This document may be duplicated and distributed only with the express permission of
Siemens, and may be passed only to authorized persons or companies with the
required technical knowledge.
1.3.2 Quality assurance
This document was prepared with great care.
· The contents of this document are checked at regular intervals
· Any corrections necessary are included in subsequent versions
· Documents are automatically amended as a consequence of modifications and
corrections to the products described
Please make sure that you are aware of the latest document revision date.
If you find lack of clarity while using this document, or if you have any criticisms or
suggestions, please contact the Product Manager in your nearest branch office. The
addresses of the Siemens Regional Companies are available at
www.siemens.com/sbt.
1.3.3 Document use/request to the reader
Before using our products, it is important that you read the documents supplied with or
ordered at the same time as the products (equipment, applications, tools, etc.)
carefully and in full.
We assume that persons using our products and documents are authorized and
trained appropriately and have the technical knowledge required to use our products
as intended.
More information on the products and applications is available:
· From the Siemens branch office near you www.buildingtechnologies.siemens.com
or from your system supplier
· From the support team at headquartersfieldsupport-zug.ch.sbt@siemens.com if
there is no local point of contact
Siemens assumes no liability to the extent allowed under the law for any losses
resulting from a failure to comply with the aforementioned points or for the improper
compliance of the same.
– Operating mode switchover contact (keycard)
– Automatic heating/cooling changeover sensor
– External room temperature or return air temperature
– Dewpoint sensor
– Electric heater enable
– Fault input
– Supply air temperature sensor (RDG160T..)
· Advanced fan control function, i.e. fan kick, fan start, selectable fan operation
(enable, disable or depending on heating or cooling mode)
· Purge function together with 2-port valve in a 2-pipe changeover system
· Reminder to clean filters
· Floor heating temperature limit
· Minimum and maximum supply air temperature limitation (RDG160T..)
· Reloading factory settings for commissioning and control parameters
· 7-day time program: 8 programmable timers to switch over between Comfort and
Economy mode (RDG100T, RDG160T..)
· Infrared remote control (RDG100T, RDG160T..)
· Selectable relay function (RDG160T..)
– For switching OFF external equipment OFF during Protection mode
– For switching ON external equipment (e.g. pump) during H/C demand
– Output heating/cooling sequence
· Wizard function to select working temperature unit °C or °F (RDG160TU,
RDG110U)
2.2 Types and features
Product
no.
Number of control outputs
On/Off PWM 3-posDC0..10
Operating voltage
RDG100
RDG100T
RDG110
RDG110U
RDG160T
RDG160TU
1)
Infrared remote control must be ordered as a separate item
2)
ECM fan output DC 0…10 V
3)
On/Off, PWM or 3-position (triac outputs)
4)
Relay output (SPDT)
5)
Can be disabled via P02 (or via DIP switches on RDG160T..)
Infrared remote controlIRA2113059
Cable temperature sensor or changeover
sensor, cable length 2.5 m (8 feet)
NTC (3 kW at 25 °C (77 °F))
Room temperature sensor
NTC (3 kW at 25 °C (77 °F))
Cable temperature sensor,
cable length 4 m (13 feet)
NTC (3 kW at 25 °C (77 °F))
Condensation motionQXA2601/
Electromotoric On/Off valve and actuator
(only available in AP, UAE, SA and IN)
Electromotoric On/Off actuatorSFA21..4863
Electromotoric On/Off actuatorSFP21..4863
QAH11.11840
QAA321747
QAP1030/UFH 1854
QXA2602/
QXA2603/
3302
QXA2604
MVI../MXI..
A6V11251892
On/Off and PWM actuators
3-position actuators
DC 0…10 V actuators
Zone valve actuators
(only available in AP, UAE, SA and IN)
*)
Thermal actuator (for radiator valves)
AC 230 V, NO
Thermal actuator (for radiator valves)
AC 24 V, NO
Thermal actuator AC 230 V
(for small valves 2.5 mm (0.1")), NC
Thermal actuator AC 24 V
(for small valves 2.5 mm (0.1")), NC
Electrical actuator, 3-position
(for radiator valves)
Electrical actuator, 3-position
(for 2- and 3-port valves/V..P45)
Electrical actuator, 3-position
(for small valves 2.5 mm (0.1"))
Electrical actuator, 3-position
(for small valves 5.5 mm (0.2"))
Electrical actuator, 3-position
(for CombiValves VPI45)
Electrical actuator, DC 0...10 V
(for radiator valves)
Electrical actuator, DC 0...10 V
(for 2- and 3-port valves/V..P45)
Electrical actuator, DC 0...10 V
(for small valves 2.5 mm (0.1"))
Electrical actuator, DC 0...10 V
(for small valves 5.5 mm (0.2"))
Electrical actuator, DC 0...10 V
(for Combi-Valves VPI45)
Electromotoric actuator, DC 0...10 V
(for valves 5.5 mm)
Electrothermal actuator,
AC 24 V, NC, DC 0…10 V, 2 m (6.6 feet)
(for radiator valves and small valves 2.5
mm (0.1"))
Electrothermal actuator,
AC 24 V, NO, DC 0…10 V, 2 m (6.6 feet)
(for radiator valves and small valves 2.5
mm (0.1"))
*)
With PWM control, it is not possible to ensure exact parallel running of 2 or more thermal actuators.
If several fan coil systems are controlled by the same room thermostat, preference should be given to
motorized actuators with On/Off or 3-position control.
NoteFor more information about parallel operation and the maximum number of actuators that can
be used, refer to Data Sheets of the selected type of actuator and the following list:
Maximum number of actuators in parallel on the RDG100..:
· 6 SS..31.. actuators (3-pos)
· 4 ST..23.. if used with On/Off control signal
· 10 SFA.., SUA.., MVI.., MXI.. On/Off actuators
· Parallel operation of SAS31.. is not available
SSD61..4861
SAS61..4581
STA634884
STP634884
Maximum number of actuators in parallel on the RDG110..:
· 10 On/Off actuators
Maximum number of actuators in parallel on the RDG160T..:
Temperature unit
selection wizard
(only for
RDG110U/RDG160TU)
Setting of the control parameters (P01, etc., mentioned throughout the document) is
described in section 4.15.
The thermostat acquires the room temperature via built-in sensor, external room
temperature sensor (QAA32), or external return air temperature sensor (QAH11.1),
and maintains the setpoint by delivering actuator control commands to heating and/or
cooling equipment. The following control outputs are available depending on the
thermostat type:
1-speed/3-speed fan:
· On/Off control on RDG100, RDG100T, RDG110..
· Modulating PI/P control with 3-position control output on RDG100, RDG100T
· Modulating PI/P control with PWM output on RDG100, RDG100T
· Modulating PI/P control with DC 0…10 V control output on RDG160T..
ECM fan:
· On/Off control on RDG160T..
· Modulating PI/P control with DC 0…10 V control output on RDG160T..
The switching differential or proportional band is 2 K (4 °F) for heating mode and 1 K
(2 °F) for cooling mode (adjustable via parameters P30 and P31).
The integral action time for modulating PI control is adjustable via parameter P35.
The temperature unit selection wizard enables to select the preferable temperature
unit display on thermostats between °C and °F under the following two situations:
1. Select the application via the DIP switches at the rear of thermostat before fitting
the front housing to the mounting plate.
2. Power up the thermostat after successfully connecting the line power.
Display
/
Concurrent display of
°C and °F
Notes
Follow the steps:
1. Rotate rotary knob to select the preferable temperature unit.
2. Press the button (OK) to confirm the selection, and the thermostat goes to
normal operating page.
· Pressing button (Esc) does not confirm the temperature selection.
· If the temperature unit is not selected, °C is used by default.
The display shows the acquired room temperature or the Comfort setpoint, selectable
via parameter P06. The factory setting displays the current room temperature.
Use parameter P04 to display the room temperature or setpoint in °F rather than °C as
needed.
If the thermostat is used in a system with manual heating/cooling changeover (P01 =
2), the heating and cooling symbols on the display show the fan coil or terminal
unit's status. Thus, the symbols are displayed even when the thermostat operates in
the neutral zone. For all other cases, the heating and cooling symbols are
displayed when the heating or cooling output is activated.
Concurrent display of the current temperature or setpoint in °C and °F (parameter
P07) is possible on the thermostats without 7-day time program.
Select the thermostat's operating mode via the operating mode button on the unit or
operating mode input (e.g. keycard occupancy sensor), when X1, X2, or D1 is set to 3
(P38, P40, P42). A corresponding setpoint is used to maintain the room temperature at
the desired level depending on the active operating mode. The following operating
modes are available:
Comfort mode
Economy mode
Protection mode
Auto Timer mode
(with RDG100T,
RDG160T.. only)
Note
AUTO
In Comfort mode, the thermostat maintains the room temperature setpoint which can
be adjusted via the rotary knob. The fan can be set to automatic or manual fan
speed: low, medium or high.
Economy mode helps save energy. Select it by pressing the operating mode button if
parameter P02 is set accordingly, or if the external operating mode switchover contact
is active (e.g. window contact).
If the external operating mode switchover contact is active, user operations are
ineffective and OFF is displayed. Control will then be according to Economy setpoints
(P11 and P12).
In Protection mode, the system is
– protected against frost (factory setting 8 °C (46 °F), can be disabled or changed via
P65)
– protected against overheating (factory setting OFF, can be enabled or changed via
P66).
In Auto Timer mode
, the thermostat automatically changes from Comfort to
AUTO
Economy mode according to the 8 preprogrammed timers.
The display shows the Auto Timer mode symbol
along with the symbol for the
AUTO
current operating mode (Comfort or Economy ).
Automatic is the default fan speed in Auto Timer mode.
Auto Timer function can be disabled with parameter P02 = 3, 4 or via DIP switch 5 on
RDG160T..
Operating mode button
The behavior of the operating mode button can be selected via parameter P02:
ExampleCooling setpoint adjustable 18…25 °C (64…77 °F)
The factory setting for the Comfort basic setpoint is 21 °C (70 °F) and can be changed
via parameter P08.
