PROFIBUS Networks
Topologies of SIMATIC NET PROFIBUS
Networks
Configuring Networks
Passive Components of RS–485 Networks
Active Components of RS–485 Networks
Passive Components for PROFIBUS–PA
Passive Components for Electrical Networks
Active Components for Optical Networks
Active Components for Wireless Networks
1
2
3
4
5
6
7
8
9
Testing PROFIBUS
Lightning and Surge Voltage Protection for
LAN Cables Between Buildings
Installing LAN Cables
Installing Instructions for SIAMTIC NET
PROFIBUS Plastic Fiber Optic with Simplex
Connenctors or BFOC Connectors and Pulling Loop for the FO Standard Cable
Installing Network Components in Cubicles
Dimension Drawings
Operating Instructions ILM / OLM / OBT
General Information
References
A
B
C
D
E
F
G
H
I
05/2000
6GK1970–5CA20–0AA1
Release 2
SIMATIC NET – Support and Training
Glossary, Index
J
Safety Guidelines
Danger
!
indicates that death, severe personal injury or substantial property damage will result if proper precau-
tions are not taken.
Warning
!
indicates that death, severe personal injury or substantial property damage can result if proper precautions are not taken.
Caution
!
indicates that minor personal injury or property damage can result if proper precautions are not taken.
Note
draws your attention to particularly important information on the product, handling the product, or to a
particular part of the documentation.
Qualified Personnel
Only qualified personnel should be allowed to install and work on this equipment Qualified persons are
defined as persons who are authorized to commission, to ground, and to tag circuits, equipment, and systems in accordance with established safety practices and standards.
Correct Usage
Note the following:
Warning
!
Trademarks
The reproduction, transmission or use of this document or its contents is not
permitted without express written authority. Offenders will be liable for
damages. All rights, including rights created by patent grant or registration of
a utility model or design, are reserved.
This device and its components may only be used for the applications described in the catalog or the
technical description, and only in connection with devices or components from other manufacturers which
have been approved or recommended by Siemens.
This product can only function correctly and safely if it is transported, stored, set up, and installed correctly, and operated and maintained as recommended.
SIMATICR, SIMATIC HMIR and SIMATIC NETR are registered trademarks of SIEMENS AG.
HCS is a registered trademark of Ensign–Bickford Optics Company.
Third parties using for their own purposes any other names in this document which refer to trademarks
might infringe upon the rights of the trademark owners.
Disclaimer of LiabilityCopyright Siemens AG 1999 All rights reserved
We have checked the contents of this manual for agreement with the hardware and software described. Since deviations cannot be precluded entirely,
we cannot guarantee full agreement. However, the data in this manual are
reviewed regularly and any necessary corrections included in subsequent
editions. Suggestions for improvement are welcomed.
Siemens AG
Bereich Automatisierungs– und Antriebstechnik
Geschäftsgebiet Industrielle Kommunikation
Postfach 4848, D-90327 Nürnberg
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
vii
Contents
viii
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
PROFIBUS NETWORKS
1
PROFIBUS NETWORKS
1.1Local Area Networks in Manufacturing and Process Automation
1.1.1General Introduction
Communication Systems
The performance of control systems is no longer simply determined by the
programmable logic controllers, but also to a great extent by the environment in
which they are located. Apart from plant visualization, operating and monitoring,
this also means a high-performance communication system.
Distributed Systems
Distributed automation systems are being used increasingly in manufacturing and
process automation. This means that a complex control task is divided into smaller
“handier” subtasks with distributed control systems. As a result, efficient
communication between the distributed systems is an absolute necessity. Such
structures have, for example, the following advantages:
SIndependent and simultaneous startup of individual sections of plant/system
SSmaller, clearer programs
SParallel processing by distributed automation systems
This results in the following:
– Shorter reaction times
– Reduced load on the individual processing units
SSystem-wide structures for handling additional diagnostic and logging functions
SIncreased plant/system availability since the rest of the system can continue to
operate if a substation fails.
A comprehensive, high-performance communication system is a must for a
distributed system structure.
1-2
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
SIMATIC NET
With SIMATIC NET, Siemens provides an open, heterogeneous communication
system for various levels of process automation in an industrial environment. The
SIMATIC NET communication systems are based on national and international
standards according to the ISO/OSI reference model.
The basis of such communication systems are local area networks (LANs) which
can be implemented in one of the following ways:
SIMATIC NET is the name of the communication networks connecting SIEMENS
programmable controllers, host computers, work stations and personal computers.
SIMATIC NET includes the following:
SThe communication network consisting of transmission media, network
attachment and transmission components and the corresponding transmission
techniques
SProtocols and services used to transfer data between the devices listed above
SThe modules of the programmable controller or computer that provide the
connection to the LAN (communications processors “CPs” or “interface
modules”).
To handle a variety of tasks in automation engineering, SIMATIC NET provides
different communication networks to suit the particular situation.
The topology of rooms, buildings, factories, and complete company complexes and
the prevalent environmental conditions mean different requirements. The
networked automation components also make different demands on the
communication system.
To meet these various requirements, SIMATIC NET provides the following
communication networks complying with national and international standards:
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
1-3
PROFIBUS NETWORKS
Industrial Ethernet/Fast Ethernet
A communication network for the LAN and cell area using baseband technology
complying with IEEE 802.3 and using the CSMA/CD medium access technique
(Carrier Sense Multiple Access/Collision Detection). The network is operated on
The actuator sensor interface (AS-i) is a communication network for automation at
the lowest level for connecting binary actuators and sensors to programmable logic
controllers via the AS-i bus cable.
PROFIBUS
A communication network for the cell and field area complying with EN 50170-1-2
with the hybrid medium access technique token bus and master slave. Networking
is on twisted pair, fiber-optic cable or wireless.
PROFIBUS-PA
PROFIBUS-PA is the PROFIBUS for process automation (PA). It connects the
PROFIBUS-DP communication protocol with the IEC 61158-2 transmission
technique.
1-4
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
1.2Basics of the PROFIBUS Network
EN 50170
SIMATIC NET PROFIBUS products and the networks they make up comply with
the PROFIBUS standard EN 50170 (1996). The SIMATIC NET PROFIBUS
components can also be used with SIMATIC S7 to create a SIMATIC MPI subnet
(MPI = Multipoint Interface).
Attachable Systems
The following systems can be connected:
SSIMATIC S5/S7/M7/C7 programmable controllers
SET 200 distributed I/O system
SSIMATIC programming devices/PCs
PROFIBUS NETWORKS
SSIMATIC operator control and monitoring devices or systems
SSICOMP IPCs
SSINUMERIK CNC numerical controls
SSIMODRIVE sensors
SSIMOVERT master drives
SSIMADYN D digital control system
SSIMOREG
SMicro-/Midimasters
SSIPOS reversing power controllers/actuators
SSIPART industry/process controllers
SMOBY identification systems
SSIMOCODE low-voltage switchgear
SCircuit breakers
SSICLIMAT COMPAS compact automation stations
STELEPERM M process control system
SDevices from other manufacturers with a PROFIBUS-compliant interface
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
1-5
PROFIBUS NETWORKS
Transmission Media
PROFIBUS networks can be implemented with the following:
The various communication networks can be used independently or if required can
also be combined with each other.
1-6
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
1.2.1Standards
SIMATIC NET PROFIBUS is based on the following standards and directives:
IEC 61158–2 to 6: 1993/2000
EN 50170-1-2: 1996
PROFIBUS User Organization Guidelines:
PROFIBUS NETWORKS
Digital data communications for measurement and control –
Fieldbus for use in industrial control systems
General purpose field communication system
Volume 2 : Physical Layer Specification and Service Definition
PROFIBUS Implementation Guide to DIN 19245
Part 3 (Draft)
Version 1.0 dated 14.12.1995
Fiber Optic Data Transfer for PROFIBUS
Version 2.1 dated 12.98
EIA RS-485: 1983
Standard for Electrical Characteristics of Generators and
Receivers for Use in Balanced Digital Multipoint Systems
SIMATIC NET PROFIBUS-PA is based on the following standards and directives:
EN 50170-1-2: 1996
General Purpose Field Communication System
Volume 2 : Physical Layer Specification and Service Definition
IEC 61158-2: 1993
Fieldbus standard for use in industrial control systems
Part 2 : Physical layer specification and service definition
EN 61158-2: 1994
Fieldbus standard for use in industrial control systems
Part 2 : Physical layer specification and service definition
PTB-Bericht W-53: 1993
Untersuchungen zur Eigensicherheit bei Feldbussystemen
Braunschweig, March 1993
PNO-Richtlinie: 1996
PROFIBUS-PA Inbetriebnahmeleitfaden (Hinweise zur Nutzung
der IEC 61158-2-Technik für PROFIBUS, Art.-Nr. 2.091)
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
1-7
PROFIBUS NETWORKS
1.2.2Access Techniques
TOKEN BUS/Master-Slave Method
Network access on PROFIBUS corresponds to the method specified in EN 50170,
Volume 2 “Token Bus” for active and “Master-Slave” for passive stations.
Master
Master
Master
Token rotation
(logical ring)
Master
Master
Slave
Master = active node
Slave = passive node
Figure 1-1Principle of the PROFIBUS Medium Access Technique
Slave
Slave
Slave
Logical token ring
Master-slave relationship
Slave
1-8
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Active and Passive Nodes
The access technique is not dependent on the transmission medium. Figure 1-1
“Principle of the PROFIBUS Medium Access Technique” shows the hybrid
technique with active and passive nodes. This is explained briefly below:
SAll active nodes (masters) form the logical token ring in a fixed order and each
active node knows the other active nodes and their order in the logical ring (the
order does not depend on the topological arrangement of the active nodes on
the bus).
SThe right to access the medium, the “Token”, is passed from active node to
active node in the order of the logical ring.
SIf a node has received the token (addressed to it), it can send frames. The time
in which it is allowed to send frames is specified by the token holding time.
Once this has expired, the node is only allowed to send one high priority
message. If the node does not have a message to send, it passes the token
directly to the next node in the logical ring. The token timers from which the
maximum token holding time is calculated are configured for all active nodes.
PROFIBUS NETWORKS
SIf an active node has the token and if it has connections configured to passive
nodes (master-slave connections), the passive nodes are polled (for example
values read out) or data is sent to the slaves (for example setpoints).
SPassive nodes never receive the token.
This access technique allows nodes to enter or leave the ring during operation.
1.2.3Transmission Techniques
The physical transmission techniques used depend on the SIMATIC NET
PROFIBUS transmission medium:
SRS-485 for electrical networks on shielded, twisted pair cables
SOptical techniques according to the PROFIBUS User Organization guideline /3/
on fiber-optic cables
SWireless techniques based on infrared radiation
SIEC 61158-2 technique for intrinsically safe and non-intrinsically safe electrical
networks in process control (PROFIBUS-PA) based on shielded, twisted pair
cables.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
1-9
PROFIBUS NETWORKS
1.2.4Transmission Techniques According to EIA Standard RS-485
EIA Standard RS-485
The RS-485 transmission technique corresponds to balanced data transmission as
specified in the EIA Standard RS-485 /4/. This transmission technique is
mandatory in the PROFIBUS standard EN 50170 for data transmission on twisted
pair cables.
