Setting time of day and weekday
+ –
24h 12 h
+ –
1. Keep the
button pressed until the time digits start to flash.
Press + or – to set the time of day.
If the current time is in 24-hour format and you wish to change to the 12-hour format,
press + passing 23:59 or press – passing 00:00.
Back to 24-hour format: same procedure with 11.59 PM.
2. Confirm the time of day by pressing
and the weekday indicator starts to flash.
3. Press + or – to set the current weekday.
4. Confirm the current weekday by pressing
.
Set time schedules
Ax
+ –
+ –
+ –
To adjust the time schedule, keep the
button pressed for 3 seconds to go to the timer
setting mode.
This mode is indicated by displaying Ax (x= auto timer 1...8) and the time flashing.
For each timer, proceed as follows:
1. The
and symbols are displayed. Press + or – to adjust the comfort mode start
time and confirm by pressing
.
2. The
and symbols are displayed. Press + or – to adjust the comfort mode end
time / Economy start time and confirm by pressing
.
3. Symbol
will flash. Press + or – to select or deselect each day and advance to the
next day.
4. Press
to confirm the settings for the actual timer and advance to the next timer.
The thermostat will leave the timer setting mode if no button is pressed within 20
seconds. All changes made after the last press of the
button will not be saved.
View the timer settings
Press the
button to sequentially review the 8 auto timers.
Reload default timer settings
+ – /
1. Set the thermostat to protectio n mode
.
2. Press + and – simultaneously for 3 seconds. Release and, within 2 seconds, press
2 times
Days Thermostat is in Comfort mode
Mo (1) – Fr (5) 6:30 – 8:30 (A1) 17:30 – 22:30 (A2)
Sa (6) 8:00 – 23:00 (A3)
Su (7) 8:00 – 22:30 (A4)
Default
settings
– In the remaining time thermostat is in Economy mode.
– Timers A5…A8 are free, no default settings.
Button lock
Press operating mode button
for 3 seconds to lock or unlock the buttons if manual
button lock is configured (parameter P14 = 2).
The thermostat automatically locks the buttons 30 sec onds after the last adjustment if
"Auto lock" is configured (P14 = 1).
The key symbol
indicates locked buttons.
Reminder to clean filters and for external faults
FIL *
AL1 *
AL2 *
This message reminds you to clean your HVAC equipment filters .
It is displayed after ………… “fan operating hours” and disappears when the thermostat
is set to Protection (
).
AL1 : ______________________
AL2 : ______________________
* Needs to be configured by your HVAC installer
Note: Economy mode
The Economy setpoints are factory-set to 15 °C for heating and 30 °C for cooling.
Use parameters P11 and P12 to adjust the values.
Important: You can set these setpoints to OFF; the thermostat then is inactive, i.e. no p rotective heating or cooling function.
Risk of frost!
Commissioning
You can adjust a number of control parameters to adapt the thermos tat to your system and optimize control performance. You c an do this during
operation via the buttons on the thermostat.
Control parameters
Proceed as follows to change the most important c ontrol parameters:
(Your HVAC installer can set additional parameters)
+ / – 1. Press the – and + buttons simultaneously at least 4 seconds.
Release, and within 2 seconds, press + again until "P01" is displayed.
2. Repeatedly press the + or – button to select the required parameter.
P01 P02 P08 P14
+-+
--
+
3171z99
End
-
+
P13
+-
3. Press + and – simultaneously. The current value of the selected parameter begins to flash, allo wing you to change the value by
repeatedly pressing + or –.
4. The next parameter is displayed when you press + and – again simultaneously.
5. Repeat steps 2 to 4 to display and change additional parameters.
6. Press + or – until “End” is displayed, and then press + and – simultaneously to save the change and exit parameter entry mode.
15 minutes after the last display or setting, all changes are saved and the thermostat will leave parameter setting mo de.
Parameter
Description
Factory setting Setting range Adj
P01 Control sequence
2-pipe…: [0…3]
1 (Cooling only)
4-pipe:. [2…4]
4 (Heating & cooling)
0 = Heating only
1 = Cooling only
2 = Manual heating or cooling
3 = Auto changeover
4 = Heating & cooling
P02 Mode selection by user via operating mode button 1 (Comfort,
Protection)
1 = Comfort, Protection
2 = Comfort, Economy, Protection
P04 Selection of °C or °F 0 (°C) 0 = °C
1 = °F
P05 Sensor calibration 0.0 °C – 3 ... +3 °C
P06 Standard temperature display 0 (Room temp.) 0 = Room temperature
1 = Setpoint
P08 Comfort basic setpoint 21 °C 5 ... 40 °C
P09 Minimum setpoint limitation in Comfort (WminComf) 5 °C 5 ... 40 °C
P10 Maximum setpoint limitation in Comfort (WmaxComf) 35 °C 5 ... 40 °C
P11 Setpoint of heating in Economy (WheatEco) 15 °C OFF, 5 °C…WcoolEco
P12 Setpoint of cooling in Economy (WcoolEco) 30 °C OFF, WheatEco…40°C
P13 *** Electric heater in cooling mod e ON OFF = disabled
ON = enabled
P14
Button lock
(Press operating mode button
for 3 seconds to lock or unlock
the buttons)
0 (Disabled) 0 = Disabled
1 = Auto lock
2 = Manual lock
*** P ar am et er P1 3 i s o nl y d i s pl ay ed fo r a pp li ca ti on "2 -p i pe wi th el h e at er ".
All temperature settings in increments of 0.5 °C.
The control parameters displayed depend on the DIP switch settings made.
Please record all changes you make!