Siemens SIMATIC IFP2200, SIMATIC IFP1900, SIMATIC IFP1500, SIMATIC IFP1900 ETH, SIMATIC IFP2200 ETH Operating Instructions Manual

...

Industrial Flat Panel IFP1500, IFP1900,
IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH

___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
Industrial Monitors Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH
Preface
Overview
1
Safety information
2
Installing and connecting the device
3
Commissioning the device
4
Operating the device
5
Maintaining and servicing your device
6
Technical information
7
Technical Support
A
List of abbreviations
B
-AF
Siemens AG Division Digital Factory Postfach 48 48 90026 NÜRNBERG GERMANY
A5E31298376-AF
Copyright © Siemens AG 2016. All rights reserved

Legal information

Warning notice system
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
Qualified Personnel
personnel qualified
Proper use of Siemens products
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
Disclaimer of Liability
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.
The product/system described in this documentation may be operated only by task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems.
Note the following:
documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.
for the specific
08/2016 Subject to change

Preface

Basic knowledge required
Scope of the operating instructions
Scope of this documentation
These operating instructions contain all the information you need for commissioning and operation of the SIMATIC Industrial Flat Panel IFP.
It is intended both for programming and testing personnel who commission the device and connect it with other units (automation systems, programming devices), as well as for service and maintenance personnel who install add-ons or carry out fault/error analyses.
A solid background in personal computers and Microsoft operating systems is required to understand this manual. General knowledge in the field automation control engineering is recommended.
These operating instructions apply to the following Industrial Flat Panels with the order
numbers 6AV7863-.....-....:
SIMATIC IFP1500, IFP1900, IFP2200
SIMATIC IFP1900 ETH, IFP2200 ETH
SIMATIC IFP1900 PRO, IFP2200 PRO
The SIMATIC Industrial Flat Panel is supplied with the following documents:
In printed form: Quick Install Guide for the device, Installation and Commissioning Instructions
Electronically as PDF file on the "Documentation and Drivers" CD/DVD:
– Operating instructions Industrial Flat Panel IFP1500, IFP1900, IFP2200,
IFP1900 ETH, IFP2200 ETH, IFP1900 PRO, IFP2200 PRO
– Operating manual SIMATIC Industry PC Panel Drivers and Tools PDT
You can find the operating manual in the PDT installation directory after installing PDT.
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH Operating Instructions, 07/2016, A5E31298376-AF
3
Preface
Conventions
Figures
History
Edition
Comment
09/2012
First Edition
11/2014
Update with IPC Wizard 2.1 and corrections
07/2015
Corrections
In these operating instructions, the SIMATIC IFP is also referred to as "Flat Panel" or "device".
The devices SIMATIC IFP1900 ETH and IFP2200 ETH are also referred to as "Ethernet Monitor" and "ETH version".
A touch device generally refers to a device with a touch screen, as opposed to a pure "display device". Touch screen is the general term for a capacitive multi-touch screen and resistive single touch screen.
The devices IFP1500, IFP1900, IFP2200, IFP1900 ETH and IFP2200 ETH are referred to as "built-in units".
The devices IFP1900 PRO and PRO IFP2200 are referred to as "PRO devices".
At some places in these operating instructions, the general term "Windows Embedded Standard" is used to refer to "Windows Embedded Standard 2009" and "Windows Embedded Standard 7". "Windows 7" is used as an abbreviation for "Windows 7 Ultimate".
This manual contains figures of the described devices. The supplied device may differ in some details from the figures. Within some of the figures, one device is used to represent all Industrial Flat Panels.
The following earlier release versions of these operating instructions have been published:
06/2014 Description of devices with capacitive multi-touch screen
06/2015 The description of the following devices has been added:
SIMATIC IFP1900 PRO, suitable for pedestal
SIMATIC IFP1900 PRO, suitable for support arm
SIMATIC IFP1900 ETH, IFP2200 ETH
07/2016 The description of the following devices has been added:
SIMATIC IFP2200 PRO, suitable for support arm
SIMATIC IFP2200 PRO, suitable for pedestal and extension components
SIMATIC IFP1900 PRO, suitable for support arm and extension components
SIMATIC IFP2200 PRO, suitable for support arm and extension components
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH
4 Operating Instructions, 07/2016, A5E31298376-AF