The setpoint in Comfort mode can be adjusted via the rotary knob.
If the "Temporary setpoint function" is enabled via parameter P69, the setpoint
adjusted via the rotary knob is set back to the Comfort basic setpoint when the
operating mode changes.
For comfort or energy saving purposes, the setpoint setting range can be limited to
minimum (P09) and maximum (P10).
· If the minimum limit P09 is set lower than the maximum limit P10, both heating and
cooling are adjustable between these 2 limits.
· The customer adjusts the desired setpoint and the thermostat controls the room
temperature accordingly.
· For 4-pipe applications*), the selected comfort setpoint is in the middle of the dead
zone (P33). The unit stops to energize the heating/cooling outputs as soon as the
room temperature reaches the dead zone.
Heating setpoint adjustable 18…25 °C (64…77 °F)
P09 ≥ P10
(energy saving concept)
Example
· If the minimum limit P09 is set higher than the limit P10, then
– The setting range of cooling setpoint is from P09…40 °C (P09…104 °F) in place
of 5…40 °C (41…104 °F)
– The setting range of heating setpoint is from 5…P10 °C (41…P10 °F) in place of
5…40 °C (41…104 °F)
This allows the user to limit the maximum heating setpoint and the minimum cooling
setpoint. This concept helps to save energy costs.
· For 4-pipe applications:
– The thermostat runs with the setpoint of the active sequence:
In heating mode, the heating setpoint is active and adjustable via rotary knob.
In cooling mode, the cooling setpoint is active and adjustable via rotary knob.
– Switching from the heating setpoint to the cooling setpoint and vice-versa
occurs when the room temperature reaches the adjusted limitation (P09 or
P10) of the inactive sequence. E.g. the thermostat is in heating sequence and
runs with the heating setpoint. When the room temperature reaches P09, the
thermostat switches to cooling mode and runs with the cooling setpoint, as
long as the room temperature does not drop below P10.
Cooling setpoint adjustable 25…40 °C (77…104 °F)
Heating setpoint adjustable 5…21 °C (41…70 °F)
Use control parameters P11 and P12 to adjust the Economy mode setpoints.
The heating setpoint is factory-set to 15 °C (59 °F), and the cooling setpoint to30 °C(86 °F).
Use control parameters P65 and P66 to adjust the Protection mode setpoints.
The heating setpoint is factory-set to 8 °C (46 °F) (frost protection) and to OFF for
cooling.
Caution
If a setpoint is set to OFF (P65, P66), the thermostat does not maintain the setpoint in
the corresponding mode (heating or cooling).
This means no protective heating or cooling function and thus risk of frost in the
heating mode or risk of overtemperature in cooling mode!
The Economy setpoints are accessible at the service level (P11, P12); the Protection
setpoints at the expert level (P65, P66).
4.4 Setpoints and sequences
4.4.1 2-pipe and 2-stage applications
On changeover applications, the Comfort setpoints for heating and cooling sequence
are the same (w).
On 2-pipe applications with electric heater, the Comfort setpoint is either at the first
heating sequence (in heating mode) or at the cooling sequence (in cooling mode).
On 2-pipe applications with radiator, the Comfort setpoint is either at the radiator
sequence (in heating mode) or at the cooling sequence (in cooling mode).
The setpoints for Economy and Protection mode are below the Comfort setpoints
(heating) and above the Comfort setpoints (cooling). They can be set via parameters
P11, P12 (Economy mode) and P65, P66 (Protection mode).
The thermostats support the following applications, which can be configured via DIPswitches at the rear of the unit. Depending on the type of thermostat, On/Off or
modulating control outputs are available.
4.5.1 Applications for fan coil systems
Applications, DIP setting, Control outputs
· 2-pipe fan coil unit
ON
OFF
1 2 3 4 5
· 2-pipe fan coil unit
and electric heater
ON
OFF
1 2 3 4 5
· 2-pipe fan coil unit
and radiator/floor
heating
ON
OFF
1 2 3 4 5
YE
B2
B2
T
YHC
M1
T
YHC
M1
(B1)
3076S02_01
B2
T
(B1)
T
T
YHC
M1
YR
Using RDG100../RDG110../RDG160T.. Using RDG100../RDG110../RDG160T.. Using RDG100../RDG110../RDG160T..
· 2-pipe/2-stage
fan coil unit
T
B2
YHC2
ON
OFF
1 2 3 4 5
· 4-pipe fan coil unit
YC
YH
ON
OFF
1 2 3 4 5
· 4-pipe fan coil unit
and electric heater
YE
B2
YC
YH
M1
3076S05_01
(B1)
ON
OFF
1 2 3 4 5
T
T
(B1)
Using RDG100../RDG110../RDG160T.. Using RDG100../RDG110../RDG160T.. Using
The water temperature acquired by the changeover sensor (QAH11.1 + ARG86.3) is
used to change over from heating to cooling mode, or vice versa.
· When thewater temperature is above 28 °C (82 °F) (adjustable via parameter
P37), the thermostat changes over to heating mode.
It stays in heating mode until the temperature falls below 16°C (61 °F) (adjustable
via parameter P36)
· When thewater temperature is below 16 °C (61 °F) (P36), the thermostat changes
over to cooling mode.
It stays in cooling mode until the temperature rises above 28°C (82 °F) (P37).
· If the water temperature is between the 2 changeover points immediately after
power-up (inside the hysteresis), the thermostat starts in previous mode.
The water temperature is acquired at 30-second intervals and the operating state is
updated accordingly.
M Operating modeCooling mode
Tw Water temperatureHeating mode
The QAH11.1 cable temperature sensor for automatic heating/cooling changeover can
be replaced by an external switch for manual, remote changeover:
Note
Manual heating/
changeover
External/return air
temperature sensor
Contact open à heating
mode
Contact closed à cooling
mode
The sensor or switch can be connected to input terminal X2 (factory setting) or X1 or
D1 (switch only), depending on the commissioning of the inputs (P38, P40, P42).
See also section 4.10 for details.
The commissioning of the parameter Operating action (P39, P41, P42) has in this
case no effect.
The assignment is fixed: Contact openà heating mode
Contact closedà cooling mode
· Manual heating/cooling changeover means selection via changeover button on the
thermostat by repeatedly pushing the button until the required mode is shown on
the display (automatic changeover is done via an external sensor/switch connected
to X1, X2, or D1)
· If manual heating/cooling changeover is commissioned (P01 = 2), then
heating/cooling mode cannot be changed via changeover sensor/switch; it will
remain in the last mode as selected locally via button.
The thermostat acquires the room temperature via built-in sensor, external room
temperature sensor (QAA32), or external return air temperature sensor (QAH11.1)
connected to multifunctional input X1 or X2.
Inputs X1 or X2 must be commissioned accordingly. See section 4.10.
The changeover sensor ensures changeover from heating to cooling mode based on
the acquired water temperature. We recommend activating the purge function
(parameter P50) with 2-port valves. This function ensures correct acquisition of the
medium temperature even if the 2-port valve is closed for an extended period of time.
The valve is then opened for 1 to 5 minutes (adjustable) at 2-hour intervals during off
hours. This function is available on all RDG variants for applications 2-pipe
changeover and on RDG160T.. also for the 4-pipe changeover.
Caution
Avoid damage from
moisture
Minimum output
on-time/off-time
Floor heating/
Floor cooling
The purge function (parameter P50) must be disabled if the thermostat is used in
compressor-based applications.
In very warm and humid climates, the fan can be run periodically or continuously at a
low fan speed (e.g. in empty apartments or shops) in Economy mode by setting
parameter P61, in order to avoid damage from moisture due to lack of air circulation.
See also section 4.9 for details.
Limit the On/Off switching cycle to protect the compressor and reduce wear and tear.
The minimum output on-time and off-time for On/Off control output can be adjusted
from 1 to 20 minutes via parameters P48 and P49.
The factory setting is 1 minute.
Readjusting the setpoint or heating/cooling mode changeover immediately results in
calculation of the output status; output Y11/Y21 may not hold the minimum 1-minute
On/Off time.
If parameter P48 or P49 is set to above 1 minute, the minimum On/Off time for the
control output is maintained as set, even if the setpoint or changeover mode is
readjusted.
This function is only available for On/Off control with RDG100, RDG100T, RDG110..,
and RDG160T...
All heating sequences can also be used for floor heating.
You can use fan coil heating/cooling sequences for floor heating or cooling by
disabling the fan via parameter P52.
Floor temperature
limitation function
Recommended values
for P51:
The temperature should be limited for 2 reasons: comfort and protection of the floor.
The floor temperature sensor, connected to multifunctional input X1 or X2, acquires
the floor temperature. If the temperature exceeds the parameterized limit (parameter
P51), the heating valve is fully closed until the floor temperature drops to a level
2 K (4 °F) below the parameterized limit.
This function is factory-set to OFF (disabled).
Input X1 or X2 must be commissioned accordingly (P38 or P40 = 1).
See section 4.10 for details.
Living rooms:
Up to 26 °C (79 °F) for long-term presence, up to 28 °C (82 °F) for short-time
presence.
Bath rooms:
Up to 28 °C (82 °F) for long-term presence, up to 30 °C (86 °F) for short-time
presence.
