Siemens RVA63.280, RVA53.280 Basic Documentation

0 (0)
Edition 1.3 Controller series B CE1P2374E
19.04.2001
Siemens Building Technologies
Landis & Staefa Division
RVA63.280, RVA53.280 Boiler and Heating Circuit Controllers
Basic Documentation
2/184 Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis &Staefa Division 19.04.2001
3/184
Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E Landis & Staefa Division Summary 19.04.2001
Contents
1 Summary.........................................................................................................8
1.1 Brief description...............................................................................................8
1.2 Features ..........................................................................................................8
1.3 Range of products.........................................................................................10
1.4 Field of use....................................................................................................11
1.5 Product liability ..............................................................................................11
2 Handling ........................................................................................................12
2.1 Installation .....................................................................................................12
2.1.1 Regulations for installation ............................................................................12
2.1.2 Mounting location ..........................................................................................12
2.1.3 Mounting procedure.......................................................................................12
2.1.4 Required cut-out............................................................................................14
2.1.5 Orientation.....................................................................................................14
2.2 Electrical installation......................................................................................15
2.2.1 Regulations for installation ............................................................................15
2.2.2 wiring.............................................................................................................15
2.3 Commissioning..............................................................................................17
2.3.1 Functional checks..........................................................................................17
2.4 Parameter settings for the end-user..............................................................21
2.4.1 Overview of end-user parameters.................................................................22
2.5 Parameter settings for the heating engineer .................................................24
2.5.1 Overview of heating engineer parameters ....................................................25
2.6 Parameter settings for the OEM....................................................................29
2.6.1 Overview of OEM parameters.......................................................................30
2.7 Operation.......................................................................................................32
2.7.1 Operating elements.......................................................................................32
2.8 Operational faults ..........................................................................................34
1 Description of end-user settings....................................................................36
User interface................................................................................................................36
1.1 Operating modes of heating circuit................................................................36
1.2 Operating mode of d.h.w. heating .................................................................38
1.3 Nominal room temperature setpoint..............................................................39
1.3.1 Temperature adjustment via room unit..........................................................40
1.4 Heating circuit selection button .....................................................................41
1.5 Chimney sweep.............................................................................................42
1.6 Manual operation...........................................................................................43
Setting the clock............................................................................................................44
1.7 Time of day....................................................................................................44
1.8 Weekday .......................................................................................................44
1.9 Date (day, month)..........................................................................................45
1.10 Year...............................................................................................................45
Time switch programs 1 and 2 ......................................................................................46
1.11 Pre-selection of weekday: for time switch programs 1 and 2 ........................46
1.12 Switching times of time switch programs 1 and 2.........................................48
Time switch program 3 (d.h.w.) .....................................................................................49
1.13 Preselection of weekday for time switch program 3 (d.h.w.).........................49
1.14 Switching times of time switch program 3 (d.h.w.) ........................................50
D.h.w. values.................................................................................................................51
4/184 Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division Summary 19.04.2001
1.15 Nominal setpoint of d.h.w. temperature (TBWw)...........................................51
Heating circuits ..............................................................................................................52
1.16 Reduced setpoint of room temperature (TRRw)............................................52
1.17 Frost protection setpoint of room temperature (TRF)....................................53
1.18 Summer / winter changeover temperature HC1 and HC2 (THG)..................54
1.19 Slope of heating curve (S) .............................................................................56
Display of actual values.................................................................................................58
1.20 Actual value of room temperature (TRx)........................................................58
1.21 Actual value of outside temperature (TAx) ....................................................58
Display of burner data....................................................................................................59
1.22 Burner hours run stage 1 (tBR1)....................................................................59
1.22.1 Counting the hours run ..................................................................................59
1.22.2 Average burner running time .........................................................................59
1.23 Burner hours run stage 2 (tBR2)....................................................................60
1.23.1 Counting the hours run ..................................................................................60
1.24 Number of burner starts stage 1....................................................................60
1.25 Number of burner starts stage 2....................................................................61
Maintenance ..................................................................................................................62
1.26 Standard times...............................................................................................62
Holidays 63
1.27 Holiday period................................................................................................63
1.28 Beginning and end of holiday period .............................................................63
1.29 Indication of BMU error code.........................................................................64
1.30 Indication of faults..........................................................................................65
2 Description of heating engineer settings........................................................67
Service values................................................................................................................67
2.1 Output test.....................................................................................................67
2.2 Input test........................................................................................................68
2.3 Display of plant type ......................................................................................69
Actual values..................................................................................................................70
2.4 Actual value of flow temperature ...................................................................70
2.5 Actual value of boiler temperature.................................................................70
2.6 Actual value of common flow temperature.....................................................70
2.7 Actual value 1 of d.h.w. temperature (TBWx)................................................71
2.8 Actual value 2 of d.h.w. temperature .............................................................71
2.9 Display of maximum flue gas temperature (TGxmax) ...................................71
2.10 Attenuated outside temperature (TAxged).....................................................72
2.11 Composite outside temperature (Taxgem) ....................................................72
2.12 Outside temperature source ..........................................................................73
Setpoints 74
2.13 Display of boiler temperature setpoint ...........................................................74
2.14 Display of common flow temperature setpoint...............................................74
2.15 Display of d.h.w temperature setpoint ...........................................................75
2.16 Display of nominal room temperature setpoint ..............................................76
2.17 Display of room temperature setpoint (TRw).................................................77
2.18 Display of flow temperature setpoint (TVw)...................................................78
2.19 Floor curing data............................................................................................79
Heat generating equipment............................................................................................80
2.20 Type of heat source.......................................................................................80
2.20.1 No heat generation or BMU...........................................................................80
2.20.2 Multi-stage burners........................................................................................80
5/184
Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E Landis & Staefa Division Summary 19.04.2001
2.21 Minimum limitation of boiler temperature (TKmin).........................................81
2.22 Extra heating for the bathroom......................................................................82
2.22.1 Extra heating for the bathroom......................................................................82
Heating circuit................................................................................................................83
2.23 Parallel displacement of heating curve..........................................................83
2.24 Room influence .............................................................................................84
2.25 Switching differential of room temperature (SDR).........................................85
2.26 Operating mode of room unit.........................................................................86
2.27 Room unit values...........................................................................................87
2.27.1 Examples of room unit assignments .............................................................88
2.28 Minimum limitation of flow temperature setpoint (TVmin)..............................89
2.29 Maximum limitation of flow temperature setpoint (TVmax)............................90
2.30 Maximum forward shift of optimum start control............................................91
2.30.1 Optimum start control....................................................................................91
2.30.2 Without room influence..................................................................................92
2.30.3 With room influence.......................................................................................92
2.31 Maximum forward shift of optimum stop control............................................93
2.31.1 Optimum stop control ....................................................................................93
2.32 Type of building construction.........................................................................94
2.33 Adaption of heating curve..............................................................................95
2.33.1 Adaption ........................................................................................................95
2.34 Locking signal gain........................................................................................97
2.35 Floor curing ...................................................................................................98
2.35.1 Temperature profile.......................................................................................98
2.35.2 Activating the function ................................................................................... 99
2.35.3 Function.........................................................................................................99
2.35.4 Display...........................................................................................................99
2.35.5 Aborting the function .....................................................................................99
D.h.w. 100
2.36 Reduced setpoint of d.h.w. temperature (TBWR) .......................................100
2.37 D.h.w. heating program...............................................................................101
2.37.1 24-hour operation setting 0 ........................................................................101