Table of contents

Preface ................................................................................................................................................... 3
1 Overview................................................................................................................................................. 9
2 Safety information ................................................................................................................................. 27
3 Installing and connecting the device ...................................................................................................... 33
1.1 Product description ................................................................................................................... 9
1.2 Scope of delivery .................................................................................................................... 12
1.3 Design of the built-in units ...................................................................................................... 13
1.3.1 IFP1500/1900/2200 Multitouch, IFP1900/2200 ETH .............................................................. 13
1.3.2 IFP1500/1900/2200 Touch ..................................................................................................... 15
1.3.3 IFP1500 Touch/Key ................................................................................................................ 16
1.3.4 Interfaces ................................................................................................................................ 16
1.3.4.1 Standard versions ................................................................................................................... 16
1.3.4.2 Ethernet Monitor devices ........................................................................................................ 17
1.3.4.3 Extended versions .................................................................................................................. 17
1.4 Design of the PRO devices ..................................................................................................... 18
1.4.1 PRO devices, suitable for support arm ................................................................................... 18
1.4.2 PRO devices, suitable for pedestal and extension components ............................................ 19
1.4.3 PRO devices, suitable for support arm and extension components ....................................... 21
1.4.4 Interfaces ................................................................................................................................ 22
1.5 Accessories ............................................................................................................................. 23
1.6 System components for PRO devices .................................................................................... 24
2.1 General safety instructions ..................................................................................................... 27
2.2 Notes about usage .................................................................................................................. 30
3.1 Preparing for installation ......................................................................................................... 33
3.1.1 Checking the delivery package ............................................................................................... 33
3.1.2 Built-in unit .............................................................................................................................. 34
3.1.2.1 Permitted mounting positions ................................................................................................. 34
3.1.2.2 Checking clearances............................................................................................................... 36
3.1.2.3 Preparing the mounting cutout ................................................................................................ 37
3.1.2.4 Labeling the function keys ...................................................................................................... 38
3.1.3 PRO devices ........................................................................................................................... 40
3.1.3.1 Permitted mounting positions ................................................................................................. 40
3.2 Installing the built-in unit ......................................................................................................... 40
3.2.1 Notes on installation................................................................................................................ 40
3.2.2 Mounting clips or mounting brackets, position for IP65 .......................................................... 41
3.2.3 Fastening the device with mounting clips or mounting brackets ............................................ 43
3.2.4 Position of the mounting clips for IP66-complaint installation................................................. 44
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH Operating Instructions, 07/2016, A5E31298376-AF
5
Table of contents
4 Commissioning the device .................................................................................................................... 63
5 Operating the device ............................................................................................................................. 65
6 Maintaining and servicing your device ................................................................................................... 73
3.3 Mounting the PRO device ...................................................................................................... 45
3.3.1 Notes on mounting ................................................................................................................. 45
3.3.2 PRO devices, suitable for support arm / pedestal and extension components ..................... 47
3.3.3 PRO devices, suitable for support arm and extension components ...................................... 49
3.4 Connecting the device ........................................................................................................... 51
3.4.1 Notes on connection .............................................................................................................. 51
3.4.2 Earthing the device ................................................................................................................ 52
3.4.3 Connecting the power supply ................................................................................................. 53
3.4.3.1 Connecting devices with 24 V DC 2-pin ................................................................................ 53
3.4.3.2 Connecting devices with 3-pin 24 V DC ................................................................................ 55
3.4.3.3 Connecting an AC power supply ............................................................................................ 56
3.4.4 Connecting IFP Standard, Extended and PRO to a PC ........................................................ 58
3.4.4.1 Overview ................................................................................................................................ 58
3.4.4.2 Standard version .................................................................................................................... 59
