Industrial Ethernet switches SCALANCE X005 / X005TS
Operating Instructions
07/2014
C79000
-G8976-C344-01
Introduction
1
Network topologies
2
Description of the device
3
Mounting
4
Connecting up
5
Maintenance and troubleshooting
6
Technical specifications
7
Approvals
8
Dimension drawings
9
Siemens AG Industry Sector Postfach 48 48 90026 NÜRNBERG GERMANY
C79000-G8976-C344-01
07/2014 Subject to change
Copyright © Siemens AG 2010 - 2014. All rights reserved
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by
personnel qualified
for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.
SCALANCE X005 / X005TS Operating Instructions, 07/2014, C79000-G8976-C344-01
3
Table of contents
1 Introduction ............................................................................................................................................. 5
1.1 On the Operating Instructions ........................................................................................................ 5
1.2 On the product ............................................................................................................................... 7
1.3 Unpacking and checking ................................................................................................................ 8
2 Network topologies ................................................................................................................................. 9
3 Description of the device ....................................................................................................................... 11
3.1 Overview SCALANCE X-000 ....................................................................................................... 11
3.2 Product characteristics ................................................................................................................. 12
3.3 TP ports (twisted pair) .................................................................................................................. 13
3.4 LEDs ............................................................................................................................................ 15
4 Mounting ............................................................................................................................................... 17
4.1 Types of installation ..................................................................................................................... 17
4.2 Installation on a DIN rail ............................................................................................................... 18
4.3 Installation on a standard rail ....................................................................................................... 20
4.4 Wall mounting .............................................................................................................................. 21
5 Connecting up ....................................................................................................................................... 23
5.1 Power supply ................................................................................................................................ 23
5.2 Grounding .................................................................................................................................... 24
5.3 IE FC RJ-45 Plug 180 .................................................................................................................. 24
6 Maintenance and troubleshooting .......................................................................................................... 27
7 Technical specifications ........................................................................................................................ 29
8 Approvals .............................................................................................................................................. 31
8.1 Approvals_intro_X-000 ................................................................................................................. 31
8.2 Note for Australia ......................................................................................................................... 32
8.3 Notes on the cULus approval ....................................................................................................... 32
8.4 Notes on the e1/E1 approval of the SCALANCE X005TS ........................................................... 32
8.5 Noise test of the SCALANCE X005TS ........................................................................................ 33
8.6 Overvoltage test of the SCALANCE X005TS .............................................................................. 33
8.7 Mechanical stability (in operation)................................................................................................ 33
9 Dimension drawings .............................................................................................................................. 35
Index..................................................................................................................................................... 37
Table of contents
SCALANCE X005 / X005TS
4 Operating Instructions, 07/2014, C79000-G8976-C344-01
SCALANCE X005 / X005TS Operating Instructions, 07/2014, C79000-G8976-C344-01
5
1
1.1
On the Operating Instructions
Purpose of the Operating Instructions
These operating instructions support you when commissioning the unmanaged Industrial Ethernet entry level switches SCALANCE X005 and SCALANCE X005TS (Transportation System).
Validity of the Operating Instructions
These operating instructions are valid for the following devices:
Device
Order number
SCALANCE X005
6GK5005-0BA00-1AA3
SCALANCE X005TS
6GK5005-0BA00-1CA3
Further documentation
The "SIMATIC NET Industrial Ethernet Twisted Pair and Fiber Optic Networks" manual contains additional information on other SIMATIC NET products that you can operate along with the SCALANCE X005 and SCALANCE X005TS IE switches in an Industrial Ethernet network.
You can order the manual "SIMATIC NET Industrial Twisted Pair and Fiber Optic Networks", release 05/2001, using the following order numbers: 6GK1970-1BA10-0AA0 German 6GK1970-1BA10-0AA1 English 6GK1970-1BA10-0AA2 French 6GK1970-1BA10-0AA4 Italian
You will also find this network manual on the Internet pages of Service & Support under the following entry ID: 1172207 (http://support.automation.siemens.com/WW/view/en/1172207
).
You will find further information in the "System Manual Industrial Ethernet" in the Manual Collection.
You will find further information on the SCALANCE system on the Internet at www.siemens.com/scalance (www.siemens.com/scalance
).
Audience
These Operating Instructions are intended for persons who commission networks with the IE switches of the SCALANCE X-000 product line.
Introduction
1.1 On the Operating Instructions
SCALANCE X005 / X005TS
6 Operating Instructions, 07/2014, C79000-G8976-C344-01
SIMATIC NET glossary
Explanations of many of the specialist terms used in this documentation can be found in the SIMATIC NET glossary.
You will find the SIMATIC NET glossary here:
SIMATIC NET Manual Collection or product DVD
The DVD ships with certain SIMATIC NET products.
On the Internet under the following entry ID:
50305045 (http://support.automation.siemens.com/WW/view/en/50305045
)
Security information
Siemens provides products and solutions with industrial security functions that support the secure operation of plants, solutions, machines, equipment and/or networks. They are important components in a holistic industrial security concept. With this in mind, Siemens’ products and solutions undergo continuous development. Siemens recommends strongly that you regularly check for product updates.
For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept. Third-party products that may be in use should also be considered. For more information about industrial security, visit
http://www.siemens.com/industrialsecurity
.