2.37.2 Operation according to the time switch programs with forward shift (d.h.w.)
Setting 1 ......................................................................................................102
2.37.3 Operation according to the local time switch program 3 (d.h.w.) Setting 2 .102
2.38 Assignment of d.h.w. heating ......................................................................103
2.39 D.h.w. charging ...........................................................................................104
2.39.1 Once per day with a forward shift of 2.5 hours Setting 0.............................104
2.39.2 Several times per day with a forward shift of 1 hour Setting 1 ....................104
2.40 Type of d.h.w. demand................................................................................105
2.41 Boost of flow temperature setpoint for d.h.w. heating (UEBW)...................107
2.42 D.h.w. priority...............................................................................................108
2.42.1 Frost protection for the plant .......................................................................108
2.42.2 Shifting priority.............................................................................................109
2.42.3 Temperature-time integral...........................................................................110
2.43 Controlling element for d.h.w.......................................................................111
LPB / system ...............................................................................................................112
2.44 LPB device address ....................................................................................112
2.45 LPB segment address.................................................................................113
2.46 LPB power supply .......................................................................................114
2.47 Display of LPB power supply.......................................................................115
2.48 Range of action of central changeover........................................................116
2.49 Automatic summer / winter changeover......................................................117
2.50 Central stand-by switch...............................................................................118
6/184 Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division Summary 19.04.2001
2.51 Clock mode..................................................................................................119
2.52 Winter- / summertime changeover...............................................................120
2.53 Summer- / wintertime changeover...............................................................120
2.54 Display of PPS communication....................................................................121
Multi-functional inputs..................................................................................................122
2.55 Input H1.......................................................................................................122
2.55.1 Changeover of operating mode ...................................................................123
2.55.2 Minimum flow temperature setpoint TVHw..................................................124
2.55.3 Heat generation lock....................................................................................124
2.55.4 Heat demand DC 0...10 V............................................................................125
2.55.5 Changeover of operating mode ...................................................................125
2.56 Minimum flow temperature setpoint contact H (TVHw) ...............................126
2.57 Maximum value of heat demand signal DC 0...10 V (H1)............................127
2.58 Operating action contact H1 and H2............................................................127
2.59 Input B31/H2................................................................................................128
2.59.1 D.h.w. sensor 2............................................................................................128
2.59.2 Minimum flow temperature setpoint (TVHw)................................................129
2.59.3 Heat generation lock....................................................................................129
2.59.4 Changeover of operating mode ...................................................................129
3 Description of OEM settings ........................................................................130
Heat generating equipment..........................................................................................130
3.1 Minimum limitation of boiler temperature (TKmin
OEM
)..................................130
3.2 Maximum limitation of boiler temperature (TKmax) .....................................130
3.3 Switching differential of the boiler temperature............................................131
3.3.1 Single-stage burner .....................................................................................132
3.3.2 2-stage burner .............................................................................................132
3.4 Minimum limitation of burner running time...................................................133
3.5 Release integral of burner stage 2...............................................................134
3.5.1 Temperature-time integral ...........................................................................134
3.6 Reset integral of burner stage 2 ..................................................................135
3.6.1 Temperature-time integral ...........................................................................135
3.7 Pump overrun time ......................................................................................136
3.8 Operating mode of the boiler .......................................................................137
3.8.1 Extended burner running time .....................................................................137
3.9 Protective boiler start-up..............................................................................138
3.9.1 Impact on 2-position loads...........................................................................138
3.9.2 Impact on modulating loads.........................................................................139
3.9.3 Temperature-time integral ...........................................................................140
3.10 Control of boiler pump .................................................................................141
Heating circuit..............................................................................................................142
3.11 Boost of flow temperature setpoint mixing valve (UEM)..............................142
3.12 Gain factor of room influence (KORR).........................................................143
3.13 Constant for quick setback and optimum start control (KON)......................144
3.13.1 Quick setback without room influence .........................................................144
3.13.2 Optimum start control without influence.......................................................144
3.14 Boost of room temperature setpoint (DTRSA).............................................145
3.14.1 Boost heating...............................................................................................145
3.15 Frost protection for the plant........................................................................146
3.15.1 Frost protection for the plant........................................................................146
3.16 Control mode of actuator .............................................................................147
3.17 Switching differential of actuator..................................................................148
3.17.1 Control of mixing valve actuator ..................................................................148
3.18 Overtemperature protection for the pump heating circuit ............................149
7/184
Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E Landis & Staefa Division Summary 19.04.2001
3.19 Heat gains (Tf).............................................................................................150
3.20 Adaption sensitivity 1 (ZAF1).......................................................................151
