CE1N3070en
01.03.2010
Building Technologies
3
070
RDH10RF RCR10/433
Wireless room temperature
controller with LCD
RDH10RF/SET
Non-programmable, for heating or cooling systems
• Operating modes: Automatic, Comfort, Energy Saving, and Frost Protection
• LCD-Display 50 x 45 (W x H)
• RDH10RF transmitter, battery-powered
• RCR10/433 receiver, mains powered
• Communication of the set is bonded ex factory
Use
The RDH10RF is used to control the room temperature in heating or cooling systems.
Typical applications:
• Homes
• Residential buildings
• Schools
• Offices
The controller can be used together with the following equipment:
• Thermal valves or zone valves
• Combi boilers
• Gas or oil burners
• Fans
• Pumps

2/12
Siemens Room temperature controllers CE1N3070en
Building Technologies 01.03.2010
Functions
The controller acquires the room temperature with its integrated sensor.
Q14
T[°C]
ON
OFF
W
SD
3031D01
T Room temperature
SD Switching differential (1 K)
W Room temperature setpoint
L1 Output signal for heating
Y2
T[°C]
ON
OFF
SD
3011D02
T Room temperature
SD Switching differential (1 K)
W Room temperature setpoint
L2 Output signal for cooling
The RDH10RF provides room temperature control only.
The digital display displays the actual room temperature and the comfort temperature
setpoint. The triangle symbol appears when the heating output is active.
Setpoints and information required for operating mode changeover are retained when
exchanging batteries. The values must be checked though.
Ordering
Please provide the name and product number when ordering: Room temperature controller RDH10RF/SET.
Valves and actuators are to be ordered as separate items.
Equipment combinations
Type of unit Product number Data sheet
Electromotoric actuator
SFA21...
4863
Electrothermal actuator (for radiator valves)
STA21...
4877
Electrothermal actuator (for small valves 2.5 mm)
STP21...
4878
2- or 3-port zone valve
MXI/MVI421…
4867
Electromotoric actuator for zone valves V..146..
SUA21
4830
Electric actuator
SUA11/22
4832
Air damper actuator
GDB…
4624
Air damper actuator
GSD/GQD…
4606
Air damper actuator
GXD…
4622
Function diagram
Temperature sensor
Display
Backup
L1
L2

3/12
Siemens Room temperature controllers CE1N3070en
Building Technologies 01.03.2010
Mechanical design
The controller consists of 4 parts:
• Plastic housing with digital display accommodating the electronics, operating ele-
ments and built-in room temperature sensor
• Baseplate (mounting base)
• Removable battery compartment
• Fold-out stand
The housing engages in the baseplate and snaps on. There is a reset button on the
rear of the unit.
1 Room temperature display in °C
2 Indicates a heat request
3 Temperature setting knob
4 Battery compartment
5
Comfort temperature setpoint
6
RF
TEST Indicates RF signal test
7
Indicates low battery power; replace batteries
Key

4/12
Siemens Room temperature controllers CE1N3070en
Building Technologies 01.03.2010
Mechanical design
The RCR10/433 receiver is located in a plastic housing with LEDs and buttons.
Signal display LED
OVERRIDE button
LEARN button
Relay display LED
OVERRIDE & LEARN
button together = RESET
function
RCR10/433
The RDH10RF is located in a plastic housing. Two buttons are visible on the rear side
when removing the baseplate.
Test button
Learn button
Test & Learn buttons together = RESET function
RDH10RF

