RDF870KN
RDF870MB
PM2.5 & IAQ
Control
en Touch Screen Room Controller / Room Unit Operating Instructions
de Raumregler mit Touchscreen / Raumgerät-Bedienungsanleitung
zh 触摸屏房间控制器/ 房间单元操作手册
A6V11439451_----_c 1
Open Source
Software (OSS)
BLANK PAGE
Leere Seite
空白页
2 A6V11439451_----_c
Introduction
Reference
pages
Application
Installation
Parameters
A6V11439451_----_c 3
Terminals
RDF870KN RDF870MB
L, N L, N AC 230 V operating voltage
Q1, Q2, Q3, Q4 Q1, Q2, Q3, Q4
X1, X2
M M Input reference ground
Y50 Y50 DC 0…10 V output
CE+, CE- - KNX bus + and - terminals
- A+, B- Modbus + and - terminals
- REF Modbus reference ground
X1, X2
Description
Fan relay with max four speeds
outputs
Multifunctional inputs 1 & 2
Status symbols:
Screen lock Heating mode
Alarm / Service reminder Valve on
Manual override Cooling mode
Protection mode Ventilation mode
Auxiliary heating active Auto fan mode
Economy mode
Selection symbols:
Room temperature VOC mode
Outdoor temperature CO2 mode
PM2.5 mode Relative humidity
Operational icons:
Increment, decrement or selection
Selection, change or move to previous or next
items
Display values, relative humidity or parameter
values, etc.
Secondary display, parameters, password /
filter hours
Setpoint mode
Fan mode or fan speed mode
Operating mode
More functions or info
4 A6V11439451_----_c
Commissioning: Download via ETS
Note: This operation applies to RDF870KN only.
1. Screen idle 3. Normal display
2. Touch digits / screen
4. Touch & hold
icon > 5 s to enter
5. Ready for downloading
address & application
Programming mode
Touch “ON“ to exit
A6V11439451_----_c 5
Commissioning: Local via DIP switches
1. Set application via
DIP switches
Refer to
2. Configure basic
control parameters
See Parameters on page
17.
6 A6V11439451_----_c
DIP switch
positions
1 2
ON OFF Room unit
OFF OFF Room controller
DIP switch setting applies to
RDF870MB only.
Current factory setting for PM2.5
control with 3 speed on/off fan
application:
· APP= 1: PM2.5 control only
· DISP: Room temp= 1; PM2.5= 1
· SEN1= 3: PM2.5 (AI) μ g/m
· SEN2= 0: no function
· FAN= 3: 3 speed fan
Application
3
(0…10 V)
Idle screen shows default PM2.5
1. Screen idle 3. Normal display / mode
2. Touch digits / screen
PM2.5
CO2 Room temperature
Normal display for ventilation
1. Screen idle 3. Normal display / mode
2. Touch digits / screen
A6V11439451_----_c 7
If unit is OFF
1. Screen idle 3. Unit being turned ON
2. Touch digits / screen 4. Normal display / mode
PM2.5 as default display value
8 A6V11439451_----_c
Adjust setpoint
1. Touch icon 2. Press or to adjust:
Single fan: On/Off only
1. Touch icon
A6V11439451_----_c 9
2. Press or to adjust:
Change fan mode:
ON > AUTO
See for fan
type selection.
Fan speed selection
Adjust 3- or 4-speed fan:
1. Touch icon
Adjust ECM fan:
1. Touch icon 2. Press or to adjust:
10 A6V11439451_----_c
2. Press or to adjust:
Auto
1: Speed 1
2: Speed 2
3: Speed 3
4: Speed 4
Depends on fan
type selection
percentage.
· Touch + or – once to
adjust speed by 5 %.
· Press and hold + or –
to quickly adjust
speed.
(See Min./Max.
settings in
Engineering mode
parameters)
Dual fan operations (RDF870MB RU only)
1. Touch icon 2. Use or and press or to
adjust:
FAN1 FAN2
depends on fan type selection and fan number configuration
Change operating modes
1. Touch icon 2. Press or to select:
ON: Comfort mode
ECO : Economy mode, a
symbol will be
shown
OFF: OFF
A6V11439451_----_c 11
Adjust timer (Fan filter alarm)
Change timer setpoint (TCSP) default value:
1. Touch timer area
once to enter time
counter setting
Reset timer:
Press and hold timer
area more than 10 s to
reset timer to 0
12 A6V11439451_----_c
2. Press or to adjust:
View alarms (RDF870KN)
1. When alarm bell is
displayed
2. Touch icon once and
press or to view
all alarms
For alarms, see alarm table on
page 14.