3.21 Adaption sensitivity 2 (ZAF2).......................................................................152
3.22 P-band mixing valve (Xp) ............................................................................153
3.23 Integral action time mixing valve (Tn)..........................................................153
3.24 Actuator running time mixing valve..............................................................153
D.h.w. 154
3.25 Maximum nominal setpoint of d.h.w. temperature (TBWmax) ....................154
3.26 Switching differential of d.h.w. temperature (SDBW) ..................................155
3.26.1 d.h.w. temperature control...........................................................................155
3.26.2 D.h.w. temperature control with 2 sensors ..................................................156
3.27 Legionella function ......................................................................................157
3.28 Setpoint of legionella function .....................................................................158
3.29 Discharge protection during d.h.w. heating.................................................159
Service 160
3.30 Continuous display......................................................................................160
3.31 Software version..........................................................................................160
3.32 Device operating hours ...............................................................................161
4 General control processes ..........................................................................162
4.1 Generation of boiler temperature setpoint...................................................163
4.2 Automatic 24-hour heating limit...................................................................164
4.2.1 Without room influence................................................................................164
4.2.2 With room influence.....................................................................................165
4.3 Quick setback with room sensor .................................................................166
4.4 Overtemperature protection mixing heating circuit......................................167
4.5 Attenuated outside temperature..................................................................168
4.6 Composite outside temperature ..................................................................169
4.7 D.h.w. push .................................................................................................170
4.8 Pump and valve kick ...................................................................................171
4.9 Protection against discharging after d.h.w. heating.....................................171
4.10 Overview of pump operation .......................................................................172
4.11 Frost protection ...........................................................................................173
4.11.1 For the boiler ............................................................................................... 173
4.11.2 For the d.h.w................................................................................................173
4.11.3 For the heating circuit..................................................................................174
5 Application examples ..................................................................................175
5.1 Plant types...................................................................................................175
5.1.1 D.h.w. heating with diverting valve..............................................................176
5.2 Supplementary information on the plant types listed...................................176
5.3 Legend to plant types..................................................................................177
5.4 Electrical connections..................................................................................177
6 Dimensions..................................................................................................178
6.1.1 Panel cut-out ...............................................................................................178
6.1.2 Combination of controllers...........................................................................178
7 Technical data.............................................................................................179
8/184 Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
1 Summary
1.1 Brief description
The ALBATROS controllers described in this documentation are designed for integration in mass-produced heat generating equipment and offer the following control choices:
Single- or 2-stage burner, 1 BMU
D.h.w. charging pump or diverting valve
3-position mixing valve and circulating pump
The range of products comprises several units that are complementary in terms of application and scope of functions. The controllers have communication capability and can be combined to form extensive heating systems. For more detailed information about the generation of LPB systems, refer to “Local Process Bus (LPB), Basic Documentation, System Engineering“, document no. CE1P2370E.
1.2 Features
Heating controller for mixing and / or pump heating circuits with:
weather-compensated flow temperature control
weather-compensated flow temperature control with room influence
2 separately controlled heating circuits (mixing or pump heating circuits)
Quick setback and boost heating
Automatic 24-hour heating limit
Automatic summer / winter changeover
Remote operation via digital room unit
The building's thermal dynamics are taken into c onsideration
Automatic adjustment of heating curve to the type of building cons truction and the
heat demand (provided a room unit is connected)
Adjustable flow temperature boost with mixing heating circuit
Floor curing function
1)
Single- or 2-stage burner
BMU
(Boiler Management Unit)
Heat generation lock with contact H
Protective boiler start-up
Protection against boiler overtemperatures (pump overrun)
Adjustable minimum and maximum limitation of boiler temperature (boiler flow
temperature)
Burner cycling protection by observing a minimum burner running time
Frost protection for the house or building, the plant, d.h.w., the heating circuit, and the
boiler
Protection for the pump and the mixing valve through periodic control (pump and valve kick)
Adjustable minimum and maximum limitation of flow temperature
Protection against overtemperatures in the pump heating circuit
Systems
Heating circuits
Heat generation
Protection for the plant
9/184
Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E Landis & Staefa Division 19.04.2001
Two 7-day heating programs
7-day heating program no. 1 for heating circuit 1
7-day heating program no. 2 for heating circuit 2
Separate 7-day heating program for d.h.w. heating
Temperature adjustment with the setpoint knob
Automatic button for efficient operation throughout the year
Chimney sweep function at the touch of a button
Manual operation at the touch of a button
Straightforward selection of operating mode via buttons
Change of operating mode with contact H
Output and input tests to assist c ommissioning and a functional test
Service connection facility for local parameter settings and data logging
D.h.w. heating with a charging pump or diverting valve
D.h.w. heating with one or 2 sensors
Reduced setpoint of d.h.w. temperature
Selectable d.h.w. program
Integrated legionella function
Selectable priority for d.h.w. heating
Adjustable boost of the d.h.w. charging temperature
Automatic d.h.w. push
D.h.w. demand with a sensor or thermostat
Protection against discharging
Communicating via Local Process Bus (LPB)
1)
Communicating via point-to-point interface (PPS)
Integrity of system architecture with all RVA... controllers
1)
Can be extended to include up to 40 heating circuits (with central bus power supply)
1)
Optional remote supervision
Fault status signals and indications (locally, LPB and PPS)
1)
Controllers of other manufacture can deliver their heat demand signal via potential­free H-contact
Controllers of other manufacture can deliver their heat demand in the form of DC 0…10 signals
Analysis with service tool
1)
Logging the number of burner hours run of stages 1 and 2
Logging the number of burner starts of stages 1 and 2
Logging the flue gas temperature
Display of plant diagram no.
1
Not with RVA53.280
Operation
D.h.w.