The medium is a shielded, twisted pair cable.
The bus cable is terminated at both ends with the characteristic impedance. Such
a terminated bus cable is known as a segment.
The attachment of the node to the bus is via a bus terminal with a tap line or a bus
connector (maximum 32 nodes per segment). The individual segments are
interconnected by repeaters.
The maximum length of a segment depends on the following:
SThe transmission rate
SThe type of cable being used
Advantages:
SFlexible bus or tree structure with repeaters, bus terminals, and bus connectors
SPurely passive passing on of signals allows nodes to be deactivated without
SSimple installation of the bus cable without specialized experience.
for attaching PROFIBUS nodes
affecting the network (except for the nodes that supply power to the terminating
resistors)
1-10
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Restrictions:
SDistance covered reduces as the transmission rate increases
SRequires additional lightning protection measures when installed outdoors
Properties of the RS-485 Transmission Technique
The RS-485 transmission technique in PROFIBUS has the following physical
characteristics:
Table 1-1Physical Characteristics of the RS-485 Transmission Technique
PROFIBUS NETWORKS
Network topology:
Medium:Shielded, twisted pair cable
Possible segment lengths:
400 m For a transmission rate of 500 Kbps
200 m For a transmission rate of 1.5 Mbps Mbps
100 m For transmission rates of 3.6 and 12 Mbps
Maximum 9
Maximum 127 per network when using repeaters
Mbps, 3 Mbps, 6 Mbps, 12 Mbps
Note
The properties listed in 1-1 assume a bus cable of type A and a bus terminator
according to the PROFIBUS standard EN 50170–1–2. The SIMATIC NET
PROFIBUS cables and bus connectors meet this specification. If reductions in the
segment length are necessary when using special versions of the bus cable with
increased d.c. loop resistance, this is pointed out in the sections on
“Configuration” and “SIMATIC NET PROFIBUS Cables”.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
1-11
PROFIBUS NETWORKS
1.2.5Transmission Techniques for Optical Components
PROFIBUS User Organization Guideline
The optical transmission technique complies with the PROFIBUS User
Organization guideline:
“Fiber Optic Data Transfer for PROFIBUS” /3/.
Integrated Optical Interfaces, OBT, OLM
The optical version of SIMATIC NET PROFIBUS is implemented with integrated,
optical ports, optical bus terminals (OBT) and optical link modules (OLM).
Duplex fiber-optic cables are used as the medium made of glass, PCF or plastic
fibers. Duplex fiber-optic cables consist of two conducting fibers surrounded by a
common jacket to form a cable.
Modules with integrated optical ports and optical bus terminals (OBTs) can be
interconnected to form optical networks only with a bus structure.
Using OLMs, optical networks can be installed using a bus, star and ring structure.
The ring structure provides a redundant signal transmission path and represents
the basis for networks with high availability.
Advantages:
SRegardless of the transmission rate, large distances can be covered between
SElectrical isolation between nodes and transmission medium
SWhen plant components at different ground potential are connected, there are
SNo electromagnetic interference
SNo additional lightning protection elements are required
SSimple laying of fiber-optic cables
SHigh availability of the LAN due to the use of a ring topology
SExtremely simple attachment technique using plastic fiber-optic cables over
two DTEs
(connections between OLM and OLM up to 15,000 m)
no shield currents
shorter distances.
1-12
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
PROFIBUS NETWORKS
Restrictions:
SFrame throughput times are increased compared with an electrical network
SThe assembly of glass fiber-optic cables with connectors requires specialist
experience and tools
SThe absence of a power supply at the signal coupling points (node attachments,
OLMs, OBTs) stops the signal flow
Characteristics of the Optical Transmission Technique
The optical transmission technique has the following characteristics:
Network topology:Bus structure with integrated optical ports and OBT;
bus, star or ring structure with OLMs
Medium:Fiber-optic cables with glass, PCF or plastic fibers
Link lengths
Number of nodes:Maximum of 127 per network (126 with ring structure with OLMs)
With glass fibers up to 15,000 m dependent on the fiber and OLM
type
with plastic fibers:
OLM:0 m to 80 m
OBT:1 m to 50 m
Kbps, 1.5 Mbps, 3 Mbps*, 6 Mbps*, 12 Mbps
* not with integrated optical ports and OBT
Note
The optical ports of the OLMs are optimized for greater distances. The direct
coupling of the optical ports of an OLM with an OBT or integrated optical ports is
not possible due to differences in the technical specifications.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
1-13
PROFIBUS NETWORKS
1.2.6Transmission Technique for Wireless Infrared Technology
The wireless PROFIBUS network uses infrared light for signal transmission. The
only transmission medium is a free line-of-sight connection between two nodes.
The maximum distance covered is approximately 15 m. Wireless networks are
implemented using infrared link modules (ILM). The nodes to be networked are
attached to the electrical port of the ILM.
Advantages:
SHigh mobility of attached plant components (for example trolleys)
SCoupling and decoupling from the fixed network with no wear and tear (for
example substitute for a slip ring)
SCoupling without cable installation (temporary setup, inaccessible areas)
SNot protocol dependent
SElectrical isolation between nodes and hardwired network
Restrictions
STransmission rate <= 1.5 Mbps
SFree line-of-sight path required between nodes
SMaximum distance covered <= 15 m
SOnly for single master networks
Characteristics of the Wireless Infrared Transmission Technique
The wireless infrared transmission technique has the following characteristics:
Network topology:Point-to-point
Point-to-multipoint
Medium:Free space with line-of-sight path
Maximum link length:15 m
Transmission rate ILM:9.6 Kbps, 19.2 Kbps, 45.45 Kbps, 93.75 Kbps, 187.5 Kbps,
500 Kbps, 1.5 Mbps
Number of nodes:Maximum 127 per network
1-14
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
1.2.7Transmission Technique for PROFIBUS-PA
IEC 61158-2 Standard
The transmission technique corresponds to the IEC 61158-2 standard (identical
with EN 61158-2).
The transmission medium is a shielded, twisted pair cable. The signal is
transmitted as a synchronous data stream Manchester-coded at 31.25 Kbps. In
general, the data line is normally also used to supply power to the field devices.
Advantages:
SSimple cabling with twisted pair
SRemote power supply via the signal cores
SIntrinsically safe operation possible (for hazardous areas)
PROFIBUS NETWORKS
SBus and tree topology
SUp to 32 nodes per cable segment
Restrictions:
STransmission rate restricted to 31.25 Kbps
Characteristics of the IEC 61158-2 Transmission Technique
The main characteristics of the IEC 61158-2 transmission technique are as follows:
Network topology:Bus, star and tree topology
Medium:
Achievable segment lengths:1900 m
Transmission rate:
Number of nodes:Maximum 127 per network
Shielded, twisted pair cable
31.25 Kbps
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
1-15
PROFIBUS NETWORKS
1-16
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Topologies of SIMATIC NET PROFIBUS
Networks
2
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2-1
Topologies of SIMATIC NET PROFIBUS Networks
2.1Topologies of RS-485 Networks
Transmission Rate
When operating SIMATIC NET PROFIBUS in the RS-485 transmission technique,
the user can select one of the transmission rates below:
Depending on the transmission rate, transmission medium, and network
components different segment lengths and therefore different network spans can
be implemented.
The bus attachment components can be divided into two groups:
SComponents for transmission rates from 9.6 Kbps to a maximum of 1.5 Mbps
SComponents for transmission rates from 9.6 Kbps to a maximum of 12 Mbps
LAN Cable
The transmission media used are the SIMATIC NET PROFIBUS cables described
in Chapter 4. The technical information below applies only to networks
implemented with these cables and SIMATIC NET PROFIBUS components.
Node Attachment
The nodes are attached to the LAN cables via bus connectors, bus terminals or
RS-485 repeaters.
Cable Termination
Each bus segment must be terminated at both ends with its characteristic
impedance. This cable terminator is integrated in the RS-485 repeaters, the bus
terminals, the ILM and the bus connectors and can be activated if required.
Before the cable terminator can be activated, the component must be supplied with
power. With the bus terminals and the bus connectors, this power is supplied by
the connected DTE, whereas the RS-485 repeater, the ILM, and the terminator
have their own power supply.
2-2
The RS-485 transmission technique allows the attachment of a maximum of 32
devices (DTEs and repeaters) per bus segment. The maximum permitted cable
length of a segment depends on the transmission rate and the LAN cable used.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Topologies of SIMATIC NET PROFIBUS Networks
Connecting Segments Using RS-485 Repeaters
By using RS-485 repeaters, segments can be interconnected. The RS-485
repeater amplifies the data signals on the LAN cables. You require an RS-485
repeater when you want to attach more than 32 nodes to a network or when the
permitted segment length is exceeded. A maximum of 9 repeaters can be used
between any two nodes. Both bus and tree structures can be implemented.
Figure 2-1 shows a typical topology using the RS-485 technique with 3 segments
and 2 repeaters.
S7-400
OP 25
OP 25
Terminating resistor activated
PG attached via tap line (6ES7 901-4BD00-0XA0)
for maintenance purposes
S7-300S7-300
PG
S7-400
Tap line
OP 25
RS-485
repeater
PG
RS-485
repeater
S7-400
Figure 2-1Topology Using the RS-485 Technique
Increasing the overall span of a network by using repeaters can lead to longer
transmission times that may need to be taken into account when configuring the
network (see Chapter 3).
2.1.1Components for Transmission Ratesup to 1.5 Mbps
All SIMATIC NET bus attachment components can be used for transmission rates
≤ 1.5 Mbps.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2-3
Topologies of SIMATIC NET PROFIBUS Networks
2.1.2Components for Transmission Rates up to
12 Mbps
The following bus attachment components can be used for transmission rates up
to 12 Mbps:
Table 2-1Bus Attachment Components for Transmission Rates up to 12 Mbps
Order number
PROFIBUS bus connector with
6GK1 500-0EA02
axial cable outlet
PROFIBUS FastConnect bus connector RS-485
Plug 180
with 180° cable outlet6GK1500-0FC00
RS-485 bus connector with vertical cable outlet
Without PG interface
With PG interface
6ES7 972-0BA11-0XA0
6ES7 972-0BB11-0XA0
PROFIBUS FastConnect RS-485 bus connector
with 90° cable outlet with insulation displacement terminal
system
max. transmission rate 12 Mbps
Without PG interface
6ES7 972-0BA50-0XA0
6ES7 972-0BB50-0XA0
With PG interface
RS-485 bus connector with 35o cable outlet
Without PG interface
With PG interface
6ES7 972-0BA40-0XA0
6ES7 972-0BB40-0XA0
SIMATIC NET 830-1T connecting cable, preassembled, fitted
with terminating resistors, as link between electrical interface
of an OLM or OBT and the PROFIBUS interface of a
PROFIBUS node.
