5/166
Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E
HVAC Products Contents 15.07.2002
4.34 Maximum forward shift of optimum start control............................................ 82
4.34.1 Optimum start control .................................................................................... 83
4.34.2 Without room influence.................................................................................. 83
4.34.3 With room influence....................................................................................... 83
4.35 Maximum forward shift of optimum stop control ............................................ 84
4.35.1 Optimum stop control ....................................................................................84
D.h.w. values .................................................................................................................85
4.36 Reduced setpoint of the d.h.w. temperature.................................................. 85
4.37 Release of d.h.w. heating .............................................................................. 85
4.37.1 24-hour operation - Setting 0......................................................................... 86
4.37.2 Operation according to heating program(s) with forward shift - Setting 1 ..... 86
4.37.3 Operation according to the d.h.w. time switch program - Setting 2 ...............87
4.38 Switching program circulating pump.............................................................. 87
4.39 Assignment of d.h.w. heating ........................................................................88
4.40 Number of d.h.w. charging cycles .................................................................88
4.40.1 Once per day with a forward shift of 2.5 hours Setting 0............................... 89
4.40.2 Several times per day with a forward shift of 1 hour Setting 1 ......................89
4.41 Type of d.h.w. demand .................................................................................. 89
4.42 Boost of the flow temperature setpoint for d.h.w. ..........................................90
4.43 D.h.w. priority................................................................................................. 91
4.43.1 Shifting priority............................................................................................... 92
4.44 Demand for heat with reduced d.h.w. setpoint ..............................................94
Cascade settings ...........................................................................................................95
4.45 Changeover of boiler sequence in a cascade ...............................................95
4.46 Exemption from automatic changeover of the boiler sequence..................... 96
4.47 Lead boiler with a fixed changeover of the boiler sequence.......................... 97
4.48 Switch-on delay lag boilers............................................................................ 98
4.49 Restart lock of BMUs..................................................................................... 98
LPB / system ................................................................................................................. 99
4.50 LPB device address....................................................................................... 99
4.51 LPB segment address ................................................................................. 100
4.52 LPB power supply........................................................................................ 100
4.53 Displaying the LPB power supply ................................................................101
4.54 Displaying the LPB communication ............................................................. 101
4.55 Range of action of central changeover........................................................ 102
4.56 Automatic summer / winter changeover ...................................................... 102
4.57 Central standby switch ................................................................................103
4.58 Clock mode.................................................................................................. 103
4.59 Winter- / summertime changeover ..............................................................104
4.60 Summer- / wintertime changeover............................................................... 105
Input H1 . .............................................................................................................. 106
4.61 Input H1 ....................................................................................................... 106
4.61.1 Changeover of operating mode (remote telephone switch) - Setting 0 / 1 107
4.61.2 Minimum setpoint of flow temperature contact H1 ......................................108
4.61.3 Heat generation lock - Setting 3 ................................................................ 108
4.61.4 Demand for heat - Setting 4 ......................................................................109
4.62 Minimum setpoint of flow temperature contact H1 ......................................110
4.63 Maximum value of heat demand signal DC 0...10 V (H1) ...........................111
4.64 Operating action of the contact connected to H1 ........................................111
5 Description of the OEM settings .................................................................. 112
Heat generation values................................................................................................ 112
5.1 Minimum limitation of the boiler temperature setpoint OEM (TKmin
OEM
).....112