The table below shows the relation between parameter, temperature source and
sensor
Note
temperature display:
Parameter P51
OFFNoBuilt-in sensorBuilt-in sensorNot active
OFFYesExternal temp. sensorExternal temp. sensorNot active
10…50˚C (50...122˚F)NoBuilt-in sensorBuilt-in sensorNot active
10…50˚C (50...122˚F)YesBuilt-in sensor
External temp.
available
Source for display of room
temperature
Output control according to
Built-in sensor + limit by
external sensor
Floor temp. limit
function
Active
The floor temperature limitation function influences the outputs listed in the table
below:
Floor temp. limit function has influence on
ApplicationOutput Y1Output Y2Output Y3
2-pipeH/C valveY1N/A
2-pipe and electric heater H/C valveElectric heaterY2Y2
2-pipe and radiatorH/C valveRadiatorY2Y2Only radiator
4-pipeHeating valve Cooling valveY1N/AY1
4-pipe and electric heater Heating valve Cooling valve Electric heaterY3N/AY3Only electric heater
2-stage1st H/C2nd H/CY1, Y2N/A
*)
If P13 = ON à electric heater in cooling mode
Heat. mode
(P01=0/2/3)
Cool. mode
(P01=1/2/3)
*)
Heat. and cool.
mode (P01=4)Remark
Only electric heater
Note
Supply air temperature
limitation (RDG160T..)
Dewpoint monitoring
Either floor temperature sensor or external room temperature sensor can be used.
This function increases the comfort in the room by keeping the supply air temperature
of the fan coil unit between the selected minimum and maximum temperature limits.
If the supply air temperature exceeds a limit, the thermostat reduces the
corresponding valve position until the supply air temperature is back in the limits.
In case the air flow is too low (especially with DC 0...10 V fans), this prevents cold air
from dumping into the room/warm air from bubbling straight up instead of circulating.
To enable this function, the multifunctional input, to which the supply air sensor is
connected, needs to be set to "Supply air sensor" (e.g. P38=9). Then the parameters
for the limits are visible (P63: minimum supply air temperature, P64: maximum supply
air temperature).
This function is only active in Comfort mode and can only be used with DC 0...10 V
actuators.
For applications with electric heater and radiator, this function is available only on the
cooling valve (in cooling mode).
Dewpoint monitoring is essential to prevent condensation on the chilled ceiling
(cooling with fan disabled, parameter P52). It helps avoid associated damage to the
building.
A dewpoint sensor with a potential-free contact is connected to multifunctional input
X1, X2 or D1. If there is condensation, the cooling valve is fully closed until no more
condensation is detected, and the cooling output is disabled temporarily.
The condensation symbol is displayed during temporary override.
The input must be commissioned accordingly (P38, P40, P42).
See section 4.10.
If the button lock function is enabled by parameter P14, the buttons will be locked or
unlocked by pressing the right button for 3 seconds.
If "Auto lock" is configured, the thermostat will automatically lock the buttons 10
seconds after the last adjustment.
The thermostat can be forced into Economy mode (e.g. when a window is opened).
The window contact can be connected to digital input D1 (or multifunctional input X1,
X2). Set parameter P42 (P38, P40) to 3.
The left button switches the operating mode from Economy to Comfort for the period
preset in P68, if the following conditions are fulfilled:
· The operating mode switchover contact is closed (connected to input X1, X2, D1,
parameter P38, P40, P42 set to 3)
· Parameter P68 (extend Comfort period) is greater than 0
During the temporary Comfort mode extension, sandglass symbol appears.
If parameter P68 (extend Comfort period) = 0, extended Comfort cannot be activated;
pressing the left button will show "OFF" (blinking 3 times).
The current operating mode can be forced temporarily into Comfort or
Economy/Protection mode. The time period is adjusted via the rotary knob:
· Extend presence: Set the device to Comfort mode for the selected time period
· Extend absence: Set the device to Economy/Protection mode for the selected time
period
To activate the function, keep the left button pressed and, within 3 seconds, turn the
rotary knob…
· clockwise for extended presence
· counterclockwise for extended absence
The rotary knob adjusts the time period:
· Extend presence: 0.00…+9:30 in steps of 30 minutes; symbol appears
· Extend absence: 0.00…–9:30 in steps of 30 minutes; symbol or appears
During the extended presence/absence period, sandglass symbol appears.
Extension/Absence functions not available in protection mode
Operating mode when
activating function
ComfortExtensionComfortProtection
ComfortAbsenceProtectionComfort
Comfort or EconomyExtensionComfortEconomy
Comfort or EconomyAbsenceEconomyComfort
Function with time program (RDG100T, RDG160T..)
User profile for operating mode
(selected via P02)
P02 = 1:
P02 = 2 à
Note
Extension/Absence functions are not available in protection mode
Operating mode when
activating function
Auto or comfortExtensionComfortAuto
Auto or comfortAbsenceProtectionAuto
Auto, Comfort or EconomyExtensionComfortAuto
Auto, Comfort or EconomyAbsenceEconomyAuto
FunctionOperating
mode
during
function
FunctionOperating
mode
during
function
Operating
mode at
the end of
function
Operating
mode at
the end of
function
Power reserve clock
for 48 h during
power failure
When the thermostat detects a power failure, all parameters and customer settings
(time program, operating mode, setpoint and fan speed) are saved internally and the
display is switched off.
The clock continues to run during power failure. After the thermostat powers up again,
the display is switched on. The thermostat reloads the previous setting and continues
to operate with the correct clock time.
If the power failure exceeds the maximum backup clock time, the correct time clock
needs to be set manually on the thermostat.
Available for
RDG100T≥ index K
RDG160T≥ index D
RDG160TU≥ index B
The following special functions are available on the RDG160T.. and allow the control
of external equipment connected to the Q1, Q2 and Q3 relay outputs.
· Switch OFF external equipment when the thermostat is in Protection Mode
· Switch ON external equipment during heating/cooling demand
· Output heating/cooling sequence
The relay output corresponding parameters need to be set to enable the function.
· Function on Q1, set parameter P72. Test relay function via diagnostic d08.
· Function on Q2, set parameter P73. Test relay function via diagnostic d09.
· Function on Q3, set parameter P74. Test relay function via diagnostic d10.
Notes
Switch OFF external
equipment in
Protection mode
Switch ON contact
during Heat/Cool
demand
· Those functions are available when DIP4 is set to OFF (EC fan).
· It is not suggested to use those functions in combination with the On/Off valve
control (P46/P47=1) to guarantee the temperature accuracy. If this combination is
requested, the total maximum current on the relay outputs (Q1+Q2+Q3) should not
exceed 2A.
The external equipment (such as: fan coil unit) can be switched OFF via relay output,
in order to reduce energy consumption when the thermostat is in Protection mode and
no temperature control is requested.
The function can be enabled by setting the corresponding Qx- parameter to 1.
Relay contact is open when the thermostat is in protection mode.
During the heating or cooling demand, the relay contact can be energized to control
an external equipment, for example to run the pump of a water system (fan coil).
To reduce the wear and tear of the HVAC equipment, the minimum output on-time and
off-time of the Qx- relay output can be adjusted from 1 to 20 minutes via parameters
P48 and P49. The factory setting is 1 minute.
The relay output remains OFF if the heating is provided ONLY by electric heater
(application 2-pipe electric heater, heating by electric heater, cooling by fan coil) or
radiator.
2-pipe water system (with one pump):
· Enable the function by selecting the corresponding output parameter to 2
· Connect the external equipment to selected relay output
· In case of heating/cooling demand, the output contact is energized
4-pipe water system (with two pumps):
· The function can be enabled by selecting the correspondent output parameters
> set one parameter to 3. The output is energized during heating demand
> set one other parameter to 4. The output is energized during cooling demand
· Connect the external equipment to the selected relay outputs
Output heating/cooling
sequence
This function switches the relay output depending on the sequence, either heating or
cooling. The output can be used for the release of a heat pump compressor.
· When the thermostat is in heating mode (even in dead zone):
> the correspondent Qx- output contact is closed.
· When the thermostat is in cooling mode (even in dead zone):
> the correspondent Qx- output contact is open.
The function can be enabled by setting the corresponding Qx- parameter to 5.
On 2-pipe applications, the thermostat controls a valve in heating/cooling mode with
changeover (automatic or manual), heating only, or cooling only. Cooling only is
factory set (P01 = 1).
Control sequence
On/Off output
The diagrams below shows the control sequence for 2-position control.
Heating modeCooling mode
T[°C] Room temperatureSDH Switching differential "Heating" (P30)
wRoom temperature setpointSDC Switching differential "Cooling" (P31)
YHC Control command "Valve" or "Compressor"
Modulating control: 3-position, PWM or DC 0…10 V
Control sequence
modulating output
The diagrams below show the control sequence for modulating PI control.
Heating modeCooling mode
T[°C]Room temperatureXpHProportional band "Heating" (P30)
wRoom temperature setpointXpCProportional band "Cooling" (P31)
YHCControl command "Valve"
Note
The diagrams only show the PI controller’s proportional part.
On 2-pipe applications with electric heater, the thermostat controls a valve in
heating/cooling mode with changeover, heating only, or cooling only plus an electric
heater.
Cooling only is factory set (P01=1) with enabled electric heater (P13).
In cooling mode, the valve receives an OPEN command if the acquired temperature is
above the setpoint.
The electric heater receives an ON command if the acquired room temperature drops
below "setpoint" minus "dead zone" (= setpoint for electric heater) while the electric
heater is enabled (parameter P13 = on).
"Setpoint for electric heater" is limited by parameter "Maximum setpoint for Comfort
mode" (P10).
In heating mode, the valve receives an OPEN command if the acquired temperature is
below the setpoint. The electric heater is used as an additional heating source when
the heating energy controlled by the valve is insufficient.
The electric heater receives an ON command, if the temperature is below "setpoint"
minus "setpoint differential" (= setpoint for electric heater).
The electric heater is active in heating mode only and the control output for the valve
is permanently disabled when manual changeover is selected (P01=2).
Remote enabling/disabling of the electric heater is possible via input X1, X2 or D1 for
tariff regulations, energy savings, etc.
Input X1, X2, or D1 must be commissioned accordingly (parameters P38, P40, P42).
See section 4.10.
Caution
On/Off electric heater
on RDG160T.. with
ECM fan
On/Off control
Control sequence
On/Off output
An electric heater must always be protected by a safety thermostat!
· With a DC 0...10 V (ECM) fan it is possible to select On/Off control for the electric
heater by setting parameter P47 = 1. The electric heater has to be connected to
output Q2.