3.4.4.3 Extended version, PRO device .............................................................................................. 59
3.4.5 Connecting Ethernet Monitor to a PC .................................................................................... 60
3.4.5.1 Overview ................................................................................................................................ 60
3.4.5.2 Connection versions .............................................................................................................. 61
3.4.6 Connecting a USB device ...................................................................................................... 61
3.4.7 Securing the cables ............................................................................................................... 62
5.1 Operator input options ........................................................................................................... 65
5.2 Operating a device with resistive single touch screen ........................................................... 66
5.3 Operating a device with capacitive multi-touch screen .......................................................... 67
5.4 Operating a Touch/Key device............................................................................................... 69
5.5 Advanced device functions .................................................................................................... 72
6.1 Cleaning the device ............................................................................................................... 73
6.2 Ethernet Monitors - Diagnostics and reset ............................................................................. 74
6.2.1 Diagnostics screen ................................................................................................................. 74
6.2.2 Restoring the factory settings for an Ethernet Monitor .......................................................... 75
6.3 Spare parts and repairs ......................................................................................................... 76
6.4 Recycling and disposal .......................................................................................................... 76
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH
6 Operating Instructions, 07/2016, A5E31298376-AF
Table of contents
7 Technical information ............................................................................................................................ 77
A Technical Support ............................................................................................................................... 111
B List of abbreviations ............................................................................................................................ 113
Glossary ............................................................................................................................................. 115
Index................................................................................................................................................... 117
7.1 Certificates and approvals ...................................................................................................... 77
7.2 Directives and declarations ..................................................................................................... 80
7.2.1 ESD guideline ......................................................................................................................... 80
7.2.2 Electromagnetic compatibility ................................................................................................. 82
7.3 Dimension drawings ................................................................................................................ 83
7.3.1 Dimension drawing of the IFP1500 Multitouch ....................................................................... 83
7.3.2 Dimension drawing of the IFP1500 Monitor and Touch ......................................................... 84
7.3.3 Dimension drawing of the IFP1900 Multitouch and IFP1900 ETH ......................................... 85
7.3.4 Dimension drawing of the IFP1900 Monitor and Touch ......................................................... 86
7.3.5 Dimension drawing of the IFP2200 Multitouch and IFP2200 ETH ......................................... 87
7.3.6 Dimension drawing of the IFP2200 Monitor and Touch ......................................................... 88
7.3.7 Dimension dimensional drawing of the IFP1900 PRO ........................................................... 89
7.3.8 Dimension drawing of the IFP2200 PRO ................................................................................ 92
7.3.9 Dimension drawing of the IFP1500 Touch/Key ...................................................................... 95
7.3.10 Dimension drawing Host Unit USB ......................................................................................... 96
7.3.11 Dimensions for labeling strips ................................................................................................. 97
7.4 Rating plate ............................................................................................................................. 98
7.5 Technical specifications .......................................................................................................... 98
7.5.1 General technical specifications ............................................................................................. 98
7.5.2 Ambient conditions ................................................................................................................ 101
7.5.2.1 Transport and storage conditions ......................................................................................... 101
7.5.2.2 Operating conditions ............................................................................................................. 102
7.5.2.3 Information on insulation tests, protection class and degree of protection........................... 105
7.6 Interface description .............................................................................................................. 106
7.6.1 24 V DC Power Supply ......................................................................................................... 106
7.6.2 DVI-D interface ..................................................................................................................... 108
7.6.3 DisplayPort ............................................................................................................................ 109
7.6.4 USB interface, Type B .......................................................................................................... 109
7.6.5 USB hub, Type A .................................................................................................................. 110
7.6.6 Ethernet ................................................................................................................................ 110
A.1 Service and support .............................................................................................................. 111
A.2 Troubleshooting .................................................................................................................... 112
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH Operating Instructions, 07/2016, A5E31298376-AF
7
Table of contents
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH
8 Operating Instructions, 07/2016, A5E31298376-AF
1
1.1