1.5 m
3 m
6XV1830-1CH15
6XV1830-1CH30
SIMATIC NET 830-2 connecting cable for PROFIBUS,
preassembled cable with two sub-D, 9-pin male connectors,
terminating resistors can be activated.
3 m
5 m
10 m
6XV1830-2AH30
6XV1830-2AH50
6XV1830-2AN10
SIMATIC S5/S7 PROFIBUS connecting cable
for connecting programming devices up to 12 Mbps
preassembled with 2 sub-D connectors, length 3 m6ES7 901-4BD00-0XA0
PROFIBUS RS-485 repeater 24 V DC, casing with IP 20
6ES7 972-0AA01-0XA0
degree of protection
Bus terminal BT12M6GK1 500-0AA10
Optical Link Module OLM V36GK1 502-_C_00
PROFIBUS Networks SIMATIC NET
2-4
6GK1970-5CA20-0AA1 Release 2 05/2000
Topologies of SIMATIC NET PROFIBUS Networks
Table 2-1Bus Attachment Components for Transmission Rates up to 12 Mbps, continued
Optical Bus Terminal OBT6GK1 500-3AA0
PROFIBUS Terminator6ES7 972-0DA00-0AA0
2.2Topologies of Optical Networks
Interfacing Electrical and Optical Networks/Components
If you want to cover larger distances with the fieldbus regardless of the
transmission rate or if the data traffic on the bus is threatened by extreme levels of
external noise, you should use fiber-optic cables instead of copper cable.
To interface electrical cables with fiber-optic cables, you have the following
possibilities:
SThe PROFIBUS nodes with a PROFIBUS DP interface (RS-485) are attached
to the optical network using an optical bus terminal (OBT) or using an optical
link module (OLM).
SPROFIBUS nodes with an integrated FO port (for example ET 200M (IM 153-2
FO), S7-400 (IM 467 FO)) can be connected directly to an optical network with
a bus topology.
SOptical networks with a larger network span or structured as redundant rings
should be implemented using OLMs.
The structure of optical networks using optical link modules (OLMs) is described in
detail in later chapters in this manual.
For information about the structure of an optical PROFIBUS network with
PROFIBUS nodes having an integrated FO interface, refer also to the ET200
system manual.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2-5
Topologies of SIMATIC NET PROFIBUS Networks
2.2.1Topology with Integrated Optical Interfaces
The optical PROFIBUS network with nodes having an integrated FO interface is
structured as a bus topology. The PROFIBUS nodes are interconnected in pairs
by duplex fiber-optic cables.
Up to 32 PROFIBUS nodes with integrated FO interfaces can be connected in
series in an optical PROFIBUS network. If a PROFIBUS node fails, the bus
topology means that all DP slaves on the side away from the DP master are no
longer obtainable for the DP master.
S7-400 with IM 467 FO
PG/PC/OP
2
Distances between 2
OBT
Terminating resistor activated
1 FO cable
2 LAN cable for PROFIBUS
Figure 2-2PROFIBUS DP Network with Nodes Having Integrated FO Interfaces
1
Plastic FO cable up to 50 m
PCF FO cable up to 300 m
1
nodes:
ET 200M with
IM 153-2 FO
1
OBT
S7-300
For short distances, the preassembled 830-1T or 830-2 connecting cables can be
used as an alternative to the PROFIBUS cable.
2
OP 25
2
other
nodes
Transmission Rate
An optical PROFIBUS network with a bus topology can be operated at the
following transmission rates:
Using a PROFIBUS optical bus terminal (OBT), an individual PROFIBUS node
without an integrated FO port or a PROFIBUS RS-485 segment can be attached to
the optical PROFIBUS network (see Figure 2-2 ).
The attachment is made to the RS-485 interface of the OBT using a PROFIBUS
cable or a preassembled connecting cable. The OBT is included in the optical
PROFIBUS bus via the FO interface.
2.2.2Topologies with OLMs
OLMs
The OLMs have a floating electrical channel (similar to the channels on a repeater)
and depending on the version, they have one or two optical channels.
Topologies of SIMATIC NET PROFIBUS Networks
The OLMs are suitable for transmission rates of 9.6 Kbps to 12 Mbps. The
transmission rate is detected automatically.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2-7
Topologies of SIMATIC NET PROFIBUS Networks
Bus Topologies
Figure 2-3 shows a typical example of a bus topology
In a bus structure, the individual SIMATIC NET PROFIBUS OLMs are connected
together in pairs by duplex fiber-optic cables.
At the start and end of a bus, OLMs with one optical channel are adequate, in
between, OLMs with two optical channels are required.
The DTEs are attached to the electrical interfaces of the OLMs. Either individual
DTEs or complete PROFIBUS segments with a maximum of 31 nodes can be
connected to the RS-485 interface.
Several optical link modules are grouped together to form a star coupler via a bus
connection of the RS-485 interfaces. This RS-485 connection allows the
attachment of further DTEs until the maximum permitted number of 32 bus
attachments per segment is reached.
S7-400
OP 25
4
Topologies of SIMATIC NET PROFIBUS Networks
Star hub
2
2
1
2
PG
S7-400
Terminating resistor activated
1 FO cable
2 LAN cable for PROFIBUS
4 PROFIBUS 830-2 connecting cable
Figure 2-4Example of a Star Topology with OLMs
Optical Channels
The OLMs are connected to the star coupler by duplex fiber-optic cables.
Both DTEs and electrical bus segments can be connected to the OLMs attached
by the duplex fiber-optic cables. Depending on the requirements and the distance,
the duplex cables can be implemented with plastic, PCF or glass (OLM only)
fibers.
2
1
4
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2-9
Topologies of SIMATIC NET PROFIBUS Networks
Monitoring FO Links
Using the echo function, the connected OLMs can monitor the fiber-optic sections.
A break on a link is indicated by a display LED and by the signaling contact
responding.
Even if only one transmission direction is lost, the segmentation triggered by the
monitoring function leads to safe disconnection of the OLM from the star coupler.
The remaining network can continue to work without problems.
Mixed Structure
The star coupler can be made up with combinations of OLM/P, OLM/G and
OLM/G-1300 modules and at the RS-485 end with all types.
Redundant Optical Rings using OLMs
Redundant optical rings are a special form of bus topology. By closing the optical
bus to form a ring, a high degree of operational reliability is achieved
Figure 2-5Network Structure in a Redundant, Optical, Two-Fiber Ring Topology
PG
3
1
2-10
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Topologies of SIMATIC NET PROFIBUS Networks
A break on a fiber-optic cable between two modules is detected by the modules
and the network is reconfigured to form an optical bus. The entire network remains
operational.
If a module fails, only the DTEs or electrical segments attached to the module are
separated from the ring; the remaining network remains operational as a bus.
The problem is indicated by LEDs on the modules involved and by their signaling
contacts.
After the problem is eliminated, the modules involved cancel the segmentation
automatically and the bus is once again closed to form a ring.
Note
To increase the availability, the duplex cables for the outgoing and incoming paths
in the ring should be routed separately.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2-11
Topologies of SIMATIC NET PROFIBUS Networks
Alternative Cabling Strategy
If the distance between two OLMs turns out to be too long, a structure as shown in
Figure 2-6 can be implemented.
Figure 2-6Alternative Cabling of a Network Structure in an Optical Two-Fiber Ring Topology
PROFIBUS Networks SIMATIC NET
2-12
6GK1970-5CA20-0AA1 Release 2 05/2000
Topologies of SIMATIC NET PROFIBUS Networks
2.2.3Combination of Integrated Optical Interfaces and OLMs
Note
The optical ports of the OLMs are optimized for greater distances. The direct
coupling of the optical ports of an OLM with an OBT or integrated optical ports is
not possible due to differences in the technical specifications.
Attaching Glass FO Cables to Buses Made up of Integrated Optical Interfaces
The operating wavelength of the integrated optical interfaces and the OBT is
optimized for the use of plastic or PCF fibers. The direct attachment of glass FO
cables is not possible.
If a link with glass FO cable is required, for example to span distances of more
than 300 m, this link must be implemented with OLMs. The attachment of glass
links to the optical bus made up of integrated optical interfaces is via the RS-485
interface of an OBT. The following schematic shows an example of an application:
ET 200M with
PG
OBT
4
1
Terminating resistor activated
1 FO cable
2 LAN cable for PROFIBUS
Figure 2-7Attachment of an Optical Glass Link to an Optical Bus Made up of Integrated Optical
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2-13
Topologies of SIMATIC NET PROFIBUS Networks
2.3Topologies of Wireless Networks
Infrared Link Module (ILM)
In SIMATIC NET, wireless PROFIBUS networks are implemented with the “Infrared
Link Module (ILM)”.
Figure 2-8PROFIBUS ILM
Maximum Length of a Link
Regardless of the transmission rate, the maximum length of a link is 15 m. The
infrared light used for data transmission is radiated at an angle of +/- 10o around
the mid axis. This means that at a distance of 11 m, an ILM illuminates a circular
area with a diameter of 4 m. The communication partner must be within this
illuminated area. There must be an uninterrupted line-of-sight path between both
ILMs. The ILMs are suitable for transmission rates of 9.6 Kbps to 1.5 Mbps.
Point-to-Point Link
To implement a point-to-point link, two ILMs are positioned opposite each other so
that each is located within the infrared light cone of the other. The maximum
distance between two modules is 15 m.
2-14
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Master OP 25
Master
PG/PC/OP
2
Topologies of SIMATIC NET PROFIBUS Networks
Infrared
link
0.5 to 15 m
ILMILM
Slave
ET 200M
2
2
Master
S7-400
Terminating resistor activated
2 LAN cable for PROFIBUS
Figure 2-9Point-to-Point Link with Two PROFIBUS ILMs
PROFIBUS
master network segment
Figure 2-9 illustrates the typical structure of a PROFIBUS network with master and
slave nodes and an infrared link with two PROFIBUS ILMs. The infrared link is
implemented as a point-to-point link between the two PROFIBUS ILMs. The two
PROFIBUS ILMs replace a cable connection between the two network segments.
Remember that only slave nodes are permitted in the slave network segment.
PROFIBUS
slave network segment
2
Slave
ET 200S
2
Point-to-Multipoint Link
Several ILMs are positioned opposite to a single ILM so that several ILMs are in
the infrared light cone of another ILM. Only the ILMs positioned opposite each
other can exchange data. A data exchange between adjacent ILMs is only possible
by using a surface that reflects infrared light. If you consider this option, remember
that the length of the link is the path from the ILM to the reflector and from the
reflector to the partner ILM. Signal attenuation will also occur since the reflector
can only reflect part of the infrared light to the partner ILM. Such losses mean a
reduction in the maximum length of a link.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2-15
Topologies of SIMATIC NET PROFIBUS Networks
Slave
ET 200M
Master
S7-400
Master
PG/PC/OP
2
Master OP 25
Slave
ET 200M
Slave
S7-300
ILM
2
Infrared
link 1
0.5 to 15 m
2
2
PROFIBUS
slave network segment 1
Infrared
Slave
ET 200M
ILM
link 2
0.5 to 15 m
ILM
2
2
PROFIBUS
slave network segment 2
Slave
S7- 300
2
Infrared
2
link 3
0.5 to 15 m
Slave
ET 200S
ILM
2
Terminating resistor activated
2 LAN cable for PROFIBUS
PROFIBUS
slave network segment 3
Figure 2-10Point-to-Multipoint Link Using PROFIBUS ILMs (One Master Subnet, Three Subnets with
Slaves)
PROFIBUS Networks SIMATIC NET
2-16
6GK1970-5CA20-0AA1 Release 2 05/2000
Topologies of SIMATIC NET PROFIBUS Networks
2.4Topologies with PROFIBUS-PA
Bus and Star Topology
With PROFIBUS-PA, the topology can be either a bus or star.