· The electric heater starts with a delay of 15 s, to make sure the fan delivers
sufficient air flow to dissipate the heat.
· To avoid overheating of the electric heater, the thermostat guarantee at least a fan
speed II (middle value between Vmin (P56) – Vmax (P55)) when the electric heater
need to be energized.
· Adaptive temperature compensation P45 need to be set accordingly
(Refer to section 4.8).
The diagrams below show the control sequence for 2-position.
Heating mode
(automatic changeover = heating or heating only)
Cooling mode
(man./auto. changeover = cooling or cooling only)
Heating mode with manual changeover (P01=2) ) on RDG100.. and RDG110..
·RDG160T.. with manual changeover works in the same way as for automatic
changeover, with 2-stage heating.
Modulating control 3-position, PWM or DC 0…10 V
Control sequence
modulating output
The diagrams below show the control sequence for modulating control.
Heating mode
(automatic changeover = heating or heating only)
T[°C] Room temperature
W Room temperature setpoint
YHC Control command "Valve" or "Compressor"
YE Control command "Electric heater"
SDH Switching differential "Heating" (P30)
SDC Switching differential "Cooling" (P31)
Xdz Dead zone (P33)
wD Setpoint differential (P34)
Cooling mode
(man. /auto. changeover = cooling or cooling only)
Heating mode with manual changeover (P01=2) on RDG100.. and RDG110..
(manual changeover = heating)
Note
· The diagrams only show the PI controller’s proportional part.
· RDG160T.. with manual changeover works in the same way as for automatic
changeover, with 2-stage heating.
Setting the sequence and the control outputs
Refer to section 4.5, 4.7.1 and 4.7.2.
T[°C] Room temperature
W Room temperature setpoint
YHC Control command "Valve"
YE Control command "Electric heater"
XpH Proportional band "Heating" (P30)
XpC Proportional band "Cooling" (P31)
Xdz Dead zone (P33)
wD Setpoint differential (P34)
4.7.5 2-pipe fan coil unit with radiator or floor heating
Heating or cooling with
radiator or floor heating
Radiator, active in
cooling mode
Radiator in heating mode
Floor heating
On/Off control
On 2-pipe applications with radiator, the thermostat controls a valve in heating/cooling
mode with changeover, heating only, or cooling only plus a radiator valve. Cooling only
is factory-set (P01=1).
In cooling mode, the valve receives an OPEN command if the acquired temperature is
above the setpoint.
The radiator receives an ON command if the acquired room temperature drops below
"setpoint" minus "dead zone" (= "setpoint for radiator").
In heating mode, the radiator receives an OPEN command if the acquired temperature
is below the setpoint. The fan coil unit is used as an additional heat source when the
heat energy controlled by the radiator is insufficient.
The fan coil unit receives an ON command if the temperature is below "setpoint"
minus "setpoint differential" (= setpoint for fan coil unit).
The radiator sequence can also be used for floor heating.
The "Floor heating limitation function" is described on page 20.
The diagrams below show the control sequence for 2-position control.
Heating modeCooling mode
T[°C] Room temperatureSDH Switching differential "Heating" (P30)
W Room temperature setpointSDC Switching differential "Cooling" (P31)
YHC Control command "Valve" or "Compressor" Xdz Dead zone (P33)
YR Control command "Radiator"wD Setpoint differential (P34)
Modulating control: 3-position, PWM or DC 0…10 V
The diagrams below show the control sequence for modulating PI control.
Heating modeCooling mode
T[°C] Room temperatureXpH Proportional band "Heating" (P30)
W Room temperature setpointXpC Proportional band "Cooling" (P31)
YHC Control command "Valve"Xdz Dead zone (P33)
YR Control command "Radiator"wD Setpoint differential (P34)
Note
The diagrams only show the PI controller’s proportional part.
"Main and secondary"
application (4-pipe with
changeover)
V2
T
B2
V1
On 4-pipe applications, the thermostat controls 2 valves in heating and cooling mode,
heating/cooling mode by manual selection, or heating and cooling mode with
changeover. Heating and cooling mode (P01=4) is factory-set.
The heating or cooling output can be released via operating mode button if parameter
P01 is set to manual (P01=2).
If parameter P01 is set to changeover (P01=3), the heating and cooling output is
swapped according to the changeover sensor input status (see automatic heating and
cooling changeover sensor, section 4.6). This mode is used for the so-called "Main
and secondary" application. This is a 4-pipe fan coil unit system with different capacity
of the 2 coils. The water circuit is changed to optimize the energy exchange
depending on the season (summer/winter):
– Winter: Large coil (V1) for heating, small coil (V2) for cooling
– Summer: Large coil (V1) for cooling, small coil (V2) for heating
3181D112
Note:
This example shows
On/Off control;
M1
T
B1
for modulating control, connect the
appropriate output
terminals.
Notes
· The factory setting for the heating and cooling changeover sensor (B2 in the above
diagram) is input X2 (P40 = 2)
· The thermostat assumes winter operation when B2 > P37
(factory setting 28 °C (82 °F))
· The thermostat assumes summer operation when B2 < P36
(factory setting 16 °C (61 °F))
The diagrams below show the control sequence for 2-position control.
Heating mode with manual selection
(P01=2) or
for P09 >= P10 in heating sequence
Heating and cooling mode (P01=04)
Cooling mode with manual selection
*)
(P01=2) or
for P09 >= P10 in cooling sequence
T[°C] Room temperature
wRoom temperature setpoint
YH Control command "Valve" (heating)
YC Control command "Valve" (cooling)
SDH Switching differential "Heating" (P30)
SDC Switching differential "Cooling" (P31)
Xdz Dead zone (P33)
*)
Modulating control: 3-position or PWM
The diagrams below show the control sequence of modulating PI control.
Heating mode with manual selection
(P01=2) or
for P09 >= P10 in heating sequence
Heating and cooling mode (P01=04)
Cooling mode with manual selection
*)
(P01=2) or
for P09 >= P10 in cooling sequence
T[°C] Room temperature
wRoom temperature setpoint
YH Control command "Valve" (heating)
YC Control command "Valve" (cooling)
XpH Proportional band "Heating" (P30)
XpC Proportional band "Cooling" (P31)
X
Dead zone (P33)
dz
*)
*)
see section 4.3.
Note
The diagrams only show the PI controller’s proportional part.
4.7.7 4-pipe fan coil unit with electric heater (RDG100..)
Heating and cooling with
auxiliary heater
Electric heating in
heating mode
Digital input "Enable
electric heater"
Caution
4-pipe application with
manual changeover
"Main and secondary"
application
On 4-pipe applications with electric heater, the thermostat controls 2 valves in heating
and cooling mode by manual selection, heating and cooling mode with automatic
changeover, heating only, or cooling only plus an electric heater.
Heating and cooling is factory-set (P01=4).
The electric heater is used as an additional heat source when the heating energy
controlled by the valve is insufficient.
The electric heater receives an ON command when the temperature is below
"setpoint" minus "1/2 dead zone" minus "setpoint differential" (= "setpoint for electric
heater").
Remote enabling/disabling of the electric heater is possible via input X1, X2, or D1 for
tariff regulations, energy saving, etc.
Input X1, X2, or D1 must be commissioned accordingly (parameters P38, P40, P42).
See section 4.10 for details.
An electric heater must always be protected by a safety thermostat!
The heating or cooling output can be released via operating mode button if parameter
P01 is set to manual (P01=2).
See section 4.7.6 for details.
On/Off control
The diagrams below show the control sequence for 2-position control.
Heating mode with manual selection (P01=2)Cooling mode with manual selection P01=2)
Heating and cooling mode (P01=4)
T[°C] Room temperature
wRoom temperature setpoint
YE Control command "Electric heater"
YH Control command "Valve" or "Comp." (H)
YC Control command "Valve" or "Comp." (C)
SDH Switching differential "Heating" (P30)
SDC Switching differential "Cooling" (P31)
Xdz Dead zone (P33)
The diagrams below show the control sequence of modulating PI control.
Heating mode with manual selection (P01=2)Cooling mode with manual selection P01=2)
Heating and cooling mode (P01=4)
T[°C] Room temperature
wRoom temperature setpoint
YE Control. command "Electric heater"
(only On/Off)
YH Control command "Valve" or "Comp." (H)
(only PWM, not 3-position)
YC Control command "Valve" or "Comp." (C)
XpH Proportional band "Heating" (P30)
XpC Proportional band "Cooling" (P31)
Xdz Dead zone (P33)
wD Setpoint differential (P34)
Note
The diagrams only show the PI controller’s proportional part.
On 2-stage applications, the thermostat controls 2 valves or compressors in heating or
cooling mode or changeover (automatic or manual).
"Cooling only" is factory-set (P01=1).
Heating mode
In heating mode, the 1st stage is activated if the acquired temperature is below the
setpoint.
The 2nd stage is activated if the acquired room temperature drops below "setpoint"
minus "setpoint differential".
Cooling mode
In cooling mode, the 1st stage is activated if the acquired temperature is above the
setpoint.
The 2nd stage is activated if the acquired room temperature rises above "setpoint"
plus "setpoint differential".
On/Off control
The diagrams below show the control sequence for 2-position control.
Heating mode (P01=0)Cooling mode P01=1)
Changeover (P01=2 or P01= 3)
T[°C] Room temperature
wRoom temperature setpoint
YHC1 Control command "Stage 1"
YHC2 Control command "Stage 2"
SDH Switching differential "Heating" (P30)
SDC Switching differential "Cooling" (P31)
Xdz Dead zone (P33)
The diagrams below show the control sequence of modulating PI control.
Heating mode (P01=0)Cooling mode P01=1)
Changeover (P01=2 or P01= 3)
T[°C] Room temperature
wRoom temperature setpoint
YHC1 Control command "Stage 1"
YHC2 Control command "Stage 2"
XpH Proportional band "Heating" (P30)
XpC Proportional band "Cooling" (P31)
Xdz Dead zone (P33)
wD Setpoint differential (P34)
Note
The diagrams only show the PI controller’s proportional part.
