measured data are compared separately for each phase.
A major advantage of the differential protection principle is the instantaneous tripping in the event of a short circuit at any point within the entire protected zone. The current transformers limit the protected zone at the ends towards the remaining system. This rigid delimitation is the reason why the differential protection scheme shows such an ideal selectivity.
The differential protection system requires a 7SD80 device as well as a set of current transformers at either end of the protected zone. Voltage transformers are not required for the differential protection functions in the 7SD80; they are, however, available to record and display measured values (voltages, power, power factor) or when using a directional overcurrent protection element.
The devices located at the ends of the protected zone exchange measuring information via protection interfac­es using communication links (usually optical fiber or copper cables).
Since fault-free data transmission is the prerequisite for the proper operation of the protection, it is continuously monitored internally.
Introduction

1.2 Application Scope

Protection Functions

The device's basic function is to detect short-circuits or ground faults in the protected zone – even weak-current or high-resistance short-circuits. Even complex multiphase faults are detected correctly, as the measured values are evaluated separately for each phase. The protection is restraint against inrush currents of power transformers. When switching a line onto a fault, it is possible to send an instantaneous trip signal. The 7SD80 line differential protection includes the differential protection functions of phase comparison protection and ground fault differential protection. Both differential protection functions operate independently of each other.
In the event of a communication failure, the devices can automatically switch to emergency operation using an integrated overcurrent protection until communication is restored. The overcurrent protection comprises two definite time-overcurrent protection elements and one inverse time-overcurrent protection element. Both ele­ments operate directional or non-directional. Additionally, the device features a third definite time-overcurrent protection element that always operates non-directionally.
For inverse time overcurrent protection, several characteristic curves of different standards are available. Alternatively, the time overcurrent protection can be used as a backup time overcurrent protection, i.e. it oper-
ates independent of and parallel to the differential protection at either end. The communication link can be used for transmitting further information. Besides measured values, it is possi-
ble to transmit binary information. All protection functions in the 7SD80 always trip 3-pole. They can work together with an integrated automatic
reclose function (optional). The automatic reclose functions enables 3-pole automatic reclosing with two reclose attempts.
The thermal overload protection protects cables and power transformers from inadmissible heating due to over­load.
Additionally, a two-element overvoltage and undervoltage protection and a four-element frequency protection can be used. A circuit-breaker failure protection monitors the response of the circuit breaker following a trip command.
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
21
Introduction
1.2 Application Scope

Control Functions

The device provides a control function which can be accomplished for activating and deactivating switchgear via operator buttons, port B, binary inputs and - using a PC and the DIGSI software - via the front interface.
The switch positions are fed back to the device via auxiliary contacts of the circuit breakers and binary inputs. The current switch positions can be read out at the device and used for plausibility monitoring and interlockings. The number of the devices to be switched is limited by the binary inputs and outputs available in the device or the binary inputs and outputs allocated for the switch position feedbacks. Depending on the equipment, one binary input (single point indication) or two binary inputs (double point indication) can be used. The release to switch can be restricted by appropriate settings for the switching authority (remote or local), and by the oper­ating mode (interlocked/non-interlocked, with or without password validation). Interlocking conditions for switching (e.g. switchgear interlocking) can be defined with the help of integrated user-configurable logic func­tions.

Messages and Measured Values; Recording of Event and Fault Data

The operational indications provide information about conditions in the power system and the device. Measure­ment quantities and values that are calculated can be displayed locally and communicated via the serial inter­faces.
Device messages can be assigned to a number of LEDs on the front cover (allocatable), can be externally pro­cessed via output contacts (allocatable), linked with user-definable logic functions and/or issued via serial in­terfaces.
During a fault (system fault) important events and changes in conditions are saved in fault protocols (Event Log or Trip Log). Instantaneous fault values are also saved in the device and may be analyzed subsequently.

Communication

The following interfaces are available for communication with external operating, control and memory systems. The USB DIGSI interface on the front cover serves for local communication with a PC. With the SIPROTEC 4
operating software DIGSI, all operation and evaluation tasks can be executed using this operator interface, for instance specifying and editing configuration parameters and settings, configuring user-specific logic functions, retrieving operational messages and measured values, inquiring device conditions and measured values, issuing control commands.
Port A is located on the bottom side of the device. This protection data interface connects the device to its partner device at the remote end of the protected object.
Alternatively, you can implement the communication link using the voltage terminals D-1 and D-2. Port B serves for central communication between the device and a control center. It can be operated via data
lines or optical fiber cables. For the data transfer, standardized protocols according IEC 60870-5-103 are avail­able. The integration of the devices into the SINAUT LSA and SICAM automation systems can also be imple­mented with this profile.
Alternatively, there are additional connection options available in connection with PROFIBUS DP and the DNP3.0 and MODBUS protocols. If an EN100 module is available, it is also possible to use the IEC61850 pro­tocol.
You can also use port B to connect a time synchronization device such as DCF77 or IRIG-B.
22
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
1.3 Characteristics
General Properties
• Powerful 32-bit microprocessor system
• Complete digital processing of measured values and control, from the sampling of the analog input values, the processing and organization of the communication between devices up to the closing and tripping com­mands to the circuit breakers.
• Total galvani c and fail-safe separation of the internal processing circuits from the measuring, control and supply circuits of the system via measuring transformers, binary input and output modules and DC or AC converters
• Suited for lines with two ends, even with transformers in the protected zone
• Easy device operation using the integrated operator panel or from a connected personal computer running DIGSI
• Storage of fault indications as well as instantaneous values for fault recording
• Digital protection data transmission; communication of the device through optical fiber cables
• Communication is possible via a single copper wire pair (typically 8 km (4.97 miles), max. 20 km (12.43 miles), depending on the used cable type, see Section 4, Technical Data).
Introduction

1.3 Characteristics

• Permanent supervision of the protection data transmission for disturbance, failure or transfer time variations

Phase Comparison Protection

• Differential protection for two ends with digital protection data transmission
• Protection for all types of short-circuits in systems with any starpoint conditioning
• Reliable distinction between load and short-circuit conditions using adaptive measureme nt methods, also for high-resistance faults with small fault currents
• High sensitivity in light load operation, highest stability against load steps and power fluctuations
• Due to phase segregated measurement, the pickup sensitivity is independent of the fault type
• Suited for feeder transformers in the protected zone
• Detection of high-resistance, weak-current faults due to high sensitivity of the protection functions
• Fast tripping also on weak or zero infeed ends (breaker intertrip)
• No frequency dependency

Ground Fault Differential Protection for Grounded Systems

• Short command time
• High sensitivity for short circuits to ground
• High stability against external ground faults by stabilizing the through-flowing ground current

Ground Fault Differential Protection for Isolated / Grounded Systems

• Short command time
• High sensitivity for short circuits to ground
• High stability against external short-circuits to ground using the magnitude and phase relationship of the ground current flowing through for stabilization
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
23
Introduction
1.3 Characteristics

External Direct and Remote T ripping

• Tripping of the local end by an external device via binary input
• Tripping of the opposite end by local protection functions or by an external device via binary input

Time Overcurrent Protection

• Optionally selectable as emergency function during protection data communication failure or as backup function or both
• A maximum of 3 definite time elements and one inverse time element, each for phase currents and ground current
• A maximum of 2 directional definite time elements and one directional inverse time element, each for phase currents and ground current
• For inverse time overcurrent protection, selection from various characteristics of different standards possible
• Blocking options e.g. for reverse interlocking with any element
• Instantaneous tripping when closing onto a short circuit possible with any element

Inrush Current Restraint

• Insensitive to inrush currents, even in the case of feeder transformers in the protected zone, and against higher-frequency transients
• High stability also for different current transformer saturation

Circuit-Breaker Failure Protection

• With independent current elements for the monitoring of the current flow through each pole of the circuit breaker
• Separate pickup thresholds for phase and ground currents
• Monitoring time element for tripping
• Initiation by the trip command of each integrated protection function
• Initiation by external trip functions possible
• Single-element or two-element
• No dropout and seal-in times

Thermal Overload Protection

• Thermal replica of the current heat losses of the protected object
• RMS measurement for all three phase currents
• Adjustable thermal and current-dependent warning elements
24
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual

Vo ltage Protection

• Overvoltage and undervoltage detection with different elements
• Two overvoltage elements for the phase-to-ground voltages
• Two overvoltage elements for the phase-to-phase voltages
• Two overvoltage elements for the positive sequence voltage
• Two overvoltage elements for the negative sequence system of the voltages
• Two overvoltage elements for the zero system of the voltages or for any other single-phase voltage
• Adjustable dropout conditions
• Two undervoltage elements for the phase-to-ground voltages
• Two undervoltage elements for the phase-to-phase voltages
• Two undervoltage elements for the positive sequence system of the voltages
• Adjustable current criterion for undervoltage protection functions

Frequency Protection 81 (Optional)

• Monitoring of falling below (f<) and/or exceeding (f>) with 4 frequency limits and time delays that are inde­pendently adjustable
Introduction
1.3 Characteristics
• Particularly insensitive to harmonics and abrupt phase angle changes
• Wide frequency range (approx. 25 Hz to 70 Hz)

Automatic Reclose Function (Optional)

• For reclosing after 3-pole open condition
• Two recl o si n g attempts
• With separate action times for each reclosing attempt, optionally without action times
• With separate dead times
• Optionally controlled by protection element pickup with separate dead times after 1-pole, 2-pole or 3-pole pickup

Monitoring Functions

• Reliability of the device is greatly increased because of self-monitoring of the internal measurement circuits, the auxiliary power supply as well as the hardware and software
• Monitoring of the current transformer and voltage transformer secondary circuits using summation and sym­metry check techniques
• Monitoring of communication with statistics showing the availability of transmission telegrams
• Check of the consistency of protection settings at both line ends: no processor system start-up with incon­sistent settings which could lead to a malfunction of the differential protection system
• Trip circuit monitoring possible
• Check of local and remote measured values and comparison of both
• Broken wire supervision for the secondary CT circuits with fast phase segregated blocking of the differential protection system in order to avoid malfunction
• Supervision of measuring voltage failure using "Fuse Failure Monitor"
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
25
Introduction
1.3 Characteristics

Flexible Protection Functions

• Up to 20 customizable protection functi ons with 3-phase or 1-phase operation
• Any calculated or directly measured variable can theoretically be evaluated
• Standard protection logic with a constant (i.e. definite time) characteristic curve
• Internal and configurable pickup and dropout delay
• Editable indication texts

User-defined Logic Functions (CFC)

• Internal and external signals can be logically combined to realize user-defined logic functions
• All common logic functions
• Time delays and limit value interrogations

Command Processing

• Switching devices can be opened and closed manually using control keys, programmable function keys, via port B (e.g. of SICAM or SCADA), or via the user interface (using a personal computer and the DIGSI oper­ating software)
• Feedback of the circuit-breaker states via the breaker auxiliary contacts (for commands with feedback)
• Plausibility monitoring of the circuit-breaker positions and interlocking conditions.

Commissioning; Operation; Maintena nce

• Indication of the local and remote measured values according to magnitude and phase angle
• Indication of the calculated differential and restraint currents
• Indication of the measured values of the communication connection, as runtime and availability

Additional Functions

• Battery-buffered clock which can be synchronized via a synchronization signal (DCF77, IRIGB via satellite receiver), binary input or system interface
• Continuous calculation and indication of operational measured values on the front display, indication of mea­sured values of the far end or all ends (for devices with active interfaces)
• Fault event memory (trip log) for the last eight network faults (faults in the power system), with real time stamps
• Fault recording and data transfer for fault recording for a maximum time range of 15 seconds.
• Switching statistics: Counting of the trip and close commands initiated by the device as well as recording of the short-circuit data and accumulation of the disconnected fault currents
• Communication with central control and memory components via serial interfaces possible (depending on the ordered variant), optionally via RS232, RS485 connection, modem or fiber optic cable
26
• Commissioning aids such as connection check, direction check and circuit-breaker check
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual

Functions 2

This chapter describes the numerous functions available on the SIPROTEC 4 device 7SD80. It shows the setting possibilities for each function in maximum configuration. Information with regard to the determination of setting values as well as formulas, if required, are also provided.
Based on the following information, it can also be determined which of the provided functions should be used.
2.1 General 28
2.2 Phase Comparison Protection and Ground Differential Protection 52
2.3 Breaker Intertrip and Remote Tripping 75
2.4 Backup Overcurrent 78
2.5 Inrush Restraint 98
2.6 Circuit-Breaker Failure Protection 50BF 101
2.7 Thermal Overload Protection 49 112
2.8 Undervoltage and Overvoltage Protection 27/59 (Optional) 116
2.9 Frequency Protection 81 (Optional) 133
2.10 Direct Local Trip 139
2.1 1 Automatic Reclosure Function 79 (Optional) 141
2.12 Circuit-Breaker Test 155
2.13 Direct Remote Trip and Transmission of Binary Information 161
2.14 Monitoring Functions 163
2.15 Flexible Protection Functions 183
2.16 Function Control 194
2.17 Additional Functions 199
2.18 Breaker Control 214
2.19 Notes on Device Operation 229
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
27
Functions

2.1 General

2.1 General
You can edit the function parameters via the user interface or service interface from a PC runni ng th e D IGSI software; some parameters can also be changed using the controls at the front panel of the device. The pro­cedure is set out in detail in the SIPROTEC 4 System Description /1/.