SpliTConnect System
The SpliTConnect tap (T tap) allows the structuring of a bus segment with DTE
attachment points. The SpliTConnect tap can also be cascaded with the
SpliTConnect coupler to form attachment distributors. Using the SpliTConnect
terminator, the tap can be extended to become the segment terminator.
Star
Main cable
PROFIBUS-PA
DP/PA coupler
(bus terminator
integrated)
24 V DC
Figure 2-11Bus and Star Topology
PROFIBUS-DP
T tap
Tap line
Field Device Power Supply via PROFIBUS-PA
When using the DP/PA bus coupler, the power for the field devices is supplied via
the data line of PROFIBUS-PA.
Design
Tap line
Distributor made
up of T taps
Bus
T tap with
integrated
bus terminator
Field devices attached
via M12 connector
The total current of all field devices must not exceed the maximum output current
of the DP/PA coupler. The maximum output current therefore limits the number of
field devices that can be attached to PROFIBUS-PA.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2-17
Topologies of SIMATIC NET PROFIBUS Networks
DP/PA coupler Ex [i]
6ES7 157-0AD00-0XA0
Protection EEx [ia] II C
I
x 90 mA
max
DP/PA coupler Ex [i]
6ES7 157-0AD80-0XA0
Protection EEx [ib] II C
x 110 mA
I
max
DP/PA coupler
6ES7 157-0ACx0-0XA0
I
x 400 mA
max
PROFIBUS-PA
I
max
24 V DC
PROFIBUS-DP
PROFIBUS-PA
I
max
24 V DC
PROFIBUS-DP
I
1
Field device
1
I
1
Field device
1
I
2
Field device2Field device
Explosion-protected area
I
2
Field device2Field device
I
3...
3...
I
3...
3...
...I
n
Field device
...I
m
Field device
...n
...m
Figure 2-12Field Device Power Supply in the Hazardous and Non-Hazardous Area
Expansion
If the maximum output current of the DP/PA coupler is exceeded, you must include
a further DP/PA coupler.
Total Cable
The total cable is the total of the main cable and all the tap lines.
When using a standard PROFIBUS-PA cable with a cross-sectional area of
0.8 mm2, the maximum length of the total cable (with a maximum number of field
devices and worst-case positioning at the end of the cable) is as follows:
S560 m for DP/PA coupler (6ES7 157-0AC00-0XA0)
S680 m for DP/PA coupler (6ES7 157-0AD80-0XA0)
S790 m for DP/PA coupler Ex [i] (6ES7 157-0AD00-0XA0)
Tap Line
The maximum permitted tap line lengths are listed in Table 2-2. You should also
remember the maximum length of the total cable (see above).
2-18
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Topologies of SIMATIC NET PROFIBUS Networks
Table 2-2Tap Line Lengths for DP/PA Couplers
Number of tap lines
1 to 12max. 120 mmax. 30 m
13 to 14max. 90 mmax. 30 m
15 to 18max. 60 mmax. 30 m
19 to 24max. 30 mmax. 30 m
Maximum length of the tap line
DP/PA couplerDP/PA coupler Ex [i]
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2-19
Topologies of SIMATIC NET PROFIBUS Networks
2.5Connectivity Devices
2.5.1DP/DP Coupler
Uses
The PROFIBUS-DP/DP coupler is used to link two PROFIBUS-DP networks
together. Byte data (0 to 244 bytes) is transmitted from the DP master of a first
network to the DP master of another network and vice-versa.
This principle corresponds to the hardware wiring of inputs and outputs. The
coupler has two independent DP interfaces with which it attaches to the two DP
networks.
The DP/DP coupler is a slave attached to the DP networks. The data exchange
between the two DP networks involves internal copying within the coupler.
2-20
Figure 2-13DP/DP Coupler
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Design
Topologies of SIMATIC NET PROFIBUS Networks
The DP/DP coupler is installed in a compact, 40 mm wide casing.
The module can be installed (vertically when possible) on a standard rail with no
gaps being necessary.
The coupler is attached to each PROFIBUS-DP network via an integrated 9-pin
sub-D connector.
Master OP 25
2
Master
S7-400
SIEMENS
2
2
DP/DP COUPLER
Master
PG/PC/OP
Terminating resistor activated
2 LAN cable for PROFIBUS
Figure 2-14Configuration Example of the DP/DP Coupler
Master
S7-300
2
Slave
ET 200M
2
Slave
ET 200M
2
How the DP/DP Coupler Works
The DP/DP coupler permanently copies output data of one network to the input
data of the other network (and vice-versa).
Parameter Assignment
The PROFIBUS-DP addresses are set using two DIP switches on the top of the
device. The configuration is set using the GSD file and the configuration tool of the
attached PROFIBUS-DP master. The data length is set with the relevant
configuration tool.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2-21
Topologies of SIMATIC NET PROFIBUS Networks
2.5.2Connecting to PROFIBUS-PA
DP/PA Bus Coupling
The DP/PA bus coupler is the link between PROFIBUS-DP and PROFIBUS-PA.
This means that it connects the process control systems with the field devices of
the process automation (PA).
The DP/PA bus coupler is made up of the following modules:
SDP/PA Coupler Ex [i] (6ES7 157-0ADx0-0XA0)
SDP/PA Coupler (6ES7 157-0ACx0-0XA0)
SDP/PA Link IM 157 (6ES7 157-0AA80-0XA0)
To implement a DP/PA link in redundant operation, you also require the following:
SBus module BM IM 157 for 2 x IM 157 (6ES7 195-7HE80-0XA0)
SBus module BM DP/PA Coupler for 1 DP/PA Coupler (6ES7 195-7HF80-0XA0)
2-22
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2.5.3DP/PA Coupler
Figure 2-15 below illustrates how the DP/PA coupler is included in the system.
Process control
level
Industrial Ethernet
Topologies of SIMATIC NET PROFIBUS Networks
“Programming, Operating
and Monitoring”
SIMATIC PCS 7 or other
tool for parameter assignment
PDM or other tool for parameter assignment
Cell level
Field level
Figure 2-15Linking the DP/PA Coupler into the System
DP master
ET200X
PROFIBUS-DP
DP/PA coupler Ex [i]
Explosion-protected
area
Uses of the DP/PA Coupler
The DP/PA coupler is available in two versions:
SDP/PA coupler Ex [i]: You can attach all field devices certified for
PROFIBUS-PA and that are located within the hazardous area.
DP/PA coupler
PROFIBUS-PA
SDP/PA coupler: You can attach all field devices that are certified for
PROFIBUS-PA and that are outside the hazardous area.
The DP/PA coupler is an accompanying component according to EN 50014 or
EN 50020 and must be installed outside the hazardous area.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2-23
Topologies of SIMATIC NET PROFIBUS Networks
Properties of the DP/PA Coupler (General)
The DP/PA coupler has the following characteristics:
SElectrical isolation between PROFIBUS-DP and PROFIBUS-PA
SConversion of the physical transmission mechanism between RS-485 and IEC
61158-2
SDiagnostics using LEDs
STransmission rate on PROFIBUS-DP 45.45 Kbps
STransmission rate on PROFIBUS-PA 31.25 Kbps
SIntegrated power supply unit
Properties of the DP/PA Coupler Ex [i]
The DP/PA coupler Ex [i] (6ES7 157-0AD00-0XA0) has the following additional
characteristics:
SType of Protection EEx [ia] II C
SIntrinsic safety
SIntegrated, intrinsically safe power supply unit and integrated barrier
The DP/PA coupler Ex [i] (6ES7 157-0AD80-0XA0) has the following
characteristics that differ from the DP/PA coupler EX [i] (6ES7 157-0AD00-0XA0):
SType of protection EEx [ib] II C
SExtended environmental conditions (SIMATIC outdoor)
Configuring the DP/PA Coupler
SThe DP/PA coupler can be used in SIMATIC S5 and S7 and with all DP masters
that support 45.45 Kbps.
SThe DP/PA coupler does not need to be configured. You must only set the
transmission rate of 45.45 Kbps for the relevant DP network during
configuration.
You then configure the PA field devices just as normal DP slaves using the DP
configuration tool and the appropriate GSD file. You can configure the PA field
devices with SIMATIC PDM or with any other vendor-specific software
configuration tool.
2-24
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2.5.4DP/PA Link
Definition
The DP/PA link consists of the IM 157 and up to a maximum of five DP/PA
couplers. The DP/PA link is a DP slave at the PROFIBUS-DP side and a PA
master at the PROFIBUS-PA side.
Uses
With the DP/PA link, you have an isolated interconnection between PROFIBUS-PA
and PROFIBUS-DP with transmission rates of 9.6 Kbps to
12 Mbps.
The DP/PA link can only be used in SIMATIC S7.
Figure 2-16 below shows where the DP/PA link fits in.
Topologies of SIMATIC NET PROFIBUS Networks
Process control
level
S7-DP master
Gateway
S7-400
Cell level
Field level
Figure 2-16Location of the DP/PA Link
Industrial Ethernet
PROFIBUS-DP
ET200X
“Programming, Operating
and Monitoring”
SIMATIC PCS 7 or other
tool for parameter assignment
PDM or other tool for parameter assignment
DP/PA Link
DP/PA coupler
12 34 5
IM 157
PROFIBUS-PA
Field devices of PROFIBUS-PA
The DP/PA link must be installed outside the hazardous area.
The DP/PA link is configured with STEP 7, Version 4.02 or higher.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2-25
Topologies of SIMATIC NET PROFIBUS Networks
Properties
The DP/PA link has the following characteristics:
SDiagnostics with LEDs and the user program
SDP slave and PA master
SCan be operated at all transmission rates (9.6 Kbps to 12 Mbps)
SOnly DP/PA couplers can be operated with an IM 157
How the DP/PA Link Works
Figure 2-17 shows how the DP/PA link with the IM 157 and the DP/PA couplers
functions.
SThe DP/PA link maps the underlying PROFIBUS-PA system on a DP slave.
SWith the DP/PA link, PROFIBUS-DP is completely isolated from
PROFIBUS-PA.
SThe PA master and PA slaves form a separate, underlying bus system.
SThe number of DP/PA couplers simply reflects the amount of current required.
All DP/PA couplers along with the attached PA field devices form one common
PROFIBUS-PA bus system.