Product description

SIMATIC Industrial Flat Panels are LCD monitors suitable for industrial use with a brilliant TFT display which can be connected to all SIMATIC IPCs as well as almost all generally available PCs.
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH Operating Instructions, 07/2016, A5E31298376-AF
9
Overview
Features of the built-in units
Additional features of the Extended versions
1.1 Product description
Rugged front
Brilliant TFT display with a wide reading angle;
Resistive single touch screen in sizes 15", 19" and 22"
Capacitive multi-touch screen available in sizes 15", 19" and 22"
Available as pure display device (monitor) or touch device
Can be placed up to 5 m from the IPC
DVI-D and DisplayPort V1.1 interface
Multi-monitoring support
Backlighting can be dimmed via software
24 V DC power supply
Degree of protection IP65 in installed state
Enclosure type: Front face only Type 4X/Type 12 (indoor use only)
Up to 16 million colors
Up to 30 m away from PC possible via DVI
Power supply (with USB) 24 V DC and 100-240 V AC
2 USB ports
Also available as touch/key version with front USB interface
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH
10 Operating Instructions, 07/2016, A5E31298376-AF
Overview
Additional features of the PRO devices
Additional features of the Ethernet Monitors
1.1 Product description
All-round dust-proof and splash-proof with IP65 degree of protection and Enclosure Type 4X / 12 (indoor use only)
Can be mounted directly on the machine
19" display, 22" display; capacitive multi-touch screen
Device versions for mounting:
– IFP PRO, suitable for support arm (flange above)
– IFP PRO, suitable for support arm and extension components (round tube)
– IFP PRO, suitable for pedestal and extension components (flange below)
Adapters and adapter sets that can be ordered separately support mounting systems from various manufacturers.
– Base adapter for device versions with flange above and flange below included in the
product package.
– For the IFP PRO device version, suitable for support arm and extension components:
- Cover for the mechanical interface below, included in the product package
- Flange mount available as accessory
Can be placed up to 30 m away via DVI
2 USB ports
Configuration and operation in the Ethernet/LAN network
Length of the Ethernet/LAN connection as customary with conventional LAN technology
Automatic establishment of connection to SIMATIC IPC
Automatic configuration using 1:1 cable connection
Ethernet Monitor software and monitor diagnostic function
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH Operating Instructions, 07/2016, A5E31298376-AF
11
Overview
1.2
Scope of delivery
Name
Figure
Number
cable; 2 m in length, for commissioning
USB connecting cable, 2 m in length2
1
Ethernet connecting cable, 2 m in length3
1
Power supply cable 230 V AC 4
1
"Documentation and Drivers" CD
1
1
2
3
4
5
6
Only for PRO devices of the type "suitable for support arm and extension components"

1.2 Scope of delivery

The product package includes the following components:
Industrial Flat Panel
Installation instructions (Quick Install Guide)
Accessory kit "Mounting clips 1
and power supply connector"
1
1
12
1
"Connecting cables" accessory kit 1 DVI connecting cable or DisplayPort connecting
Base adapter 5
Cover for mechanical interface 6
Not with PRO devices Not with standard display device (monitor) Only with devices of the Ethernet Monitor type Only with devices with AC power supply Only for PRO devices of the type "suitable for support arm" and "suitable for pedestal and
extension components"
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH
12 Operating Instructions, 07/2016, A5E31298376-AF
1
1
1
Overview
1.3
Design of the built-in units
1.3.1

IFP1500/1900/2200 Multitouch, IFP1900/2200 ETH

Front view and bottom view
Display/touch screen
Recesses for mounting clips
Mounting seal

1.3 Design of the built-in units

This section describes the design of the multi-touch devices, using the IFP1900 Multitouch as an example.
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH Operating Instructions, 07/2016, A5E31298376-AF
13
Overview
Rear view
Rating plate
Interface name
Equipotential bonding
Retaining elements for strain relief of the connecting cables
1.3 Design of the built-in units
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH
14 Operating Instructions, 07/2016, A5E31298376-AF
Overview
1.3.2

IFP1500/1900/2200 Touch

Front view and side view
Display/touch screen
Recesses for mounting clips
Mounting seal
Rear view
1.3 Design of the built-in units
This section describes the design of the monitor and touch devices, using the IFP1500 Touch as an example.
See section "IFP1500/1900/2200 Multitouch".
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH Operating Instructions, 07/2016, A5E31298376-AF
15
Overview
1.3.3

IFP1500 Touch/Key

Front view
Display and function keys with LED
Alphanumeric keys
Control keys
Cursor keys
USB port
1.3.4