4.7.9 Chilled/heated ceiling and radiator applications
Appl
ication for
Set basic
See
Sequences
7
\
\
\
/
\
\
Application for
Set basic
See section
Sequences
ü
ü
7
\
\
ü
ü
ü
ü
ü
–
\
\
ü
ü
For chilled/heated ceiling and radiator,
· set the corresponding basic application
· disable the fan (P52)
The following applications are available:
chilled/heated ceiling,
radiator
Chilled/heated ceiling with
changeover
Chilled/heated ceiling and
electric Heater
(cooling only: disable electric
heater via P13)
Chilled/heated ceiling and
radiator
Chilled ceiling and radiator
Chilled/heated ceiling, 2-stage
application
2-pipe4.7.3
2-pipe and electric
heater
2-pipe and radiator4.7.5
4-pipe4.7.6
2-stage heating or
cooling
section
4.7.4
4.7.8
H(\ )
C( / )
El. H + H (
El. H + C ( 7\ / )
C( / )
H + rad ( \ r\ )
Rad + C ( r\ / )
H + C (
H + H (
C + C ( // )
Refer to section 4.5.2 for details about the product type and control outputs.
4.7.10 Compressor applications (general)
For compressor applications,
· set the corresponding basic application
· disable the fan (P52) or set the fan speed (P53)
The following applications are available:
)
)
)
Notes
chilled/heated ceiling,
radiator
1-stage compressor
1-stage compressor and
electric heater
(cooling only: disable
electric heater via P13)
1-stage compressor
for heating and cooling
1-stage compressor with
reversing valve (for
details, see below)
2-stage compressor
application
2-pipe4.7.3
2-pipe and electric
heater
4-pipe4.7.6
4-pipe4.7.6
2-stage heating or
cooling
4.7.4
4.7.8
H(\ )
C( / )
El. H + H (
El. H + C ( 7\ / )
C( / )
H + C (\ / )
H + C (\ / )
H + H (
C + C ( // )
)
)
· Minimum On/Off time:P48/P49
· Fan operation:P52 (0 = disabled, 1 = enabled)
· Fan speed:P53 (1 = 1-speed, 2 = 3-speed)
Refer to section 4.5.3 for details about the product type and control outputs.
4.7.11 1-stage heating or cooling with reversing valve (RDG110..)
C1
On this application, the thermostat controls a compressor in heating or cooling mode
with changeover (automatic or manual). Cooling only is factory-set (P01=1).
· Set basic application "4-pipe" (see section 4.7.6)
· Connect compressor and reversing valve as follows:
ON
OFF
1 2 3
RV
Hardware
On/Off control
This application is available with RDG110.. only.
The diagrams below show the control sequences for 2-position control.
Heating mode with manual selection
(P01 = 2)
Cooling mode with manual selection
(P01 = 2)
Heating and cooling mode (P01=04)
T[°C] Room temperature
wRoom temperature setpoint
Y11 Control command "Compressor" (H)
Y21 Control command "Compressor" (C)
Y12 Control command "Reversing valve"
(heating = ON)
SDH Switching differential "Heating" (P30)
SDC Switching differential "Cooling" (P31)
Xdz Dead zone (P33)
Different control output signals are available depending on the thermostat type, the
position of DIP switches 4 and 5, and parameters P46 and P47 (see section 4.7.2).
Control output
Product no.
RDG100
RDG100T
RDG110
RDG110U
RDG160T
RDG160TU
On/OffPWM3-positionDC 0…10 V
Y1, Y2, Y3
(3 x N.O.)
Y11/Y12,
Y21/Y22 (2 x
SPDT)
Q1, Q2
(2 x N.O.)
Y1, Y3,
(2 x PWM)
Y1/Y2, Y3/Y4
(2 x/ )
Y10, Y20
(2 x DC 0…10 V)
The valve or compressor receives the ON command via control output Y1 or Y3
(RDG110..: Y11/Y21, RDG160T..: Q1/Q2) when
1. the acquired room temperature is below the setpoint (heating mode) or above the
setpoint (cooling mode).
2. the control outputs have been inactive for more than the "Minimum output off-time"
(factory setting 1 minute, adjustable via parameter P48).
OFF command when
1. the acquired room temperature is above the setpoint (heating mode) or below the
setpoint (cooling mode).
2. the valve has been active for more than the "Minimum output on-time" (factory
setting 1 minute, adjustable via parameter P49).
Electric heater control
signal (On/Off)
Caution
Note!
The electric heater receives an ON command via the auxiliary heating control output
(Y.., see Mounting Instructions) when
1. the acquired room temperature is below "Setpoint for electric heater"
2. the electric heater has been switched off for at least 1 minute
The OFF command for the electric heater is output when
1. the acquired room temperature is above the setpoint (electric heater)
2. the electric heater has been switched on for at least 1 minute
A safety thermostat (to prevent overtemperatures) must be provided externally.
On RDG160T.. the electric heater can be controlled via the 2-position output (Q2) by
setting P47 = 1.
When an electric heater is connected directly to the On/Off output (RDG160T..: Q2,
RDG110..:Y21), the current causes the relay contact to heat up. This falsifies the
reading of the internal temperature sensor. The thermostat compensates the
temperature if the rated current/power of the electric heating is entered in the
parameters.
RDG110:
P46 (load current electric heater): Factory setting: 1 A, setting range: 1…5 A.
RDG110U:
P46 is not available for AC 24 V operating voltage with electric heater controlled via
external relay.
3-position
control signal
Synchronization
PWM control
This function is available with RDG100 and RDG100T.
Heating: Output Y1 provides the OPEN command, and Y2 the CLOSE command to
the 3-position actuator. Relay function Y1/Y2 and wiring can be tested via diagnostic
parameter d05. Cooling: Idem with Y3 and Y4. Relay function Y3/Y4 and wiring can be
tested via diagnostic parameter d06.
The factory setting for the actuator's running time is 150 seconds. It can be adjusted
via parameters P44 (Y1 and Y2) or P45 (Y3 and Y4).
The parameters are only visible if 3-position is selected via DIP switches 4 and 5.
1. When the thermostat is powered up, a closing command for the actuator running
time + 150% is provided to ensure that the actuator fully closes and synchronizes
to the control algorithm.
2. When the thermostat calculates the positions "fully close" or "fully open", the
actuator's running time is extended + 150% to ensure the right actuator position is
synchronized to the control algorithm.
3. After the actuator reaches the position calculated by the thermostat, a waiting time
of 30 seconds is applied to stabilize the outputs.
This function is available with RDG100 and RDG100T.
The demand calculated by PI control from the current room temperature and setpoint
is provided via Y1 and Y3 to the valve actuator as a PWM signal (pulse width
modulation) for thermal actuators. The output is activated for a period proportional to
the heating/cooling demand and then switched off for the rest of the PWM interval.
The interval is 150 seconds (factory setting). It can be adjusted via parameters P44
(Y1) or P45 (Y3). These parameters are only visible if 2-position is selected via DIP
switches 4 and 5 and if PWM is selected via P46 and P47.
Note!
PWM for thermal valve
For PWM, the integral time (P35) must be set to 0.
For thermal valve actuators, set the running time to 240 seconds.
actuators
Note!
· Never apply PWM to an electromotoric actuator.
· It is not possible to ensure exact parallel running of 2 or more thermal valve
actuator. If several fan coil units are driven by the same thermostat, preference
should be given to electromotoric actuators with On/Off or 3-position position
control.
For electric heaters, set the running time to 90 seconds.
To avoid burn-off of mechanical contacts by frequent switching, use a current valve in
place of a relay or contactor.
DC 0...10 V control
DC 0...10 V
for valve actuators
DC 0...10 V
for electric heaters
Note!
Note!
For PWM, the integral time (P35) must be set to 0.
This function is available with RDG160T.. only.
The demand calculated by PI control from the current room temperature and setpoint
is provided via Y10 and Y20 to the valve actuator as a continuous
DC 0...10 V signal.
For applications with 3-speed fan, the electric heater can be controlled only via DC
output.
· The demand calculated by PI control from the current room temperature and
setpoint is provided via Y20 as a continuous DC 0...10 V signal.
· The signal converter (SEM61.4) converts the DC 0...10 V signal to AC 24 V PDM
pulses for the current valve.
· The current valve (SEA45.1) supplies the electric heater with AC 50…660 V pulsed
current.
For applications with ECM fan (DC signal) on RDG160T.., the electric heater can be
controlled via the On/Off output (Q2) by setting P47 = 1.
Adaptive temperature compensation: see 4.7.4.
L
G
FF
3181D21
G0
N
Y
N1
DC 0 ... 10 V
G
PWM
AC 24 V
G0
Y1L
Y E
Y1 G
F...
U1
N1RDG160T..
G
Y1
Q
K...
5.7 kW
max.
U1Signal converter SEM61.4 (see Data
Sheet N5102)
Y1Current valve SEA45.1 (see Data
Sheet N4937)
K… Safety loop (e.g. safety thermostat
and high-temperature cutout)
FFVery fast-acting fuse
F… Overcurrent trip
The fan operates in automatic mode or at the selected speed with manual mode.
In automatic mode, the fan speed depends on the setpoint and the current room
temperature. When the room temperature reaches the setpoint, the control valve
closes and the fan switches off or stays at fan speed I (minimum fan speed) according
to the setting of parameters P15 and P60.
Factory setting for "Fan in the dead zone":
· Fan speed OFF: P15 = 0, P60 = OFF.
Only one fan output at a time is on, either Q1, Q2 or Q3.
Selection fan output
on RDG160T..
The type of the fan output (DC 0...10 V, 3-speed or 1-speed) can be set via
DIP switch 4, local HMI (P53).