DP/PA Link
DP
IM 157
DP slave
DP/PA coupler
(max. 5)
S7 backplane bus
PA
PAPA
P A master
PA
2-26
Figure 2-17The DP/PA Link with DP/PA Couplers
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Rules
Topologies of SIMATIC NET PROFIBUS Networks
The following rules must be taken into account when extending PROFIBUS-PA:
SThere can be a maximum of 31 PA field devices in a PROFIBUS-PA system
SOnly one device supplying power (=DP/PA coupler) can be connected in a
physical PROFIBUS-PA segment.
SA maximum of 31 PA field devices can be attached to a DP/PA link. The
maximum number of attachable PA field devices per physical PROFIBUS-PA
segment or per DP/PA coupler is limited by the maximum output current of the
DP/PA coupler and the I/O data to be transferred.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2-27
Topologies of SIMATIC NET PROFIBUS Networks
2.5.5Connecting PROFIBUS-DP to RS-232C
Design
Figure 2-18DP/RS-232C Link for PROFIBUS-DP
The DP/RS-232C link consists of a compact 70 mm housing for standard rail
mounting. Ideally the module should be installed vertically. The modules can be
inserted one beside the other without gaps being necessary. The module is
attached to PROFIBUS-DP via a 9-pin sub-D female connector. The RS-232C
interface is implemented as a 9-pin sub-D connector.
2-28
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Uses
Topologies of SIMATIC NET PROFIBUS Networks
The PROFIBUS-DP/RS-232C link is a converter between an RS-232C (V.24)
interface and PROFIBUS-DP. Devices with an RS-232C interface can be linked to
PROFIBUS-DP with the DP/RS-232C link. The DP/RS-232C link supports the
procedures 3964 R and free ASCII protocol.
Master
S7-400
SIEMENS
Configuration
with STEP 7
PROFIBUS-DP
PROFIBUS
LAN cable
DP/RS-232C Link
Figure 2-19Example of a Configuration with DP/RS-232C Link
How the DP/RS-232C Link Works
The PROFIBUS-DP/RS-232C link is connected with the device over a
point-to-point connection. The PROFIBUS-DP/RS-232C link converts to the
PROFIBUS-DP protocol. Consistent data are transferred in both directions. A
maximum of 224 bytes of user data can be transferred per frame.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Device
RS-232C
Serial procedure
2-29
Topologies of SIMATIC NET PROFIBUS Networks
Parameter Assignment
The PROFIBUS-DP address can be set using two switches on the front panel. To
configure the unit, you use the GSD file and the configuration tool of the connected
device, for example STEP 7.
2.5.6 Connecting with the DP/AS-Interface Link 65
Design
Figure 2-20DP/AS-Interface Link 65
The DP/AS-interface link has a robust aluminum die-cast casing with the degree of
protection IP 65. In terms of water tightness, it complies with the standard
“Enclosures for Electrical Equipment UL 50, Type 4”, and is suitable for
temperatures from -25 °C to +60 °C. On the casing, there are diagnostic LEDs for
PROFIBUS-DP and the AS interface. The node address for PROFIBUS-DP can be
set using DIL switches or using an EEPROM. To set the address using the
EEPROM, you can use the ET 200 handheld. The DP/AS-interface link can be
installed anywhere and in any position. The attachment to PROFIBUS-DP is via a
12-pin round connector, the attachment to AS-interface is via a 4-pin modular
connector (M12 AS-interface attachment).
2-30
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Uses
Topologies of SIMATIC NET PROFIBUS Networks
The DP/AS-interface link connects the PROFIBUS-DP fieldbus with the
AS-interface. The DP/AS-interface link 65 can be connected to any
PROFIBUS-DP master capable of handling parameter assignment and diagnostic
frames with a length of 32 bytes. The DP/AS-interface link 65 allows the
actuator-sensor interface to be used as a subnet for PROFIBUS-DP. You can
therefore combine the advantages of PROFIBUS-DP and AS-interface in a
common bus system.
Field level networking with PROFIBUS-DP
External power supply
24 V DC
DP/AS-Interface Link 65
Passive modules
(without slave ASIC)
Active modules
(with slave ASIC)
AS-i power supply
Actuator/sensor
with slave ASIC
AS-i
cable
Figure 2-21Example of a Configuration with DP/AS-Interface Link 65
Branch
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2-31
Topologies of SIMATIC NET PROFIBUS Networks
How the DP/AS-Interface Link 65 Works
The DP/AS-interface link 65 links PROFIBUS-DP with the AS-interface with degree
of protection IP 65. The DP/AS-interface link 65 can be connected to any
PROFIBUS-DP master that can send parameter assignment frames with a length
of 32 bytes. To act as a connectivity device between the two bus systems, the
DP/AS-interface link has the functionality of an AS-interface master towards the
AS-interface and the functionality of a PROFIBUS-DP slave towards
PROFIBUS-DP. Up to 31 DP/AS-interface slaves can be attached to the
DP/AS-interface link. The DP/AS-interface link is therefore a modular slave with up
to 31 modules from the point of view of PROFIBUS-DP.
Parameter Assignment
Like all other components of the distributed I/O system ET 200, the
DP/AS-interface link is an integral part of STEP 7 and COM PROFIBUS. You can
display information about working with the parameter assignment software and
configuring at any time using the context-sensitive help.
2-32
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Topologies of SIMATIC NET PROFIBUS Networks
2.5.7Connecting with the DP/AS-Interface Link 20
Design
Figure 2-22DP/AS-Interface Link 20
The DP/AS-interface link 20 consists of a small, compact casing with degree of
protection IP20. The LEDs on the front panel indicate the following:
SAS-Interface statuses
SAttached and active slaves and their operability
SPROFIBUS slave address
SPROFIBUS bus errors and diagnostics
The DP/AS-interface link 20 also has a button with which the operating mode can
be changed, with which the existing configuration can be adopted and for setting
the PROFIBUS slave address.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2-33
Topologies of SIMATIC NET PROFIBUS Networks
Uses
The DP/AS-interface link 20 implements a small, cost-effective link between
PROFIBUS and AS-interface. The DP/AS-interface link 20 requires no additional
power supply, the power is supplied on the AS-interface cable. The AS-interface
segment can be started up without PROFIBUS-DP being in operation.
The DP/AS-interface link 20 is a PROFIBUS-DP slave (complying with EN 50170)
and AS-interface master in one unit and provides a simple link between
PROFIBUS-DP and the AS-interface. The DP/AS-interface link 20 allows system
attachment of the following:
SPROFIBUS-DP master, for example CP 342-5 for S7-300, CP 443-5 extended
for S7-400, CP 5431 FMS/DP or IM 308C for SIMATIC S5, CP 5412 (A2) for
PC or CP 5611/CP 5511 for PCs with DP-SOFTNET software.
SOther systems with DP master functionality
Field level networking with PROFIBUS-DP
AS-i power supply
Actuator/sensor
with slave ASIC
ADR
DP/AS-Interface
BF
Link 20
DIA
19
24
29
SF
4
14
23
28
APF
3
8
13
18
22
2
7
12
17
27
CER
AUP
1
6
11
16
21
26
31
CM
0910
15
20
25
30
5
6GK7 1415 2AA0
DP/AS-Interface Link 20
Passive modules
(without slave ASIC)
AS-i
cable
X 2
34
Active modules
(with slave ASIC)
Branch
Figure 2-23Example of a Configuration with DP/AS-Interface Link 20
2-34
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
How the DP/AS Interface Link 20 Works
With the DP/AS-interface link 20, up to 248 binary elements are accessible to a DP
master on the AS-interface (124 inputs and 124 outputs). You can therefore
combine the advantages of PROFIBUS-DP and AS-interface in a plant. The
DP/AS-interface link 20 can be used in the AS-interface standard mode (M2). In
this mode, the data bits of the slaves are accessible. The following master calls are
supported.
SChange address
SWrite parameters
SRead configuration data
SSet configuration mode
SConfigure actual configuration
Parameter Assignment
The DP/AS-interface link 20 is supported by STEP 7 (V4.1 and higher) and COM
PROFIBUS (V 3.2 and higher). The type and GSD files are shipped along with the
manual. On the AS-interface side, no special configuration is necessary; the
AS-Interface segment can be put into operation without PROFIBUS.
Topologies of SIMATIC NET PROFIBUS Networks
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2-35
Topologies of SIMATIC NET PROFIBUS Networks
2.5.8Connecting PROFIBUS-DP to instabus EIB
Design
Uses
Figure 2-24DP/EIB Link
The DP/EIB link allows a connection between the two open standard systems for
industrial automation PROFIBUS-DP and building automation instabus EIB. This
provides an ideal connection between the high performance of the PROFIBUS
components and the extreme flexibility of the instabus EIB system.
The DP/EIB link is a DP slave (complying with EN 50170) and at the same time a
node on the instabus EIB.
The displays and operating controls are as follows:
SLED for EIB bus errors
SLED for PROFIBUS bus errors
SLED for power supply OK
SCoding switch for the PROFIBUS address
SProgramming button for EIB.
The DP/EIB link can be used wherever PROFIBUS or instabus EIB is used; in
other words, a distinction can be made between two areas of application:
2-36
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Building Automation
In other words, we are assuming that instabus EIB exists and that you want to
use, for example, an S7 PLC for administrative control tasks or, for example, an
HMI system for central operator control and monitoring. The main emphasis here
is in offices or apartment blocks etc.
The simplest option for connecting these systems to instabus EIB is provided by
the DP/EIB link since these systems generally access the peripheral devices via
PROFIBUS.
The main areas of application are as follows:
S(Primary) open-loop control, closed-loop control and monitoring of heating
systems
SVentilation, air-conditioning, and
SEnergy management and optimization
Industrial Automation
Topologies of SIMATIC NET PROFIBUS Networks
In this case, we assume that PROFIBUS exists and that you would like to include
the electrical components of an assembly line, plant or production building in the
automation. The main emphasis here is the equipment of industrial buildings
themselves.
Applications include, for example, the following:
Slighting control
Sshutter control,
Smeasurement of temperature, wind strength, or the position of the sun,
Sdoor control and
Sbuilding access controls.
The instabusEIB is specifically designed for such tasks and provides a wide
selection of components and a large network span (maximum 1000 m per bus). Up
to 11,520 instabus EIB devices are possible in one network (a maximum of 15
areas each with a maximum of 12 buses each with up to 64 nodes).
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2-37
Topologies of SIMATIC NET PROFIBUS Networks
Step 7 or COM PROFIBUS
EIBRS-232
interface
S7-300ET 200S
PROFIBUS
ET 200M
instabus EIB
ETS2
+
Figure 2-25 Example of a System Structure using DP/EIB Link
How the DP/EIB Link Works
The data objects of the instabus EIB are mapped in the PROFIBUS I/O area.
The structuring of the PROFIBUS slave I/O area and the number of EIB data
objects with which the DP master communicates is decided by a selectable profile.
In total, five different profiles are available that allow the user to adapt the DP/EIB
link to the relevant application and to make optimum use of the memory resources
of the DP master.