Interfaces

1.3.4.1
Standard versions
X80 connector for 24 V DC power supply
X71 DVI-D interface
X70 DisplayPort interface
X60 USB Type B
1.3 Design of the built-in units
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH
16 Operating Instructions, 07/2016, A5E31298376-AF
Overview
1.3.4.2
Ethernet Monitor devices
X80 connector for 24 V DC power supply
X1 Ethernet port
Reset button
X70 DisplayPort interface
X61/X62 USB Type A
X60 USB Type B
1.3.4.3
Extended versions
Connection for 100 to 240 V AC power supply
X61/X62 USB Type A
X80 connector for 24 V DC power supply
X63 USB link interface
X71 DVI-D interface
X60 USB Type B
X70 DisplayPort interface
1.3 Design of the built-in units
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH Operating Instructions, 07/2016, A5E31298376-AF
17
Overview
1.4
Design of the PRO devices
1.4.1

PRO devices, suitable for support arm

Front view and side view
Display with touch screen
Enclosure
Backplane cover
Top view
Mechanical interface for fastening

1.4 Design of the PRO devices

The following figures show the design of the devices using IFP1900 PRO suitable for support arm as an example.
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH
18 Operating Instructions, 07/2016, A5E31298376-AF
Overview
Rear view
Mechanical interface for fastening
Rating plate
Enclosure
Backplane cover
1.4.2

PRO devices, suitable for pedestal and extension components

Front view and side view
Display with touch screen
Enclosure
Backplane cover
1.4 Design of the PRO devices
The following figures shows the design of the devices using IFP1900 PRO suitable for pedestal and extension components as an example.
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH Operating Instructions, 07/2016, A5E31298376-AF
19
Overview
Bottom view
Mechanical interface for fastening
Rear view
Backplane cover
Enclosure
Rating plate
Mechanical interface for fastening
1.4 Design of the PRO devices
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH
20 Operating Instructions, 07/2016, A5E31298376-AF
Overview
1.4.3

PRO devices, suitable for support arm and extension components

Front view and side view
Display with touch screen
Enclosure
Mechanical interface for fastening (round tube)
Terminal compartment cover
Mechanical interface below
1.4 Design of the PRO devices
The following figures show the design of the devices using IFP1900 PRO suitable for support arm and extension components as an example.
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH Operating Instructions, 07/2016, A5E31298376-AF
21
Overview
Rear view
Mechanical interface for fastening (round tube)
Terminal compartment cover
Nameplate
Mechanical interface below
Lower cover, included in the product package
1.4.4

Interfaces

Protective conductor terminal
X61/X62 USB Type A
X80 connector for 24 V DC power supply
X63 USB link interface
X71 DVI-D interface
X60 USB Type B
X70 DisplayPort interface
1.4 Design of the PRO devices
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH
22 Operating Instructions, 07/2016, A5E31298376-AF
Overview
1.5
Accessories
Introduction
All Industrial Flat Panels
Name
Specification
Article number
3 m long
6AV7860-0BH30-0AA0
3 m long
6AV7860-0DH30-0AA0
3 m long
6AV7860-0CH30-0AA0
5 m long
6AV7860-0CH50-0AA0
15"
6AV2124-6QJ00-0AX0
19"
6AV2124-6UJ00-0AX0
22"
6AV2124-6XJ00-0AX0
For resistive touch screen
6AV7672-1JB00-0AA0
For capacitive and resistive touch screen
6AV2181-8AV20-0AX0
Built-in units
Name
Specification
Article number
Mounting clips service pack
20 pieces
6AV6671-8XK00-0AX3
Mounting brackets service pack
2 x 8 latch fasteners
6AV7672-1JC00-0AA0
Extended version
Name
Specification
Article number
10 m long
6AV7860-1EX21-0AA1
15 m long
6AV7860-1EX21-5AA1
20 m long
6AV7860-1EX22-0AA1
30 m long
6AV7860-1EX23-0AA1