If application is set via DIP switches and DIP 4 = Off:
· DC 0...10 V fan (ECM) on Y50 is selected
· Parameter P53 = 3 (ECM fan) cannot be modified
· 1-speed/3-speed fan output is not selectable
If application is set via DIP switches and DIP 4 = On
· 3-speed fan on Q1, Q2, Q3 is selected, parameter P53 = 2
· 1-speed fan (on Q1) can be selected via HMI (P53 = 1)
· DC 0...10 V (ECM) fan output is not selectable
· 3-speed fan output is enabled only if the application has also been selected
with modulating
heating/cooling control
(PWM, 3-pos or
DC 0...10 V)
Heating/Cooling
Q3
1-speed or
Q2
3-speed fan
Q1
Off
The individual switching points for ON of each fan stage can be adjusted via control
parameters P55…P57. The fan speed switch off point is 20% below the switch on
point. The diagrams below show fan speed control for modulating PI control.
wRoom temperature setpoint
QFan speed
YH Control demand "Heating"
YC Control demand "Cooling"
XpH Proportional band "Heating" (P30)
XpC Proportional band "Cooling" (P31)
X
Dead zone (P33)
dz
Fan speed switching point high (P55)
Fan speed switching point med (P56)
Fan speed switching point low (P57)
The diagram only shows the PI control's proportional part.
3-speed/ECM fan
control with On/Off
heating/cooling control
Heating/Cooling
1-speed or
Q3
3-speed fan
Q2
Q1
ECM fan
On applications with 2-position control:
1) The switching point for low fan speed is synchronized to the heating/cooling
output. Parameter "Switching point fan speed low" P57 is not relevant.
2) The maximum switching range of the fan (XpH
Fan/
XpC
) is defined by the
Fan
switching differential (SDH/SDC) via a look-up table.
T [°C]Room temperature
wRoom temperature setpoint
QFan speed
YControl command "Valve"
SDHSwitching differential "Heating" (P30)
SDCSwitching differential "Cooling" (P31)
XdzDead zone (P33)
XpH
Switching range for fan "Heating"
Fan
(Table)
XpC
Switching range for fan "Cooling"
Fan
(Table)
Fan 3-speed switching point high (P55)
Fan 3-speed switching point med (P56)
Fan_max Max. ECM fan speed (P55)
Fan_min Min. ECM fan speed (P56)
The thermostat can control a 1-speed or 3-speed fan (selected via control parameter
P53).
A 1-speed fan is connected to terminal Q1, a 3-speed fan to terminals Q1, Q2 and Q3.
Control sequence
for DC 0...10 V fan
(ECM) and DC 0...10 V
valves (RDG160T..)
Manual operation
DC 0...10 V fan
When DC 0...10 V Fan and DC 0...10 V valve output control is selected, the fan
switching points can be set via the following parameters:
– P55: ECM fan max. output
– P56: ECM fan min. output
– P57: Switching point fan
100%
0%
XpH
Q
100%
0%
Xdz
wRoom temperature setpoint
QFan speed
Y
w
XpC
T[°C]
H
Y
C
Control demand "Heating"
Control demand "Cooling"
XpHProportional band "Heating"
(P30)
XpCProportional band "Cooling"
Fan_on
Fan_min
X
dz
Fan_min Min. fan speed (P56)
(P31)
Dead zone (P33)
Fan_on Fan switch-on point (P57)
The diagram only shows the PI control’s proportional part.
Fan speed 1 I = Min. fan speed
Fan speed 2 II = half-way between min. fan speed and max. fan speed
Fan speed 3 III = Max. fan speed
2 sequences
heating/cooling
Fan operation as per
heating/cooling mode,
or disabled
100%
Fan III
Fan II
Fan I
=
=
Fan_min
0%
w
Xdz
Fan_max
T[°C]
3191Z115_01
Note: The control signals
"Heating" and "Cooling" are not
influenced by the manual
setting of fan speeds.
By heating only with electric heater, manual fan speed 1 I cannot be selected to
guarantee the necessary minimum air flow for the electric heater and to avoid
overheating of the system.
For heating or cooling with 2 sequences (e.g. heating with a heating coil and an
electric heater, or 2-stage cooling), the fan is always synchronized with the first
sequence.
Fan operation can be limited to be active with cooling only or heating only, or even be
totally disabled via control parameter "Fan operation" P52.
When fan operation is disabled, the fan symbol on the display disappears and
pressing the fan button has no impact.
This function allows you to use the thermostat on universal applications such as
chilled/heated ceilings and radiator, etc. (see section 4.7.9).
In automatic mode, a dwelling time of 2 minutes (factory setting) is active. The fan
maintains each speed for at least 2 minutes before it changes to the next speed. This
minimum on-time can be adjusted from 1…6 minutes via parameter P59.
Fan kick P60, P61
Note
Fan operation in dead
zone P15
In automatic fan mode and with the room temperature in the dead zone, the control
valve is normally closed and the fan disabled. With the "Fan kick" function, the fan can
be released from time to time at low speed for minimum on-time (see above) even if
the valve is closed.
This function can be used to avoid damage from moisture due to a lack of air circulation, or to allow a return air temperature sensor to acquire the correct room
temperature.
Q1
0
Periodic fan kickMinimum
on-time
Periodic fan kickMinimum
on-time
The periodic fan kick time can be selected individually for Comfort mode via parameter
P60, and for Economy mode via parameter P61.
· Fan kick value "0" means the fan runs continuously in the dead zone.
· Fan kick value “1” and higher: value in minutes
· Fan kick value "OFF" means the fan does not run in the dead zone.
Via parameter P15 in "Service Level", the fan speed in the dead zone (in Comfort
mode) can be set according to customer preference.
The following options are available:
· Fan does not run in the dead zone (P15=0)
· Fan runs at low speed in Heating and Cooling mode (P15=1)
· Fan runs at low speed in Cooling mode only (P15=2)
Fan start
Fan overrun for electric
heater
The functions "Fan in dead zone" (P15) and "Fan kick" (P60) are combined as follows:
· P60 = 0Fan runs continuously in the dead zone, P15 has no influence
· P60 = OFF Fan operation in dead zone according to P15
When the fan starts from standstill, it starts at speed 3 III for 1 second to ensure safe
fan motor start by overcoming inertia and friction (selected via parameter P58).
Q
1 sec
Q3
Q2
Q1
0
3181D22
T
When the electric heater is switched off, the fan overruns for 60 seconds (parameter
P54) to avoid overtemperature of the electric heater or prevent the thermal cutout from
responding.
In case of fan failure, the thermostat cannot protect the electric heater against
overtemperature. For this reason, the electric heater must feature a separate safety
device (thermal cutout).
Clean fan filter
reminder
Fan in Auto Timer
mode (RDG1..T)
Fan start delay
The "Clean fan filter reminder" function counts the fan operating hours and displays
message "FIL" to remind the user to change/clean the fan filter as soon as the
threshold is reached. This does not impact the thermostat's operation, which continues
to run normally. The function is set via parameter P62 (default = Off (0)).
The "Clean filter reminder" is reset when the operating mode is manually set to
Protection and back.
In Auto Timer mode, the default fan mode is automatic. The fan mode can be
changed to Manual by pressing the FAN button. The fan returns to the automatic
default mode after each switchover from Comfort to Economy mode, and vice versa.
To let the heating/cooling coil reach its temperature, the fan start can be delayed by a
time period set via parameter P67.
Function available with:
RDG100..: On/Off control outputs
RDG110..: On/Off control outputs
RDG160T..: On/Off and DC control outputs, 3-speed and DC fan
The thermostat has 2 multifunctional inputs X1 and X2 and a digital input D1.
A sensor type NTC like the QAH11.1 (AI, analog input) or a switch (DI, digital input)
can be connected to the input terminals. The functionality of the inputs can be
configured via parameters P38 for X1, P40 for X2, and P42 for D1.
#Function of inputDescriptionType
X1/X2
0Not usedNo function.---1External/return air
temperature
2Heating/cooling
changeover
3Operating mode
switchover
4Dewpoint monitorDigital input for a dewpoint sensor to detect condensation. Cooling is
5Enable electric heater Digital input to enable/disable the electric heater via remote control.DIDI
6FaultDigital input to signal an external fault
9Supply air
temperature limitation
(RDG160T.. only)
Sensor input for external room temperature sensor or return air
temperature sensor to acquire the current room temperature, or floor
heating temperature sensor to limit the heating output.
Note: The room temperature is acquired by the built-in sensor if the
floor temperature limitation function is enabled via parameter P51.
Sensor input for automatic heating/cooling changeover function.
A switch can also be connected rather than a sensor Important: Switch
closed means always cooling, (this cannot be changed), see section
4.6.
Digital input to switch over the operating mode to Economy.
If the operating mode switchover contact is active, user operations are
ineffective and "OFF" is displayed.
stopped if condensation occurs.
(example: dirty air filter).
If the input is active, "ALx" is displayed
(Alarm x, with x = 1 for X1, x = 2 for X2, x = 3 for D1).
Note: Fault displays do not influence the thermostat's operation. They
merely represent a visual signal.
Sensor input to acquire the supply air temperature.
The thermostat controls the room temperature via the built-in sensor.
The control output (DC 0...10 V) is reduced if the supply air temperature
exceeds the min/max limits (P63, P64).
AI
AI/(DI)DI
DIDI
DIDI
DIDI
AI--
Type
DI
Operational action can be changed between normally open (NO) and normally closed
(NC) via parameter P39, P41 (or P43 if it is a digital input).
Each input X1, X2 or D1 must be configured with a different function (1…5, 9).
Exception: 1, 2 or 3 inputs can be configured as alarm inputs (6).
X1 is factory-set to "External sensor" (1), X2 to "Heating/cooling changeover" (2), and
D1 to "Operating mode changeover" (3).
If a multifunctional input is configured as analog: "Err" will be displayed when the
output is out of range (0...49 °C (32...120 °F)), open or shorted.
For more details, refer to section 4.5.
· For inputs X1, X2, or D1, one physical switch can be used for up to 20 thermostats
(parallel connection).
Caution! DO NOT mix X1/X2 (mains potential) and D1.