2.1.1 Functional Scope

The 7SD80 relay comprises protection functions and additional functions. The hardware and firmware are de­signed for this scope of functions. Additionally, the control functions can be matched to the system require­ments. Individual functions can be activated or deactivated during the configuration procedure or the interaction of functions be modified.
2.1.1.1 Description
Setting the Scope of Functions
Example for the configuration of the scope of functions: A system consists of overhead lines and underground cables. Since automatic reclosing is only needed for the
overhead lines, the automatic reclosing function is disabled for the relays protecting the underground cables. The available protection functions and additional functions can be configured as Enabled or Disabled. For
some functions, there is a choice between several alternatives possible, as described below. Functions configured as Disabled are not processed in the 7SD80. There are no messages issued and the
corresponding settings (functions, limit values) are not queried during configuration.
Note
Available functions and default settings depend on the ordered variant of the relay (see A.1 for details).
28
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
2.1.1.2 Setting Notes
Setting the Scope of Functions
Your protection device is configured using the DIGSI software. Connect your personal computer either to the USB port on the device front or to port B on the bottom side of the device depending on the device version (ordering code). The operation via DIGSI is explained in the SIPROTEC 4 System Description.
The Device Configuration dialog box allows you to adjust your device to the prevailing system conditions. Password no. 7 is required (for parameter set) to change configuration parameters in the device. Without the
password you can only read the settings but not edit and transmit them to the device.
Special Settings
Most settings are self-explaining. The special cases are described in the following. If you want to use the setting group change function, set address 103 Grp Chge OPTION to Enabled. In this
case, you can select up to four different groups of function parameters between which you can switch quickly and conveniently during operation. Only one setting group can be used when selecting the option Disabled.
The differential protection function 87 DIFF.PROTEC. (address 112) as a main function of the device should always be Enabled. This also applies to the supplementary functions of the differential protection such as breaker intertrip.
Functions
2.1 General
The external trip initiation (address 122 DTT Direct Trip) is a command that is initiated from an external device for tripping the local circuit breaker.
At address 126 Back-Up O/C, you can set the characteristic group which the time overcurrent protection uses for operation. In addition to the definite-time overcurrent protection an inverse-time overcurrent protection can be configured that either operates according to an IEC characteristic (50(N) 51(N) IEC) or to an ANSI char­acteristic (50(N) 51(N)ANSI). This selection is independent of whether the time overcurrent protection is in­tended to operate as emergency protection (only in case of protection communication failure) or as indepen­dent backup protection. Device versions equipped with directional overcurrent protection (MLFB position 14 = R or S) additionally provide a directional definite time overcurrent protection element and a directional inverse time overcurrent protection element. The characteristic curves of the two inverse time overcurrent protection elements are identical. The different characteristic curves are shown in the Technical Data (Section 4.6). You can also disable the time overcurrent protection (Disabled).
Set to Disabled, the entire time overcurrent protection can be disabled. For overload protection you can define in address 142 49 whether the function is to be Enabled or Disabled. In address 139 you can set the breaker failure protection to Enabled or Disabled. The setting option
enabled w/ 3I0> subjects the ground current and the negative sequence current to a plausibility check. If the device features an automatic reclosing function, address
133 and 134 are of importance. Automatic re­closure is only permitted for overhead lines. It must not be used in any other case. If the protected object con­sists of a combination of overhead lines and other equipment (e.g. overhead line in unit with a transformer or overhead line/cable), reclosing is only permissible if it is ensured that reclosing will only be performed in the event of a fault on the overhead line. If no automatic reclosing function is desired for the feeder at which 7SD80 operates, or if an external device is used for reclosure, set address 133 79 Auto Recl. to Disabled. Or you can enter the number of desired reclosing attempts there. Y ou can select 1 AR-cycle or 2 AR-cycles.
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
29
Functions
2.1 General
The AR control mode at address 134 allows a maximum of four options. On the one hand, it can be deter­mined whether the automatic reclosure cycles are carried out according to the fault type detected by the pickup of the starting protective function(s) or according to the type of trip command. On the other hand, the auto­matic reclosing function can be operated with or without action time.
The setting Trip ... (with trip command ..., default setting) allows you to specify different dead times for each automatic reclose cycle.
The setting Pickup ... (with pickup ...) allows you to enter different dead times for the automatic reclose cycles for 1
-phase, 2-phase and 3-phase short circuits. The pickup status of the protection functions at the instant the trip command disappears is decisive here. This operating mode enables making the dead times de­pendent on the type of fault also for three-pole reclosure cycles. Tripping is always three-pole.
The setting ... w/ Tact (with ... action time) provides an action time for each automatic reclose cycle. The action time is started by a general pickup of all protection functions. If there is no trip command yet when the action time has expired, the corresponding automatic reclosure cycle cannot be executed. Section 2.11 pro­vides detailed information on this topic. For time graded protection this setting is recommended. If the protec­tion function which is to operate with automatic reclosure does not have a general pickup signal for starting the action times, select ... w/o Tact (without action time).
Address 137 27/59 allows activating the voltage protection function with a variety of undervoltage and over­voltage protection elements.
For the trip circuit supervision enter the number of trip circuits to be monitored at address 140 74 Trip Ct Supv: 1 trip circuit, 2 trip circuits or 3 trip circuits, unless you omit it (Disabled).
If the device is connected to voltage transformers, specify this condition in address 144 V-TRANSFORMER. The voltage-based functions, for instance the directional overcurrent protection elements, the ground fault differen­tial protection in resonant-grounded/isolated systems or determination of the voltage-based measured values, can only be activated if voltage transformers are connected.
The flexible protection functions can be configured via parameter FLEXIBLE FUNC.. You can create up to 20 flexible functions by setting a checkm ark in front of the desired function. If the checkmark of a function is re­moved, all settings and configurations made previously will be lost. After re-selecting the function, all settings and configurations are in default setting. The flexible function can be configured in DIGSI at „ Settings“, „Addi­tional Functions“ and „Settings“. The routing is done, as usual, under „Settings“ and „Masking I/O“. If you want to use the flexible protection function, the device must be connected to voltage transformers.
30
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
2.1.1.3 Settings
Addr. Parameter Setting Options Default Setting Comments
103 Grp Chge OPTION Disabled
Enabled
112 87 DIFF.PROTEC. Enabled
Disabled
122 DTT Direct Trip Disabled
Enabled
124 50HS SOTF Disabled
Enabled
126 Back-Up O/C Disabled
50(N) 51(N) IEC 50(N) 51(N) ANSI 50(N) 67(N) IEC 50(N) 67(N) ANSI
133 79 Auto Recl. Disabled
1 AR-cycle 2 AR-cycles
134 AR control mode PU w/ActionTime
PU w/o ActionT. Trip w/ActionT. Trip w/oActionT
136 81 O/U Disabled
Enabled
137 27/59 Disabled
Enabled
139 50BF Disabled
Enabled enabled w/ 3I0>
140 74 Trip Ct Supv Disabled
1 trip circuit 2 trip circuits 3 trip circuits
142 49 Disabled
Enabled
144 V-TRANSFORMER Not connected
connected ONLY VN
Disabled Setting Group Change Option
Enabled 87 Differential protection
Disabled DTT Direct Transfer Trip
Disabled 50HS Instantaneous SOTF
50(N) 51(N) IEC Backup overcurrent
Disabled 79 Auto-Reclose Function
Trip w/ActionT. Auto-Reclose control mode
Disabled 81 Over/Underfrequency Protec-
tion
Disabled 27, 59 Under/Overvoltage Protec-
tion
Disabled 50BF Breaker Failure Protection
Disabled 74TC Trip Circuit Supervision
Disabled 49 Thermal Overload Protection
connected Voltage transformers
Functions
2.1 General
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
31
Functions
2.1 General
Addr. Parameter Setting Options Default Setting Comments
617 ServiProt (CM) Disabled
T103 Port B usage T103 DIGSI TIME SYNCH
- FLEXIBLE FCT. 1.. 20 Flexible Fu nction 01
Please select Flexible Functions Flexible Function 02 Flexible Function 03 Flexible Function 04 Flexible Function 05 Flexible Function 06 Flexible Function 07 Flexible Function 08 Flexible Function 09 Flexible Function 10 Flexible Function 11 Flexible Function 12 Flexible Function 13 Flexible Function 14 Flexible Function 15 Flexible Function 16 Flexible Function 17 Flexible Function 18 Flexible Function 19 Flexible Function 20
32
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual

2.1.2 Device, General Settings

The device requires some general information. This may be, for example, the type of annunciation to be issued in the event of an occurrence of a power system fault.
2.1.2.1 Description
Command-dependent Messages "No Trip – No Flag"
The indication of messages masked to local LEDs and the generation of additional messages can be made dependent on whether the device has issued a trip signal. This information is then not output if during a system disturbance one or more protection functions have picked up but no tripping by the 7SD80 resulted because the fault was cleared by a different device (e.g. on another line). These messages are then limited to faults in the line to be protected.
The following figure illustrates the creation of the reset command for stored messages. By the moment of the device dropout, the presetting of the parameter610 FltDisp.LED/LCD decides, whether the new fault will be stored or reset.
Functions
2.1 General
Figure 2-1 Creation of the reset command for the latched LED and LCD messages
Spontaneous Messages on the Display
You can determine whether or not the most important data of a fault event is displayed automatically after the fault has occurred (see also Subsection "Fault Messages" in Section "Auxiliary Functions").
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
33
Functions
2.1 General
2.1.2.2 Setting Notes
Fault Display
A new pickup by a protection element generally turns off any previously lit LEDs so that only the latest fault is displayed at any one time. It can be selected whether the stored LED displays and the spontaneous fault indi­cations on the display appear upon the new pickup, or only after a new trip signal is issued. In order to select the desired displaying mode, select the submenu Device in the SETTINGS menu. Under address 610 FltDisp.LED/LCD the two alternatives Target on PU and Target on TRIP ("No trip – no flag") can be selected.
Use parameter 615 Spont. FltDisp. to specify whether or not a spontaneous fault message should appear automatically on the display (YES) or not (NO).
Selection of Default Display
The start page of the default display appearing after startup of the device can be selected in the device data via parameter 640 Start image DD. The pages available for each device version are listed in the Appendix A.5.
Protection Interface Test Mode
To check the communication quality of the two 7SD80 devices during commissioning, set parameter 650 PDI Test Mode to ON. The availability of the communication link via the protection interface is displayed as a sta-
tistical value (see Section 2.17.2).
2.1.2.3 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
Addr. Parameter Setting Options Default Setting Comments
610 FltDisp.LED/LCD Target on PU
Target on TRIP
615 Spont. FltDisp. NO
YES
625A T MIN LED HOLD 0 .. 60 min; 0 min Minimum hold time of latched
640 Start image DD image 1
image 2 image 3 image 4 image 5 image 6 image 7 image 8
650 PDI Test Mode OFF
ON
Target on PU Fault Display on LED / LCD
NO Spontaneous display of flt.annun-
ciations
LEDs
image 1 Start image Default Display
OFF PDI Test Mode
34
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
2.1.2.4 Information List
Functions
2.1 General
No. Information Type of In-
Comments
formation
- Test mode IntSP Test mode
- DataStop IntSP Stop data transmission
- UnlockDT IntSP Unlock data transmission via BI
- Reset LED IntSP Reset LED
- SynchClock IntSP_Ev Clock Synchronization
- >Light on SP >Back Light on
- HWTestMod IntSP Hardware Test Mode
- Error FMS1 OUT Error FMS FO 1
- Error FMS2 OUT Error FMS FO 2
- Distur.CFC OUT Disturbance CFC
- Brk OPENED IntSP Breaker OPENED
- Feeder gnd IntSP Feeder GROUNDED 1 Not configured SP No Function configured 2 Non Existent OUT Function Not Available 3 >Time Synch SP >Synchronize Internal Real Time Clock 5 >Reset LED SP >Reset LED 11 >Annunc. 1 SP >User defined annunciation 1 12 >Annunc. 2 SP >User defined annunciation 2 13 >Annunc. 3 SP >User defined annunciation 3 14 >Annunc. 4 SP >User defined annunciation 4 15 >Test mode SP >Test mode 16 >DataStop SP >Stop data transmission 51 Device OK OUT Device is Operational and Protecting 52 ProtActive IntSP At Least 1 Protection Funct. is Active 55 Reset Device OUT Reset Device 56 Initial Start OUT Initial Start of Device 60 Reset LED OUT_Ev Reset LED 67 Resume OUT Resume 68 Clock SyncError OUT Clock Synchronization Error 69 DayLightSavTime OUT Daylight Saving Time 70 Settings Calc. OUT Setting calculation is running 71 Settings Check OUT Settings Check 72 Level-2 change OUT Level-2 change 73 Local change OUT Local setting change 110 Event Lost OUT_Ev Event lost 113 Flag Lost OUT Flag Lost 125 Chatter ON OUT Chatter ON 126 ProtON/OFF IntSP Protection ON/OFF (via system port) 140 Error Sum Alarm OUT Error with a summary alarm 160 Alarm Sum Event OUT Alarm Summary Event 177 Fail Battery OUT Failure: Battery empty 181 Error A/D-conv. OUT Error: A/D converter 182 Alarm Clock OUT Alarm: Real Time Clock 183 Error Board 1 OUT Error Board 1
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
35
Functions
2.1 General
No. Information Type of In-
Comments
formation
184 Error Board 2 OUT Error Board 2 185 Error Board 3 OUT Error Board 3 186 Error Board 4 OUT Error Board 4 187 Error Board 5 OUT Error Board 5 190 Error Board 0 OUT Error Board 0 191 Error Offset OUT Error: Offset 193 Alarm adjustm. OUT Alarm: Analo g input adjustment invalid 194 Error neutralCT OUT Error: Neutral CT different from MLFB 320 Warn Mem. Data OUT Warn: Limit of Memory Data exceeded 321 Warn Mem. Para. OUT Warn: Limit of Memory Parameter exceeded 322 Warn Mem. Oper. OUT Warn: Limit of Memory Operation exceeded 323 Warn Mem. New OUT Warn: Limit of Memory New exceeded 2054 Emer. mode OUT Emergency mode 32200 PDITestFOon/OFF IntSP PDI Test Mode FO ON/OFF 32201 PDITestCuon/OFF IntSP PDI Test Mode Cu ON/OFF 32202 PDI Test Mode OUT PDI Test Mode 32203 PDI Test remote OUT PDI Test Mode remote 32224 PDI FO: AGING OUT PDI FO: aging (distance damping high) 32225 PDI Cu: AGING OUT PDI Cu: aging (distance damping high)
36
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual

2.1.3 General Power System Data (Power System Data 1)

The device requires certain data regarding the network and substation so that it can adapt its functions to this data depending on the application. The data required include for instance rated data of the substation and the measuring transformers, polarity and connection of the measured quantities, if necessary features of the circuit breakers, and others. Furthermore, there are several function parameters associated with several functions rather than one specific protection, control or monitoring function. The Power System Data 1 can generally only be changed from a PC running DIGSI and are discussed in this section.
2.1.3.1 Setting Notes
Polarity of Current Transformers
In address 201 CT Starpoint the polarity of the current transformers must be entered, in other words, the location of the CT starpoint (Figure 2-2). The setting defines the measuring direction of the device (current in line direction is defined as positive at both line ends). The reversal of this parameter also reverses the polarity of the ground current input I
.
N
Functions
2.1 General
Figure 2-2 Polarity of current transformers
Nominal Values of Transformers
In addresses 203 Vnom PRIMARY and 204 Vnom SECONDARY the device obtains information on the primary and secondary rated voltage (phase-to-phase voltage) of the voltage transformers.
The voltage connection is required for all functions that work on the basis of power or voltage values, e.g. ground fault differential protection in resonant-grounded/isolated systems, directional overcurrent protection, voltage protection, frequency protection, and to display and record the voltages.
Please make sure that the rated secondary transformer current matches the rated current of the device. Correct entry of the primary data is a prerequisite for the correct computation of operational measured values
with primary magnitude. If the settings of the device are performed with primary values using DIGSI, these primary data are an indispensable requirement for the correct function of the device.
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
37
Functions
2.1 General
Current Connection
The device features four current measurement inputs, three of which are connected to the set of current trans­formers. Various possibilities exist for the fourth current input I
• Connection of the I protected feeder (normal connection, see Appendix, A.3a):
Address 220 is then set to: I4 transformer = In prot. line and address 221 I4/Iph CT = 1.
• Connection of the I CT or core balance CT, see Appendix, A.3):
Address 220 is then set to: I4 transformer = In prot. line and address 221 I4/Iph CT is set:
:
4
input to the ground current in the neutral point of the set of current transformers on the
4
input to a separate ground current transformer on the protected line (e.g. a summation
4
Example Phase current transformers 500 A/5 A Core balance CT 300 A / 5AI4/IphCT = 300/500 = 0.6
• Connecting the I4 input to the starpoint current of a transformer; this is used for the ground fault differential protection:
Address 220 is then set to: I4 transformer = and address 221I4/Iph CT depends on the transforma­tion ratio of the starpoint transformer to the transformer set of the protected line.
• If the input I4 is not required, set: Address 220 I4 transformer = Not connected, Address 221 I4/Iph CT is then irrelevant. In this case, the neutral current is calculated by summing the phase currents.
Rated Frequency
The rated frequency of the system is set at address 230 Rated Frequency. The factory setting of the model variant must only be changed if the device is to be used for a purpose other than intended when ordering. You can set 50 Hz or 60 Hz.
:
System Starpoint
The manner in which the system neutral point is grounded must be considered for the correct processing of ground faults and double ground faults. Accordingly, set address 207 SystemStarpoint = Grounded, Peterson-C.Gnd. or Isolated. For low-resistance or high-resistance („impedance grounded“) systems, set Grounded.
Depending on the setting of this parameter, the ground fault differential protection uses either the measured ground current (Grounded) or the values calculated from the power values (Peterson-C.Gnd. or Isolated).
38
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Command Duration
In address 240 the minimum trip command duration TMin TRIP CMD is set. It applies to all protection and control functions that can initiate a trip command. It also determines the duration of the trip pulse when a circuit­breaker trip test is initiated via the device. This parameter can only be set in DIGSI at Display Additional Set- tings.
In address 241 the maximum close command duration TMax CLOSE CMD is set. This applies to all close com­mands issued by the device. It also determines the length of the close command pulse when a circuit-breaker test cycle is issued via the device. It must be long enough to ensure that the circuit breaker has securely closed. An excessive duration causes no problem since the cl osing command is interrupted in the event that another trip is initiated by a protection function. This parameter can only be set in DIGSI at Display Additional Set-
tings.
Circuit-Breaker Test
7SD80 allows a circuit-breaker test during operation using a trip-and-close command entered on the front panel or from DIGSI. The duration of the trip command is set as explained above. Address 242 T-CBtest-dead determines the duration from the end of the trip command until the start of the close command for this test. It should not be less than 0.1 s.
Pickup Thresholds of the Binary Inputs (BI Thresholds)
Functions
2.1 General
At address 260 Threshold BI 1 to 266 Threshold BI 7 you can set the pickup thresholds of the binary inputs of the device. The settings Thresh. BI 176V, Thresh. BI 88V or Thresh. BI 19V are possible here.
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
39
Functions
2.1 General
2.1.3.2 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
Addr. Parameter Setting Options Default Setting Comments
201 CT Starpoint towards Line
towards Busbar 203 Vnom PRIMARY 0.4 .. 500.0 kV 10.0 kV Rated Primary Voltage 204 Vnom SECONDARY 80 .. 125 V 100 V Rated Secondary Voltage (Ph-Ph) 205 CT PRIMARY 10 .. 20000 A 400 A CT Rated Primary Current 206 CT SECONDARY 1A
5A
towards Line CT Starpoint
1A CT Rated Secondary Current
207 SystemStarpoint Grounded
Grounded System Starpoint is Peterson-C.Gnd. Isolated
220 I4 transformer Not connected
In prot. line I4 current transformer is In prot. line
221 I4/Iph CT 0.010 .. 5.000 1.000 Matching ratio I4/Iph for CT's 230 Rated Frequency 50 Hz
50 Hz Rated Frequency 60 Hz
240A TMin TRIP CMD 0.02 .. 30.00 sec 0.10 sec Minimum TRIP Command Dura-
tion
241A TMax CLOSE CMD 0.01 .. 30.00 sec 1.00 sec Maximum Close Command Dura-
tion
242 T-CBtest-dead 0.00 .. 30.00 sec 0.10 sec Dead Time for CB test-autoreclo-
sure
260 Threshold BI 1 Thresh. BI 176V
Thresh. BI 176V Threshold for Binary Input 1 Thresh. BI 88V Thresh. BI 19V
261 Threshold BI 2 Thresh. BI 176V
Thresh. BI 176V Threshold for Binary Input 2 Thresh. BI 88V Thresh. BI 19V
262 Threshold BI 3 Thresh. BI 176V
Thresh. BI 176V Threshold for Binary Input 3 Thresh. BI 88V Thresh. BI 19V
263 Threshold BI 4 Thresh. BI 176V
Thresh. BI 88V Thresh. BI 19V
264 Threshold BI 5 Thresh. BI 176V
Thresh. BI 88V Thresh. BI 19V
265 Threshold BI 6 Thresh. BI 176V
Thresh. BI 88V Thresh. BI 19V
266 Threshold BI 7 Thresh. BI 176V
Thresh. BI 88V Thresh. BI 19V
40
Thresh. BI 176V Threshold for Binary Input 4
Thresh. BI 176V Threshold for Binary Input 5
Thresh. BI 176V Threshold for Binary Input 6
Thresh. BI 176V Threshold for Binary Input 7
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual

2.1.4 Oscillographic Fault Records

The 7SD80 multifunctional protection with control is equipped with a fault record memory. The instantaneous values of the measured values
i
, iB, iC, iN, iNs and vA, vB, vC, 3I0
A
diff
, 3I0
rest
(voltages in accordance with connection) are sampled at intervals of 1.0 ms (for 50 Hz) and stored in a revolving buffer (20 samples per cycle). In the event of a fault, the data is stored for a set period of time, but not for more than 5 seconds. Up to 8 fault events can be recorded in this buffer. The fault record memory is automatically updated with every new fault so that there is no acknowledgment for previously recorded faults required. In ad­dition to protection pickup, the recording of the fault event data can also be started via a binary input or via the serial interface.
2.1.4.1 Description
The data of a fault event can be read out via the device interface and evaluated with the help of the SIGRA 4 graphic analysis software. SIGRA 4 graphically represents the data recorded during the fault event and also calculates additional information from the measured values. Currents and voltages can be presented either as primary or as secondary values. Signals are additionally recorded as binary tracks (marks) e.g. "pickup", "trip".
Functions
2.1 General
If port B of the device has been configured correspondingly, the fault record data can be imported by a central controller via this interface and evaluated. Currents and voltages are prepared for a graphic representation. Signals are additionally recorded as binary tracks (marks) e.g. "pickup", "trip".
The retrieval of the fault data by the central controller takes place automatically either after each protection pickup or after a tipping.
Note
The signals used for the binary tracks can be allocated in DIGSI.
2.1.4.2 Setting Notes
Specifications
The actual storage time encompasses the pre-fault time PRE. TRIG. TIME (address 411) ahead of the ref­erence instant, the normal recording time and the post-fault time POST REC. TIME (address 412) after the storage criterion has reset. The maximum storage time for each fault recording (MAX. LENGTH) is entered in address 410. Recording per fault must not exceed 5 seconds. A total of 8 records can be saved. However, the total length of time of all fault records in the buffer must not exceed 25 seconds.
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
41
Functions
2.1 General
2.1.4.3 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
Addr. Parameter Setting Options Default Setting Comments
402A WAVEFORMTRIGGERSave w. Pickup
Save w. TRIP Start w. TRIP
403A WAVEFORM DATA Fault event
Pow.Sys.Flt.
410 MAX. LENGTH 0.30 .. 5.00sec 2.00 sec Max. length of a Waveform
411 PRE. TRIG. TIME 0.05 .. 0.50 sec 0.25 sec Captured Waveform Prior to
412 POST REC. TIME 0.05 .. 0.50 sec 0.10 sec Captured Waveform after Event 415 BinIn CAPT.TIME 0.10 .. 5.00 sec; 0.50 sec Capture Time via Binary Input
Save w. Pickup Waveform Capture
Fault event Scope of Waveform Data
Capture Record
Trigger
2.1.4.4 Information List
No. Information Type of In-
formation
- FltRecSta IntSP Fault Record ing Start 4 >Trig.Wave.Cap. SP >Trigger Waveform Capture 30053 Fault rec. run. OUT Fault recording is running
Comments
42
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual

2.1.5 Change Group

Up to four different setting groups can be created for establishing the device's function settings.
2.1.5.1 Description
Changing Setting Groups
During operation the user can switch back and forth setting groups locally, via the operator panel, binary inputs (if so configured), the service interface using a personal computer, or via the system interface. For reas ons of safety it is not possible to change between setting groups during a power system fault.
A setting group includes the setting values for all fu nctions that have been selected as Enabled during con­figuration (see Section 2.1.1.2). In 7SD80 relays, four independent setting groups (A to D) are available. While setting values may vary, the selected functions of each setting group remain the same.
2.1.5.2 Setting Notes
Functions
2.1 General
General
If setting group change option is not required, Group A is the default selection. Then, the rest of this se ction is not applicable.
If the changeover option is desired, group changeover must be set to Grp Chge OPTION = Enabled (address
103) when the function extent is configured. For the setting of the function parameters, each of the required setting groups A to D (a maximum of 4) must be configured in sequence. The SIPROTEC 4 System Description gives further information on how to copy setting groups or reset them to their status at delivery and also how to change from one setting group to another.
Subsection 3.1 of this manual tells you how to change between several setting groups externally via binary inputs.
2.1.5.3 Settings
Addr. Parameter Setting Options Default Setting Comments
301 ACTIVE GROUP Group A
Group B Group C Group D
302 CHANGE Group A
Group B Group C Group D Binary Input Protocol
Group A Active Setting Group is
Group A Change to Another Setting Group
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
43
Functions
2.1 General
2.1.5.4 Information List
No. Information Type of In-
formation
- P-GrpA act IntSP Setting Group A is active
- P-GrpB act IntSP Setting Group B is active
- P-GrpC act IntSP Setting Group C is active
- P-GrpD act IntSP Setting Group D is active 7 >Set Group Bit0 SP >Setting Group Select Bit 0 8 >Set Group Bit1 SP >Setting Group Select Bit 1
Comments

2.1.6 General Protection Data (Power System Data 2)

The general protection data (P.System Data 2) include settings associated with all functions rather than a specific protection, monitoring or control function. In contrast to the P.System Data 1 as discussed before, they can be changed over with the setting groups and set on the operator panel of the device.
2.1.6.1 Setting Notes
Rated Values of Protected Lines
With address 1103 FullScaleVolt. you inform the device of the primary nominal voltage (phase-to-phase) of the equipment to be protected (if voltages are applied). This setting influences the displays of the operational measured values in %.
The primary nominal current (address 1104 FullScaleCurr.) is that of the protected object. For cables the thermal continuous current-loading capacity can be selected. For overhead lines the rated current is usually not defined. set the rated current of the current transformers (as set in address 205 CT PRIMARY, Section
2.1.3.1). If the current transformers have different nominal currents at the ends of the protected object, set the highest nominal current value for all ends.
This setting will not only have an impact on the indication of the operational measured values in per cent, but must also be exactly the same for each end of the protected object, since it is the basis for the current comparison at the ends.
General Line Data
The directional values (power, power factor, work and based on work: minimum, maximum, average and threshold values), calculated in the operational measured values, are usually defined positive in direction to the protected object. This requires that the connection polarity for the entire device is configured accordingly in the P.System Data 1 (compare also „Polarity of the Current Transformers“, address 201). But it is also possible to define the „forward“ direction for the protection functions and the positive direction for the power etc. differ­ently, e.g. so that the active power flow (from the line to the busbar) is indicated in the positive sense. To do so, set address 1107 P,Q sign to reversed. If the setting is not reversed (default), the positive direction for the power etc. corresponds to the „forward“ direction for the protection functions.
44
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Circuit-Breaker Status
Information regarding the circuit-breaker position is required by various protection and supplementary functions to ensure their optimal functionality. The device has a circuit-breaker status recognition which processes the status of the circuit-breaker auxiliary contacts and contains also a detection based on the measured currents and voltages (see also Section 2.16).
In address 1130 the residual current PoleOpenCurrent is set, which will definitely not be exceeded when the circuit-breaker pole is open. If parasitic currents (e.g. through induction) can be excluded when the circuit breaker is open, this setting may be very sensitive. Othe rwise this setting must be increased. Usually the pre­setting is sufficient. This parameter can only be set in DIGSI at Display Additional Settings.
The seal-in time SI Time all Cl. (address 1132) de termines the period of time during which the active protection functions are enabled following each energization of the line. This time is started when the internal switching detection function recognizes closing of the circuit breaker or if the circuit-breaker auxiliary contacts or a binary device input signal that the circuit breaker was closed. The time must therefore be longer than the command time of these protection functions plus a safety margin. This parameter can only be set in DIGSI at Display Additional Settings.
In address 1134 Line Closure the criteria for the internal recognition of line energization are determined. Only with ManCI means that only the manual close signal via binary input or the integrated control is eval­uated as closure. I OR V or ManCl means that additionally the measured currents or voltages are used to determine closure of the circuit breaker, whereas 52a OR I or M/C implies that either the currents or the states of the circuit-breaker auxiliary contacts are used to determine closure of the circuit breaker. If the voltage transformers are not arranged on the line side, the setting 52a OR I or M/C must be used. In the case of I or Man.Close only the currents or the manual close signals are used to recognize closing of the circuit break­er.
Functions
2.1 General
Before each closing detection, the circuit breaker must be recognized as being open for the settable time 1133 T DELAY SOTF.
Address 1135 Reset Trip CMD determines under which conditions a trip command is reset. If CurrentOpenPole is set, the trip command is reset as soon as the current disappears. It is important that the value set in address 1130 PoleOpenCurrent(see above) is undershot. If Current AND 52a is set, the circuit-breaker auxiliary contact must send a message that the circuit breaker is open. It is a prerequisite for this setting that the position of the auxiliary contacts is allocated via a binary input.
For special applications, in which the device trip command does not always lead to a complete cutoff of the current, the setting Pickup Reset can be chosen. In this case, the trip command is reset as soon as the pickup of the tripping protection function drops off and - just as with the other setting options- the minimum trip command duration (address 240) has elapsed. The setting Pickup Reset makes sense, for instance, during the test of the protection equipment, when the system-side load current cannot be cut off and the test current is injected in parallel to the load current.
While the time SI Time all Cl. (address 1132, see above) is activated following each recognition of line energization, SI Time Man.Cl (address 1150) defines the time following manual
closure during which special influence on the protection functions is activated. This parameter can only be set in DIG S I at Display Additional Settings.
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
45
Functions
2.1 General
Note
For CB T est and automatic reclosure the CB auxiliary contact status derived with the binary inputs >CB1 ... No. 371, 410 and 411) are relevant for the circuit-breaker test and for automatic reclosure to be able to indicate the circuit-breaker position. The other binary inputs >CB ... (no. 379 and 380) are used to detect the status of the line (address 1134) and to reset the trip command (address 1135). Address 1135 is also used by other pro­tection functions, e.g. switching on overcurrent. For applications with 2 circuit breakers per feeder (1.5 circuit­breaker systems or ring bus), the binary inputs >CB1... must be connected to the correct circuit breaker. The binary inputs >CB... then need the correct signals for detecting the circuit-breaker status. In certain cases, an additional CFC logic may be necessary.
For commands via the integrated control (local control, DIGSI, serial interface) address 1152 Man.Clos. Imp. determines whether a close command via the integrated control function should be treated by the pro­tection regarding the MANUAL CLOSE (like instantaneous re-opening when switching onto a fault). This address also informs the device to which switchgear this applies. You can select from the switching devices which are available to the integrated control. Select the circuit breaker which operates for manual closure and, if required, for automatic reclosure (usually Q0). If none is set here, a CLOSE command via the control will not generate a MANUAL CLOSE impulse for the protection function.
46
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Functions
2.1 General
2.1.6.2 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings". The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
Addr. Parameter C Setting Options Default Setting Comments
1 103 FullScaleVolt. 0.4 .. 500.0 kV 10.0 kV Measurem:FullScaleVolt-
age(Equipm.rating)
1104 FullScaleCurr. 10 .. 20000 A 400 A Measurem:FullScaleCur-
rent(Equipm.rating)
1107 P,Q sign not reversed
reversed
not reversed P,Q operational measured
values sign
1 130A PoleOpenCurrent 1A 0.05 .. 1.00 A 0.10 A Pole Open Current
5A 0.25 .. 5. 00A 0.50 A
Threshold
1131A PoleOpenVoltage 2 .. 70 V 30 V Pole Open Voltage
Threshold
1 132A SI Time all Cl. 0.01 .. 30.00 sec 0.10 sec Seal-in Time after ALL clo-
sures
1 133A T DELAY SOTF 0.05 .. 30.00 sec 0.25 sec minimal time for line open
before SOTF
1134 Line Closure o nly with ManCl
I OR V or ManCl
only with ManCl Recognition of Line Clo-
sures with 52a OR I or M/C I or Man.Close
1 135 Reset Trip CMD CurrentOpenPole
CurrentOpenPole RESET of Trip Command Current AND 52a Pickup Reset
1150A SI Time Man.Cl 0.01 .. 30.00 sec 0.30 sec Seal-in Time after
MANUAL closures
1152 Man.Clos. Imp. (Setting options depend
on configuration)
None MANUAL Closure Impulse
after CONTROL
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
47
Functions
2.1 General
2.1.6.3 Information List
No. Information Type of In-
Comments
formation
301 Pow.Sys.Flt. OUT Power System fault 302 Fault Event OUT Fault Event 356 >Manual Close SP >Manual close signal 357 >Blk Man. Close SP >Block manual close cmd. from external 361 >FAIL:Feeder VT SP >Failure: Feeder VT (MCB tripped) 371 >Bkr1 Ready SP >Breaker 1 READY (for AR,CB-Test) 378 >52 faulty SP >52 Breaker faulty (for 50BF) 379 >52a 3p Closed SP >52a Bkr. aux. contact (3pole closed) 380 >52b 3p Open SP >52b Bkr. aux. contact (3pole open) 383 >Enable ARzones SP >Enable all AR Zones / Elements 385 >Lockout SET SP >Lockout SET 386 >Lockout RESET SP >Lockout RESET 410 >52a Bkr1 3p Cl SP >52a Bkr1 aux. 3pClosed (for AR,CB-Test) 411 >52b Bkr1 3p Op SP >52b Bkr1 aux. 3p Open (for AR,CB-Test) 501 Relay PICKUP OUT Relay PICKUP 502 Relay Drop Out OUT Relay Drop Out 503 Relay PICKUP ØA OUT Relay PICKUP Phase A 504 Relay PICKUP ØB OUT Relay PICKUP Phase B 505 Relay PICKUP ØC OUT Relay PICKUP Phase C 506 Relay PICKUP G OUT Relay PICKUP GROUND 510 Relay CLOSE OUT Relay GENERAL CLOSE command 511 Relay TRIP OUT Relay GENERAL TRIP command 530 LOCKOUT IntSP LOCKOUT is active 533 Ia = VI Primary fault current Ia 534 Ib = VI Primary fault current Ib 535 Ic = VI Primary fault current Ic 536 Definitive TRIP OUT Relay Definitive TRIP 545 PU Time VI Time from Pickup to drop out 546 TRIP Time VI Time from Pickup to TRIP 561 Man.Clos.Detect OUT Manual close signal detected 562 Man.Close Cmd OUT CB CLOSE command for manual closing 563 CB Alarm Supp OUT CB alarm suppressed 590 Line closure OUT Line closure detected
48
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual

2.1.7 EN100-Module 1

2.1.7.1 Description
The EN100-Module 1 enables integration of the 7SD80 in 100-Mbit communication networks in control and automation systems with the protocols according to IEC 61850 standard. This standard permits uniform com­munication of the devices without gateways and protocol converters. Even when installed in heterogeneous environments, SIPROTEC 4 relays therefore provi de for open and interoperable operation. Parallel to the process control integration of the device, this interface can also be used for communication with DIGSI and for inter-relay communication via GOOSE.
2.1.7.2 Information List
Functions
2.1 General
No. Information Type of In-
formation
009.0100 Failure Modul IntSP Failure EN100 Modul
009.0101 Fail Ch1 IntSP Failure EN100 Link Channel 1 (Ch1)
009.0102 Fail Ch2 IntSP Failure EN100 Link Channel 2 (Ch2)
Comments

2.1.8 Protection Interface

2.1.8.1 Description
General
For a layout of lines with two ends, you need one protection interface for each device. Depending on the order­ing code, the device features a protection interface via optical fiber (Prot FO) and/or a protection interface via copper connection (Prot Cu). To connect Prot Cu, use the voltage terminals D1 and D2.
The input of the protection interface Prot Cu has an insulated design. The integrated overvoltage protection reduces the insulation strength. Use an external isolating transformer to increase the insulation strength. The ordering data can be found in Section A.1 under Accessories.
If the device has 2 protection interfaces, the data are preferably exchanged with the device at the other end of the protected object via the FO protection interface. If the optical fiber link fails, the device automatically switch­es to the Cu protection interface. When the optical fiber link is restored, the FO protection interface automati­cally resumes communication.
If you want to have the communication link monitored, you have to define the minimum reception level, the maximum permissible fault rate and monitoring times for each device during parameterization. The device's role within the communication line, i.e. whether it operates as master or slave, is defined in the differential pro­tection topology. For further information, please refer to 2.2.1.
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
49
Functions
2.1 General
Figure 2-3 Connecting 2 7SD80 devices via protection data interfaces
Communication Failure
The communication is continuously monitored by the devices. Single faulty data telegrams are not a direct risk if they occur only occasionally. They are recognized and counted in the device which detects the disturbance and can be read out as statistical information.
If several faulty or no telegrams are received, this is considered a communication disturbance. A correspond­ing indication is issued.
2.1.8.2 Setting Notes
General
The protection interfa ces c onn ect t he devices via optical fiber or copper cables. The communication is perma­nently monitored by the devices. Address 4510 TD-DATA DISTURB defines after which time delay the user is informed about a faulty or missing telegram.
Once a fault has been detected in the protection interface communication, the time at address 4512 Td ResetRemote is started for resetting the remote signals. Please note that only the time of the device whose remote end has failed is effective.
Protection Interface Optical Fiber
If you use an optical fiber connection, switch it ON or OFF at address 4501 PDI FO. Address 4502 PDI FO TER allows you to enter the permissible maximum fault rate in percent. At address 4503 PDI FO level you can define the minimum receiving level. Notes on the settings are given in the Technical Data.
Protection Interface Copper Cable Cu
If you use a copper cable connected to the voltage terminals of the device, switch it ON or OFF at address 4601 PDI Cu.
Address 4602 PDI Cu TER allows you to enter the permissible maximum fault rate in percent. At address 4604 PDI Cu MAX ATT you can set the maximum attenuation.
50
At address 4605 PDI Cu S/N you can define the minimum signal/noise ratio. At address 4603 PDI Cu mode you can specify the transmission parameters. Notes on the settings are given in the Technical Data.
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Functions
2.1 General
2.1.8.3 Settings
Addr. Parameter Setting Options Default Setting Comments
4501 PDI FO ON
OFF 4502 PDI FO TER 0.5 .. 20.0 % 1.0 % PDI FO max. telegram error rate 4503 PDI FO level -30 .. -10dBm -28 dBm PDI FO min. receive level 4510 TD-DATA DISTURB 0.05 .. 2.00 sec 0.10 sec Time delay for data disturbance
4512 Td ResetRemote 0.00 .. 300.00 sec; 0.00 sec Remote signal RESET DELAY for
4601 PDI Cu ON
OFF 4602 PDI Cu TER 0.5 .. 20.0 % 1.0 % PDI Cu max. telegram error rate 4603 PDI Cu mode 01
02
03
04
05
06 4604 PDI Cu MAX ATT 0 .. 46 dB 46 dB PDI Cu maximum attenuation 4605 PDI Cu S/N 6 .. 30 dB 6 dB PDI Cu min signal to noise ratio
ON Protection Data Interface fiber
optic
alarm
comm.fail
ON Protection Data Interface copper
01 PDI Cu operation mode
2.1.8.4 Information List
No. Information Type of In-
formation
3217 PDI FO mirror OUT PDI FO data mirror 3218 PDI Cu mirror OUT PDI Cu data mirror 3227 >PDI FO stop SP >PDI FO is stopped 3228 >PDI Cu stop SP >PDI Cu is stopped 3230 PDI FO faulty OUT PDI FO failure 3232 PDI Cu faulty OUT PDI Cu failure 3243 PDI FO con. to. VI PDI FO connected to relay ID 3244 PDI Cu con. to. VI PDI Cu connected to relay ID 3258 PDI FO TER OUT PDI FO telegram error rate exceeded 3259 PDI Cu TER OUT PDI Cu telegram error rate exceeded 32227 PDI-FO RQ LOW OUT PDI-FO receive level to low 32228 PDI-Cu ATT HIGH OUT PDI-FO attenuation to high 32229 PDI-Cu S/N LOW OUT PDI-FO signal to noise ratio to low
Comments
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
51
Functions

2.2 Phase Comparison Protection and Ground Differential Protection

2.2 Phase Comparison Protection and Ground Differential Protection
The differential protection can be used in solid or resistive grounded, isolated and resonant-grounded systems. It comprises a phase comparison protection and a ground differential protection. The sensitive ground element
operates directionally or non-directionally. The following chapter describes the functions
• Differential protection topology
• Phase comparison protection
• Ground current differential protection in grounded systems
• Ground fault differential protection in resonant-grounded/isolated systems
• Differential protection test and commissioning

2.2.1 Differential Topology

The devices at both ends of the protected object communicate over their protection interfaces with one device acting as master, the other as slave.
The device configured as master can perform the time synchronization for both devices.
2.2.1.1 Setting Notes
Protection Data Topology
At address 4701 ID OF MASTER and 4702 ID OF SLAVE you can enter the device identification number of the two protection devices at the line ends.
Use address 4710 LOCAL RELAY to define which of the two devices acts as master and which as slave. If you want the master to perform the time synchronization for both devices, please observe for which of the
two device a stable time signal is available.
2.2.1.2 Settings
Addr. Parameter Setting Options Default Setting Comments
4701 ID OF MASTER 1 .. 65534 1 Identification number of Master 4702 ID OF SLAVE 1 .. 65534 2 Identification number of Slave 4710 LOCAL RELAY Master
Slave
Master Local relay is
2.2.1.3 Information List
No. Information Type of In-
formation
3491 Master Login OUT Master in Login state 3492 Slave Login OUT Slave in Login state
52
Comments
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual

2.2.2 Phase Comparison Protection

2.2.2.1 Description
General
The phase comparison protection evaluates the phase currents at both ends of the protected object. The two 7SD80 devices at the ends of the protected object communicate over their protection interfaces. The phase­specific comparison and the resulting decision to trip the circuit breaker is made separately for each end.
The digitalized currents are first filtered to suppress DC components and higher harmonics.
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
Figure 2-4 Phase comparison protection, determination of the input variables
These filtered values are available to a sensitive dynamic element and a static element. By comparing the po­larity of the currents at the two ends of the protected object, they recognize whether the fault is external or in­ternal. An internal fault applies if the polarity of the fault currents is identical on both sides; an internal fault or a load step occurs with different polarities.
If the comparison shows without any doubt that a fault is present, the trip command is sent. It is maintained over a set minimum command duration.
The phase comparison protection may trip only at one end in case of single-end infeed. The non-feeding end can also be switched off by means of a transfer trip signal.
Element Idyn
The dynamic filter algorithm generates the value idyn(t). It represents the current change of the filtered value (fundamental component) over two cycles. If the current change exceeds the set threshold 87L Idyn>, the phase comparison protection is started.
The polarity of the current change is transmitted to the device at the remote end of the protected object. The dynamic element operates very sensitively in case of internal faults. In case of external faults, the method
is very stable even during different primary rated currents or different saturation of the current transformers at the two ends.
Element Istat
The static element Istat operates directly with the filtered fundamental value. If the amplitude of the fundamen­tal component exceeds the set threshold 87L Isteady>, the phase comparison protection is started.
The polarity of the current is transmitted to the device at the remote end of the protected object. The static element is insensitive towards low fault currents.
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
53
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
Pickup Logic
The dynamic and the static element pick up independently of each other selectively for each phase. To prevent tripping during an energization, a separate dynamic switch-on threshold 87L Idyn close> is
used. The pickup is maintained over 2 measuring cycles. After the 2 measuring cycles have expired, the dynamic
sign comparison is blocked. If the pickup is successful, an internal pickup signal is transmitted to the other device. The element Idyn is blocked if the frequency deviates by more than 10 % from the rated frequency. The function is blocke d if t he comm unic ation b etwe en th e two devices at the ends of the protected object fails
for more than two measuring cycles. This function can also be blocked via binary input „>87L block“. The following figure shows the formation of the phase-specific pickup of the elements 87L Isteady> and 87L
Idyn>.
Figure 2-5 Logic diagram of the phase comparison protection, phase-selective generation of the Istat and Idyn signal
54
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
The pickup signals created locally, signs of idyn and istat and the blocking information are sent to the device at the opposite end.
Figure 2-6 Phase comparison protection, sending the differential protection information to the opposite
end
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
55
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
The received pickup and blocki ng inform ation is comp ared with the own dif ferential protection information and element-specific pickup indications are created.
Figure 2-7 Phase comparison protection, receiving the differential protection information from the opposite
end
The following figure shows the formation of the phase-specific pickup of the phase comparison protection.
Figure 2-8 Logic diagram of phase comparison protection for pickup in a grounded system
56
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
The following figure shows the pickup behavior of the phase comparison protection in resonant-grounded or isolated systems.
Figure 2-9 Phase comparison protection in resonant-grounded/isolated systems
Y ou will find the logic diagram for the general pickup of the differential protection and the differential protection tripping in Section 2.2.5.
2.2.2.2 Setting Notes
General
The phase comparison protection can be switched ON or OFF at address 1201 87L PCC-Prot.. This requires the differential protection to be set to Enabled at address 112 87 DIFF.PROTEC..
For cables and long lines, the capacitive charging current is decisive for determining the pickup values. The charging current is calculated as follows:
I
=2π · f
C
where
I
C
f
Nom
CB' referred rated capacitance of the line in F/km V
Nom
s line length in km
· CB' ·s·V
Nom
Nom
/3
charging current in A rated power system frequency in Hz
rated system voltage in V
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
57
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
Pickup Values for Resistive or Solid Grounded, Resonant-grounded and Isolated Systems
At address 1202 87L Idyn> you can set the dynamic tripping threshold. The value for 87L Idyn> should be set to at least 0.2 of the largest primary transformer rated current and larger than 2.5 to 3 times the capacitive charging current of the line. If inductances can be connected in the protected zone (common-mode reactor or transformers) for energized lines, 87L Idyn> should be greater than the maximum expected inrush current.
The dynamic tripping threshold for closing is set in address 1203 87L Idyn close>. The value for 87L Idyn close> should be 87L Idyn>, but it should equal at least 3 times the value of the capacitive charging current of the protected line. If inductances are present in the protected zone (common-mode reactor or trans­formers), 87L Idyn close> should be set greater than the maximum expected inrush current.
The static tripping threshold is set in address 1204 87L Isteady>. The static tripping threshold should be set to a value that is larger than the transformer rated current plus at least 3 times the capacitive charging current of the line. If inductances are present in the protected zone (common-mode reactor or transformers), 87L Isteady> must be set greater than the maximum expected inrush current.
At address 1205 87L I min you can enter the threshold for releasing the pickup signal. The value should at least correspond to the setting of 87L Idyn>, but not exceed the largest transformer rated current of the con­stellation.
Note
When using different transformers in the constellation, set identical primary setting values. The secondary setting values can be different.
Time Delays
The trip time delay for 87L Isteady> is set in address 1206 87L Trip Delay. With the inrush current detection activated, the time delay 87L Trip Delay must be at least 20 ms for the
blocking by the inrush current detection to be effective. In resonant-grounded or isolated systems, transients must have subsided before tripping takes place. The delay should be at least 3 cycles (60 ms at 50 Hz and 54 Ms at 60 Hz). For large systems, the time delay must be increased accordingly (see Figure 2-16).
At address 1208 87L: T EFdetect you set the time after which an evolving fault is detected. The parameter is disabled in resonant-grounded or isolated power systems. In the specified time, the 1-phase trip command of the dynamic element 87L: T EFdetect is not forwarded to the tripping logic.
Address 1207 87L Man. Close allows you to set the behavior of the phase comparison protection for manual closing for 87L Isteady>. In this case, tripping can be DELAYED or UNDELAYED (see Figure 2-16).
At parameter 1214 87L:Inrush blk. you can enable or disable the blocking function for the phase compar­ison in case of inrush. If the parameter is enabled, tripping of the element 87L Idyn> is generally delayed by one cycle. Inrush blocking can thus become effective.
58
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
2.2 Phase Comparison Protection and Ground Differential Protection