Systems
1
Logging
10/184 Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
1.3 Range of products
The following units and accessories are designed for use with the ALBATROS range:
RVA63.280 Boiler and heating circuit controller RVA53.280 "
QAA10 Digital room sensor QAA50 Digital room unit QAA70 Digital, multi-functional room unit
QAC31 Outside sensor (NTC 600) QAC21 Outside sensor (Ni 1000) QAZ21 Immersion sensor with cable QAD21 Strap-on temperature sensor Pt1000 Flue gas sensor (third party product)
AGP2S.02M
1
LPB (2 poles) violet AGP2S.02G Room unit (2 poles ) blue AGP2S.06A Sensor (6 poles) white AGP2S.04G Sensor (4 poles) grey AGP2S.02G Room unit PPS2 (2 poles) blue AGP2S.04C Sensor (4 poles) yellow AGP3S.02D Mains(2 poles) black AGP3S.05D Burner (5 poles) red AGP3S.03B Pumps (3 poles) brown AGP3S.03K Actuator (3-poles) green AGP3S.04F Pumps (4 poles) orange AGP3S.03K Actuator 2 (3 poles) green
1
Not with RVA53.280
Controllers
Room units
Sensor
Screw type terminal strips (Rast 5)
11/184
Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E Landis & Staefa Division 19.04.2001
1.4 Field of use
OEMs
Manufacturers of combi and heating boilers
Residential and non-residential buildings with own zone heating and d.h.w. heating
facility
Residential and non-residential buildings with central heating plant
Standard heating systems, such as:
radiator, convector, underfloor and ceiling heating systems, and radiant panels
Suited for
heating plants with 2 heating circuitsdifferent types of heating systems (creation of extensive systems)several heating zones (creation of extensive systems)
With or without d.h.w. heating
Heating boilers with single- or 2-stage oil or gas burners
Gas boilers with BMU
(Boiler Management Unit)
1.5 Product liability
The products may only be used in building services plant and applications as described above
When using the products, all requirements specified in "Technical data" and "Handling" must be satisfied
When using the products in a system, all requirements contained in the documentation “Local Process Bus (LPB), Basic Documentation, System Engineering“ (document no. CE1P2370E) must be satisfied
The local regulations (for installation, etc.) must be complied with
Target market
Types of buildings
Types of heating systems
Heat generating equipment
12/184 Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
2 Handling
2.1 Installation
2.1.1 Regulations for installation
.
Air circulation around the controller must be ensured, allowing the unit to emit the heat produced by it. A clearance of at least 10 mm must be provided for the controller's cooling slots which are situated a the top and bottom of the housing. The space should not be accessible and no objects should be placed there. If the controller is enclosed in another closed (insulating) casing, a clearance of up to 100 mm must be observed on all sides
The controller is designed conforming to the directives for safety class II mounted in compliance with these regulations
Power to the controller may be supplied only after it is completely fitted in the cut-out. If this is not observed, there is a risk of electric shock hazard near the terminals and through the cooling slots
The controller may not be exposed to dripping water
Permissible ambient temperature when mounted and when readyto
operate: 0...50 °C
2.1.2 Mounting location
In the boiler front
In the control panel front
2.1.3 Mounting procedure
Turn off power supply
Pull the prefabricated cables through
the cut-out
Plug the connectors into the respective sockets at the rear of the controller
è Note:
The connectors are coded to make certain they cannot be mixed up.
2373Z05
1. Making the connections
13/184
Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E Landis & Staefa Division 19.04.2001
Check to ensure the fixing levers are turned inward
Check to make certain there is sufficient space between the front panel and the fixing levers
2373Z06
Slide the controller into the panel cut­out without applying any force
è Note:
Do not use any tools when inserting the unit into the cut-out. If it does not fit, check the size of the cut-out and the position of the fixing levers.
2373Z07
Tighten the 2 screws on the front of the controller
è Note:
Tighten the screws only slightly, applying a torque of maximum 20 Ncm. When tightening the screws, the fixing levers automatically assume their correct positions.
2373Z08
2. Check
3. Fitting
4. Fixing
14/184 Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
2.1.4 Required cut-out
The controller's mounting dimensions are 91 x 137 mm Due to the dimensions of the front, however, the standard spacing is 144 mm The controller can be fitted in front panels of different thicknesses
The mechanical mounting facility makes it possible to arrange several controllers in a row in one cut-out. In that case, it is merely necessary to have a wider panel cutout. Also refer to "Dimensions" in Index.
2373Z09
2.1.5 Orientation
To avoid overtemperatures inside the controller, the inclination may be no more than 30° and there must be a clearance of at least 10 mm above and below the cooling slots. This allows the controller to emit the heat generated during operation.
1
0
m
m
m
a
x
.
3
0
°
2
3
7
1
Z
1
6
1
0
m
m
Dimensions of cut-out
Combination of controllers
15/184
Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E Landis & Staefa Division 19.04.2001
2.2 Electrical installation
2.2.1 Regulations for installation
Prior to installing the controller, the power supply must be turned off
The connections for mains and low voltage are separated
The wiring must be made in compliance with the requirements of safety class II. This
means that sensor and mains cables may not be run in the sameduct
2.2.2 wiring
When using prefabricated cables with connectors, the electrical installation is very straightforward, owing to coding.