You configure the system (in other words set a profile) via PROFIBUS using, for
example STEP 7 or COM PROFIBUS. The number of data objects specified by the
selected profile can be assigned to the required instabus EIB components with the
instabusEIB configuration software ETS 2.
Due to the database entry of the DP/EIB link, the instabus EIB configuration
software ETS 2 is capable of displaying the number and data type of the valid
instabusEIB data objects to the user. This allows a simple error-free assignment to
be made. Following configuration, the PROFIBUS-DP master can both write and
read the instabus EIB data objects.
Siemens
EIB product database
2-38
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Configuring
Topologies of SIMATIC NET PROFIBUS Networks
The link module can be configured as a DP slave, for example with the standard
tools STEP 7 or COM PROFIBUS and on the instabus EIB using the configuration
software ETS 2.
SDP
A GSD file is supplied with the manual. The DP slave address is set with a
coding switch on the DP/EIB link.
Sinstabus EIB
The database entry of the DP/EIB link for instabus EIB configuration software
ETS 2 is supplied with the DP/EIB manual.
For further details, refer to the DP/EIB link manual.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
2-39
Topologies of SIMATIC NET PROFIBUS Networks
2-40
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Configuring Networks
Configuring Networks
3
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
3-1
Configuring Networks
3.1Configuring Electrical Networks
PROFIBUS Networks
PROFIBUS networks were specially designed for use in an industrial environment
and one of their main features is their degree of immunity to electromagnetic
interference resulting in high data integrity. To achieve this degree of immunity,
certain guidelines must be adhered to when configuring electrical networks.
Parameters
The following parameters must be taken into account when planning an electrical
network:
SThe transmission rate required for the task
(within a network, only one uniform transmission rate can be used)
SThe required number of nodes
SThe type of network components required (bus terminals, bus connectors,
connecting cables)
SThe LAN cables to be used
SThe required segment lengths
SThe electromagnetic and mechanical environment of the cabling (for example
surge voltage protection, cable route)
SThe number of RS-485 repeaters between any two DTEs is limited to a
maximum of 9
SIncreasing the overall span of a network by using repeaters can lead to longer
transmission times that may need to be taken into account when configuring the
network (see Section 3.3).
Cable Termination
Regardless of the transmission rate, the ends of all segments must be terminated
by activating the terminating resistor in the connector. After the terminating resistor
has been activated, no further cable sections are permitted.
The terminating resistor is only effective when it is supplied with voltage. This
means that the corresponding DTE or the RS-485 repeater must be supplied with
power. As an alternative, the PROFIBUS terminator can be used as a permanent
terminating resistor.
3-2
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Configuring Networks
Note
The power supply to terminating resistors must not be interrupted by turning off
the DTE or repeater or by unplugging the bus connector or tap line. If the power
supply to the terminating resistors cannot be guaranteed, the PROFIBUS
terminator must be used.
3.1.1Segments for Transmission Rates up to a Maximum of 500 Kbps
Transmission Rates up to a Maximum of 500 Kbps
The following maximum segment lengths can be implemented with the SIMATIC
NET PROFIBUS LAN cables:
Table 3-1 Possible Segment Lengths
Segment Length for Cable Type
Transmission Rate
in Kbps
9.61000 m900 m
19.21000 m900 m
45.451000 m900 m
93.751000 m900 m
187.51000 m700 m
500 400 m 400 m
– FC Standard Cable
– FC Robust Cable
– FC FRNC Cable
– FC Food Cable
– FC Underground Cable
– SIENOPYR–FR Marine Cable
The maximum permitted number of bus attachments (DTEs, repeaters, OLMs,
BT12 M,...) to one segment is 32.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
3-3
Configuring Networks
Length of the Tap Lines
If you do not attach the LAN cable directly to the bus connector (for example,when
using a PROFIBUS bus terminal), you must take into account the maximum
possible tap line length!
The following table shows the maximum permitted lengths of tap lines per bus
segment:
Table 3-2Lengths of the Tap Lines per Segment
Transmission
rate
Max. length of the tap
lines per segment
Number of nodes with tap line
length of ...
1.5 m or 1.6 m3 m
9.6 –93.75 Kbps96 m3232
187.5 Kbps75 m3225
500 Kbps30 m2010
3.1.2Segments for a Transmission Rate of 1.5 Mbps
Transmission Rate 1.5 Mbps
The following maximum segment length can be implemented with the SIMATIC
NET PROFIBUS LAN cable:
Table 3-3 Possible Segment Lengths
Segment Length for Cable Type
Transmission Rate
in Kbps
1.500 200 m 200 m
– FC Standard Cable
– FC Robust Cable
– FC FRNC Cable
– FC Food Cable
– FC Underground Cable
– SIENOPYR–FR Marine Cable
Each attachment of a node to the LAN cable represents a capacitive mismatch that
has no effect at lower transmission rates. At a transmission rate of 1.5 Mbps,
however, problems can arise due to these mismatches if the following guidelines in
terms of type, number and distribution of node attachments are not adhered to.
3-4
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Configuring Networks
Value Factors
To be able to define permitted configurations, a method is necessary with which
the attached components can be evaluated in terms of their capacitive bus load.
This is achieved by assigning value factors to the components
(see Table 3-4 ).
PROFIBUS interfaces implemented as 9-pin sub-D female connectors (CPs,
OLMs...), do not have their own value factors. These are already taken into
account in the values listed in the table.
Table 3-4Values for Segments at 1.5 Mbps
Product NameV alue (V)
Bus terminal with 1.5 m long tap line
(Order no. 6GK1 500-0AA00, Version 2)
Bus terminal with 1.5 m long tap line, with PG interface
(Order no. 6GK1 500-0DA00, Version 2)
Bus terminal with 3.0 m long tap line
(Order no. 6GK1 500-0BA00, Version 2)
Bus connector with 30° cable outlet
(Order no. 6ES7 972-0BA30-0XA0)
Bus connector with axial cable outlet (Order no.: 6GK1 500-0EA02)
Bus connector with axial cable outlet for FastConnect system (Order no.: 6GK1 500-0FC00)
Bus connector with 90° cable outlet (Order no.: 6ES7 972-0BA11-0XA0)
Bus connector with 90° cable outlet with PG interface (Order no.: 6ES7 972-0BB11-0XA0)
Bus connector with 90° cable outlet for FastConnect system (Order no.: 6ES7
972-0BA50-0XA0)
Bus connector with 90° cable outlet with PG interface (Order no.: 6ES7 972-0BB50-0XA0)
Bus connector with 35° cable outlet (Order no.: 6ES7 972-0BA40-0XA0)
Bus connector with 35° cable outlet with PG interface
(Order no.: 6ES7 972-0BB40-0XA0)
Bus terminal BT12M (Order no. 6GK1500-0AA10) 0.1
RS-485 repeater (attachment of bus segments) (Order no. 6ES7 972-0AA01-0XA0)0.1
PROFIBUS terminator (active RS-485 attachment element)
(Order no. 6ES7 972-0DA01-0AA0)
SIMATIC S5/S7 connecting cable for 12 Mbps PG attachment to PROFIBUS-DP (Order
no.: 6ES7 901-4BD00-0XA0)
1.5
1.5
2.5
0.7
0.1
0.1
0.5
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
3-5
Configuring Networks
Rules
At a transmission rate of 1.5 Mbps, the following rules apply to the permitted
number of nodes and their distribution/layout on a SIMATIC NET PROFIBUS
segment:
1. The maximum permitted number of nodes on any segment is 32.
2. The sum of the values of all the connection elements in a segment must be
≤ 25.
3. The rules for the distance between adjacent connection elements are as follows
(distance in this case is the length of the LAN cable):
3.1 If the distance between adjacent connection elements is greater than
3.2 If the distance between adjacent connections elements is greater than the
10 m, the values of the connection elements can be ignored.
sum of the two values of the elements in meters, the layout is not
critical and no additional conditions need to be taken into account.
The value of the PG connecting cable, SIMATIC S5/S7 connecting cable
12 Mbps must be added to the value of the corresponding
connection element.
3.3 If the minimum clearance described in 3.2 is not kept to, this results in
a group being formed and the following additional conditions must be met:
– Attachment elements can be arranged as close to each other as
required providing the sum of their values does not exceed the value 5.
– The distance in meters between two adjacent groups must be at least
as large as the sum of the values of the two groups.
3-6
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Table 3-5Examples Illustrating the Configuration Rules
Configuring Networks
No special conditions if the length of the LAN cable
between two DTEs > 10 m
No special conditions if the length of the LAN cables between two DTEs is greater than the sum of
values of both DTEs.
If a bus terminal or a bus connector has a PG interface, a connected PG connecting cable must be
taken into account when calculating the values.
Take the values of a group into account if the sum
of the values is greater than the LAN cable between the DTEs.
Elements can be close to each other providing the
total value of a group does not exceed 5.
LAN cable > 10 m
> 10 m
S7-400
S7-300
Bus cable, e.g. 5 m
V = 1.5 + 1.0 + 0.1 = 2.6
5 m > 2.6 m (sum of the values in
meters)
S7-400
V = 1.0
5 m
V = 1.5
V = 0.1
S7-300
LAN cable e.g. 0.5 m group
V = 1.5 + 1.5
0.5 m < 3 m ⇒ group formed ⇒ sum of the values ≤ 5
S7-400
S7-400
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
V = 1.5
0.5 m
V = 1.5
3-7
Configuring Networks
3.1.3Segments for Transmission Rates up to a Maximum of
12 Mbps
Transmission Rate up to a Maximum of 12 Mbps
Table 3-6Possible Segment Lengths
Segment Length for Cable Type
Transmission Rate
in Mbps
3100 m100 m
6100 m100 m
12100 m100 m
– FC Standard Cable
– FC Robust Cable
– FC FRNC Cable
– FC Food Cable
– FC Underground Cable
– SIENOPYR–FR Marine Cable
When planning segments for transmission rates from 3 Mbps to a maximum of 12
Mbps, the following factors must be taken into account:
STo attach DTEs to bus segments, only the bus connectors permitted for 12
Mbps or the BT12M bus terminal can be used.
SThe maximum length of a segment must not exceed 100 m.
SThe maximum number of bus attachments (nodes, OLMs, RS-485 repeaters,...)
in one segment is restricted to 32.
STo attach a programming device or PC via a tap line, only the “SIMATIC S5/S7
connecting cable, 12 Mbps, order no. 6ES7901-4BD00-0XA0” can be used.
Note
If several bus connectors are used at electrically short distances (in other words,
the cable length between adjacent connectors is less than 1 m) (for example,
several slaves in one cubicle), avoid disconnecting several bus connectors at the
same time for longer periods. Disconnecting more than one bus connector does
not necessarily mean errors but may well reduce the reliability (immunity to noise)
of a segment.
3-8
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Configuring Networks
3.1.4Configuring Electrical Networks with RS-485 Repeaters
RS-485 Repeater
To increase the number of nodes (>32) in a network or to extend the cable length
between two nodes, segments can be connected together using RS-485 repeaters
to form a network. Figure 3-1 illustrates how several segments can be connected
together with repeaters to create a network.