View alarms (RDF870MB)
1. When alarm bell is
displayed
A6V11439451_----_c 13
2. Touch icon once and
press or to view
all alarms
For alarms, see to alarm table
on page 14.
View alarms (RDF870MB room unit)
1. When alarm bell is
displayed
Priority Alarm/Service Display Error code * Type Product
1 Bus power supply
2 Device address error
4 External fault input 1
5 External fault input 2
6 Clean filter reminder
7 Internal sensor error
8 EEPROM error
9 External error
*
Error codes are for RDF870KN only.
14 A6V11439451_----_c
2.
Alarm AL originates in the
controller when RDF870MB
works as a room unit.
BUS 5000 Fault RDF870KN
Adr 6001
AL1 9001 RDF870..
AL2 9002
FIL 3911
Er1 Er2 Er3 -
-
RDF870KN
RDF870..
RDF870..
RDF870..
RDF870..
RDF870..
Parameter mode user access
1. Touch &
hold icon
> 5 s
2. Enter first password via or
PAS: Password
Factory: 00 00
3. Enter second password via or
Note: Press the
Setting icon to exit
or re-enter the
password if not
correct
4. After 6 seconds
P: Successful login F: Failed login
A6V11439451_----_c 15
5. Edit parameters
Value of current
selected parameter
Decrement
or
Previous
available value
Previous
parameter
current selected
Parameter
Increment
Next
available value
Next
parameter
6. Exit parameter mode
Touch the setting
mode icon to exit
16 A6V11439451_----_c
Passwords can
be modified
both HMI and
or
NOTE:
system.
Engineering parameters
Item Description Range Factory settings
Modbus address
MODA
Modbus baud rate
MODB
setting
Modbus data frame
MODF
format
Application selection 1: PM2.5 control only
APP
Symbol display
DISP
enable/disable
1)
SEN1
selection
A6V11439451_----_c 17
1…247 1
1: 9600 bps
2: 19200 bps
0: 1/8/E/1
1: 1/8/O/1
2: 1/8/N/1
3: 1/8/N/2
2: PM2.5 + CO2 control
3: CO2 control only
0: Disable display
1: Enable display
0: No function
1: Temperature (AI)
(NTC 10k)
2: Temperature (AI)
(0…10 V)
3: PM2.5 (AI) μg /m
(0…10 V)
4: CO2 (AI) ppm (0…10 V)
5: VOC (AI) % (0…10 V)
3
2: 19200 bps
0: 1/8/E/1
1: PM2.5 control
only
1) Room Temp= 1;
2) Outside
Temp= 0;
3) PM2.5= 1;
4) VOC= 0;
5) CO2 = 0;
3: PM2.5 (AI)
μ g/m
(0…10 V)
3
Item Description Range Factory settings
6: VOC (AI) mg/m³ (0…10 V)
7: R.h. (AI) % (0…10 V)
8: Alarm input (DI)
9: Dummy AI (0…10 V)
(RU only)
Operating action if
DIL1
1)
SEN2
selection
Operating action if
DIL2
PM2.5 sensor high
PMH
PM2.5 sensor low
PML
CO2 sensor high
CO2H
range
18 A6V11439451_----_c
10: Dummy DI (RU only)
0: Normally open / Open
0: No function
1: Temperature (AI)
(NTC 10k)
2: Temperature (AI)
(0…10 V)
3: PM2.5 (AI) μg /m
(0…10 V)
4: CO2 (AI) ppm (0…10 V)
5: VOC (AI) % (0…10 V)
6: VOC (AI) mg/m³ (0…10 V)
7: R.h. (AI) % (0…10 V)
8: Alarm input (DI)
9: Dummy AI (0…10 V)
(RU only)
10: Dummy DI (RU only)
3
0: Normally open / Open
0: Normally open /
0: No function
0: Normally open /
Max. of low range…1000 500
0…Min. of high range 0
Max. of low range…2000 2000
Item Description Range Factory settings
CO2 sensor low range 0…Min. of high range 0
CO2L
VOC sensor high
UOCH
VOC sensor low
UOCL
range
HUMH
range
Humidity sensor low
HUML
Temperature sensor
TEMH
Temperature sensor
TEML
PM2.5 setpoint high
SPMH
range
PM2.5 setpoint low
SPML
range
CO2 setpoint high
SPCH
CO2 setpoint low
SPCL
Fan type selection 1: 1 speed fan (ON/OFF)
FAN
ECM fan output limit
ECMH
ECM fan output limit
ECML
Filter time display 0: Disable 0: Disable
TC
A6V11439451_----_c 19
Max. of low range…100 5