Rear of controller
2.2.2.1 Connection terminals of RVA63.280
2374A01
4 654M21M M
FN23F234 LF2F45F23
3M143M1
M
B8MB1
H1B2B3MB9MDA6MBDB
B12
A7
MD
B31/H2
B41
F2NY1
Y2
F6
Q2
L
F4
K4
F5
K5
F1
Q3/Y3
Q6
F3
Y5
Y6
2.2.2.2 Connection terminals of RVA53.280
2374A08
4 654M21M M
FN23F234 LF2F45F23
3M143M1
M
B8MB1
H1B2B3
M
B9MDA6
B12
A7
MD
B31/H2
B41
F2NY1
Y2
F6
Q2
L
F4
K4
F5
K5
F1
Q3/Y3
Q6
F3
Y5
Y6
Note
16/184 Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
Terminal Terminals Connector Color
MD Ground room unit bus (PPS) AGP2S.02G blue A7 Room unit bus HC2 (PPS)
- Not used AGP2S.04C yellow B12 Flow sensor mixing valve HC2 M Ground sensors B8 Flue gas sensor B31/H2 D.h.w. sensor 2 / contact H2 AGP2S.04G grey B1 Flow sensor mixing valve HC1 M Ground sensors
- Not used H1 Changeover contact AGP2S.06A white B2 Boiler sensor B3 D.h.w. sensor 1 / control thermostat M Ground sensors
- Not used B9 Outside sensor MD Ground PPS (RG1, BMU) AGP2S.02G blue A6 PPS (RG1, BMU) MB Ground bus (LPB) AGP2S.02M violet DB Data bus (LPB)
Terminal Terminals Connector Color
Y6 Mixing valve HC2 CLOSED AGP3S.03K green Y5 Mixing valve HC2 OPEN F3 Phases Y5 and Y6
- Not used AGP3S.04F orange Q6 Circulating pump mixing heating circuit 2 Q2 Circulating pump mixing heating circuit 1 F6 Phase Q2 Y2 Mixing valve CLOSED AGP3S.03K green Y1 Mixing valve OPEN F2 Phase Y1and Y2 Q3/Y3 D.h.w.charging pump / d.h.w. diverting
valve
AGP3S.03B brown
- Not used F1 Phase Q3/Y3
- Not used AGP3S.05D red K5 Burner stage 2 F5 Phase burner stage 2 K4 Burner stage 1 F4 Phase burner stage 1 L Live AC 230 V (mains connection) AGP3S.02D black N Neutral (mains connection)
Low voltage side
Mains voltage side
17/184
Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E Landis & Staefa Division 19.04.2001
2.3 Commissioning
To commission the controller:
Make certain that mounting and electrical installation are in compliance with the relevant requirements
Make all plant-specific settings as described in section "Parameter settings"
Reset the attenuated outside temperature
Make the functional checks
2.3.1 Functional checks
To facilitate commissioning and fault tracing, the controller allows output and input tests to be made. With these tests, the controller’s inputs and outputs can be checked.
Buttons Explanation Line
1 Press one of the line selection buttons.
This will take you to the programming mode.
2 Press both line selection buttons for at least 3
seconds. This will take you to the programming mode “Heating engineer” and, at the same time, to the output test.
3 Press the + or - button repeatedly, which will take you
one test step further:
Test step 0 All outputs are switched according to normal control
operation
Test step 1 All outputs are deactivated
Test step 2 Burner stage 1 (K4) is activated
Test step 3 Burner stages 1 and 2 (K4 + K5) are activated
Test step 4 D.h.w. charging pump / divertingvalve (Q3/ Y3) is
activated
Test step 5 Heating circuit 1 / boiler pump (Q2) is activated
Test step 6 Mixingvalve HC1OPEN (Y1) isactivated
Test step 7 Mixing valve HC1 CLOSED (Y2) is activated
Test step 8 Heating circuit pump HC2 (Q6) is activated
Test step 9 Mixingvalve HC2OPEN (Y5) isactivated
Test step 10 Mixing valve HC2 CLOSED (Y6) is activated
4 By pressing any of the operating mode or line
selection buttons, you leave the programming mode and thus the output test. Note: If no button is pressed for about 8 minutes, the controller will automatically return to the operating mode selected last.
Prerequisites
Output test
18/184 Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
b)
c)
2374Z03
a)
a) The pointerbelow the symbol indicates the output activated b) The numberindicates the current test step c) The number indicates the selected setting line
Display
19/184
Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E Landis & Staefa Division 19.04.2001
Buttons Explanation Line
1 Press one of the line selection buttons.
This will take you to the programming mode.
2 Press both line selection buttons for at least 3
seconds. This will take you to the programming mode "Heating engineer”.
3
-
Press line selection button UP until you reach line 52. This will take you to the input test.
4 Press the + or - button repeatedly, which will take you
one test step further:
Test step 0 Display of boiler temperature acquired with sensor
B2
Test step 1 Display of d.h.w. temperature acquired with sensor
B3
Test step 2 Display of input B31/H2/B41 according to the
function selected on line 174 [°C or ooo or ---].
Test step 3 Display offlow temperature HC1 acquired with
detector B1
Test step 4 Display offlow temperature HC2 acquired with
detector B12
Test step 5 Display of outside temperature acquired with
sensor B9
Test step 6 Display of room temperature acquired withroom
unit connected to A6
Test step 7 Display of room temperature acquired withroom
unit connected to A7
Test step 8 Display ofthe flue gas temperature acquired with
sensor B8
Test step 9 Display of input H1 according to the function
selected on line 170 [°C / 000 / - - -].
5 By pressing any of the operating mode buttons, you
leave the programming mode and thus the input test. Note: If no button is pressed for about 8 minutes, the controller will automatically return to the operating mode selected last.
Continuous display
The selected sensor values are updated within a maximum of 5 seconds. An open-circuit is displayed as – – –. A short-circuit is displayed as o o o.
Input test
Note
20/184 Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
b)
c)
2374Z04
a)
a) The numberindicates the current test step b) Displayed value of the temperature measured c) The number indicates the selected setting line
Display
21/184
Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E Landis & Staefa Division 19.04.2001
2.4 Parameter settings for the end-user
The following settings can be made to meet the individual needs of the end-user.
Buttons Explanation Line
1
Press one of the line selection buttons UP/DOWN.
This will take you directly to the programming mode "End-user”.
2
Press the line selection buttons to select the required line.
The parameter list on the next 2 pages contains all available lines.
•••
3
Press the + or - button to set the required value. The setting will be stored as soon as you leave the programming mode or change to another line.
The parameter list on the next 2 pages contains all settings that can be made.
4
By pressing any of the operating mode buttons, you leave the programming mode "End-user”.
è Note:
If no button is pressed for about 8 minutes, the controller will automatically return to the operating mode selected last.