5/12
Siemens Room temperature controllers CE1N3070en
Building Technologies 01.03.2010
Notes
Mount the room temperature controller in a location where the air temperature can be
measured as accurately as possible without being adversely affected by direct solar
radiation or other sources of heat or cooling.
The controller is delivered with a fold-out stand and may be used as a "mobile" device
(Note: Pay attention to mounting location).
Mounting height is approximately 1.5 m above the floor.
The unit can be fitted to a recessed conduit box.
Fix the baseplate prior to mounting the controller. The receiver does not require a
baseplate. Connect the electrical connections and fit and secure the receiver in compliance with local regulations (also refer to the separate mounting instructions).
Mount the controller on a flat wall.
If there are thermostatic radiator valves in the reference room, set them to their fully
open position.
For commissioning please refer to the Operating Instruction CE1B3070xx
Controller and receiver are maintenance-free except for the controller battery.
If battery symbol appears, the batteries are almost empty and must be replaced.
Simultaneously press the TEST and LEARN buttons on the rear side of the controller to
reset it (reset function).
Simultaneously press the OVERRIDE and LEARN buttons to reset the receiver (reset
function).
All individual settings are reset to the default values.
Mounting, installation
and commissioning
Maintenance
Change of batteries
Reset

6/12
Siemens Room temperature controllers CE1N3070en
Building Technologies 01.03.2010
Override allows for temporarily overwriting the active value from the sender.
Override responds differently depending on the radio connection (normal or fault).
Example A: Normal connection between sender and recipient
Press the OVERRIDE button to overwrite the value for ca. 14 minutes. The value
then returns to the setpoint.
Example B: Faulty connetion between sender and recipient
Press the OVERRIDE button to permanently overwrite the value. The value
returns to the setpoint after the connection between sender and recipient works
again.
RF state RF LED
Power up (First 5 seconds)
Flash RED + GREEN (Amber)
(5 seconds)
Power up (After 5 seconds)
RED
Press OVERRIDE switch Flash RED + GREEN (Amber)
(5 seconds)
Learning period No LED
Software reset RED
RF receive GREEN
No RF within last 25 minutes RED
Manual override
(RF receive)
Flash GREEN
Manual override
(No RF receive)
Flash RED
Relay state Relay LED
From OUT to ON (First 5 seconds) Flash YELLOW
ON YELLOW
From ON to OFF (After 5 seconds) Flash YELLOW
OFF OFF
OVERRIDE
RF LED
Relay LED

7/12
Siemens Room temperature controllers CE1N3070en
Building Technologies 01.03.2010
Technical data
Operating voltage DC 3 V (2 x 1.5 V AA alkaline batteries)
Battery life >1 year (AA alkaline batteries)
Internal:
Thermistor 10 kΩ ± 1% at 25 °C
Switching differential SD 1 K (fixed)
Setpoint setting range 5…30 °C
Factory setting comfort setpoint 20 °C
Resolution of settings and displays
Setpoints 0.5 °C
Actual value displays 0.5 °C
Operation IEC 721-3-3
Climatic conditions Class 3K5
Temperature 0…+40 °C
Humidity <90% r.h.
Transport IEC 721-3-2
Climatic conditions Class 2K3
Temperature -25…+60 °C
Humidity <95% r.h.
Mechanical conditions Class 2M2
Storage IEC 721-3-1
Climatic conditions Class 1K3
Temperature -10…+60 °C
Humidity <90% r. h.
conformity to
EMC directive 2004/108/EC
Low-voltage directive 2006/95/EC
Radio equipment 1999/5/EC
N474
C-tick conformity to
Test standards and requirements EN 61000-6-3, AS/NZS 4251.1: 1999
Test standards for radio equipment AS/NZS 4268: 2003
Product safety
Automatic electrical controls for EN 60 730-1 and
household and similar use EN 60 730-2-9
Information technology equipment Safety - General Requirements EN 60950-1
Generic standards - Compliance to
lower power electronic apparatus EN 50371-1
Electromagnetic compatibility and radio
spectrum matters–Short range devices EN 300220-3 V1.1.1
Electromagnetic compatibility and radio
spectrum matters – EMC EN 301489-3 V1.4.1
Safety class III as per EN 60950-1
Pollution degree 2
Degree of protection of housing IP20
Weight (incl. package)
RDH10RF/SET 515 g
Color of housing front Signal-white RAL 9003
Housing material ABS (LCD lens: PC)
Power supply
Sensor inputs
Operational data
Environmental conditions
Standards
General