0…Min. of high range 0
Max. of low range…100 100
0…Min. of high range 0
Max. of low range…100 50
-50…Min. of high range 0
Max. of low range…500 100
0…Min. of high range 12
Max. of low range…2000 1500
0…Min. of high range 500
3: 3 speed fan
3: 3 speed fan
4: 4 speed fan
5: ECM fan
Max. of ECML…100 % 80 %
0…Min. of ECMH 30 %
Item Description Range Factory settings
1: °F (degrees Fahrenheit)
2)
PM2.5 ECO mode
PMES
setpoint
2)
CO2 ECO mode
COES
setpoint
Buzzer function 0: Disable
BUZZ
Temperature unit 0: °C (degrees Celsius)
UNIT
Keylock function 0: Unlock
LOCK
0…100 60
500…1500 1000
1: Enable
0: °C (degrees
0: Unlock
1: Locked
2: Setpoint only
3: Operating mode only
4: Setpoint and fan speed
OPSL
Operating mode
selection
0: ON/OFF
1: ON/ECO/OFF
2: ON/ECO/Protection/OFF
(RU only)
1: ON/ECO/OFF
3: ON/ECO/Protection (room
Internal temperature
CALT
20 A6V11439451_----_c
-5…5 K 0
RDF870KN available parameters and their order of appearance:
· Room controller:
APP > DISP > SEN > FAN > OPSL > TC > UNIT > LOCK > BUZZ > CALT > APP
RDF870MB available parameters and their order of appearance:
· Room controller:
MODA > MODB > MODF >APP > DISP > SEN > FAN > OPSL > TC > UNIT
> LOCK > BUZZ > CALT > MODA
· Room unit:
MODA > MODB > MODF > LOCK > BUZZ > CALT > MODA
1)
Room controller: 0…8; Room unit: 0…10
2)
The setpoint cannot be changed in ECO mode.
Restriction for sensor selection:
1. If SEN1 and SEN2 are configured with the same selection type 1…8, they
cannot be the same sensor types:
· For type 1…8, sensor1 cannot be the same as sensor2.
· For sensor types with the same function such as 1&2 or 5&6, if
one sensor type is 1 or 5, the other one cannot be 2 or 6.
A6V11439451_----_c 21
Firmware Setpoint Settings
Item Description Range Factory
PM2.5SPPM2.5 setpoint SPML…SPMH 60
CO2 SP CO2 setpoint SPCL…SPCH 1000
T SP Temperature setpoint T SP L…T SP H 24
T SP H Temperature setpoint
T SP L Temperature setpoint
VOC SP VOC setpoint %: 0…100
HUMSPHumidity setpoint 0…100 % 50 %
P811) Device address (KNX
only)
1)
P81 is only for ETS and local HMI does not support P81:
· During powering up, there is a startup delay (TwaitDevice = tWaitMin +
DeviceAdr * 200ms) before the processing signal is processed.
· When P81=255(default), the device does not process the signal
according to heartbeat and COV mechanism. But it can respond when
another device is polling.
· The local HMI does not support P81.
· When individual address is changed via ETS, P81 is updated
automatically after device downloads it from ETS.
22 A6V11439451_----_c
Max. of low range…200 (°C) 50
-50…Min. of high range (°C) 5
1…255 255
settings
0.6 mg/m3 or
Expert Mode Parameters
Item Description Range Factory
PMP PM2.5 control factor Xp 0…1000 50
CO2P CO2 control factor Xp 0…2000 100
PMDB PM2.5 control loop
CODB CO2 control loop
deadband
OPAF Operating mode settings
after power failure/reset
FANT Fan minimum on time
FSET Reload factory settings 0: OFF = Disable
EPAS Engineer mode password 0000…4999 0000
Room controller workflow:
EPAS > XPAS > PMP > PMI > PMDB > CO2P > CO2I > CODB > OPAF > FANT >
FSET > SW > EPAS
RDF870MB Room unit workflow: EPAS > XPAS > SW > EPAS
A6V11439451_----_c 23
0…20 10
0…100 50
0: Return to previous
operating mode / user
setting
1: Off
1…6 min 2 min
1: ON = Reload start
“--””---””----” is displayed
while reloading
0: Return to
0: OFF = Disable
previous
operating
mode / user
setting