2.2.3 Ground Current Differential Protection in Grounded Systems

The ground current differential protection of the 7SD80 operates as a stabilized (restrained) differential protec­tion in grounded systems. The two 7SD80 devices exchange the phasors of the ground currents and the asso­ciated restraining quantities over their protection interfaces. The restraining currents and the current phasors are summed up in each device and compared to a pickup characteristic. In the event of an internal short-circuit, the associated circuit breaker is tripped.
2.2.3.1 Description
Basic Principle / Influencing Variables
In healthy operation, both ends of a line carry the same current. This current flows into one side of the consid­ered zone and leaves it again on the other side. A difference in current is a clear indication of a fault within this line section.
If the actual current transformation ratios are the same, the secondary windings of the current transformers CT1 and CT2 at the line ends can be connected to form a closed electric circuit with a secondary current I; a mea­suring element M which is connected to the electrical balance point remains at zero current in healthy opera­tion.
Functions
When a fault occurs in the zone limited by the transformers, a current i currents I
+ I2 flowing in from both sides is fed t o the measuring element. As a result, the simple circuit ensures
1
+ i2 which is proportional to the fault
1
reliable tripping of the protection if the fault current flowing into the protected zone during a fault is high enough for the measuring element M to respond.
Figure 2-10 Basic principle of the differential protection for a line with two ends
This principle only applies to the primary system as long as quadrature-axis components of current are negli­gible. Quadrature-axis components of current can be caused by line capacitances or excitation currents of transformers and parallel reactors.
The secondary currents which are applied to the devices via the current transformers, are subject to measuring errors caused by the response characteristic of the current transformers and the input circuits of the devices. Transmission errors such as signal jitters can also cause deviations of the measured quantities. As a result of all these influences, the total sum of all currents processed in the devices in healthy operation is not exactly zero. The ground current differential protection is stabilized against these influences.
Additional measuring errors which may arise in the device itself by hardware tolerances, calculation tolerances, deviations in time or due to the „quality“ of the measured quantities such as harmonics and deviations in fre­quency, are also estimated by the device and increase the local self-restraining quantity automatically. Here, the permissible variations in the protection data transmission and processing periods are also considered.
For transient inrush currents the devices have a separate inrush current restraint feature.
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
59
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
Evaluation of Measured Values
The ground current differential protection in grounded systems evaluates the sum of the ground current pha­sors.
Each device calculates a ground current at each end of the protected object (fundamental component of the ground current) and transmits it to the partner device. The received and the locally measured ground current phasor is added to the ground differential current. The ground differential current value equals the fault current that the differential protection system „sees“. In the ideal case, it equals the short-circuit current. In healthy op­eration, the differential current value is low and for lines about similar to the capacitive charging current.
The restraining quantity counteracts the ground differential current. It is the total of the maximum measured errors at the ends of the protected object and is calculated from the current measured quantities and power system parameters that were set. Therefore, the highest possible error value of the current transformers within the nominal range and/or the short-circuit current range is multiplied with the current flowing through each end of the protected object. The total value, including the measured internal errors, is then transmitted to the other end. This is the reason why the restraint current is a replica of the greatest possible measurement error of the entire differential protection system.
The pickup characteristic of the differential protection is derived from the restraining characteristic I
diff
= I
rest
(45°
curve) which is cut off below the setting value 87N L: I-DIFF>. It complies with the equation
I
= 87N L: I-DIFF> + Σ (current transformer errors and other measuring errors).
rest
If the calculated differential current exceeds the pickup threshold and the greatest possible measurement error, the fault must be internal (grayed area in the illustration).
60
Figure 2-11 Pickup characteristic of the ground differential protection
If it is desired that an internal fault should initiate a TRIP command and additionally a local current of a specific quantity should exist, the value of this current can be set at address 1225 87N L: I>RELEAS. The default setting for this parameter is zero so that this additional criterion does not become effective.
The differential current and the restraint current 3I0diff and 3I0restr are included in the fault record.
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Blocking / Interblocking
The ground current differential protection can be blocked via a binary input. The blocking at one end of a pro­tected object affects all ends via the communications link (interblocking). If the overcurrent protection is config­ured as an emergency function, all devices will automatically switch to this emergency operation mode.
Pickup Logic
The following figure illustrates the pickup logic of the ground current differential protection for grounded sys­tems.
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
Figure 2-12 Ground current differential protection pickup, grounded system
Y ou will find the logic diagram for the general pickup of the differential protection and the differential protection tripping in Section 2.2.5.
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
61
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
2.2.3.2 Setting Notes
General
The operating mode of the ground differential protection depends on the neutral point treatment in the protected zone. In grounded systems, address 207 SystemStarpoint must be set to Grounded.
The ground differential protection can be switched ON or OFF at address 1221 87N L: Protect.. This re­quires the ground differential protection to be set to Enabled at address 112 87 DIFF.PROTEC.. The setting Alarm only is only relevant for ground fault detection in resonant-grounded or isolated systems.
If a device is switched off or if the ground differential protection is disabled or blocked in a device, calculation of measured values becomes impossible. The entire ground differential protection system of both ends is blocked in this case.
Pickup Value Ground Current Differen t ial Pro tecti on
The current sensitivity is set at address 1222 87N L: I-DIFF>. It is determined by the entire current flowing into a protected zone in case of a fault. This is the total fault current regardless of how it is distributed between the ends of the protected obj ect.
This pickup value must be set to a value that is higher than the total steady-state quadrature-axis component of current of the protected object. For cables and long overhead lines, the charging current has to be consid­ered in particular. It is calculated from the operational capacitance (see Section 2.2.2.2).
Time Delays
Considering the variations of voltage and frequency, the value set should be at least 2,5 to 3 times higher than the calculated charging current. Moreover, the pickup value should not be smaller than 15 % of the primary rated current of the largest transformer in the protection configuration.
If setting is performed from a personal computer using DIGSI, the parameters can be set either as primary or as secondary quantities. If secondary quantities are set, all currents must be converted to the secondary side of the current transformers.
In special application cases, it may be advantageous to delay the tripping of the differential protection using an additional timer, e.g. in case of reverse interlocking. The time delay 87N L: T-DELAY (address 1224) is only started upon detection of an internal fault. This parameter can only be set in DIGSI at Display Additional Set- tings.
With the inrush current restraint activated, the time delay 87N L: T-DELAY must be at least 20 ms for the blocking by the inrush current restraint to be effective.
If it is desired that a TRIP command is generated in the event of an internal fault only if simultaneously the current of the local line end has exceeded a specific quantity, then this current threshold can be set for enabling the differential protection TRIP at address 1225 87N L: I>RELEAS. This parameter can only be set in DIGSI at Display Additional Settings.
62
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Functions
2.2 Phase Comparison Protection and Ground Differential Protection

2.2.4 Ground Fault Differential Protection in Resonant-grounded/Isolated Systems

The ground fault differential protection can be applied in power systems whose starpoint is not grounded or grounded through an arc suppression coil (Petersen coil). It is based on the power values. Th is requires the phase voltages or the 3V0 voltage (Appendix A.3, Figure A-11) to be connected to the devices at both ends of the protected object.
2.2.4.1 Description
General
Single-phase ground faults are not detected by the short-circuit protection since no short circui t current flow s. The power system operation is not immediately affected by a ground fault (the voltage triangle is maintained, Figure 2-13). Therefore, fast tripping is usually not required or desired. The ground fault is to be detected, in­dicated and the affected piece of equipment is to be localized, if possible, eliminating the ground fault by initi­ating appropriate switching operations.
The 7SD80 enables the precise localization of the piece of equipment (line) affected by the ground fault. In resonant-grounded systems, a core balance current transformer must be used to detect the ground current.
Figure 2-13 Ground fault in non-grounded neutral system
Pickup
Pickup occurs when the settable threshold for the displacement voltage 3·V state measured quantities, the ground fault detection can be delayed by a configurable time after the displace­ment voltage has occurred.
Determination of the Phase Affected by the Ground Fault
Following pickup caused by the displacement voltage, the phase affected by the ground fault is determined first. T o do this, the individual phase-to-ground voltages are measured. If the voltage magnitude for any given phase is below the setting value V
, that phase is detected as the ground faulted phase as long as the remaining
min
phase-to-ground voltages are simultaneously above the setting value V
is exceeded. To obtain steady-
0
.
max
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
63
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
Sensitive Ground Fault Direction Determinati on
The direction of the ground fault can be determined from the direction of the ground fault current in relation to the displacement voltage. The only restriction is that the active or reactive current components must be avail­able with sufficient magnitude at the point of measurement.
In networks with isolated starpoint, the ground fault current flows as capacitive current from the healthy lines via the measuring point to the point of ground fault. For the determination of the direction the capacitive reactive power is most relevant.
In networks with arc suppression coils, the Petersen coil superimposes a corresponding inductive current on the capacitive ground fault current when a ground fault occurs, so that the capacitive current at the point of fault is compensated. Depending on the measuring point in the system the resultant measured current may be in­ductive or capacitive. Therefore, the reactive current is not suited for direction determination of the ground cur­rent. In this case, only the ohmic (active) residual current which results from the losses of the Petersen coil can be used for direction determination. This residual ground fault residual current is only about some per cent of the capacitive ground fault current.
The active and reactive component of the power is decisive for the ground fault protection pickup. A fault in forward direction must be detected at both ends of the protected object for the ground fault differential
protection to pick up. In case of a single feeder, the residual current per watt at the opposite end of the infeed can be so weak that it
is impossible to determine the direction at that end. In this case, the amplitudes of the active currents of the two ends are additionally compared to initiate pickup and localize the ground fault.
Pickup Logic
The amplitude of the active current (resonant-grounded system) and the reactive current (for isolated starpoint) are included in the fault record. The local wattmetric ground current or reactive current is recorded as Iee1, the wattmetric ground current or the reactive current of the opposite end as Iee2.
The following figure shows the pickup logic of the ground fault differential protection resonant-grounded or iso­lated systems.
64
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
Figure 2-14 Ground fault differential protection pickup, isolated/resonant-grounded system
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
65
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
If only the V0 voltage is connected, only parameter 1226 87N L: 3V0> is effective. The threshold checks 87N L:Vph-g min and 87N L:Vph-g max (parameter 1227 and 1228) are not relevant.
You will find the logic diagram for the differential protection trip in Section 2.2.5.
2.2.4.2 Setting Notes
General
The operating mode of the ground differential protection depends on the neutral point treatment in the protected zone. In resonant-grounded or isolated system, you have to set Peterson-C.Gnd. or Isolated at address 207 SystemStarpoint.
The ground differential protection can be switched ON or OFF at address 1221 87N L: Protect.. If set to Alarm only, an indication will be output when a fault is detected. Tripping is not initiated. This requires the ground differential protection to be set to Enabled at address 112 87 DIFF.PROTEC..
If a device is switched off at any end of the protected object or if the protection interface communication is in­terrupted, a calculation of measured values becomes impossible. The function then operates locally and only issues directional indications and pickup indications but no pickup and tripping indications of the ground fault differential protection.
Pickup Values
The pickup threshold of the displacement voltage is set in address 1226 87N L: 3V0>. At address 1229 87N L: IN(s)> you can enter the minimum current for direction determination. The pickup
current is to be set as high as possible to avoid false pickup of the device provoked by unbalanced currents in the system and by current transformers. Dependent on the grounding of the network starpoint, the magnitude of the capacitive ground fault current (for isolated networks) or the wattmetric residual current (for compensated networks) is decisive.
In isolated systems, a ground fault in a cable will allow the total capacitive ground fault currents of the entire electrically connected system, with the exception of the faulted cable itself, to flow through the measuring point as the latter flows directly to the fault location (i.e. not back via the measuring point). Enter about half of this ground fault current as pickup value.
In resonant-grounded systems directional determination is made more difficult since a much larger reactive current (capacitive or inductive) is superimposed on the critical wattmetric (active) current. Therefore, depend­ing on the system configuration and the position of the arc-compensating coil, the total ground current supplied to the device may vary considerably in its values with regard to magnitude and phase angle. The device, how­ever, must evaluate only the active component of the ground fault current, the ground fault residual current, that is I all the instrument transformers . Furthermore, the device must not be set to operate too sensitive. When apply­ing this function in resonant-grounded systems, a reliable direction determination can only be achieved when toroidal current transformers are connected. Here the following rule of thumb applies: set the value to half the expected measured current, whereby only the residual wattmetric current is used. Residual wattmetric current predominantly derives from losses of the Petersen coil.
·cosϕ. This requires extremely high accuracy, particularly with regard to phase angle measurement of
E
66
For phase determination 87N L:Vph-g min (address 1227) is the criterion that applies to the ground-faulted phase if simultaneously the other two phase voltages 87N L:Vph-g max (address 1228) have been exceed­ed. Accordingly, the setting 87N L:Vph-g min must be set smaller than the minimum phase-to-ground voltage that occurs during operation. This setting, too, is uncritical. 40 V (default setting) should always be cor­rect. 87N L:Vph-g max must be greater than the maximum phase-to-ground voltage occurring during oper­ation, but less than the minimum phase-to-phase voltage occurring during operation. For V
= 100 V , the value
N
must therefore be 75 V (default setting). The definite detection of the phase affected by the ground fault is a further prerequisite for alarming a ground fault. When connecting the voltage V0 (Appendix A.3, Figure A-11), the check of the phase voltages does not take place.
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
2.2 Phase Comparison Protection and Ground Differential Protection
Time Delays
The ground fault is detected and reported only when the displacement voltage has applied for at least the time 87N L:TD-F.det. (address 1230). This stabilizing time also takes effect when ground fault conditions change (e.g. change of direction).
The tripping can be delayed via the time delay 87N L:TripDelay (address1231). With the inrush current restraint activated, the time delay 87N L:TripDelay must be at least 20 ms for the
blocking by the inrush current restraint to be effective.

2.2.5 Differential Protection Pickup Logic and Tripping Logic

2.2.5.1 Description
Pickup Logic
Once the differential protection function has reliably registered a fault within its tripping zone, the signal “87(N)L Gen.Flt.“ (general pickup of the differential protection) is generated. For the differential protection function itself, this pickup signal is of no concern since the tripping conditions are available at the same time. This signal, however, is required to initiate the internal or external supplementary functions, e.g. fault recording, automatic reclosing.
Functions
Figure 2-15 General pickup
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
67
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
Tripping Logic
The following figure shows the tripping logic of the differential protection.
Figure 2-16 Differential protection trip
If the pickup signals apply for longer than the configurable trip time delay, the differential protection trips.

2.2.6 87 Differential Protection

The following tables provide an overview of the parameters and information of the functions:
- phase comparison protection
- Ground current differential protection in grounded systems
- ground fault differential protection in resonant-grounded/isolated systems
68
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
2.2.6.1 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings". The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
Addr. Parameter C Setting Options Default Setting Comments
1201 87L PCC-Prot. OFF
ON
1202 87L Idyn> 1A 0.20 .. 20.00 A; 0.33 A Dynamic trip threshold
5A 1.00 .. 100.00 A; 1.65 A 1203 87L Idyn close> 1A 0.20 .. 20.00 A; 0.33 A Dynamic trip threshold line
5A 1.00 .. 100.00 A; 1.65 A 1204 87L Isteady> 1A 0.50 .. 20.00 A; 1.33 A Steady pick up threshold
5A 2.50 .. 100.00 A; 6.65 A 1205 87L I min 1A 0.10 .. 20.00 A; 1.00A Minimal phase current
5A 0.50 .. 100.00 A; 5.00 A
ON Phase current comparison
protection
closure
1206 87L Trip Delay 0.00 .. 0.10 se c 0.00 sec Trip Delay 1207 87L Man. Close DELAYED
UNDELAYED
DELAYED Trip response after manual
close
1208 87L: T EFdetect 0.00 .. 32.00 sec 0.00 sec Evolving fault detect.time
1ph faults
1214 87L:Inrush blk. NO
NO Inrush blocking
YES
1221 87N L: Protect. OFF
ON 87N L protection ON Alarm Only
1222 87N L: I-DIFF> 1A 0.10 .. 20.00 A 0.30 A 3I0-DIFF> Pickup value
5A 0.50 .. 100.00 A 1.50 A 1224A 87N L: T-DELAY 0.00 .. 300.00 sec; 0.00 sec 3I0-DIFF Trip time delay 1225A 87N L: I>RELEAS 1A 0.00 .. 20.00 A 0.00 A Min.current to release 3I0-
5A 0.00 .. 100.00 A 0.00 A
DIFF-Trip
1226 87N L: 3V0> 5 .. 150 V 50 V 3V0> pickup 1227 87N L:Vph-g min 10 .. 100 V 40 V Vph-g min of faulted phase 1228 87N L:Vph-g max 10 .. 100 V 75V Vph-g max of healthy
phases
1229 87N L: IN(s)> 0.003 .. 1.000 A 0.050 A IN(s)> to release direction-
al element
1230 87N L:TD-F.det. 0.00 .. 320.00 sec 1.00 sec Time delay for fault detec-
tion 1231 87N L:TripDelay 0.00 .. 320.00 sec 0.00 sec Trip Delay 1233 CT Err. I1 0.003 .. 1.600 A 0.050 A Current I1 for CT Angle
Error 1234 CT Err. F1 0.0 .. 5.0 ° 0.0 ° CT Angle Error at I1
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
69
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
Addr. Parameter C Setting Options Default Setting Comments
1235 CT Err. I2 0.003 .. 1.600 A 1.000 A Current I2 for CT Angle
Error 1236 CT Err. F2 0.0 .. 5.0 ° 0.0 ° CT Angle Error at I2 1237 87NL:Inrush blk NO
NO Inrush blocking
YES
2.2.6.2 Information List
No. Information Type of In-
Comments
formation
3190 Test 87 IntSP 87 Set test state of 87 3191 Commiss.87 IntSP 87 Set Commissioning state of 87 3192 Test 87 remote OUT 87 Remote relay in test state 3193 Comm. 87 active OUT 87 Commissioning state is active 3197 >Test 87 ON SP 87 >Set test state of 87 3198 >Test 87 OFF SP 87 >Reset test state of 87 3199 Test 87 ON/off IntSP 87 Test state of 87 ON/OFF 3200 Test 87 ONoffBI IntSP 87 Test state ON/OFF via BI 3260 >Comm. 87 ON SP 87 >Commissioning state ON 3261 >Comm. 87 OFF SP 87 >Commissioning state OFF 3262 Comm 87 ON/OFF IntSP 87 Commissioning state ON/OFF 3263 Comm 87 ONoffBI IntSP 87 Commissioning state ON/OFF via BI 32100 >87L block SP >87L Protection blocking signal 32102 87L active OUT 87L Protection is active 32103 87L Fault A OUT 87L Fault detection A 32104 87L Fault B OUT 87L Fault detection B 32105 87L Fault C OUT 87L Fault detection C 32107 87L is blocked OUT 8 7L Protection is blocked 32108 87L is OFF OUT 87L Protection is switched off 32109 87L allow A OUT 87L A released 32110 87L allow B OUT 87L B released 32111 87L allow C OUT 87L C released 32112 87 CTRatioAlarm OUT 87 CT primary ratio is too high 32113 87L receive blk OUT 87L receive blocking 32114 87L send blk OUT 87L send blocking 32115 87L IDYN> A OUT 87L IDYN> A 32116 87L IDYN> B OUT 87L IDYN> B 32117 87L IDYN> C OUT 87L IDYN> C 32118 87L ISTAT> A OUT 87L ISTAT> A 32119 87L ISTAT> B OUT 87L ISTAT> B 32120 >87N L block SP >87N L Protection blocking signal 32121 >87N L active OUT >87N L: Protection is active 32122 87(N)L Gen.Flt. OUT 87(N)L Fa ult detection 32124 >87N L I> Flt. OUT >87N L: Fault detection of I-Diff> 32125 87(N)L Gen.TRIP OUT 87(N)L General TRIP
70
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
No. Information Type of In-
formation
32126 87N L block OUT 87N L: Protection is blocked 32127 87N L OFF OUT 87N L: Protection is switched off 32128 87N L 3V0> OUT 87N L: detection 3V0> pickup 32129 87N L Forward OUT 87N L: detection Forward 32130 87N L Reverse OUT 87N L: detection Reverse 32131 87N L UndefDir OUT 87N L: detection Undef. Direction 32132 87N L rec. blk OUT 87N L: receive blocking 32133 87N L send blk OUT 87N L: send blocking 32134 87N L PU OUT 87N L: pickup 32150 87L ISTAT> C OUT 87L ISTAT> C
Comments