8/12
Siemens Room temperature controllers CE1N3070en
Building Technologies 01.03.2010
Receiver RCR10/433
Operating voltage
Power
AC 230 V +10/−15%
<10 VA
Frequency 50...60 Hz
Switching capacity of relays
Voltage
Current
AC 24...250 V
8 (3) A
Relay contacts
Switching voltage Max. AC 250 V
Min. AC 24 V
Switching current Max. 8 A res., 3 A ind.
At AC 250 V Min. 200 mA
Contact life at AC 250 V Guide value:
At 5 A res. 1 x 10
5
cycles
Insulating strength
Between relay contacts and coil AC 5,000 V
Between relay contacts (same pole) AC 2,500 V
Connection terminals Screw terminals
For solid wires 2 x 1.5 mm
2
For stranded wires 1 x 2.5 mm
2
(min. 0.5 mm2)
Operation
Climatic conditions
Temperature
Humidity
IEC 60 721-3
Class 3K3
0...+45 °C
<85% r.h.
Storage and transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
IEC 60 721-3
Class 2K3
− 25...+70 °C
<93% r.h.
Class 2M2
conformity
EMC directives
Low-voltage directives
Radio equipment
2004/108/EC
2006/95/EC
1999/5/EC
Product safety
Automatic electrical controls for EN 60 730-1 and
household and similar use EN 60 730-2-9
Information technology equipment Safety - General Requirements EN 60950-1
Generic standards - Compliance to
lower power electronic apparatus EN 50371-1
Electromagnetic compatibility and radio
spectrum matters–Short range devices EN 300220-3 V1.1.1
Electromagnetic compatibility and radio
spectrum matters – EMC EN 301489-3 V1.4.1
Approval
In the following countries
All ECC countries,
Norway, Iceland and Switzerland
Safety class
Degree of pollution
II as per EN 60 730
2
Color
Unit front
Base
Signal-white RAL 9003
Gray RAL 7035
Dimensions 83x104x32 mm
General unit data
Outputs
Switching outputs
(LX, L1, L2)
Electrical connections
Environmental conditions
Standards

9/12
Siemens Room temperature controllers CE1N3070en
Building Technologies 01.03.2010
Connection diagram
L Live, AC 230 V
Lx Live, AC 24…250 V
L1 N.O. contact, AC 24…250 V / 8 (3) A
L2 N.C. contact, AC 24…250 V / 8 (3) A
M1 Circulating pump
N Neutral conductor
Nx Neutral conductor
N2 Receiver RCR10/433
Y1 Actuating device
L – N AC 230 V / Lx – Nx AC 24…250 V
Application examples
Wireless room temperature controller with
receiver control of a gas-fired wall-hung
boiler
Wireless room temperature controller with
receiver control of atmospheric gas burner
Y1
2252S04
M1
N2
T
N1
T
N1
2255S05
E1
N2
Wireless room temperature controller with
receiver control of a heating circuit pump
(precontrol by manual mixing valve)
Wireless room temperature controller with
receiver control of cooling equipment
F1 Thermal reset limit thermostat
F2 Safety limit thermostat
M1 Circulating pump
E1 Cooling equipment
N1 Room temperature controller RDH10RF
N2 Receiver RCR10/433
Y1 3-port valve with manual adjustment
Y2 Magnetic valve

10/12
Siemens Room temperature controllers CE1N3070en
Building Technologies 01.03.2010
Dimensions
Room temperature
controller
Room temperature
controller mounting
plate
Room temperature
controller with foldout stand

11/12
Siemens Room temperature controllers CE1N3070en
Building Technologies 01.03.2010
Room temperature
receiver with mounting plate

12/12
Siemens Room temperature controllers CE1N3070en
Building Technologies 01.03.2010
© 2007-2010 Siemens Schweiz AG Subject to change