Siemens RDF800KN, RDF800KN/NF User Manual

CB1N3174en 2014
-09-10
s
3
174
RDF800KN RDF800KN/NF
Touch Screen Flush-mount Room Thermostats with KNX Communications
For 2-pipe, 2-pipe with electrical heater, and 4-pipe fan coil units
For universal applications
For use with compressors in DX type equipment
KNX bus communications (S-mode and LTE mode)
Large display with backlight
2P / PI / P control
Outputs for ON/OFF or 3-position control
Outputs for 3-speed or 1-speed fan
2 multifunctional inputs for keycard contact, external sensor, etc.
Independent function for window contact and presence detector
Operating modes: Comfort, Economy and Protection
Automatic or manual fan speed control
Automatic or manual heating / cooling changeover
Minimum and maximum limitation of room temperature setpoint
Control depending on the room or the return air temperature
Adjustable commissioning and control parameters
Commissioning with Synco ACS, ETS4 or via local HMI
Interoperation into Synco 700
Integration into Desigo via group (ETS4) or via individual addressing
Integration into third-party system via group addressing (ETS4)
AC 230 V operating voltage
RDF800KN: Mounting on round box, with min 60 mm diameter or recessed
square 86 mm box with 60.3 mm fixing centers and min 40 mm depth
RDF800KN/NF: Mounting on recessed square 86 mm box with 60.3 mm
fixing centers and min 40 mm depth, requires additional mounting frame
2 / 20
Siemens RDF800KN… CB1N3174en Building Technologies Touch Screen Flush-mount Room Thermostats with KNX Communications 2014-09-10
Use
Room temperature control (heating or cooling) in individual rooms and zones by means of:
2-pipe fan coil units
2-pipe fan coil units with electrical heater
4-pipe fan coil units
Chilled /heated ceiling
Chilled /heated ceiling and electrical heater
Chilled ceiling and radiator / under floor heating
Compressors in DX-type equipment
Compressors in DX-type equipment with electrical heater
The RDF800KN... controls:
One single or 3-speed fan
One or two ON/OFF valve actuators
One ON/OFF valve actuator and one 1-stage electrical heater
One 3-position valve actuator
One 1-stage compressor in DX-type equipment, or one 1-stage compressor with
electrical heater
Used in systems with:
Heating or cooling mode
Automatic heating/cooling changeover
Manual heating/cooling changeover
Heating and cooling mode (such as 4-pipe system)
The room thermostats are delivered with a fixed set of applications. The relevant application is selected and activated during commissioning using one of the following tools:
Synco ACS
ETS4
Local DIP switch and HMI
Functions
Room temperature control via built-in temperature sensor or external room temperature / return air temperature sensor
Changeover between heating and cooling mode (automatically via local sensor or bus, or manually)
Selection of applications via DIP switches or commissioning tool
Selection of operating mode via touch screen
Temporary Comfort mode extension
1- or 3-speed fan control (automatically or manually)
Display of current room temperature or setpoint in °C and/or °F
Minimum and maximum limitation of room temperature setpoint
Keylock function: unlock, total lock and setpoint
2 multifunctional inputs, freely selectable for:
Window contact
Presence detector
External room temperature or return air temperature sensor
Fault input
Monitor input for temperature sensor or switch state
Sensor for automatic heating / cooling changeover (RDF…)
Dew point sensor (RDF…)
Electric heater enable (RDF…)
Advanced fan control function, such as: fan kick, fan start delay, and selectable
fan operation (enable, disable or depending on heating or cooling mode)
3 / 20
Siemens RDF800KN… CB1N3174en Building Technologies Touch Screen Flush-mount Room Thermostats with KNX Communications 2014-09-10
Purge function together with 2-port valve in a 2-pipe changeover system
Reminder to clean fan filters (adjust with P62)
Floor heating temperature limitation
Reload factory settings for commissioning and control parameters
Wizard function for easy commissioning via HMI
KNX bus (terminals CE+ and CE-) for communication with Synco or KNX
compatible devices
Display of time of day via KNX bus
Display of outdoor temperature via KNX bus on INFO page
Time scheduling and central control of setpoints via KNX bus
With a Synco RMx7xx controller, the energy demand signal of the thermostat is
used to optimize energy supply
Applications
The thermostats support the following applications, which can be configured using the DIP switches on the inner side of the thermostat's front panel or a commissioning tool.
All DIP switches need to be set to OFF (factory setting) to select an application via commissioning tool.
Remote configuration, via commissioning tool (factory setting)
Synco ACS
ETS4
DIP switches
Remote configuration
4 / 20
Siemens RDF800KN… CB1N3174en Building Technologies Touch Screen Flush-mount Room Thermostats with KNX Communications 2014-09-10
Applications for fan coil systems
Application and output signal, DIP switches, diagram
2-pipe fan coil unit ON/OFF (heating or cooling)
1ON2 3
2-pipe fan coil unit with el. heater (heating or cooling) ON/OFF
1
ON
2 3
3076D20
(B1)
M1
V1
T
B2
T
T
(B1)
V1
M1
3171D21
T
B2
E1
T
(B1)
T
(B1)
2-pipe fan coil unit 3-position (heating or cooling)
1
ON
2 3
4-pipe fan coil unit ON/OFF (heating and cooling)
1
ON
2
3
30
76D2
0
(B1)
M1
V1
T
B2
T
T
(B1)
T
V2
V1
M1
3076D22
(B1)
T
(B1)
V1 Heating or heating / cooling valve actuator
B1 Return air temperature sensor or external room
temperature sensor (optional)
V2 Cooling valve actuator
B2 Changeover sensor (optional)
E1 Electric heater
M1 3- or 1-speed fan
5 / 20
Siemens RDF800KN… CB1N3174en Building Technologies Touch Screen Flush-mount Room Thermostats with KNX Communications 2014-09-10
Applications for Universal systems
Application and output signal, DIP switches, diagram
Chilled / heated ceiling ON/OFF (heating or cooling)
1
ON
2
3
Chilled / heated ceiling with electric heater (heating or cooling) ON/OFF
1
ON
2 3
3191S11
N1
T
B1
T
B2
T
D3
V1
3191S12
N1
T
E1
B1
T
B2
T
D3
V1
Chilled / heated ceiling 3-position (heating or cooling)
1ON2 3
Chilled ceiling and radiator ON/OFF (heating and cooling)
1
ON
2
3
3191S11
N1T
B1
T
B2
T
D3
V1
3191S13
N1T
B1
T
D3
V2
V1
V1 Heating or heating / cooling valve actuator
B1 Return air temperature sensor or external room
temperature sensor (optional)
V2 Cooling valve actuator
B2 Changeover sensor (optional)
E1 Electric heater
D3 Dewpoint sensor
6 / 20
Siemens RDF800KN… CB1N3174en Building Technologies Touch Screen Flush-mount Room Thermostats with KNX Communications 2014-09-10
Applications for heat pump systems
Application and output signal, DIP switches, diagram
1-stage compressor ON/OFF (heating or cooling)
1ON2 3
1-stage compressor with electric heater (heating or cooling) ON/OFF
1
ON
2 3
3181S31
N1
T
B1
T
D3
3181S32
N1T
E1
B1
T
D3
1-stage compressor ON/OFF (heating and cooling)
1ON2 3
3181S35
N1
T
B1
T
D3
N1 Thermostat
Terminal Y1: Heating (H&C) or Heating/Cooling
Terminal Y2: Cooling (H&C)
B1 Return air temperature sensor or external room
temperature sensor (optional)
E1 Electric heater
D3 Dewpoint sensor
Loading...
+ 14 hidden pages