1.5 Accessories

This section contains the number of accessories available at the time of publication of the operating instructions. You will find additional accessories on the Internet at:
Industry Mall (https://mall.industry.siemens.com)
Expansion components and accessories (http://www.automation.siemens.com/mcms/pc-
based-automation/en/industrial-pc/expansion_components_accessories)
Ethernet cable accessories (https://support.industry.siemens.com/cs/ww/en/view/98278804
DVI line
DisplayPort line
USB line
5 m long 6AV7860-0BH50-0AA0
5 m long 6AV7860-0DH50-0AA0
)
Protective foil for the touch screen
Touch pen
Cable set (DVI/USB cable)
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH Operating Instructions, 07/2016, A5E31298376-AF
23
Overview
Touch/Key Extended version
Name
Article number
Drivers" CD/DVD.
Ethernet Monitors
Name
Specification
Article number
TP Cord RJ45/RJ45, 15 m
6XV1870-3QN15
TP Cord RJ45/RJ45, 20 m
6XV1870-3QN20
TP Cord RJ45/RJ45, 30 m
6XV1870-3QN30
TP Cord RJ45/RJ45, 50 m
6XV1870-3QN50
1.6
System components for PRO devices
Base adapter
Seal
Channel cable
Mechanical interface to the PRO device
Cover
Mechanical interface to the support arm or pedestal including seal

1.6 System components for PRO devices

Film for labeling the function keys (slide-in labels)
Recommended Ethernet RJ45 cables (selection)
Print templates for the slide-in labels are available on the "Documentation and
6AV7672-0DA00-0AA0
Additional Ethernet cables: See link "Accessories Ethernet cables" at the beginning of this section.
PRO devices of the type "suitable for support arm" or "suitable for pedestal" can be mounted on the support arm or pedestal using the base adapter. A base adapter is included with the corresponding PRO devices. The base adapter can also be ordered separately.
Article number: 6AV7674-1KA00-0AA0
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH
24 Operating Instructions, 07/2016, A5E31298376-AF
Overview
Adapter sets and couplings
Adapter version
Suitable for supporting arm systems
Article number
SIEMENS
RITTAL
ROLEC
BERNSTEIN
All information subject to change.
1.6 System components for PRO devices
The following mechanical adapter versions are also available for mounting a PRO device of the types "suitable for support arm" and "suitable for pedestal" via the base adapter:
A Siemens VESA adapter set for VESA compatible systems
Manufacturer-specific adapter or couplings
The following table shows the available Siemens adapter sets and examples of vendor­specific adapter versions:
Adapter set VESA75
Adapter set VESA100
Adapter for Siemens PRO Panel
Intermediate plate
Screws
Adapter for Siemens PRO Panel
Intermediate plate
Screws
Coupling for Siemens SIMATIC PRO
No intermediate plate required
Coupling with integrated adaptation for PRO devices
VESA75-compatible systems 6AV7674-0KE00-0AA0
VESA100-compatible systems 6AV7674-0KD00-0AA0
CP40 steel
CP60/120 for support arm
connection 120 × 65 mm
profiPlus-50
taraPLUS for ∅ 65 mm hole circle
CS-3000 1015300187 RAL 9006
6206.500
142.024.000
White aluminum
1015300043 RAL 7016 Anthracite grey
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH Operating Instructions, 07/2016, A5E31298376-AF
25
Overview
Flange mount
Flange mount
Ring groove for fastening on PRO device with setscrews
Mechanical interface to support arm
1.6 System components for PRO devices
A flange mount is available for mounting a PRO device of the type "suitable for support arm and extension components".
Article number: 6AV7674-1KF00-0AA0
You can find additional system components for PRO devices on the Internet (
https://mall.industry.siemens.com/mall/en/WW/Catalog/Products/10299123?tree=CatalogTr
ee).
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH
26 Operating Instructions, 07/2016, A5E31298376-AF
2
2.1