Continuou s display
Description
Setting
22/184 Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
2.4.1 Overview of end-user parameters
RVA63.280
RVA53.280
Function
Range
Unit
Resolution
Factory setting
Setting the clock
1 1 Time of day 0...23:59 h / min 1 min 00:00 2 2 Weekday 1...7 Day 1 day 1 3 3 Date (day, month) 01.01...31.12 tt.MM 1 ­4 4 Year 1999...2099 jjjj 1 -
Time switch program 1
5 5 Pre-selection of weekday
1-7 7-day block
1...7 Individual days
1-7 / 1...7 Day 1 day -
66
Switch-on time 1. Period
- -:- -...24:00 h / min 10 min 06:00
77
Switch-off time 1. Period
- -:- -...24:00 h / min 10 min 22:00
88
Switch-on time 2. Period
- -:- -...24:00 h / min 10 min - -:- -
99
Switch-off time 2. Period
- -:- -...24:00 h / min 10 min - -:- -
10 10
Switch-on time 3. Period
- -:- -...24:00 h / min 10 min - -:- -
11 11
Switch-off time 3. Period
- -:- -...24:00 h / min 10 min - -:- -
Time switch program 3 (d.h.w.)
19 19 Pre-selection of weekday
1-7 7-day block
1...7 Individual days
1-7 / 1...7 Day 1 day -
20 20 Switch-on time 1. Period - -:- -...24:00 h / min 10 min 06:00 21 21 Switch-off time 1. Period - -:- -...24:00 h / min 10 min 22:00 22 22 Switch-on time 2. Period - -:- -...24:00 h / min 10 min - -:- ­23 23 Switch-off time 2. Period - -:- -...24:00 h / min 10 min - -:- ­24 24 Switch-on time 3. Period - -:- -...24:00 h / min 10 min - -:- ­25 25 Switch-off time 3. Period - -:- -...24:00 h / min 10 min - -:- -
D.h.w.
26 26 Nominal setpoint of d.h.w. temperature (TBWw)
TBWRw Line 120 TBWmax Line 50 (OEM)
TBWR...TBWmax °C 1 55
Heating circuit
27 27 Reduced setpoint of room temperature
(TRRw)
TRF Frost protection setpoint of room temperature,
line 28
TRN Setpoint knob heating circuit 1 or 2
TRF...TRN °C 0,5 16
28 28 Frost protection setpoint of room temperature
(TRFw)
TRRw Line 27
4...TRRw °C 0,5 10
29 29 Summer / winter c hangeover temperature
(THG)
8...30 °C 0,5 17
30 30 Slope of heating curve (S)
- : - - Inactive(only HC2)
2.5...40 Active
- : - - / 2,5...40 - 0,5 15
33 33 Actual value of room temperature (TRx) 0...50 °C 0,5 ­34 34 Actual value of outside temperature (TAx)
To reset the attenuated outside temperature to TAx, press the + and- buttons simultaneously for 3 seconds.
-50...+50 °C 0,5 -
23/184
Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E Landis & Staefa Division 19.04.2001
RVA63.280
RVA53.280
Function
Range
Unit
Resolution
Factory setting
Heat generating equipment
35 35 Burner hours run stage 1 or BMU (tBR1) 0...65535 h 1 0 36 36 Burner hours run stage 2 (tBR2) 0... 65535 h 1 0 37 37 Number of burner starts stage 1 0... 65535 - 1 0 38 38 Number of burner starts stage 2 0... 65535 - 1 0
Standard values
39 39 Standard times for switching programs 1, 2, 3
(lines 6...11 and 20...25)
To activate, press the + and - buttonssimultaneously for 3 seconds
----
Holidays
40 40 Holiday period 1...8 - 1 1 41 41 Beginning of holiday period
- -.-- No holiday period programmed Month, day
To reset the selected holiday period, press the + and - buttons simultaneously for 3 seconds.
--.--
01.01...31.12
tt.MM 1 -
42 42 End of holiday period
- -.-- No holiday period programmed Month, day
To reset the selected holiday period, press the + and - buttons simultaneously for 3 seconds.
--.--
01.01...31.12
tt.MM 1 -
Service
49 49 Indication of BMU error code
0...255 Error code
0...255 - 1 -
50 50 Indication of faults 0...255 - 1 -
24/184 Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
2.5 Parameter settings for the heating engineer
Configuration and parameter settings to be made by the heating engineer.
Buttons Explanation Line
1
Press one of the line selection buttons UP/DOWN.
This will take you directly to the programming mode "End-user”.
2
Press both line selection buttons for at least 3 seconds.
This will take you directly to the programming mode "Heating engineer”.
3
Press the line selection buttons to select the required line.
The parameter list on the next 2 pages contains all available lines.
•••
4
Press the + or - button to set the required value. The setting will be stored as soon as you leave the programming mode or change to another line.
The parameter list on the next 2 pages contains all settings that can be made.
5
By pressing any of the operating mode buttons you leave the programming mode "Heating engineer”.
è Note:
If no button is pressed for about 8 minutes, the controller will automatically return to the operating mode selected last.
