Operating Instructions
RDG100/110/140/160
RDG – the electronic room thermostat that allows you to set the ideal room temperature you want. The thermostat satisfies your individual needs in all operating modes: Comfort, Economy and Protection. The fan operates either in Automatic mode or at the selected speed when using Manual mode. You can either rely on the factory settings or make adjustments that suit your individual needs.
Main display
Room temperature in
Room temperature
degrees Celsius Room temperature in degrees Fahrenheit Button lock active
Alert indicator
Condensation in the room
Temporary timer function active Additional user information
Operating mode button
Fan mode button
Rotary knob Manual:
s
Operating mode
Heating mode
Electric heater on
Cooling mode
Comfort
Economy Protection mode: Protection against frost Indicator for selecting mode
Fan mode
Automatic
Changing the room temperature
The room temperature setpoint can be adjusted with the rotary knob when
Comfort mode
Turn the rotary knob clockwise (+) to increase, or counterclockwise (-) to
decrease the current room temperature setpoint for Comfort mode
The setting range is from 5...40 °C, unless limited by parameters P09 and P10 (for parameter settings, see reverse side).
is active
Adjusting the fan speed
Note: If desired, Protection mode. Use P15 to set the fan speed in dead zone.
Press the fan mode button until the desired fan mode is reached
In Automatic mode
dependin temperature reaches the setpoint, the fan stops (factory setting) or runs at low speed (P15).
In Manual mode, the fan operates independentl
speed: Low / medium / high
ou can change the fan mode selector option via P03: Manually only, or manually includin
on the setpoint and the actual room temperature. When the room
, the fan speed is automatically selected by the thermostat
Selecting Comfort mode
Press the operating mode button until symbol appears, indicating that
Comfort mode is selected
Low / medium / high
and always runs at the same
In Comfort mode, the thermostat maintains the setpoint which can be readjusted
with the rotary knob
Selecting Protection mode
The setpoints for Protection mode can be changed by your HVAC installer if desired: Changes made by installer: Frost protection: ____________ ˚C Heat protection: ______________˚C
Selecting Economy mode
In Economy mode, the room temperature is maintained at a lower or higher setpoint, thus savin energy and money.
Important: The setpoint for Economy can be set to OFF. This means that the thermostat is deactivated! Risk of frost, i.e. no protective heating or cooling function is provided!
Energy saving tips without sacrificing comfort:
• Air out rooms for short periods of time only, but properly, with the windows wide open
• Never allow the room temperature to exceed 21 °C through heating, and to fall below 25.5 °C through cooling
Button lock
Press the operating mode button until symbol appears, indicating that
Protection mode is selected
In Protection mode, the plant stops operating. If the room temperature falls
below 8 °C, heating is switched on however to protect the room against frost
When selecting Economy, make sure that parameter P02 is set to 2
Press the operating mode button until symbol
You can chan
(for parameter settings, see reverse side)
To lock or unlock the buttons manually, press and hold the fan mode button for
3 seconds. The buttons are locked or unlocked in this manner if P14 is set to 2
If P14 is set to 1, the thermostat automatically locks the buttons 10 seconds after
the last adjustment
e the preselected setpoint by adjusting parameters P11 and P12
appears
y
g
Temporary timer for extended presence or absence
The Comfort and Economy modes can be temporarily extended by 0.5 to 9.5 hours using the temporary timer.
1. To set the temporar
timer, press and hold the operating mode button for maximum 3 seconds. While holding the button, turn the rotary knob clockwise or counterclockwise as required. a) Turn the rotary knob clockwise to extend Comfort mode.
Display:
0....+9:30
b) Turn the rotary knob counterclockwise to extend Economy mode.
Display:
2. Release the operating mode button and the mode is temporarily changed, indicated by
After the temporary timer has elapsed, the thermostat will resume operation in the operatin
0....-9:30
.
mode
that was active before:
Extended Comfort mode New operating mode = Economy Extended Economy mode New operating mode = Comfort
If Economy cannot be selected via the operating mode button (P02≠2), Protection mode will be
used for extended absence instead!
The temporary timer function is aborted whenever a new setting is made
Note: Extended Comfort mode is also possible when an external contact such as a keycard switch or central time clock is active To enable this function, the time for the extended period must be set via parameter P68.
Changing from heating to cooling mode
Depending on the type of plant, the changeover from heating to cooling (or vice
versa) is made either automatically by a changeover sensor or a remote change­over switch, or manually by pressing the operating mode button (see parameter P01)
To select cooling or heating manually (P01=2), press the operating mode button
until the desired mode appears
With automatic changeover or continuous heating / cooling, symbols
indicate that the system currently operates in heating or cooling mode
With manual changeover, symbol
appears, indicating that the system currently
operates in heating or cooling mode
/
Control parameters
If you want to change control parameters, proceed as follows:
1. Press both buttons simultaneously for at least 3 seconds.
2. Release them and, within 2 seconds, press the right button again for 3 seconds. The display shows P01.
3. Select the required parameter by turning the rotary knob.
4. Press button
(OK). The current value of the selected parameter starts blinking and can be
changed by turning the rotary knob.
5. Press button
If you wish to adjust additional parameters, repeat steps 3 through 5, or press
(OK) to confirm the adjusted value, or (Esc) to cancel the change.
(Esc) to leave the
parameter setting mode.
Parameter list
No. Parameter name Default value Setting range Adj.
P01 Control sequence 2-pipe / 2-
stage: 1 = cooling only
4-pipe:
0 = heating only 1 = cooling only 2 = H/C changeover, manually 3 = H/C changeover, auto 4 = heating and cooling
4 = H and C
P02 Mode selection via operating
mode button
1
1 = Comfort / Protection mode 2 = Comfort / Economy / Protection mode
P03 Mode selection via fan mode
button
0 0 = Auto / Manual
1 = Manual 2 = Auto / Manual / Protection mode
P04 Selection of °C or °F 0 0 = °C
1 = °F P05 Sensor calibration 0.0 K – 3…3 K P06 Standard temperature display 0 0 = Room temperature
1 = Setpoint P07 Additional display information 0 0 = --- (no display)
1 = ˚C and ˚F P08 Comfort basic setpoint 21 °C 5…40 °C P09 Minimum setpoint limitation in
5 °C 5…40 °C
Comfort mode
P10 Maximum setpoint limitation in
35 °C 5…40 °C
Comfort mode
P11 Setpoint for heating in Economy
15 °C OFF, 5 °C…WcoolEco
mode (WheatEco)
P12 Setpoint for cooling in Economy
30 °C OFF, WheatEco…40°C
mode (WcoolEco)
P13 Electric heater in cooling mode ON OFF = Disabled
ON = Enabled P14 Button lock 0 0 = Disabled
1 = Automatic
2 = Manual P15 Fan speed in dead zone
(Comfort mode)
The control parameters displayed depend on the DIP switch settings made
0 0 = Disabled
1 = Stage 1 (H or C)
2 = Stage 1 (Cooling only)