· For sensors on inputs X1, X2, or D1, the cable length is max. 80 m.
4.11 Auto timer (RDG100T, RDG160T.. only)
The thermostat provides an Auto Timer mode with 8 programmable timers.
Each timer can be assigned to one or several days. In this mode, the thermostat
automatically changes over between Comfort and Economy mode according to the
preprogrammed timers.
12-hour and 24-hour
format
1. Press the program mode button to enter the programming mode menu.
2. Press button (OK) to enter the setting mode for the time of day.
The time digits start blinking.
3. Turn the rotary knob clock- or counterclockwise to set the time of day.
If the current time of day is in 24-hour format and you wish to change it to 12-hour
format, turn the knob clockwise passed 23:59 or counterclockwise passed 00:00.
If the current time of day is in 12-hour format and you wish to change it to 24-hour
format, turn the knob clockwise passed 12:00 pm or counterclockwise passed 12:00
am.
4. Confirm the time of day by pressing the right button
The weekday indicator starts blinking.
5. Turn the rotary knob clock- or counterclockwise to set the current weekday.
6. Confirm the current weekday by pressing button (OK).
7. Press the program mode button (Esc) to leave the program mode.
Note
· RDG100T: Time and weekday are always visible on the display, even when auto
timer is OFF (P02 = 3 or 4).
· RDG160T..: Time and weekday are NOT visible on the display when auto timer is
disabled, either by setting P02 to 3, 4 or DIP5 to ON.
After a power failure, the time of day will blink to indicate power was lost.
However the auto timer will continue to run with the time before the power loss
occurred. Enter the setting mode to adjust the time of day if needed.
Setting the timers
(RDG1x0T.. only)
The RDG100T and RDG160T.. provide 8 programmable timers A1…A8. Each timer
has a Comfort mode start and end time that can be applied to one or several
weekdays. To set an auto timer, proceed as follows:
1. Press the program mode button twice to select "Auto timer setting" on the
"Programming mode" menu.
2. Turn the rotary knob to the desired timer A1…A8 that you wish to adjust and
press button (OK).
3. Turn the rotary knob to adjust the Comfort mode start time and confirm by
pressing button (OK).
4. Turn the rotary knob to adjust the Comfort mode end time or Economy start time
respectively and confirm by pressing button (OK).
5. Weekday , and blink. Press button (OK) to select or button (Esc) to
deselect each day and advance to the next day.
6. After the 7th day is adjusted, all selected weekdays blink.
Confirm setting for actual timer by pressing button (OK) and advance to the
next timer. To adjust the next timer, repeat step 3…6 or press button (Esc) to
leave the setting mode.
settings
Notes
· To save your adjustments, remember to press button (OK) in step 6 above before
pressing button (Esc) to leave the programmable timer setting mode.
· Auto timer can be disabled via parameter P02 (=3 or 4), (RDG1..T..) or via DIP5 =
ON on RDG160T...
· RDG100T: Time and weekday are always visible on the display, even when auto
timer is OFF (P02 = 3 or 4).
· RDG160T..: Time and weekday are NOT visible on the display when auto timer is
disabled, either by setting P02 to 3, 4 or DIP5 to ON.
You can view the 8 timers in sequence:
1. Press the program mode button twice to select the "Auto timer setting" in
programming mode.
2. Turn the rotary knob to review the 8 auto timers.
3. Press button (Esc) to return to normal operation.
When the room temperature is outside the measuring range, i.e. above 49 °C (120 °F)
or below 0 °C (32 °F), the limiting temperatures blink, e.g. "0 °C (32 °F)" or "49 °C
(120 °F)".
In addition, the heating output is activated if the current setpoint is not set to "OFF",
the thermostat is in heating mode and the temperature is below 0 °C (32 °F).
For all other cases, no output is activated.
The thermostat resumes Comfort mode after the temperature returns to within the
measuring range.
When the built-in sensor fails and no external sensor is connected, the thermostat
shows the fault message "Er1" on the display. The thermostat needs to be replaced if
the room temperature needs to be measured with the built-in sensor.
4.13 Infrared remote control
Use the IRA211 infrared remote control to operate a thermostat with built-in infrared
receiver. The following operations can be carried out remotely:
· Select Protection, Comfort or Auto Timer mode
· Adjust setpoint in Comfort mode
· Select fan mode "Automatic" or "Manual"
ON
OFF
1 2 3 4 5
A buzzer in the thermostat indicates remote control command reception.
Infrared remote control can be disabled via parameter P70.
4.14 DIP switches
Use the DIP switches at the rear of the thermostat to commission the thermostat's
basic application prior to snapping it to the base.
– The application is set via DIP switches 1…3
– The function of the control outputs (2-position or 3-position) is set via DIP switches
4 and 5 for RDG 100 and RDG100T.
– For RDG160T.. (DC 0…10 V), DIP switches 4 select either DC fan (DIP4=OFF) or
3-speed fan (DIP4=ON). DIP5 set to ON disables the time program functions and
the time is not visible anymore on the display.
For details concerning connection of peripheral devices and setting of the DIP
switches, refer to the Mounting Instructions:
A number of control parameters can be readjusted to optimize control performance.
These parameters can also be set during operation without opening the unit. In the
event of a power failure, all control parameter settings are retained.
The control parameters are assigned to 2 levels:
· "Service level", and
· "Expert level" with "Diagnostics and test"
The "Service level" contains a small set of parameters to set up the thermostat for the
HVAC system and to adjust the user interface. These parameters can usually be
adjusted any time.
Change parameters at the "Expert level" carefully, as they impact control performance
and functionality of the thermostat.
Parameter setting
Enter only "Service level"
Enter "Expert level" and
"Diagnostics and test"
Adjusting parameters
Resetting parameters
Change the parameters as follows:
1. Press left and right button simultaneously for 4 seconds.
Release and press the right button again within 2 seconds until the display shows
"P01".
Continue with step 2.
1. Press left button and right button simultaneously for 4 seconds.
Release and press the left button again within 2 seconds until the temperature
disappears. Turn the rotary knob counterclockwise min. ½ rotation.
The display shows "Pxx".
Continue with step 2.
2. Select the required parameter by turning the rotary knob.
3. Press button (OK); the current value of the selected parameter starts blinking
and can be changed by turning the rotary knob.
4. Press button (OK) to confirm the adjusted value or press button (Esc) to
cancel the change.
5. If you wish to adjust additional parameters, repeat steps 2…4.
6. Press button (Esc) to leave the parameter setting mode.
The factory setting for the control parameters can be reloaded via parameter P71, by
changing the value to "ON". Confirm by pressing the right button.
The display shows "8888" during reloading.
4.15.1 Parameters of the "Service level" – Degree Celsius
Service level
Name
Parameter
P01 Control sequenceWith 2-pipe/
P02 Operating mode profile (operating mode
button)
P03 Fan mode selection00 = Auto – Manual
P04 Selection of °C or °F0 (°C)0 = degrees Celsius (°C)
P05 Sensor calibration (internally, externally)0 K– 3...3 K
P06 Standard temperature display00 = room temperature
P07 Display info line
(2nd line of LCD)
P08 Comfort setpoint21 °C5...40 °C
P09 Min. setpoint for Comfort mode5 °C5...40 °C
P10 Max. setpoint for Comfort mode35 °C5...40 °C
P11 Economy heating setpoint15 °COFF, 5...WcoolE-saving;
P12 Economy cooling setpoint30 °COFF, WHeatEco...40 °C;
P13 Electric heater in cooling modeONON: Enabled
P14 Button lock function00 = unlocked
4.15.2 Parameters of the "Expert level with diagnostics and test" –
Expert level
ü
ü
ü
ü
Degree Celsius
NameFactory setting Range
Parameter
P30 P-band/switching differential in heating mode2 K0.5…6 K
P31 P-band/switching differential in cooling mode1 K0.5…6 K
P32 P-band/switching differential for radiator2 K0.5…6 K
P33 Dead zone in Comfort mode2 K0.5…5 K
P34 Setpoint differential (wD)2 K0.5…5 K
P35 Integral action timeRDG100.. 5 min.0…10 min.
P36 Heating/cooling changeover switching point
cooling (X1/X2)
P37 Heating/cooling changeover switching point
heating (X1/X2)
P38 Functionality of X11 = external
P39 Operating action of X1 if digital inputNONO = normally open/open
P40 Functionality of X22 = H/C
P41 Operating action of X2 if digital inputNONO = normally open/open
P42 Functionality of D13 = operating
P43 Operating action of D1 if digital inputNONO = normally open/open
P44 Running time of Y1/Y2 output
(only with modulating PI control)
P45 Running time of Y3/Y4 output
(only with modulating PI control)
P45 Power of electric heater on Q2 (for adaptive
temperature compensation)
P46 Output Y1/Y2 (if not parameterized as 3-pos.)On/Off (1)1 = On/Off
P46 Outputs Y10 (DC) or Q1 (2-pos)DC 0...10 V (2) 1 = On/Off
P46 Load current of electric heater on Y21 (for
adaptive temperature compensation, not
available for RDG110U)
P47 Output Y3/Y4 (if not parameterized as 3-pos.)On/Off (1)1 = On/Off
P47 Outputs Y20 (DC) or Q2 (2.pos)DC 0...10 V (2) 1 = On/Off
P48 Min. output on time
2-position control output
P48 Min. output ON time on Q1, Q2 and Q3, Relay
function P72, P73, P74 ( =2,3,4,5):
P49 Min. output off time
2-position control output
P49 Min. output OFF time on Q1, Q2 and Q3 Relay
function P72, P73, P74 ( =2,3,4,5):
P50 Purging function (only when changeover with
local sensor is selected)
P51 Floor heating limit temperatureOFFOFF, 10...50 °C
· P46, P47: Setting to 2-position or 3-position is made with DIP switches 4 and 5.
Expert level
Notes
· P45 (RDG160T..) and P46 (RDG110) to compensate for heat dissipation of the
electric heater relay.