The RS-485 repeaters support all transmission rates from
9.6 Kbps to 12 Mbps.
S7-300
ET200S
OP 25
OP 25
ET200M
OP 25
S7-300
RS-485
repeater
S7-300
OP 25
OP 25
PG
ET200M
ET200S
OP 25
Terminating resistor activated
Figure 3-1Layout of an Electrical PROFIBUS Network Using RS-485 Repeaters
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
3-9
Configuring Networks
Configuring
When configuring an electrical network with RS-485 repeaters, the following
conditions must be taken into account:
SThe maximum segment length for the transmission rate must be adhered to
(see Table 3-1, Table 3-3, Table 3-6,)
SThe maximum number of bus attachments (nodes, OLMs, RS-485 repeaters,...)
in one segment is restricted to 32. There may be further restrictions at a
transmission rate of 1.5 Mbps (see Section 3.1.2).
SThe maximum number of nodes in one network is limited to 127.
SA maximum of 9 RS-485 repeaters can be installed between two nodes.
3-10
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
3.2Configuring Optical Networks
Configuration Parameters for Optical Networks
When configuring optical PROFIBUS networks, the following parameters must be
taken into account:
SUsing fiber-optic cables, only point-to-point links can be established.
SThe maximum signal attenuation of the transmission path (the power budget)
must be within the permitted values.
SThe minimum or maximum permitted transmission rates of the components
(only one uniform transmission rate can be used in a network).
SThe cascading rules for the components used.
SThe maximum permitted number of nodes in the network.
SIn large-span networks, the transmission delay time.
Configuring Networks
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
3-11
Configuring Networks
3.2.1How a Fiber-Optic Cable Transmission System Works
Introduction
This section describes the structure and functions of an optical transmission
system. The information here will help you to understand the rules for calculating
the optical power budget in the next section.
Transmission Path
An optical transmission path consists of a transmitter, the optical fiber, and a
receiver.
Power supply
Signal
converter
Electr . signal
(digital/analog)
Figure 3-2Structure of a Link
E / O
converter
Transmitter
The transmitter in an optical digital transmission system consists of a signal
converter that converts the digital signals from the electronics in to a pulse type
suitable for the electro-optical converter, and an electro-optical converter (E/O
converter) that converts the electric pulses to optical signals. In SIMATIC NET
PROFIBUS, LEDs (LED = Light Emitting Diode) are used as E/O converters. The
LEDs are specially adapted to the various transmission media.
For more detailed information about the various fiber-optic cables for SIMATIC
NET PROFIBUS, refer to Chapter 7.
3-12
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Receiver
Attenuation
Configuring Networks
The receiver of a digital optical transmission system consists of an optoelectric
converter (a photodiode), that converts the optical signals to electrical signals and
a signal converter that converts the electrical pulses received from the diode into
signals compatible with the connected electronics.
The attenuation of the transmission path is determined by the following factors:
SThe choice of optical fiber
SThe wavelength of the transmit diodes
SThe type of connector
SWith glass optical fibers, the number of splices (including repair splices)
SThe length of the optical fiber (cable length)
SThe link power margin on the link (for example for aging and temperature
dependency of the LEDs and photodiodes).
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
3-13
Configuring Networks
3.2.2Optical Power Budget of a Fiber-Optic Transmission System
Optical Power Budget
Transmitter
The transmitted optical power P
and the received optical power P
out
rec
are
specified in dBm, the attenuation caused by connectors and the fiber is specified in
dB.
dBm is a reference unit and describes the logarithmic ratio of the power level to the
reference power P0=1mW. The following formula applies:
Px [in dBm] = 10*log(Px [in mW] / P0)
Examples:
Transmitter Power PxTransmitter Power as Logarithmic Power
10 mW
1 mW
1
µW
Ratio Px to P
o
+ 10 dBm
0 dBm
– 30 dBm
Depending on the fiber being used, the minimum and maximum optical power that
can be coupled into a fiber is specified. This power is reduced by the attenuation of
the connected transmission path resulting from the fiber itself (length, absorption,
scattering, wavelength) and the connectors used.
Receiver
3-14
The receiver is characterized by its optical sensitivity and its dynamic range. When
configuring an optical link, you should make sure that the power reaching the
receiver does not exceed its dynamic range. If the power falls below the minimum,
this increases the bit error rate (BER) due to the signal-to-noise ratio of the
receiver. If the maximum received power is exceeded, saturation and overload
effects increase pulse distortion and therefore also increase the bit error rate.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Power Budget
The power budget of an optical link not only takes into account the attenuation in
the fiber itself, temperature and aging effects but also the attenuation values of the
connectors and splices and therefore provides exact information about whether or
not an optical link can be implemented. The starting point for calculating the
maximum transmission path length is the minimum transmitter power that can be
coupled into the fiber type. To simplify matters, the budget is calculated in dBm and
dB.
The following is subtracted from the minimum transmitter power:
Configuring Networks
SThe attenuation of the fiber a
SThe input power required at the receiver
The coupling losses at the send and receive diodes are already taken into account
in the information about the transmitter power and receiver sensitivity.
Plastic and PCF FO Cables
Plastic and PCF FO cables can only be used on short distances due to their
relatively high fiber attenuation. They are installed in one piece. Fiber-optic
connections with couplers or splices should not be considered since they further
reduce the distance that can be covered.
The maximum permitted cable lengths are listed in Tables 3-7 and 3-8.
Glass FO Cables
Glass FO cables can span distances in the kilometer range. It is often not possible
to install cables over such distances in one piece. The fiber-optic path must then
be put together in cable sections.
The couplers or splices where the sections are joined always involve certain
attenuation losses.
With transmission paths using glass fibers, the following aspects must also be
taken into account:
[in dB/km or dB/m] (see manufacturers data)
FOC
SThe attenuation of splices
SThe attenuation of connectors
SWhen calculating the power budget, a link power margin of at least 3 dB (at a
wavelength of 860 nm) or at least 2 dB (at a wavelength of 1300 nm) must be
maintained.
Splices
Along with the splices, future repair splices must also be taken into account.
Depending on the route of the cables and the risk of mechanical damage, one or
more future repairs (approximately 1 per 500 m) should also be included in the
budget. A repair always means two splices since a new section of cable must be
inserted (the length depending on the accuracy of the test equipment).
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
3-15
Configuring Networks
Link Power Margin
When calculating the power budget, a link power margin of at least 3 dB (at a
wavelength of 860 nm) or at least 2 dB (at a wavelength of 1300 nm) must be
maintained.
If the link power margin calculated is lower, the transmission path will not be
reliable in its currently planned form. This means that the transmission path may
well function when it is first started up since components are normally better than
their rated performance (particularly when brand new) but due to aging,
replacement of components as a result of repairs and changing environmental
conditions, the bit error rate will tend to rise to an unreliable level the longer the
equipment is in use.
Note
To avoid possible errors during the installation of the transmission path, when
installing glass fibers, the installed sections must be tested during installation and
the measured values logged (see Section A-2 “Testing FO Transmission Paths”).
Work Sheet
Section 3.2.4 of this manual contains a work sheet for calculating the power budget
of glass fiber-optical links.
3-16
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
3.2.3Cable Lengths for Plastic and PCF FO Paths
The length of the transmission path on fiber-optic cables is not dependent on the
transmission rate.
Each node on the optical PROFIBUS network has repeater functionality so that the
following distance information relates to the distance between two adjacent,
interconnected PROFIBUS nodes.
The maximum cable length between two PROFIBUS nodes depends on the type
of fiber-optic cable used and the optical network components.
Table 3-7Permitted Cable Lengths with Integrated Optical Interfaces or OBT
Configuring Networks
Fiber-optic cable
SIMATIC NET
PROFIBUS
Plastic fiber-optic,
duplex cord
Plastic fiber-optic,
standard cable
PCF fiber-optic,
standard cable
Table 3-8Permitted Cable Lengths in an OLM Network
Fiber-optic cable
SIMATIC NET
PROFIBUS
Plastic fiber-optic,
duplex cord
Plastic fiber-optic,
standard cable
PCF fiber-optic,
standard cable
Maximum cable
lengths between two
nodes (in m)
501550
501550
3009300
Maximum cable
lengths between two
nodes (in m)
501550
802480
40012400
For 1 Network (= 32
nodes) (in m)
For 1 Network (= 32
nodes) (in m)
Note
SOptical buses can contain max. 32 integrated optical interfaces in series.
SSeveral buses of up to 32 integrated optical interfaces can only be linked
via OBTs (optical repeaters).
SIn optical networks (bus, star, ring) containing only OLMs, the number of
OLMs is limited to 122.
SThe number of all optical components (integrated interfaces, OBTs,
OLMs) in the optical PROFIBUS network must be specified in the
configuration tool as the “Number of OLM, OBT” parameter (see Section
3.3). This number must not exceed 122.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
3-17
Configuring Networks
Mixing Plastic Fiber-Optic and PCF Fiber-Optic
To make the best use of the different cable lengths, the plastic fiber-optic cables
and PCF fiber-optic cables can be mixed.
For example, connection between distributed local DP slaves using plastic
fiber-optic (distances t 50 m) and connection between DP master to the first DP
slave of the bus topology with PCF fiber-optic (distance u 50 m).
3.2.4Calculating the Power Budget of Glass Fiber Optical Links with
OLMs
Calculation Examples
The following work sheets show typical calculations of the power budget for
SIMATIC NET PROFIBUS glass optical fibers, one with OLM/G11, OLM/G12 at a
wavelength of 860 nm and one with OLM/G11-1300 and OLM/G12-1300 at a
wavelength of 1300 nm.
Note
Please note that the information on fiber attenuation in the data sheets and type
specifications of fiber-optic cables are based on measurements with narrow-band
laser light sources exactly adapted to the wavelengths.
The LED transmission elements used in practice produce a wider band spectrum
whose mid frequency deviates slightly from the measured wavelength.
You should therefore use the following attenuation values on all connections with
SIMATIC NET multimode glass fiber-optic cable between SIMATIC NET
PROFIBUS components:
3.5 dB/km at 860 nm
1.0 dB/km at 1310 nm
Note
The following distances between two OLMs must not be exceeded regardless of the
optical power budget:
OLM/P11, OLM/P12400 m
OLM/G11, OLM/G12, OLM/G12-EEC3 km
OLM/G11-1300, OLM/G12-130015 km
3-18
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Power budget for OLM/G11, G12 for a point-to-point link with the wavelength
λ = 860 nm
Attenuation on the cable
Fiber type
Attenuation
a
FOC
62.5/125 µm3.5 dB/km2.85 kmL* a
Cable length L
=10.0 dB
FOC
Attenuation for connectors
a
Conn
Number
0.4 dB 1Number *
a
Conn
Attenuation caused by splices+
a
Spl
0.2 dB 3Number * a
Number
Spl
Configuring Networks
+
+
0.4 dB
0.6 dB
Attenuation of the transmission patha
Characteristic data of the OLM/G11, G12
maximum power coupled into 62.5/125 µm fiber
P
out, min
–13 dBm
Receiver sensitivity
Prec
, min
–28 dBm
Maximum permitted attenuationa
Link power margina
The transmission path can be implemented as planned.