Continuou s display
Description
Setting
25/184
Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E Landis & Staefa Division 19.04.2001
2.5.1 Overview of heating engineer parameters
RVA63.280
RVA53.280
Function
Range
Unit
Resolution
Factory setting
Service values
51 51 Output test
0 Control mode according to the operating state 1 Alloutputs OFF 2 Burnerstage 1 ON K4 3 Burnerstages 1 and 2 ON K4 / K5 4 D.h.w. chargingpump ON Q3/Y3
D.h.w. diverting valve OPEN Q3 / Y3 5 Heating circuit pump 1 Q2 6 Mixing valve 1 open Y1 7 Mixing valve 1 close Y2 8 Heating circuit pump 2 Q6 9 Mixing valve 2 open Y5 10 Mixing valve 2 close Y6
0...10 - 1 0
52 52 Input test
0 Boiler sensor B2 1 D.h.w. sensor 1 B3 2 Display of input B31/H2 B31 3 Flow sensor HC1 B1 4 Flow sensor HC2 B12 5 Outside sensor B9 6 Room sensor 1 RG1, A6 7 Room sensor 2 RG2, A7 8 Flue gassensor B8 9 Display of input H1 H1
0...9 - 1 0
53 53 Display of plant type 1...127 - 1 -
Actual values
55 55 Actual value of flow temperature (TVx)
Input B1/B12
0...140 °C 1 -
56 56 Actual value of boiler temperature (TKx)
Input B2/B4
0...140 °C 1 -
57 - Actual value of common flow temperature 0...140 °C 1 ­61 61 Actual value 1 of d.h.w. temperature (TBWx)
(Higher temperature)
0...140 °C 1 -
62 62 Actual value 2 of d.h.w. temperature (TBWx)
(Lower temperature)
0...140 °C 1 -
63 63 Display of maximum flue gas temperature
(TGxmax)
To make a reset to the current value, press the + and – buttons simultaneously for 3 seconds
0...350 °C 1 -
65 65 Attenuated outside temperature(TAxged) -50...+50 °C 0.5 ­66 66
Composite outside temperature
(Taxgem) -50...+50 °C 0.5 -
67 -
Outside temperature source
- - . - - Nosignal
00.01...14.16 Address
- -:- / 00.01...14.16
-1-
Setpoints
68 68 Display of boiler temperature setpoint 0...140 °C 1 ­69 - Display of common flow temperature setpoint 0...140 °C 1 ­70 70 Display of d.h.w temperature setpoint 0...140 °C 1 ­71 71 Display of nominal room temperature
setpoint
Nominal setpoint incl. room unit readjustment
0...35 °C 0,5 -
73 73 Display of room temperature setpoint (TRw) 0...35 °C 0,5 ­75 75 Display of flow temperature setpoint 0...140 °C 1 -
26/184 Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
RVA63.280
RVA53.280
Function
Range
Unit
Resolution
Factory setting
77 - Floor curing data
Day Flow temperature setpoint
0...32
0...95
­°C
1-
Heat generating equipment
80 80 Type of heat source
0 No heatgeneration or PPS-BMU 1 Single-stage burner 2 2-stage burner
0...2 - 1 2
81 81 Minimum limitation of boiler temperature (TKmin)
Tkmin
OEM
Line 1 OEM
Tkmax Line2OEM
TKmin
OEM
...TKmax °C 1 40
82 82 Extra heating for the bathroom
(HK2 ist pump heating circuits) 0Inactive 1Active
0/1 - 1 0
Heating circuit
100 100 Parallel displacement of heating curve -4,5...+4,5 °C (K) 0,5 0,0 101 101 Room influence
0Inactive 1Active
0/1 - 1 1
102 102 Switching differential of the room temperature
(SDR)
--.- Inactive
0.5...4.0 Active
- -:-...4,0 °C (K) 0,5 - -:-
103 103 Operating mode of room unit
0 Parallel action: Roomunit 1 on heating circuit 1
Room unit 2 on heating circuit 2
1 Crossed action: Room unit 1 on heating circuit 2
Room unit 2 on heating circuit 1
2 Serial action: Room unit 1 on heating circuits1
and 2
0...2 - 1 0
104 104 Room unit values
0 Parallel action: Roomunit 1 on heating circuit 1
Room unit 2 on heating circuit 2
1 Crossed action: Room unit 1 on heating circuit 2
Room unit 2 on heating circuit 1
2 Serial action: Room unit 1 on heating circuits1
and 2
0...2 - 1 0
105 105 Minimum limitation of flow temperature setpoint
(TVmin)
TVmax Line 107
8...TVmax °C 1 8
107 107 Maximum limitation of flow temperature setpoint
(TVmax)
Tvmin Line 105
TVmin...95 °C 1 80
109 109 Maximum forward shift of optimum start control
0 forwardshift/OFF
00:00...06:00 hh:mm 10 min 00:00
110 110 Maximum forward shift of optimum stop control
0 Noforwardingshift
00:00...06:00 hh:mm 10 min 00:00
113 113 Type of building construction
0Heavy 1 Light
0/1 - 1 1
114 114 Adaption of heating curve
0Inactive 1Active
0/1 - 1 1
115 115 Gain of locking signal 0...200 % 1 100
27/184
Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E Landis & Staefa Division 19.04.2001
RVA63.280
RVA53.280
Function
Range
Unit
Resolution
Factory setting
116 - Floor curing
0Off 1 Functional heating 2 Floor curing 3 Functional and floor curing heating
0...3 - 1 0
D.h.w.
120 120 Reduced setpoint of d.h.w. temperature (TBWR)
TBWw Line 26
8...TBWw °C 1 40
121 121 D.h.w. heating program
0 24 h/day 1 Heating program with forward shift 2 Timeswitchprogram3
0...2 - 1 1
123 - Assignment of d.h.w. heating
0 Local heating circuit 1 All heatingcircuits in the segment 2 All heatingcircuits in the system
0...2 - 1 2
124 124 D.h.w. charging
0 Once perday with a forward shift of 2.5 hours 1 Severaltimesperdaywitha1hforwardshift
0/1 - 1 1
125 125 Type of d.h.w. demand
0Sensor 1 Control thermostat
0/1 - 1 0
126 126 Boost of the flow temperature setpoint for d.h.w.
heating (UEBW)
0...30 °C (K) 1 16
127 127 D.h.w. priority
0 Absolute (mixing and pump heating circuit) 1 Shifting (mixing and pump heating circuit) 2 None (parallel) 3 Mixing heating circuit (shifted)
Pump heating circuit (absolut)
0...3 - 1 1
128 128 Controlling element for d.h.w.