2.2.7 Differential Protection Test and Commissioning

2.2.7.1 Differential Protection Test
General
If differential protection test mode (test mode in the following) is activated, the differential protection is blocked in the entire system. Depending on the configuration, the overcurrent protection acts as emergency function.
In the local device all currents from the other devices are set to zero. The local device only evaluates the locally measured currents, interprets them as differential current but does not send them to the other devices. This enables measuring the thresholds of the differential protection. Moreover, the test mode prevents in the local device that tripping of the differential protection generates a transfer trip signal.
The test mode can be activated/deactivated as follows:
• Operation panel: Menu Control/Taggings/Set: „Test mode“
• Via binary inputs (no. 3197 „>Test 87 ON“, no. 3198 „>Test 87 OFF“) if this was routed
• In DIGSI with Control / Taggings: „Diff: Test mode“ The test mode status of the other device of the line protection system is indicated on the local device by the
indication „Test 87 remote“ (No. 3192).
Mode of Operation
Below, the logic is shown in a simplified way:
Figure 2-17 Logic diagram of the test mode
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
71
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
Depending on the way used for controlling the test mode, either the indication „Test 87 ON/off“ (no. 3199) or „Test 87 ONoffBI“ (no. 3200) is generated. The way used for deactivating the test mode always has to be identical to the way used for activating. The indication „Test 87“ (no. 3190) is generated independently of the chosen way. When deactivating the test mode via the binary inputs, a time delay of 500 ms becomes effective.
The following figures show possible variants for controlling the binary inputs. If a switch is used for the control (Figure 2-19), it has to be observed that binary input „>Test 87 ON“ (no. 3197) is parameterized as NO contact and that binary input „>Test 87 OFF“ (no. 3198) is parameterized as NC contact.
Figure 2-18 External push-button wiring for controlling the differential protecti on test mode Bu1 Push-button „Switching off the differential protection test mode“ Bu2 Push-button „Switching on the differential protection test mode“
Figure 2-19 External switch wiring for controlling the differential protection test mode S Switch „Switching the differential protection test mode on/off“
1) Binary input as make contact
2) Binary input as break contact
If a test switch is to be used for changing to test mode, we recommend the following procedure:
• Block the differential protection via a binary input.
• Use the test switch to activate/deactivate the test mode.
• Reset the blocking of the differential protection via the binary input.
72
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
2.2 Phase Comparison Protection and Ground Differential Protection
2.2.7.2 Differential Protection Commissioning
General
In differential protection commissioning mode (commissioning mode in the following) the differential protection does not generate TRIP commands. The commissioning mode is intended to support the commissioning of the differential protection.
You can check:
• transformer polarity, using the constellation measured values
• differential currents
• restraint currents By editing parameters, the operating point of the differential protection can be changed without any risk up to
the generation of a pickup.
Functions
Figure 2-20 Commissioning mode - overview
The commissioning mode is activated on a device of the protective device constellation and also affects the device at the other end of the protected object (indication no. 3193„Comm. 87 active“). The commissioning mode has to be deactivated on the device on which it was activated.
The commissioning mode can be activated/deactivated as follows:
• Operation panel: Menu Control/Taggings/Set: „Commissioning mode“
• Via binary inputs (no. 3260 „>Comm. 87 ON“, no. 3261 „>Comm. 87 OFF“) if this was routed
• In DIGSI with Control / Taggings: „Diff: Commissioning mode“
Mode of Operation
Below, the logic is shown in a simplified way:
Figure 2-21 Logic diagram of the commissioning mode
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
73
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
There are two ways to set the commissioning mode. The first way is to use a command (commissioning mode on / commissioning mode off) which is generated either when operating the integrated keypad or when oper­ating with DIGSI. The second way is to use the binary inputs (no. 3260 „>Comm. 87 ON“, no. 3261 „>Comm. 87 OFF“).
Depending on the way used for controlling the commissioning mode, either the indication „Comm 87 ON/OFF“ (no. 3262) or „Comm 87 ONoffBI“ (no. 3263) is generated. The way used for deactivating the commissioning mode always has to be identical to the way used for activating. The indication „Commiss.87“ (no. 3191) is generated independently of the chosen way.
The following figures show possible variants for controlling the bin ary inputs. If a switch is used for control (Figure 2-23), it has to be observed that binary input „>Comm. 87 ON“ (no. 3260) is parameterized as NO contact and that binary input „>Comm. 87 OFF“ (no. 3261) is parameterized as NC contact.
Figure 2-22 External push-button wiring for controlling the differential protection commissioning mode Bu1 Push-button „Switching off the differential protection commissioning mode“ Bu2 Push-button „Switching on the differential protection commissioning mode“
Figure 2-23 External switch wiring for controlling the differential protection commissioning mode S Switch „Switching the differential protection commissioning mode on/off“
1) Binary input as make contact
2) Binary input as break contact
74
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
2.3 Breaker Intertrip and Remote Tripping
The 7SD80 device allows transmitting a trip command created by the local differential protection to the other end of the protected object (intertripping). Likewise, any desired command of another internal protection func­tion or of an external protection, monitoring or control equipment can be transmitted for remote tripping.

2.3.1 Description

Transmit Circuit
The transmission signal can originate from two different sources (Figure 2-24). If the parameter 85 DT: SEND is set to YES, each tripping command of the differential protection is routed immediately to the transmission function „ITrp.sen. A“ to "...C“ (intertrip) and transmitted via the protection data interfaces and c ommunication links.
The send function can be triggered via binary input „>85 DT 3pol“ (remote tripping). The transmission signal can be delayed with 85 DT: TD-BI and prol onged with 85 DT:T-PROL BI.
Functions

2.3 Breaker Intertrip and Remote Tripping

Figure 2-24 Logic diagram of the intertrip — transmission circuit
Receive Circuit
On the receiving end the signal can lead to a trip. Alternatively, it can also cause an alarm only. In this way it is possible to determine for each end of the protected object whether the received signal is to trip at this partic­ular end or not.
If the received signal is to cause the trip, it will be forwarded to the tripping logic of the device.
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
75
Functions
2.3 Breaker Intertrip and Remote Tripping
Figure 2-25 Logic diagram of the intertrip — receiving circuit
Additional Options
Since the signals for remote tripping can be set to just generate an indication, any other desired signals can be transmitted as well. After the binary input(s) have been activated, the signals which are set to cause an alarm at the receiving end are tr ansmitted. These alarm s can in turn execute any desired actions at the receiving end.

2.3.2 Setting Notes

General
The intertrip function for tripping caused by the differential protection can be activated (YES) or deactivated (NO) at address 1301 85 DT: SEND.
To ensure that the faulted line is cleared, the intertrip function must be activated. In some applications, e.g. a single feed, it may be desirable to switch off the feeding end only. In such exceptional cases, the intertrip func­tion is not needed.
Intertrip / Remote Tripping
The activated intertrip function starts automatically when the differential protection trips at only one end. If the relevant binary inputs are allocated and activated by an external source, the intertrip signal is transmitted
as well. In this case, the signal to be transmitted can be delayed with address 1303 85 DT: TD-BI. This delay stabilizes the originating signal against dynamic interferences which may possibly occur on the control cabling. Address 1304 85 DT:T-PROL BI is used to extend a signal after it has been effectively injected from an ex- ternal source.
76
The reaction of a device when receiving an intertrip/remote tripping signal is set in address 1302 85 DT: RECEIVE. If it is desired to cause tripping, set the value Trip. If the received signal, however, is supposed to cause an alarm only, Alarm only must be set if this indication is to be further processed externally.
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
2.3 Breaker Intertrip and Remote Tripping
The setting times depend on the individual case of application. A delay is necessary if the external control signal originates from a disturbed source and a restraint seems appropriate. Of course, the control signal has to be longer than the delay for the signal to be effective. If the signal is processed externally at the receiving end, a prolongation time might become necessary for the transmitting end so that the reaction desired at the receiving end can be executed reliably.
Release Thresholds
Before the release for tripping is given, the phase and ground currents must exceed settable thresholds. You can set these thresholds at the following addresses:
1305 85 DT Iph rel. for the minimum phase current
1306 85 DT 3I0 rel. for the minimum ground current 3I0

2.3.3 Settings

The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec­ondary nominal current of the current transformer.
Addr. Parameter C Setting Options Default Setting Comments
Functions
1301 85 DT: SEND YES
NO
1302 85 DT: RECEIVE Alarm only
Trip
1303 85 DT: TD-BI 0.00 .. 30.00 sec 0.00 sec 85 DT: Delay for intertrip
1304 85 DT:T -PROL BI 0.00 .. 30.00 sec 0.00 sec 85 DT : Prol. for intertrip via
1305 85 DT Iph rel. 1A 0.0 .. 25.0 A; 0.0 A 85 DT minimal Phase
5A 0.0 .. 125.0 A; 0.0 A
1306 85 DT 3I0 rel. 1A 0.0 .. 25.0 A; 0.0 A 85 DT minimal 3I0 Current
5A 0.0 .. 125.0 A; 0.0 A
YES 85 DT: State of transm.the
intertrip cmd
Trip 85 DT: React.if intertrip
cmd is receiv.
via bin.input
bin.input
Current to rel. trip
to rel. trip

2.3.4 Information List

No. Information Type of In-
formation
3504 >85 DT 3pol SP >86 DT: >Intertrip 3 pole signal input 3517 85 DT Gen. TRIP OUT 85 DT: General TRIP 17525 85 DT rec.3pole OUT 85 DT: Received 3pole 17526 85 DT sen.3pole OUT 85 DT: Sending 3pole
Comments
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
77
Functions

2.4 Backup Overcurrent

2.4 Backup Overcurrent
The 7SD80 features an overcurrent protection function which can be used as either backup or emergency over­current protection. All elements are independent of each other and can be combined as desired.
The overcurrent protection has two overcurrent elements with definite trip time and one overcurrent protection element with inverse time delay for the phase currents and for the ground current. These elements operate di­rectionally or non-directionally.
One additional definite-time overcurrent protection element always operates non-directionally. It features an additional release input and can act as emergency element if the other elements are used for backup purposes.
The elements are independent of each other and can be combined in any way. Blocking by external criteria via binary inputs is possible.

2.4.1 Operating Modes

Emergency Overcurrent Protection
The differential protection as a whole can only operate correctly if both devices receive the data of the respec­tive other device properly. The emergency overcurrent protection in contrast requires only the local currents. Acting as emergency overcurrent protection, it automatically replaces the differential protection as short-circuit protection if data communication of the differential protection is faulty (emergency operation). The differential protection is blocked in this case.
Backup Time Overcurrent Protection
If the overcurrent protection is set as backup time overcurrent protection, it will work independently of the other protection and monitoring functions, i.e. also independently of the differential protection. The backup overcur­rent protection can also act as the only short-circuit protection if no suitable channels for the communication between the protection devices are available yet during the initial commissioning. It can be used as busbar pro­tection via reverse interlocking in combination with other protec tion devices or as backup protection function for protection device failure at continuing lines.

2.4.2 Non-directional Overcurrent Protection

Measured Quantities
The phase currents are fed to the device via the input transformers of the measuring input. The ground current 3I
is calculated from the phase currents.
0
Definite Time High-set Element 50-1
Each phase current is compared with the setting value 50-B2 PICKUP after numerical filtering; the ground current is compared with 50N-B2 PICKUP. A trip command is issued after pickup of an element and expiration of the associated time delays 50-B2 DELAY or 50N-B2 DELAY. The dropout value is about 7 % below the pickup value, but at least 5 % of the rated current.
Figure 2-26 shows the logic diagram of the 50-1 elements. They can be blocked via binary input „>BLOCK 50-
B2“. Additionally, the ground current element can be blocked separately via the binary input „>BLOCK 50N­B2“.
78
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Functions
2.4 Backup Overcurrent
The binary input „>5X-B InstTRIP“ and the evaluation of the indication „switch“ (onto fault) are common to all elements. They may, however, separately affect the phase and/or ground current elements.
Parameter 50-B1 DELAY (address 2618) determines whether a non-delayed trip of this element via binary input „>5X-B InstTRIP“ is possible (YES) or impossible (NO). This parameter is also used for fast tripping before reclosing
If parameter 50-B2 Inrush (address2625) is set to YES, the element is blocked.
Figure 2-26 Logic diagram of the 50-1 element
Definite Time Overcurrent Element 50-2
The logic of the overcurrent elements 50-2 is the same as the logic of the 50-1 elements described above. In all names, -1 has to be replaced by -2. The parameter names of the 50-2 elements are listed in secti on 2.4.4.
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
79
Functions
2.4 Backup Overcurrent
Definite Time Overcurrent Element 50-3
The 50-3 element operates independently of the other elements. Its logic corresponds to the 50-1 and 50-2 el­ements described above, but operates non-directional only.
If parameter 50-STUB Inrush (address 2653) is set to YES, the element is blocked.
Figure 2-27 Logic diagram of the 50-3 element
Inverse Time Overcurrent Element 51
The logic of the inverse overcurrent element basically operates in the same way as the other elements. The time delay, however , is calculated based on the type of the set characteristic, the intensity of the current and a time multiplier (following figure). A pre-selection of the available characteristics was already carried out during the configuration of the protection functions. Furthermore, an additiona l constant time delay 51-B AddT- DELAY or 51N-B AddTdelay may be selected which is added to the inverse time. The possible characteristics are shown in the Technical Data.
80
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Functions
2.4 Backup Overcurrent
The non-directional and the directional inverse time overcurrent element 51 always uses the same character­istic curve that is parameterized via 2642 (IEC) or 2643 (ANSI). Different inverse times and additional times can be parameterized here.
The following figure shows the logic diagram. The setting addresses of the IEC characteristic curves are shown by way of example. In the setting notes (Section 2.4.4), the different setting addresses are described in detail.
If parameter 51-B Inrush (address 2637) is set to YES, the element is blocked.
Figure 2-28 Logic diagram of the 51 element (inverse time overcurrent protection) - example for IEC characteristic
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
81
Functions
2.4 Backup Overcurrent
Pickup Logic and Tripping Logic
The pickup signals of the individual phases (or ground) and of the individual elements are interlinked in such a way that both the phase information and the element which has picked up are indicated (Table 2-1).
Table 2-1 Pickup signals of the single phases
Internal indication Display Output indication No.
50-2 PU A 50-1 PU A 50-3 PU A 51 PU A
50-2 PU B 50-1 PU B 50-3 PU B 51 PU B
50-2 PU C 50-1 PU C 50-3 PU C 51 PU C
50-2 PU N 50-1 PU N 50-3 PU N 51 PU N
50-1 PU A 50-1 PU B 50-1 PU C 50-1 PU N
50-2 PU A 50-2 PU B 50-2 PU C 50-2 PU N
50-3 PU A 50-3 PU B 50-3 PU C 50-3 PU N
51 PU A 51 PU B
PU C
51 51 PU N
(All pickups) „5X-B PICKUP“ 7161
2-26 2-27
2-28 2-26
2-27 2-28
2-26 2-27
2-28 2-26
2-27 2-28
2-26 2-26 2-26 2-26
2-26 2-26 2-26 2-26
2-27 2-27 2-27 2-27
2-28 2-28 2-28 2-28
„5X-B Pickup ØA“ 7162
„5X-B Pickup ØB“ 7163
„5X-B Pickup ØC“ 7164
„5X-B Pickup Gnd“ 7165
„50(N)-B2 PICKUP“ 7192
„50(N)-B1 PICKUP“ 7191
„50-STUB PICKUP“ 7201
„51(N)-B PICKUP“ 7193
82
The trip is signaled specifically for each element, e.g. „50(N)-B2 TRIP“.
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual

2.4.3 Directional Overcurrent Protection

Measured Quantities
The phase currents are fed to the device via the input transformers of the measuring input. The ground current 3I
is calculated from the phase currents.
0
For the directional Iph> elements, the used measuring voltage is determined by the fault type. The current phase-to-ground voltage is used
• for 1-phase or 3-phase faults,
• if the phase-to-ground voltage is > 4 V,
• not within the first 50 ms after short-circuit inception as the present voltage is disturbed by transients during this time.
The saved phase-to-ground voltage is used
• for 1-phase or 3-phase faults,
• up to max. 2 sec. after saving the phasors
• if there was not pickup before short-circuit occurrence.
The unfaulted phase-to-phase voltage is used
• for 1-phase faults
• for unfaulted phase-to-ground voltages
• if the voltage value is > 70% of the rated voltage.
Functions
2.4 Backup Overcurrent
The negative-sequence system quantities V
• for 1-phase or 2-phase faults
> 50 mA and V2 > 5 V.
•if I
2
When using the negative-sequence system quantities, it is the short circuit with the higher current which deter­mines the direction in case of two 1-phase short circuits.
If none of the above measured quantities is available, an already existing result of the direction determination is used or the directional element is blocked for the corresponding phase.
The behavior in the even to a measuring voltage failure can be set. The elements operate directionally or non­directionally.
The time overcurrent protection only operates directionally if all 3 phase-to-ground voltages are connected. Address 144 must be set to connected here.
Directional Characteristic
The directional characteristic of the directional overcurrent elements is fixed. The angle difference ϕ(V calculated from the voltage phasors and current phasors using the impedance Z termined using the depicted directional characteristic.
and I2 are used
2
)-ϕ(I) is
= V/I and the direction is de-
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
83
Functions
2.4 Backup Overcurrent
Figure 2-29 Directional characteristic of the time overcurrent protection
Definite Time Overcurrent Element 67-1
The directional overcurrent elements basically work in the same way as the non-directional elements. Pickup, however, depends on the result of the direction determination. The direction determination is accomplished using the measured quantities and the corresponding directional characteristics.
67-B2 PICKUP is used as setting values for the phase current; 67N-B2 PICKUP is used for the ground cur­rent. A trip command is issued after pickup of an element and expiration of the associated time delays 67-B2 DELAY or 67N-B2 DELAY. The dropout value is approximately 7% below the pickup value, but at least 1.8% of the nominal current, below the pickup value.
Figure 2-30 shows the logic diagram of the 67-1 elements. They can be blocked via the binary input . Addition­ally, the ground current element can be blocked separately via the binary input „>BLOCK 67N-TOC“.
The binary input „>5X-B InstTRIP“ and the evaluation of the indication „switch“ (onto fault) can act sepa­rately on the directional phase and/or ground element.
Parameter 67(N)-B2 Pil/BI (address 2628) determines whether a non-delayed trip of this element via binary input „>5X-B InstTRIP“ is possible (YES) or impossible (NO). This parameter is also used for instan­taneous tripping before automatic reclosing.
The indications or are created from the individual directional indications ( to ) determined specifically for the phase or current if a valid direction was determined for a phase or ground current (forward or reverse). These indications can then be transmitted to another device where they can cause instantaneous tripping there if an overcurrent element of the receiving device has picked up, too. The indications must be linked via CFC to this end.
84
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Functions
2.4 Backup Overcurrent
Figure 2-30 Logic diagram of the 67-1 element
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
85
Functions
2.4 Backup Overcurrent
Definite Time High-set Element 67-2
The directional overcurrent element basically works in the same way as the non-directional element. Pickup, however, depends on the result of the direction determination. The direction determination is accomplished using the measured quantities and the corresponding directional characteristics.
67-B1 PICKUP is used as setting values for the phase current; 67N-B1 PICKUP is used for the ground cur­rent. A trip command is issued after pickup of an element and expiration of the associated time delays 67-B1 DELAY or 50N-B1 DELAY. The dropout value is approximately 7% below the pickup value, but at least 1.8% of the nominal current, below the pickup value.
Figure 2-30 shows the logic diagram of the 67-1 elements. The same applies analogously to the high-set current element 67-2.
Inverse Time Overcurrent Element 67-TOC
The logic of the inverse overcurrent element basically operates in the same way as that of the non-directional element. Pickup, however, depends on the result of the direction determination. The direction determination is accomplished using the measured quantities and the corresponding directional characteristics.
The time delay, however, is calculated based on the type of the set characteristic, the intensity of the current and the time factor 67-TOC TD ANSI or 67N-TOC TD ANSI. Furthermore, an additional constant time delay 67-TOC AddTDel. or 67N-TOC AddTDel may be selected which is added to the inverse time. The possible characteristics are shown in the Technical Data.
The indications or are created from the individual directional indications ( to ) determined for the phase and ground current provided that a valid directional result (forward or reverse) was determined for the phase or ground current. These indications can then be transmitted to another device where they can cause instanta­neous tripping if an overcurrent element of the received device has picked up, too. The indications must be linked via CFC to this end.
The following figure shows the logic diagram of the directional 67-TOC element. The setting addresses for the IEC characteristics are shown by way of example. In the setting notes (Section 2.4.4), the different setting ad­dresses are described in detail.
The non-directional and the directional inverse time overcurrent element 51 always uses the same character­istic curve that is parameterized via 2642 (IEC) or 2643 (ANSI). Different inverse times and additional times can be parameterized here.
86
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Functions
2.4 Backup Overcurrent
Figure 2-31 Logic diagram of the 67 TOC element (directional, inverse time overcurrent protection) - example for IEC
characteristic
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
87
Functions
2.4 Backup Overcurrent
Pickup Logic and Tripping Logic
The pickup signals of the individual phases (or ground) and of the individual elements are interlinked in such a way that both the phase information and the element which has picked up are indicated (Table 2-1).
Table 2-2 Pickup signals of the single phases
Internal indication Display Output indication No.
67-1 PU A 67-2 PU A 67-TOC PU A
67-1 PU B 67-2 PU B 67-TOC PU B
67-1 PU C 67-2 PU C 67-TOC PU C
67-1 PU N 67-2 PU N 67-TOC PU N
67-1 PU A 67-1 PU B 67-1 PU C 67-1 PU N
67-2 PU A 67-2 PU B 67-2 PU C 67-2 PU N
67-TOC PU A 67-TOC PU B 67-TOC PU C 67-TOC PU N
(All pickups)
2-30 2-31
2-30 2-31
2-30 2-31
2-30 2-31
2-30 2-30 2-30 2-30
2-31 2-31 2-31 2-31
„67(N)-B2 PICKUP“ 7251
„67(N)-B1 PICKUP“ 7250
„67(N)-TOC PICK.“ 7252
The trip is signaled specifically for each element, e.g. „67(N)-B2 TRIP“.
Behavior during Measuring Voltage Failure
An element-specific parameter, e.g. 67(N)-B1 on FFM allows you to define how the directional overcurrent protection acts when the measuring voltage fails. The overcurrent protection then works either Non- Directional or it is .
88
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual

2.4.4 Setting Notes

General
The setting notes described in the following apply to non-directional and directional overcurrent protection.
Operating Modes
You set the operating mode of the overcurrent protection elements specifically for each element. The setting applies collectively to the corresponding phase and ground element.
50-1, 3I0> address 2620 50-2, 3I0>> address 2610 50N, 3I0p address 2630 50-3, 3I0>>> address 2650
The following settings are possible:
• If set to ON, the time overcurrent protection operates independently of the other protection functions as backup overcurrent protection.
• If set to Only Emer. prot, the overcurrent protection operates as emergency function.
•Set to OFF, the element is disabled.
Functions
2.4 Backup Overcurrent
Direction
The elements 50-1, 50-2 and 50N operate directionally and non-directionally. The direction is set specifically for each element. The setting applies collectively to the corresponding phase
and ground element.
50-1, 3I0> address 2621 50-2, 3I0>> add ress 2611 50N, 3I0p address 2631
The following settings are possible:
Non-Directional
Forward
Reverse
The operating mode of the directional element in the event of measuring voltage failure is set specifically for each element. The setting applies collectively to the corresponding phase and ground element.
50-1, 3I0> address 2622 50-2, 3I0>> add ress 2612 50N, 3I0p address 2632
The following settings are possible:
Non-Directional
BLOCKED
The 50-3 element always operates non-directionally.
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
89
Functions
2.4 Backup Overcurrent
Inrush Blocking
Y ou can specify for each element of the overcurrent protection whether the element will be blocked when inrush is detected. The setting applies collectively to the corresponding phase and ground element.
50-1, 3I0> address 2625 50-2, 3I0>> address 2615 50N, 3I0p address 2637 50-3, 3I0>>> address 2653
Pickup Values
The elements can be combined. The pickup values are determined by the type of protected object. The pickup values are set specifically for each element:
50-B2 PICKUP, 67-B2 PICKUP address 2623 50N-B2 PICKUP, 67N-B2 PICKUP address 2626 50-B1 PICKUP, 67-B1 PICKUP address 2613 50N-B1 PICKUP, 67N-B1 PICKUP address 2616 51-B PICKUP, 67-TOC PICKUP address 2633 51N-B PICKUP, 67N-TOC PICKUP address 2638
The setting of the current pickup value is basically determined by the maximum operational current. Pickup due to overload must be excluded as the device operates as short-circuit protection in this mode with correspond­ingly short command times and not as overload protection. A pickup value setting of about 10% is recommend­ed for line protection, and a setting of about 20% of the expected peak load is recommended for transformers and motors.
The ground current elements detect the smallest anticipated ground fault current. For very long lines with small source impedance or on applications with large reactances (e.g. transformers,
series reactors), the 50-2 elements can also be used for current grading. In this case, they must be set such that they do not pickup reliably on a short circuit at the line end.
For the inverse time elements a safety margin between pickup value and setting value has already been im­plemented. Pick up only occurs at a current which is approximately 10% above the set value. Please bear this in mind when specifying the setting values of the inverse time elements.
If an element is not required, set the pickup value to ∞.
90
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Time Delays
Functions
2.4 Backup Overcurrent
The time delays are set specifically for each element:
50-B2 DELAY, 67-B2 DELAY addess 2624 50N-B2 DELAY, 67N-B2 DELAY addess 2627 50-B1 DELAY, 67-B1 DELAY addess 2614 50N-B1 DELAY, 67N-B1 DELAY addess 2617 51-B TD IEC, 67-TOC TD IEC addess 2634 (IEC characteristic) 51N-B TD IEC, 67N-TOC TD IEC addess 2639 (IEC characteristic) 51-B TD ANSI, 67-TOC TD ANSI addess 2635 (ANSI characteristic) 51N-B TD ANSI, 67N-TOC TD ANSI addess 2640 (ANSI characteristic)
They are determined by the time grading chart created for the power system. If used as emergency overcurrent protection, shorter tripping times are advisable as this function is only activated in the case of the loss of the local measuring voltage.
The times for the ground current elements can be set shorter, according to a separate time grading chart for ground currents.
You can set additional time delays for definite-time elements with IEC characteristic.
51-B AddT-DELAY, 67-TOC AddTDel. addess 2636 51N-B AddTdelay, 67N-TOC AddTDel addess 2641
Instantaneous Tripping via Binary Input
Binary input „>5X-B InstTRIP“ allows you to bypass the time delays. The binary input applies to all ele­ments collectively.
You can specify for each element whether instantaneous tripping takes effect. The setting applies collectively to the corresponding phase and ground element.
50-1, 3I0> address 2628 50-2, 3I0>> add ress 2618 50N, 3I0p address 2644
The following settings are possible:
• If set to YES, the element trips instantaneously when the binary input is activated.
• When set to NO, the set time delays take effect.
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
91
Functions
2.4 Backup Overcurrent
Characteristic Curves for the 50N Element
During configuration of the scope of functions at address 126, the available characteristics were determined. Depending on the selection made there, only the parameters associated with this characteristic curve are ac­cessible.
The inverse time elements enable the user to select different characteristic curves. Address 126 allows you to specify whether you work with IEC characteristics (50(N) 51(N) IEC) or ANSI characteristics(50(N) 51(N)ANSI).
If you work with IEC characteristics, you can select the following setting options at address 2642:
Normal Inverse
Very Inverse
Extremely Inv.
LongTimeInverse If you work with ANSI characteristics, you can select the following setting options at address 2643:
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv. The characteristics and equations they are based on are listed in the „Technical Data“. They apply for direc-
tional and non-directional elements alike.
92
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
2.4 Backup Overcurrent