=11.0 dB
Path
max
max
= P
– a
– P
out, min
= 4.0 dB
Path
= 15.0 dB
rec, min
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
3-19
Configuring Networks
Power Budget for OLM G11-1300, G12-1300 for One Point-to-Point
Link at Wavelength
Attenuation on the cable
Fiber type
62.5/125 µm1.0 dB/km9 kmL* a
Attenuation for connectors
a
Conn
1 dB 0Number *
Attenuation caused by splices+
a
Spl
0.2 dB 5Number * a
λ = 1310 nm
Attenuation
a
FOC
Number
Number
Cable length
L
a
Conn
=9.0 dB
FOC
+
+
Spl
0 dB
1.0 dB
Attenuation of the transmission patha
Data of the OLM/G11-1300, G12-1300 power that
can be coupled into 62.5/125 µm fibers
P
out, min
–17 dBm
Receiver sensitivity
Prec
, min
–29 dBm
Maximum permitted attenuationa
Link power margina
The transmission path can be implemented as planned.
Note
The maximum length of fiber-optic cable that can be supplied in one piece depends on the
cable type but is approximately 3 km per drum. Longer links must therefore be put together
using more than one piece of cable. To connect the sections of cable, coupling elements or
splices must be used reducing the maximum possible cable length due to their attenuation.
=10.0 dB
Path
max
max
= P
– a
– P
out, min
= 2 dB
Path
= 12 dB
rec, min
3-20
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Configuring Networks
Blank form for a power budget using OLMs
Attenuation for the OLM/G11, G12, G11-1300 or G12-1300 for one point-to-point link with wavelength λ
=
Attenuation on the cable
Fiber type
( µm )
Attenuation
a
in dB/km
FOC
Attenuation of connectors
(dB)Number
a
Conn
Attenuation caused by splices
(dB)Number
a
Spl
Cable length L
in km
L* a
= dB
FOC
Number *
a
Conn
Number * a
+
Spl
dB
dB
Attenuation of the transmission patha
Power that can be coupled
into µm fiber
P
(dBm)
out, min
Receiver sensitivity
, min
Prec
(dBm)
Maximum permitted attenuationa
Link power margina
=dB
Path
max
max
= P
– a
– P
out, min
= dB
Path
= dB
rec, min
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
3-21
Configuring Networks
3.3Transmission Delay Time
The system reaction time of a PROFIBUS network depends largely on the
following:
SThe type of system being used (single or multiple master system)
SThe maximum reaction time of the individual nodes
SThe amount of data to be transmitted
SThe bus configuration (topology, cable lengths, active network components)
The bus parameters are adapted (configured) to the particular PROFIBUS network
using configuration software such as COM PROFIBUS or STEP 7.
Using optical link modules, extremely large PROFIBUS networks can be created.
These allow the use of long optical fiber links and the cascading of large numbers
of components. Each time the data packet passes through an OLM there is a
delay.
Due to the delays caused by cables and network components and the monitoring
mechanisms in the network components, the PROFIBUS network parameter “Slot
Time” must be adapted to the network span, the network topology and the
transmission rate.
3-22
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
3.3.1Configuring Optical Buses and
Star Topologies with OLMs
Creating a System Overview
You configure the PROFIBUS network, for example with SIMATIC STEP 7. The
bus-specific configuration begins with the creation of the system overview in the
hardware configuration dialog “HW Config” of STEP 7 (V5.0).
Configuring Networks
Figure 3-3“HW Config” Dialog in STEP 7 (V5.0)
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
3-23
Configuring Networks
Setting the PROFIBUS Properties
In the “Properties – PROFIBUS” dialog, you can set the highest station address
(HSA), the transmission rate and the bus profile.
Figure 3-4”Properties – PROFIBUS” Dialog
3-24
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Entering the Cabling Configuration
You can make the settings for the cabling configuration (number of OLMs, cable
length) in the “Cables” tab under “Options”.
Configuring Networks
Figure 3-5“Options” –> “Cables” Tab
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
3-25
Configuring Networks
Checking the Bus Parameters
Based on the entries made, the configuration tool can check whether the slot time
is feasible in the selected communication profile. If the system would exceed the
value, due to the additional delays of OLM and FO cables, the parameters are
adapted. The newly calculated bus parameters are displayed in the “Bus
Parameters” dialog.
Figure 3-6Bus Parameters Adapted to the System
3-26
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Configuring Networks
3.3.2Configuring Redundant Optical Rings with OLMs
The following configuration conditions must be satisfied in redundant optical rings:
1. Configuration of a Non-Existent Node
2. Raising the retry value to at least the value 3
3. Checking and adaptation of the slot time
To set the parameters under point 2. and 3., use the user-specific profile of the
configuration tool. There is an example of adopting the bus parameters in STEP 7
at the end of this section.
Configuration of a Non-existent Node
The value of the HSA (Highest Station Address) parameter must be set on all
DTEs so that there is at least one address in the network between bus address 0
and the value of HSA that is not used by a node; in other words, there is an
address gap. You can obtain this address gap simply by increasing the value of the
HSA parameter by one higher than the highest node address in the network.
Note
If this condition is not or is no longer satisfied, the optical bus will no longer close
to form redundant optical ring following segmentation. The fault message (LED
and signaling contact) of the two OLMs affected is not canceled even after the
fault has been eliminated.
Raising the Retry Value to at Least the Value 3
If a fault occurs requiring a switchover to the redundant system (for example wire
break), there is a switching time during which correct data transmission is not
possible. To ensure a “bumpless” switchover for the application, it is advisable to
set the number of frame retries on the PROFIBUS master to at least 3.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
3-27
Configuring Networks
Checking and Adapting the Slot Time
To allow a “bumpless” return from the optical bus to the optical ring after the fault
has been eliminated, there must be no frame on the network at the switch-back
time. The network is briefly free of frames when a master addresses a device
whose address is configured but does not actually exist.
The master waits for a response until the configured slot time has elapsed. The
OLM recognizes this frame–free state and closes the optical bus in the middle of
this query sequence to form the optical ring again.
The slot time must be set to approximately twice the value you would use in a
non-redundant network.
Calculate the slot time according to the following formula:
Slot time = a + (b x length
) + (c x number
FOC
OLM
)
Slot timeis the monitoring time in bit times
Length
FOC
is the sum of all FO cables (segment lengths) in the network.
The lengths must be specified in km.
Number
OLM
is the number of PROFIBUS OLMs in the network
The factors a, b and c depend on the transmission rate and can be found in Tables
3–9 and 3–10.
3-28
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Table 3-9 Constants for Calculating the
Slot Time with DP Standard
(redundant optical ring)
Configuring Networks
Transmission
abc
rate
12 Mbps1651 24028
6 Mbps951 12024
3 Mbps551 6024
1.5 Mbps351 3024
500 Kbps251 1024
187.5 Kbps171 3.7524
93.75 Kbps171 1.87524
45.45 Kbps851 0.90924
19.2 Kbps171 0.38424
9.6 Kbps171 0.19224
Table 3-10 Constants for Calculating the
Slot Time with DP/FMS (”Universal”) and DP
with S5–95U (redundant optical ring)
Transmission
abc
rate
12 Mbps1651 24028
6 Mbps951 12024
3 Mbps551 6024
1.5 Mbps2011 3024
500 Kbps771 1024
187.5 Kbps771 3.7524
93.75 Kbps451 1.87524
45.45 Kbps851 0.90924
19.2 Kbps181 0.38424
9.6 Kbps171 0.19224
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
3-29
Configuring Networks
Note
The slot time calculation takes into account only the optical network and the
attachment of nodes to the OLM in each case via a maximum 20 m long RS-485
bus segment. Longer RS-485 bus segments must be included by adding them to
the length
With the OLM/G11-1300 and OLM/G12-1300, the minimum slot times shown in the
following table must be maintained at transmission rates of 12 Mbps, 6 Mbps, 3
Mbps and 1.5 Mbps.
Table 3-11 Minimum Slot Time for
.
FOC
OLM/G11-1300 and OLM/G12-1300
Transmission rateMinimum slot
time
12 Mbps3800 t
6 Mbps2000 t
3 Mbps1000 t
1.5 Mbps530 t
Bit
Bit
Bit
Bit
When configuring the slot time, use the minimum slot time as shown in Table 3-11
if the calculated slot time is less than the minimum slot time.
Note
If the slot time is configured with a value that is too low, this can lead to
malfunctions and error displays on the OLM. The system LED flashes red/green.
3.3.3Example of Configuring the Bus Parameters in STEP 7
Structure of the Network Example
The example assumes a redundant optical ring with the following structure:
S20 OLM G12 modules in the redundant optical ring
S20 km total ring length
STransmission Rate 1.5 Mbps
SNodes attached directly to OLMs
S“PROFIBUS-DP” bus protocol
3-30
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Calculation of the Slot Time
For the transmission rates of 1.5 Mbps selected in the example, Table 3-9 lists the
following values
a = 351
b = 30
c = 24
On this basis, the slot time is calculated as follows:
Slot time = 351 + (30 x 20) + (24 x 20) = 1431
Entering the Bus Parameters
This means that the following three bus parameters must be entered for the
example:
Slot time (T_slot_Init) = 1431
Retries (Retry_Limit) = 3
Highest station address (HSA)= 126 (default)
Configuring Networks
These values are entered in STEP 7 in the “Bus Parameters” dialog for the
“User-Defined” bus profile.
You must then trigger the recalculation of the bus parameters with the
“Recalculate” button.
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
3-31
Configuring Networks
Note
Since the formula includes the delays of all fiber-optic and RS-485 cables, the
“Consider Cable Configuration” check box must not be activated in the “Cables”
tab on the “Options” dialog.
Figure 3-7“Bus Parameters/User-Defined” Dialog in STEP 7 (V5.0)
3-32
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Passive Components for RS-485 Networks
4
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
4-1
Passive Components for RS-485 Networks
4.1SIMATIC NET PROFIBUS Cables
PROFIBUS Cables
A variety of SIMATIC NET PROFIBUS cables are available allowing optimum
adaptation to a variety of environments.
All the information about segment lengths and transmission rates refer only to
these cables and can only be guaranteed for these cables.
Notes on Installing RS-485 LAN Cables
LAN cables are impaired by mechanical damage. How to install LAN cables
correctly is described in detail in Appendix C.
To make it easier to measure the length of cables, they have a marker every
meter.
Overview
Table 4-1 is an overview of the LAN cables for PROFIBUS showing their
mechanical and electrical characteristics.
If you require a cable with characteristics that are not covered by the range of
products described here, please contact your local SIEMENS office or
representative (see Appendix I.2).
4-2
PROFIBUS Networks SIMATIC NET
6GK1970-5CA20-0AA1 Release 2 05/2000
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.