0 Charging pump 1 Diverting valve
0/1 - 1 0
LPB / system
140 - LPB device address
0 Standalone
1...16 Deviceaddress (system)
0...16 - 1 0
141 - LPB segment address
0 Heat source segment
1...14 Heat consumption segments
0...14 - 1 0
142 - LPB power supply
0 Off (centralbus power supply
1) Auto (buspower supply via controller)
0/1 - 1 1
143 - Display of LPB power supply On / OFF - ­145 - Range of action of central changeover
0 In the segment 1 In thesystem (if segment address = 0)
0/1 - 1 1
146 - Automatic summer / winter changeover
0 Local changeover 1 Central changeover of all heating circuits
0/1 - 1 0
147 - Central stand-by switch
1)
0Off 1ON
0/1 - 1 0
148 - Clock mode
0 Autonomous clock 1 System time without adjustment 2 (System time with adjustment) 3 System clock (master)
0...3 - 1 0
28/184 Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
RVA63.280
RVA53.280
Function
Range
Unit
Resolution
Factory setting
150 150 Winter- / summertime changeover 01.01...31.12 tt.MM 1 25.03 151 151 Summer- / wintertime changeover 01.01...31.12 tt.MM 1 25.10 155 155 Display of PPS communication (A6)
0 0 0 Short-circuit
- - - No communication
0...255 OK communication
000/---/0...255 - 1 -
156 156 Display of PPS communication room unit 2 (A7)
000 Short-circuit
- - - No communication, no room unit
0...255 Room unit number, communication OK
0...255 - 1 0
Multifunktional inputs (H1) (H2/B31)
170 170 Input H1
0 Changeover of operating mode of all HC and d.h.w. 1 Changeover of operating mode of all HC 2 Min. flow temperature setpoint(TVHw) 3 Heat generation lock 1 Demand for heat DC 0...10 V 5 Changeover of operating mode HC1 6 Changeover of operating mode HC2
0...6 - 1 0
171 171 Minimum flow temperature setpoint contact H
(TVHw)
...TKmax Line 2 OEM
8...TKmax °C 1 70
172 172 Maximum value of heat demand signal (DC 0...10
V) H1
5...130 °C 1 100
173 173 Operating action contacts H1 and H2
0N.C. 1N.O.
0/1 - 1 1
174 174 Input B31/H2
0 D.h.w. sensor 2 1 Min. flow setpoint (TVHw) 2 Heat generation lock 1 Changeover of operating mode HC1 4 Changeover of operating mode HC2
0...4 - 1 0
1)
This line is active only if the unit is addressed as the heat generation master. Also refer to "LPB device address" in Index.
29/184
Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E Landis & Staefa Division 19.04.2001
2.6 Parameter settings for the OEM
Boiler-specific settings and protective functions for the boiler manufacturer.
Buttons Explanation Line
1
Press one of the line selection buttons UP/DOWN.
This will take you directly to the programming mode "End-user”.
2
9s
Press both line selection buttons for at least 9 seconds.
A special display for entering the code will appear.
3
CODE
Press buttons
and to enter the required
combination of the access code.
If the combination of buttons is correct, you reach the programming mode “OEM”.
è Wrong code: If the code has been entered incorrectly, the display will change to the "Parameter settings for the heating engineer”.
4
Press the line selection buttons to select the required line.
The parameter list on the next 2 pages contains all available lines.
•••
5
Press the + or - button to set the required value. The setting will be stored as soon as you leave the programming mode or change to another line.
The parameter list on the next 2 pages contains all settings that can be made.
6
By pressing any of the operating mode buttons you leave the programming mode “OEM”.
è Note:
If no button is pressed for about 8 minutes, thecontroller will automatically return to the operating mode selected last.
continuo us display
2374Z10
Whether correct or incorrect, each push of a button will be adopted asa digit of the code. As a confirmation, the respective digit changes to 1.
Description
Setting
Example
30/184 Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
2.6.1 Overview of OEM parameters
RVA63.280
RVA53.280
Function
Range
Unit
Resolution
Factory setting
Heat generating equipment
1 1 Min. limitation of boiler temperature OEM
(TKmin
OEM
)
Tkmin Line 81
8...TKmin °C 1 40
2 2 Maximum limitation of boiler temperature
(TKmax)
Tkmin Line 81
TKmin...120 °C 1 80
3 3 Switching differential of the boiler temperature 0...20 °C (K) 1 8 4 4 Min. limitation of burner running time 0...10 min 1 4 5 5 Release limit (integral) of burner stage 2 0...500 °C (K) min 1 50 6 6 Reset limit (integral) of burner stage 2 0...500 °C (K) min 1 10 8 8 Pump overrun time
(after burner OFF)
0...20 min 1 5
9 9 Operating mode of boiler
0 Continuous mode: Ohneverlängerter
burner running time
1 Automatic mode: Ohne verlängerter
burner running time
2 Automatic mode: Mit verlängerter
burner running time
0...2 - 1 1
10 10 Protective boiler start-up
0No 1Yes
0/1 - 1 1
12 12 Control of boiler pump
0 Mixed temperature requisition 1 Parallel to burner operation
0/1 - 1 0
Heating circuit
30 30 Boost of flow temperature setpoint mixing
valve (UEM)
0...50 °C (K) 1 10
31 31 Gain factor of room influence (KORR) 0...20 - 1 4 32 32 Constant for quick setback and optimum start
control (KON)
0...20 - 1 2
33 33 Boost of room temperature setpoint (DTRSA)
(with boost heating)
0...20 °C (K) 1 5
34 34 Frost protection for the plant
0Inactive 1Active
0/1 - 1 1
35 35 Control mode of actuator (Y1 / Y5)
0 2-position (Y1) / (Y5) 1 3-position (Y1,Y2 / Y5,Y6)
0/1 - 1 1
36 36 Switching differential of actuator
For 2-position mixing valve
0...20 °C (K) 1 2
37 37 Overtemperature protection for the pump heating
circuit
0Inactive 1Active
0/1 - 1 1
38 38 Heat gains (Tf) -2...+4 °C 0,1 0 39 39 Adaption sensitivity 1 (ZAF1) 1...15 - 1 15 40 40 Adaption sensitivity 2 (ZAF2) 1...15 - 1 15 41 41 P-band mixing valve (Xp) 1...100 °C (K) 1 32 42 42 Integral action time mixing valve (Tn) 10...873 s 1 120
Loading...
+ 154 hidden pages