2.4.5 Settings

Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings". The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
Addr. Parameter C Setting Options Default Setting Comments
2603A 67N dir. meas. V0/I0 or V2/I2
with V0/I0 with V2/I2
2610 Op.Mode50(N)-B1 ON
Only Emer. prot OFF
2610 Op.Mode67(N)-B1 ON
Only Emer. prot OFF
261 1 67(N)-B1 Dir. Non-Directional
Forward Reverse
2612 67(N)-B1 on FFM Non-Directional
BLOCKED
V0/I0 or V2/I2 67N, Measurement of di-
rection
OFF Operating Mode 50(N)-B1
OFF Operating Mode 67(N)-B1
Non-Directional 67(N)-B1 Direction
BLOCKED 67(N)-B1 Direct. stage on
Fuse Failure
Functions
2613 50-B1 PICKUP 1A 0.10 .. 25.00 A; 2.00 A 50-B1 Pickup
5A 0.50 .. 125.00 A; 10.00 A 2613 67-B1 PICKUP 0.10 .. 25.00 A; 2.00 A 67-B1 Pickup threshold 2614 50-B1 DELAY 0.00 .. 30.00 sec; 0.30 sec 50-B1 Delay 2614 67-B1 DELAY 0.00 .. 30.00 sec; 0.30 sec 67-B1 set time delay 2615 50-B1 Inrush NO
NO 50-B1 Inrush blocking
YES
2615 67-B1 Inrush NO
NO 67-B1 Inrush blocking
YES
2616 50N-B1 PICKUP 1A 0.05 .. 25.00 A; 0.50 A 50N-B1 Pickup
5A 0.25 .. 125.00 A; 2.50 A 2616 67N-B1 PICKUP 0.05 .. 25.00 A; 0.50 A 67N-B1 Pickup threshold 2617 50N-B1 DELAY 0.00 .. 30.00 sec; 2.00 sec 50N-B1 Delay 2617 67N-B1 DELAY 0.00 .. 30.00 sec; 2.00 sec 67N-B1 set time delay 2618 50(N)-B1 Pil/BI NO
YES
2618 67(N)-B1 Pil/BI NO
YES
2620 Op.Mode50(N)-B2 ON
YES Instantaneous trip via Pilot
Prot./BI
NO Instantaneous trip via Pilot
Prot./BI
Only Emer. prot Operating Mode 50(N)-B2 Only Emer. prot OFF
2620 Op.Mode67(N)-B2 ON
Only Emer. prot Operating Mode 67(N)-B2 Only Emer. prot OFF
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
93
Functions
2.4 Backup Overcurrent
Addr. Parameter C Setting Options Default Setting Comments
2621 67(N)-B2 Dir. Non-Directional
Non-Directional 67(N)-B2 Direction Forward Reverse
2622 67(N)-B2 on FFM Non-Directional
BLOCKED
BLOCKED 67(N)-B2 Direct. stage on
Fuse Failure
2623 50-B2 PICKUP 1A 0.10 .. 25.00 A; 1.50 A 50-B2 Pickup
5A 0.50 .. 125.00 A; 7.50 A 2623 67-B2 PICKUP 0.05 .. 50.00 A; 1.50 A 67-B2 Pickup threshold 2624 50-B2 DELAY 0.00 .. 30.00 sec; 0.50 sec 50-B2 Delay 2624 67-B2 DELAY 0.00 .. 30.00 sec; 0.50 sec 67-B2 set time delay 2625 50-B2 Inrush NO
NO 50-B2 Inrush blocking
YES
2625 67-B2 Inrush NO
NO 67-B2 Inrush blocking
YES
2626 50N-B2 PICKUP 1A 0.05 .. 25.00 A; 0.20 A 50 N-B2 Pickup
5A 0.25 .. 125.00 A; 1.00 A 2626 67N-B2 PICKUP 0.05 .. 25.00 A; 0.20 A 67N-B2 Pickup threshold 2627 50N-B2 DELAY 0.00 .. 30.00 sec; 2.00 sec 50N-B2 Delay 2627 67N-B2 DELAY 0.00 .. 30.00 sec; 2.00 sec 67N-B2 set time delay 2628 50(N)-B2 Pil/BI NO
YES
2628 67(N)-B2 Pil/BI NO
YES
2630 Op.Mode 51(N)-B ON
NO Instantaneous trip via Pilot
Prot./BI
NO Instantaneous trip via Pilot
Prot./BI
OFF Operating Mode 51(N)-B Only Emer. prot OFF
2630 Op.Mode67(N)TOC ON
Only Emer. prot
OFF Operating Mode 67(N)-
TOC
OFF
2631 67(N)-TOC Dir. Non-Directional
Non-Directional 67(N)-TOC Direction Forward Reverse
2632 67(N)-TOCon FFM Non-Directional
BLOCKED
BLOCKED 67(N)-TOC Direct. stage
on Fuse Failure
2633 51-B PICKUP 1A 0.10 .. 4.00 A; ∞∞A 51-B Pickup
5A 0.50 .. 20.00 A; ∞∞A 2633 67-TOC PICKUP 0.10 .. 4.00 A; ∞∞A 67-TOC Pickup threshold 2634 51-B TD IEC 0.05 .. 3.00 sec; 0.50 sec 51-B Time Dial for IEC
characteristic
2634 67-TOC TD IEC 0.05 .. 3.00 sec; 0.50 sec 67-TOC Time Dial for IEC
characteristic
2635 51-B TD ANSI 0.50 .. 15.00 ; 5.00 51-B Time Dial for ANSI
characteristic
94
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Functions
2.4 Backup Overcurrent
Addr. Parameter C Setting Options Default Setting Comments
2635 67-TOC TD ANSI 0.50 .. 15.00 ; 5.00 67-TOC Time Dial for
ANSI characteristic
2636 51-B AddT-DELAY 0.00 .. 30.00 sec 5.00 sec 51-B Additional Time
Delay
2636 67-TOC AddTDel. 0.00 .. 30.00 sec 5.00 sec 67-TOC Additional Time
Delay
2637 51-B Inrush NO
NO 51-B Inrush blocking
YES
2637 67-TOC Inrush NO
NO 67-TOC Inrush blocking
YES
2638 51N-B PICKUP 1A 0.05 .. 4.00 A; ∞∞A 51N-B Pickup
5A 0.25 .. 20 .0 0A; ∞∞A
2638 67N-TOC PICKUP 0.05 .. 4.00 A; ∞∞A 67N-TOC Pickup thresh-
old
2639 51N-B TD IEC 0.05 .. 3.00 sec; 0.50 sec 51N-B Time Dial for IEC
characteristic
2639 67N-TOC TD IEC 0.05 .. 3.00 sec; 0.50 sec 67N-TOC Time Dial for
IEC characteristic
2640 51N-B TD ANSI 0.50 .. 15.00 ; 5.00 51N-B Time Dial for ANSI
characteristic
2640 67N-TOC TD ANSI 0.50 .. 15.00 ; 5.00 67N-TOC Time Dial for
ANSI char.
2641 51N-B AddTdelay 0.00 .. 30.00 sec 0.00 sec 51N-B Additional Time
Delay
2641 67N-TOC AddTDel 0.00 .. 30.00 sec 0.00 sec 67N-TOC Additional Time
Delay
2642 IEC Curve Normal Inverse
Normal Inverse IEC Curve Very Inverse Extremely Inv. LongTimeInverse
2642 IEC Curve Normal Inverse
Normal Inverse IEC Curve Very Inverse Extremely Inv. LongTimeInverse
2643 ANSI Curve Inverse
Short Inverse Long Inverse Moderately Inv. Very Inverse Extremely Inv. Definite Inv.
2643 ANSI Curve Inverse
Short Inverse Long Inverse Moderately Inv. Very Inverse Extremely Inv. Definite Inv.
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
Inverse ANSI Curve
Inverse ANSI Curve
95
Functions
2.4 Backup Overcurrent
Addr. Parameter C Setting Options Default Setting Comments
2644 51(N)-B PilotBI NO
YES
NO Instantaneous trip via Pilot
Prot./BI
2644 67(N)TOC Pil/BI NO
YES
2650 50(N)-STUB OpMo ON
Only Emer. prot
NO Instantaneous trip via Pilot
Prot./BI
OFF 50(N)-STUB Operating
Mode
OFF
2651 50-STUB PICKUP 1A 0.10 .. 25.00 A; 1.50 A 50-STUB Pickup
5A 0.50 .. 125.00 A; 7.50 A 2652 50-STUB DELAY 0.00 .. 30.00 sec; 0.30 sec 50-STUB Delay 2653 50-STUB Inrush NO
NO 50-STUB Inrush blocking
YES
2654 50N-STUB PICKUP 1A 0.05 .. 25.00 A; 0.20 A 50N-STUB Pickup
5A 0.25 .. 125.00 A; 1.00 A 2655 50N-STUB DELAY 0.00 .. 30.00 sec; 2.00 sec 50N-STUB Delay 2656 50STUB Pilot/BI NO
YES
NO Instantaneous trip via Pilot
Prot./BI

2.4.6 Information List

No. Information Type of In-
formation
7104 >BLOCK 50-B1 SP >BLOCK 50-B1 Backup OverCurrent 7105 >BLOCK 50-B2 SP >BLOCK 50-B2 Backup OverCurrent 7106 >BLOCK 51-B SP >BLOCK 51-B Backup OverCurrent 7107 >BLOCK 50N-B1 SP >BLOCK 50N-B1 Backup OverCurrent 7108 >BLOCK 50N-B2 SP >BLOCK 50N-B2 Backup OverCurrent 7109 >BLOCK 51N SP >BLOCK 51N Backup OverCurrent 7110 >5X-B InstTRIP SP >50(N)/51(N) BackupO/C InstantaneousTrip 7112 >BLOCK 67-TOC SP >BLOCK Backup OverCurrent 67-TOC 7114 >BLOCK 67N-TOC SP >BLOCK Backup OverCurrent 67N-TOC 7115 >BLOCK 67-B1 SP >BLOCK Backup OverCurrent 67-B1 7116 >BLOCK 67N-B1 SP >BLOCK Backup OverCurrent 67N-B1 7117 >BLOCK 67-B2 SP >BLOCK Backup OverCurrent 67-B2 7118 >BLOCK 67N-B2 SP >BLOCK Backup OverCurrent 67N-B2 7130 >BLOCK 50-STUB SP >BLOCK 50-STUB 7132 >BLOCK 50N-STUB SP >BLOCK 50N-STUB 7152 5X-B BLOCK OUT 50(N)/51(N) Backup O/C is BLOCKED 7153 5X-B ACTIVE OUT 50(N)/51(N) Backup O/C is ACTIVE 7154 50(N)-B2 OFF OUT Backup O/C stage 50(N)-B2 is sw. OFF 7155 50(N)-B1 OFF OUT Backup O/C stage 50(N)-B1 is sw. OFF 7156 50(N)-STUB OFF OUT Backup O/C stage 50(N)-STUB is sw. OFF 7157 51(N)-B OFF OUT Backup O/C stage 51(N)-B is sw. OFF 7161 5X-B PICKUP OUT 50(N)/51(N) Backup O/C PICKED UP
Comments
96
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Functions
2.4 Backup Overcurrent
No. Information Type of In-
Comments
formation
7162 5X-B Pickup ØA OUT 50(N)/51(N) Backup O/C PICKUP Phase A 7163 5X-B Pickup ØB OUT 50(N)/51(N) Backup O/C PICKUP Phase B 7164 5X-B Pickup ØC OUT 50(N)/51(N) Backup O/C PICKUP Phase C 7165 5X-B Pickup Gnd OUT 50(N)/51(N) Backup O/C PICKUP GROUND 7191 50(N)-B1 PICKUP OUT 50(N)-B1 Pickup 7192 50(N)-B2 PICKUP OUT 50(N)-B2 Pickup 7193 51(N)-B PICKUP OUT 51(N)-B Pickup 7201 50-STUB PICKUP OUT 50-STUB Pickup 7211 5X-B TRIP OUT 50(N)/51(N)-B General TRIP command 7221 50(N)-B1 TRIP OUT 50(N)-B1 TRIP 7222 50(N)-B2 TRIP OUT 50(N)-B2 TRIP 7223 51(N)-B TRIP OUT 51(N)-B TRIP 7235 50-STUB TRIP OUT 50-STUB TRIP 7250 67(N)-B1 PICKUP OUT 67(N)-B1 Pickup 7251 67(N)-B2 PICKUP OUT 67(N)-B2 Pickup 7252 67(N)-TOC PICK. OUT 67(N)-TOC Pickup 7253 67(N) TRIP OUT 67(N) General TRIP command 7254 67(N)-B1 TRIP OUT 67(N)-B1 TRIP 7255 67(N)-B2 TRIP OUT 67(N)-B2 TRIP 7256 67(N)-TOC TRIP OUT 67(N)-TOC TRIP 7257 67 forward ØA OUT 67 Phase A forward 7258 67 forward ØB OUT 67 Phase B forward 7259 67 forward ØC OUT 67 Phase C forward 7260 67N forward GND OUT 67N Gnd forward 7261 67 reverse ØA OUT 67 Phase A reverse 7262 67 reverse ØB OUT 67 Phase B reverse 7263 67 reverse ØC OUT 67 Phase C reverse 7264 67N reverse GND OUT 67N Gnd forward 7265 67(N) forward OUT 67(N) forward 7266 67(N) reverse OUT 67(N) reverse 7267 >67(N) InstTRIP SP >67(N) BackupO/C InstantaneousTrip 17530 67(N) BLOCK OUT 67(N) Backup O/C is BLOCKED 17531 67(N) ACTIVE OUT 67(N) Backup O/C is ACTIVE 17532 67(N)-B2 OFF OUT Backup O/C stage 67(N)-B2 is sw. OFF 17533 67(N)-B1 OFF OUT Backup O/C stage 67(N)-B1 is sw. OFF 17534 67(N)-TOC OFF OUT Backup O/C stage 67(N)-TOC is sw. OFF 17535 67(N) PICKUP OUT 67(N) Backup O/C PICKED UP 17536 67 Pickup ØA OUT 67 Backup O/C PICKUP Phase A 17537 67 Pickup ØB OUT 67 Backup O/C PICKUP Phase B 17538 67 Pickup ØC OUT 67 Backup O/C PICKUP Phase C 17539 67N Pickup Gnd OUT 67N Backup O/C PICKUP GROUND
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
97
Functions

2.5 Inrush Restraint

2.5 Inrush Restraint

2.5.1 Description

If the protected zone of the device reaches beyond a transformer, a high inrush current must be anticipated when switching on the transformer. This current flows into the protected zone, but does not leave it again.
The inrush current can amount to a multiple of the rated current and is characterized by a considerable 2nd harmonic content (double rated frequency) which is practically absent during a short circuit. If the second har­monic content in the differential current exceeds a selectable threshold, tripping is blocked.
The inrush restraint has an upper limit: It no longer takes effect when a (configurable) current value is sur­passed since, in this case, it can only be an internal high-current fault.
Figure 2-32 shows a simplified logic diagram. The condition for the inrush current detection is examined in each device in which this function has been activated. The blocking condition is transmitted to the other device so that it is effective at both ends of the protected object.
Figure 2-32 Logic diagram of the inrush restraint for one phase
Since the inrush restraint operates individually for each phase, the protection is fully operative when the trans­former is switched onto a single-phase fault, in which case it is possible for an inrush current to flow through one of the undisturbed phases. It is, however, also possible to set the protection in such a way that when the permissible harmonic content in the current of only one single phase is exceeded, not only the phase with the inrush current but also the remaining phases of the differential stage are blocked. This cross-block function can be limited to a selectable duration. Figure 2-33 shows the logic diagram.
The cross-block function also affects both devices since it not only extends the inrush current detection to all three phases but also sends it to the other device via the communication link.
98
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Figure 2-33 Logic diagram of the cross-block function for one end

2.5.2 Setting Notes

Functions
2.5 Inrush Restraint
The inrush current detection is required for the following applications:
• For the differential protection if an inductance is located in the protected zone.
• For the time overcurrent protection if a transformer is located in the protected zone or if the protected line ends on a transformer.
Inrush current detection can be turned ON or OFF at address 2301INRUSH REST.. It is based on the evaluation of the second harmonic which exists in the inrush current. Ex-works a ratio of 15 %
of the 2nd HARMONIC I
is set under address 2302, which can normally be taken over. However, the com-
2fN/IfN
ponent required for restraint can be parameterized. In order to be able to achieve a higher degree of restraint in case of exceptionally unfavorable inrush conditions, you may also set a smaller value.
However, if the local measured current exceeds a value set in address 2305 MAX INRUSH PEAK, there will be no inrush restraint. The peak value is decisive. The set value should be higher than the maximum inrush current peak value that can be expected. For transformers set the value above √2·I
NTransf./ukTransf.
. If a line ends on a transformer, a smaller value may be selected, considering the damping of the current by the line imped­ance.
The crossblock function can be activated (YES or deactivated (NO) in address 2303 CROSS BLOCK. The time after exceeding of the current threshold for which this crossblock is to be activated is set under address 2310 CROSSB 2HM. With the setting ∞ the crossblock function is always active until the second harmonic content in all phases has dropped below the set value.
SIPROTEC, 7SD80, Manual E50417-G1140-C474-A1, Release date 09.2011
99
Functions
2.5 Inrush Restraint

2.5.3 Settings

Addr. Parameter Setting Options Default Setting Comments
2301 INRUSH REST. OFF
ON
2302 2nd HARMONIC 10 .. 45 % 15 % 2nd. harmonic in % of fundamen-
2303 CROSS BLOCK NO
YES 2305 MAX INRUSH PEAK 1.1 .. 25.0 A 15.0 A Maximum inrush-peak value 2310 CROSSB 2HM 0.00 .. 60.00 sec; 0.00 sec Time for Crossblock with 2nd har-
OFF Inrush Restraint
tal
NO Cross Block
monic

2.5.4 Information List

No. Information Type of In-
formation
3102 2nd Harmonic A OUT Tolerance invalid in phase A 3103 2nd Harmonic B OUT Tolerance invalid in phase B 3104 2nd Harmonic C OUT Tolerance invalid in phase C
Comments
100
E50417-G1140-C474-A1, Release date 09.2011
SIPROTEC, 7SD80, Manual
Loading...