To stay informed about product updates as they occur, sign up for a product-specific newsletter. For more information, visit http://support.automation.siemens.com
.
Introduction
1.2 On the product
SCALANCE X005 / X005TS Operating Instructions, 07/2014, C79000-G8976-C344-01
7
1.2
On the product
What is possible?
The SCALANCE X005 and SCALANCE X005TS IE switches allow the cost-effective installation of small Industrial Ethernet linear bus or star structures with switching functionality. The devices are designed for installation in a cabinet.
Note
It is not possible to use a SCALANCE
X005 or SCALANCE X005TS in a redundant ring
because they do not support redundancy.
Note
If devices are supplied over long 24 V power supply lines or networks, measures are necessary to prevent interference by strong electromagnetic pulses on the supply lines. These can result, for example, due to lightning or switching of large inductive load
s.
One of the tests used to attest the immunity of these devices to electromagnetic interference is the "surge immunity test" according to EN 61000
-4-5. This test requires overvoltage
protection for the power supply lines. A suitable device is, for exampl
e, the Dehn Blitzductor
BVT AVD 24 V type no. 918 422 or a comparable protective element.
Manufacturer: DEHN+SÖHNE GmbH+Co.KG Hans Dehn Str.1 Postfach 1640 D
-92306 Neumarkt,
Germany
Components of the product
The following components are supplied with a SCALANCE X005 or SCALANCE X005TS:
SCALANCE X005 or SCALANCE X005TS IE switch
2-terminal plug-in block (power supply)
Product information
Introduction
1.3 Unpacking and checking
SCALANCE X005 / X005TS
8 Operating Instructions, 07/2014, C79000-G8976-C344-01
Accessories
Component
Packaging unit
Order number
IE FC Stripping Tool
1
6GK1901-1GA00
IE FC blade cassettes
1
6GK1901-1GB00
IE FC TP standard cable GP
1
6XV1840 2AH10
IE FC TP trailing cable
1
6XV1840-3AH10
IE FC TP marine cable
1
6XV1840-4AH10
IE FC TP trailing cable GP
1
6XV1870-2D
IE FC TP flexible cable GP
1
6XV1870-2B
IE FC RJ-45 Plug 180
1
6GK1 901-1BB10-2AA0
IE FC RJ-45 Plug 180
10
6GK1 901-1BB10-2AB0
IE FC RJ-45 Plug 180
50
6GK1 901-1BB10-2AE0
1.3
Unpacking and checking
Unpacking and checking
WARNING
Do not use any parts that show evidence of damage
If you use damaged parts, there is no guarantee that the device will function according to the specification.
If you use damaged parts, this can lead to the following problems:
Injury to persons
Loss of the approvals
Violation of the EMC regulations
Damage to the device and other components
Use only undamaged parts.
1. Make sure that the package is complete.
2. Check all the parts for transport damage.
WARNING
If the SCALANCE X005TS device is operated in an ambient temperature of between 60 and 65 °C, the temperature of the device housing may be higher than 65 . The device must therefore be installed so that it is only accessible to service personnel or users that are aware of the reason for restricted access and the required safety measures at an ambient temperature of 60 to 65 °C.
SCALANCE X005 / X005TS Operating Instructions, 07/2014, C79000-G8976-C344-01
9
2
Switching technology allows extensive networks to be set up with numerous nodes and simplifies network expansion.
Which topologies can be implemented?
Using the SCALANCE X005 and SCALANCE X005TS IE switches, you can implement star topologies.
Note
Keep to the maximum permitted cable lengths of the devices you are using. You will find the permitted cable lengths in the section "
Technical specifications (Page 29)".
Star topology
Figure 2-1 Example of a star topology with SCALANCE X005
Network topologies
SCALANCE X005 / X005TS
10 Operating Instructions, 07/2014, C79000-G8976-C344-01
SCALANCE X005 / X005TS Operating Instructions, 07/2014, C79000-G8976-C344-01
11
3
3.1
Overview SCALANCE X-000
Table 3- 1 Overview of the product characteristics
X005
X005TS
SIMATIC environment
+
+
Diagnostics LED
+
+
24 VDC + +
2 x 24 VDC - -
Compact housing
(securing collar, etc.)
+ +
Signaling contact + on-site operation
-
-
Diagnostics: Web, SNMP, PROFINET
-
-
C-PLUG - -
Ring redundancy with RM
-
-
Passive ring redundancy
-
-
Standby redundancy
-
-
IRT capability - -
Fast learning - -
Passive listening
-
-
Log table - -
SNTP + SICLOCK - -
Cut Through - -
Table 3- 2 Overview of the connection options
X005
X005TS
TP (RJ-45)
Fast Ethernet 10 / 100 Mbps
5 5
Description of the device
3.2 Product characteristics
SCALANCE X005 / X005TS
12 Operating Instructions, 07/2014, C79000-G8976-C344-01
3.2
Product characteristics
Possible attachments
The SCALANCE X005 and SCALANCE X005TS have five RJ-45 jacks for connection of end devices or other network segments.
Figure 3-1 SCALANCE X005
Note
The SCALANCE X005 shown above has the same construction as the SCALANCE X005TS.