General safety instructions

Machinery Directive
WARNING
The device may only be used in machines which comply with the Machinery Directive
Hazardous areas
WARNING
Explosion Hazard
Risque d'Explosion
The Machinery Directive specifies precautions to be taken when commissioning and operating machinery within the European Economic Area.
Failure to follow these precautions is a breach of the Machinery Directive. Such failure may also cause personal injury and damage depending on the machine operated.
The machine in which the HMI device is to be operated must conform to Directive 2006/42/EC.
When operating the HMI device in hazardous areas the following warning applies.
Do not disconnect while circuit is live unless area is known to be non-hazardous. Substitution of components may impair suitability for Class I, Division 2 or Zone 2.
Ne pas déconnecter pendant que le circuit est sous tension, sauf si la zone est non­dangereuse. Le remplacement de composants peut compromettre leur capacité à satisfaire à la Classe I, Division 2 ou Zone 2.
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH Operating Instructions, 07/2016, A5E31298376-AF
27
Safety information
Strong high-frequency radiation
NOTICE
Observe immunity to RF radiation
Additional notes for built-in units
WARNING
The device constitutes open equipment
Life-threatening voltages are present with an open control cabinet
2.1 General safety instructions
The device has increased immunity to RF radiation according to the specifications on electromagnetic compatibility in the technical specifications.
Radiation exposure in excess of the specified immunity limits can impair device functions, result in malfunctions and therefore injuries or damages.
Read the information on immunity to RF radiation in the technical specifications.
The device constitutes open equipment. This means that the device may only be installed in enclosures or cabinets which provide front access for operating the device.
When you open the control cabinet, some areas or components may be conducting life-threatening voltages.
Contact with these areas or components may result in death by electric shock.
Switch off the power supply to the cabinet before opening it.
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH
28 Operating Instructions, 07/2016, A5E31298376-AF
Safety information
Industrial Security
Disclaimer for third-party software updates
Notes on protecting administrator accounts
See also
2.1 General safety instructions
Siemens provides products and solutions with industrial security functions that support the secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens’ products and solutions only form one element of such a concept.
Customer is responsible to prevent unauthorized access to its plants, systems, machines and networks. Systems, machines and components should only be connected to the enterprise network or the internet if and to the extent necessary and with appropriate security measures (e.g. use of firewalls and network segmentation) in place.
Additionally, Siemens’ guidance on appropriate security measures should be taken into account. For more information about industrial security, please visit (http://www.siemens.com/industrialsecurity
Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends to apply product updates as soon as available and to always use the latest product versions. Use of product versions that are no longer supported, and failure to apply latest updates may increase customer’s exposure to cyber threats.
).
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed under (http://www.siemens.com/industrialsecurity
This product includes third-party software. Siemens AG only provides a warranty for updates/patches of the third-party software, if these have been distributed as part of a Siemens software update service contract or officially released by Siemens AG. Otherwise, updates/patches are undertaken at your own risk. You can find more information about our Software Update Service offer on the Internet at Software Update Service
http://www.automation.siemens.com/mcms/automation-software/en/software-update-
(
service).
A user with administrator privileges has extensive access and manipulation options in the system.
Therefore, ensure there are adequate safeguards for protecting the administrator accounts to prevent unauthorized changes. To do this, use secure passwords and a standard user account for normal operation. Other measures, such as the use of security policies, should be applied as needed.
).
Technical Support (https://support.industry.siemens.com)
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH Operating Instructions, 07/2016, A5E31298376-AF
29
Safety information
2.2
Notes about usage
NOTICE
Device is approved for indoor use only
Industrial applications
Use in residential areas
Note Device is not intended for use in residential areas
The device is not intended for use in residential areas. Operating the device in residential areas can affect radio or TV reception.

2.2 Notes about usage

The device may be damaged if operated outdoors.
"Indoor use only"
Operate the device indoors only.
The device is designed for industrial use. It conforms to the following standards:
Requirements of the emission standard for industrial environments, EN 61000-6-4: 2007
Requirements for interference immunity EN 61000-6-2: 2005
Immunity to interference acc. to EN 55024
Radio interference suppression acc. to EN 55022, Class B
If you operate the device in a residential area, you must ensure conformance to Class B limits according to EN 55011 regarding the emission of radio interference.
Suitable measures for achieving the degree of noise suppression for Limit Class B include, for example:
Install built-in units in grounded control cabinets
Use of filters in electrical supply lines
Individual acceptance is required.
Industrial Flat Panel IFP1500, IFP1900, IFP2200, IFP1900 PRO, IFP2200 PRO, IFP1900 ETH, IFP2200 ETH
30 Operating Instructions, 07/2016, A5E31298376-AF