· If no sensors or switches are connected, it is not necessary to disable the inputs
(P38, P40 or P42 = no function), the thermostat recognizes if a sensor is connected
(but diagnostic shows "Err").
Name
Parameter
P52 Fan operation10 = disabled
P53 Fan speed3-speed1 = 1-speed
P53 Fan speed
P54 Fan overrun time
(only when electric heater is used)
P55 Switching point fan speed high100%80..100%
P55 ECM fan max. outputECM: 80%ECM: fan min…100%xxx
P56 Switching point fan speed medium65%30...75%
P56 ECM fan min. outputECM: 30%ECM: 1%...fan max.xxx
P57 Switching point fan speed low10%1...15%
P57 ECM: Switching point fanECM:10%ECM: 1..100%xxx
P58 Fan start boosterONON: Enabled
P59 Fan min. on time2 min.1...6 min
P60 Fan kick interval in Comfort mode
(time until next kick)
P61 Fan kick interval in Economy mode
(time until next kick)
P62 Clean filter reminder running timeOFF (0)OFF, 100…9900 hours
P63 Minimum supply air temperatureOFFOFF, 0…P64 °C
P64 Maximum supply air temperatureOFFOFF, 0…P64 °C
P65 Protection heating setpoint8 °COFF, 5…W Cool Prot;
P66 Protection cooling setpointOFFOFF, W Heat Prot…40;
P67 Fan start delay RDG100../110/110U
(W Cool Prot = 40 °C max.)
(W Heat Prot = 5 °C min.)
0...360 s
ON = enabled
ON = enabled
ON = reload start
1= Switch OFF in Protection
2= Switch ON in H/C demand (2-pipe)
3= Switch ON in H demand (4-pipe)
4= Switch ON in C demand (4-pipe)
5= Status active sequence (H or C)
1= Switch OFF in Protection
2= Switch ON in H/C demand (2-pipe)
3= Switch ON in H demand (4-pipe)
4= Switch ON in C demand (4-pipe)
5= Status active sequence (H or C)
1= Switch OFF in Protection
2= Switch ON in H/C demand (2-pipe)
3= Switch ON in H demand (4-pipe)
4= Switch ON in C demand (4-pipe)
5= Status active sequence (H or C)
(W Cool Prot = 104 °F max.)
(W Heat Prot = 41 °F min.)
0...360 s
ON = enabled
ON = enabled
ON = reload start
1= Switch OFF in Protection
2= Switch ON in H/C demand (2-pipe)
3= Switch ON in H demand (4-pipe)
4= Switch ON in C demand (4-pipe)
5= Status active sequence (H or C)
1= Switch OFF in Protection
2= Switch ON in H/C demand (2-pipe)
3= Switch ON in H demand (4-pipe)
4= Switch ON in C demand (4-pipe)
5= Status active sequence (H or C)
1= Switch OFF in Protection
2= Switch ON in H/C demand (2-pipe)
3= Switch ON in H demand (4-pipe)
4= Switch ON in C demand (4-pipe)
5= Status active sequence (H or C)
Do not mount on a wall in niches or bookshelves, behind curtains, above or near heat
sources, or exposed to direct solar radiation.
Mount about 1.5 m (5 feet) above the floor.
Mounting
Wiring
· The room thermostat must be mounted in a clean, dry indoor place and must not be
exposed to drip or splash water.
See Mounting Instructions (M3181.. or M3183..) enclosed with the thermostat.
· Comply with local regulations to wire, protection and earth the thermostat.
Warning!
No internal line protection for supply lines to external consumers (Q1, Q2, Q3,
Yx or Yxx)
Risk of fire and injury due to short-circuits!
· Adapt the line diameters as per local regulations to the rated value of the installed
overcurrent protection device.
· The AC 230 V mains or AC 24 V supply line must have a circuit breaker with a rated
current of no more than 10 A. For AC 24 V US installations, use Class 2 rated
power supplies.
· Properly size the cables to the thermostat, fan and valve actuators for AC 230 V
mains voltage.
· Use only valve actuators rated for AC 230 V on RDG100.., RDG110 and on
RDG160T if AC 230 V is connected to the "L" terminal.
· Use only 3-speed fan rated with AC 24 V on RDG160TU.
· Isolate the cables of inputs X1-M/X2-M and D1-GND if the conduit box carries
AC 230 V mains voltage.
· On the RDG100.. and RDG110, inputs X1-M and X2-M carry mains potential.
If the sensor’s cables are extended, they must be suited for mains voltage.
· Inputs X1-M, X2-M or D1-GND of different units (e.g. summer/winter switch) may be
connected in parallel with an external switch. Consider overall maximum contact
sensing current for switch rating.
· Selectable relay function (RDG160T..). Consider overall maximum current though
the relays.
· Disconnect power supply before removing the thermostat from the mounting plate!
1. Select the application via the DIP switches at the rear of thermostat before fitting
the front panel to the mounting plate.
2. Power up the thermostat after successfully connecting the line power. The
thermostat starts to reset and all LCD segments flash, indicating that the reset is
correct.
After the reset, which takes about 3 seconds, the thermostat is ready for
commissioning by qualified HVAC staff. The control parameters of the thermostat can
be set to ensure optimum performance of the entire system (see section 4.15).
Temperature unit
selection wizard
RDG110U/RDG160TU)
Notes
Control sequence
Compressor-based
application
Calibrate sensor
Adaptive temperature
compensation for electric
heater
The temperature unit selection wizard enables to select the preferable temperature
unit display on thermostats between °C and °F.
1. Rotate rotary knob to select the preferable temperature unit to be displayed and
operated.
2. Confirm the selection by pressing button (OK), which leads the thermostat
advance to normal operating page.
· Pressing button (Esc) does not confirm the temperature selection.
· If the temperature unit is not selected, °C is used by default.
· The control sequence may need to be set via parameter P01 depending on the
application. The factory setting for the 2-pipe application is "Cooling only"; and
"Heating and cooling" for the 4-pipe application.
· When the thermostat is used in connection with a compressor, the minimum output
on-time (parameter P48) and off-time (parameter P49) for Y11/Y21 must be
adjusted to avoid damage to the compressor and shortening its life.
· Recalibrate the temperature sensor if the room temperature displayed on the
thermostat does not match the room temperature measured. To do this, change
parameter P05.
· When an electric heater is connected directly to output Y21, the rated current of the
electric heating should be entered in parameter 46 (RDG110 only, device index Dand higher), see section 4.8.
Default setting: 1 A for loads £ 1 A.
Setpoint and setpoint
setting range limitation
· We recommend to review the setpoints and setpoint setting ranges (parameters
P08…P12) and change them as needed to achieve maximum comfort and save
energy.
See also Operating Instructions (B3181.1) enclosed with the thermostat.
Layout
Button operation
RDG100
RDG110
RDG110U
RDG100T
RDG160T
RDG160TU
1
1
4
2
1 Operating mode button/Esc
2 Button to enter the time and to set the timers
3 Fan mode button/OK
4 Rotary knob for setpoint and parameter adjustment
· When the thermostat is in normal operation, the actual operating mode and status
are indicated by symbols.
· When a button is pressed, the thermostat goes into mode selection.
The backlit LCD will turn on, all possible mode selection options (symbols) will turn
on, indicator element (arrow) will appear on the current mode/status.
· When the button is pressed again, the indicator element will change to the next
mode symbol and so on.
· After the last press and a timeout of 3 seconds, the newly selected mode is
confirmed, the other elements disappear.
· After a timeout of 20 seconds, the LCD backlight will turn off.
4
User actionEffect, description
Press left buttonGo into Operating mode selection
Press left button >3 secondsSet thermostat to Protection mode
Keep left button depressed and
turn rotary knob clockwise
Keep left button depressed and
turn rotary knob counterclockwise
Press left button while "Operating mode
switchover" is activated
Press right button >3 secondsActivate/deactivate button lock
Press right button for fan coil unitChange fan mode
Press right button for chilled ceiling (P52=0) Set thermostat to Protection mode
Turn rotary knobAdjust the room temperature setpoint
Press left and right button >3 seconds,
release, then press right button >3 seconds
Press left and right button for 3 seconds,
release, press left button for 3 seconds,
then turn rotary knob counterclockwise min. ½
rotation
Activate temporary timer "Extend presence" and
set the time (for details, see page 22)
Activate temporary timer "Extend absence" and
set the time (for details, see page 22)
Activate "Extend Comfort mode"
(for details, see page 22)
Go to parameter setting mode Service level
Go to parameter setting mode Expert level,
diagnostics and test
Only on RDG100T and RDG160T..:
Press center buttonGo to timer settings
Press center buttonSwitch ON backlight if timer settings is disable
Confirmation of parameters24Indicates that room temperature is displayed
21Weekday 1…7: 1 = Monday/7 = Sunday
22Fault
Temporary timer function (visible when operating
23
mode is temporarily extended due to extended
presence or absence)
63/80
5.3 Disposal
The device is considered electrical and electronic equipment for disposal in terms
of the applicable European Directive and may not be disposed of as domestic
garbage.
· Dispose of the device through channels provided for this purpose.
· Comply with all local and currently applicable laws and regulations.
The product environmental declaration CE1E3181 and CE1E3181_1*) contains data
on environmentally compatible product design and assessments (RoHS compliance,
materials composition, packaging, environmental benefit, disposal).
General
Connection terminalsSolid wires or prepared stranded
1 x 0.4…2.5 mm2(14 gauge)
or 2 x 0.4…1.5 mm2 (16 gauge)
Note: For sensors on inputs X1, X2, or D1, the cable length is max. 80 m (262 feet).
Wiring cross section on
Min, 1.5 mm2(16 gauge)
L, N, Q1, Q2, Q3, Y1, Y2, Y3, Y4, Y11, Y21
Housing front colorRAL 9003 white
Weight RDG100../RDG110..
RDG160T..
*) The documents can be downloaded from http://siemens.com/bt/download.