Siemens RDF400, RDF300 Series, RDF600 Series, RDF300.02, RDF400.01 Series Manual

...
CE1N3076en 2018-12-27
Building Technologies
s
076
RDF300, RDF300.02, RDF340 RDF400.01 RDF600 RDF600T
Flush-mounted room thermostats
RDF300… RDF340 RDF400… RDF600...
for 2-pipe, 2-pipe with el. heater and 4-pipe fan coil units
for use with compressors in DX type equipment
· RDF300 / RDF400 / RDF600/RDF600T: AC 230 V operating voltage, on/off or 3-position control outputs
· RDF340…:AC 24 V, operating voltage, DC 0…10 V control outputs
· Output for 3-speed or 1-speed fan
· 2 multifunctional inputs for keycard contact, external sensor, etc.
· Operating modes: Comfort, Economy and Protection
· Automatic or manual fan speed control
· Automatic or manual heating/cooling changeover
· Adjustable commissioning and control parameters
· Minimum and maximum setpoint limitation
· User and parameter settings can be retained o r restored with power loss
Additional features
· Backlit LCD (RDF300.02, RDF400.01, RDF600, RDF600T)
· Infrared remote control receiver (RDF400.01, RDF600T)
· Auto Timer mode with 8 programmable timers (RDF400.01, RDF600T)
Type of mounting / suitable conduit boxes
· RDF600... for round CEE box, with min 60 mm diameter, min 40 mm depth
· RDF3… / RDF400... for recessed square box with 60.3 mm fixing centers
2/14
Siemens RDF300…/RDF340 / RDF400… / RDF 600... Flush-mounted Room thermostats CE1N3076en Building Technologies 2018-12-27
Use
To control the room temperature in individual rooms and zones that are:
· Heated or cooled with 2-pipe fan coil units
· Heated or cooled with 2-pipe fan coil units with electrical heater
· Heated and cooled with 4-pipe fan coil units
· Heated or cooled with compressor in DX type equipment
· Heated or cooled with compressor in DX type equipment with electrical heater
· Heated and cooled with compressor in DX type equipment
The RDF300… / RDF400… / RDF600... control:
· One 1- or 3-speed fan
· One or 2 on/off valve actuators
· One on/off valve actuator and one 1-stage electrical heater
· One 3-position valve actuator
· One 1-stage compressor in DX type equipment or one 1-stage compressor with
electrical heater
The RDF340… controls:
· One 1- or 3-speed fan
· One or 2 DC 0…10 V valve actuators
· One DC 0…10 V valve actuator and one modulating electrical heater (DC 0…10 V)
Used in systems with:
· Heating or cooling mode
· Automatic heating/cooling changeover
· Manual heating/cooling changeover
· Heating and cooling mode (e.g. 4-pipe system)
Functions
· Maintain room temperature via built-in temperature sensor or external room
temperature / return air temperature sensor
· Automatic or manual changeover between heating and cooling mode
· Select applications via DIP switches
· Select operating mode via the operating mode button on the thermostat
· 1- or 3-speed fan control (automatic or manual)
· Display current room temperature or setpoint in °C and/or °F
· Minimum and maximum setpoint limitation
· Key lock (automatic and manual)
· 2 multifunctional inputs, freely selectable for:
Operating mode switchover contact (key card)Automatic heating/cooling changeover sensorExternal room temperature or return air temperature sensorDewpoint sensorElectrical heater enableAlarm input
· Advanced fan control function, i.e. fan kick, fan start, selectable fan operation
(enable, disable or depending on heating or cooling mode)
· Purge function together with 2-port valve in a 2-pipe changeover system
· Reminder to clean filters
· Floor heating temperature limit
· Reload factory settings for commissioning and control parameters
· 7-day time program: 8 programmable timers to switch over between Comfort and
Economy mode (RDF400.01 / RDF600T)
· Backlit LCD (RDF300.02 / RDF400.01 / RDF600 / RDF600T)
· Optional infrared remote control ( RDF400.01 / RDF600T)
Applications
3/14
Siemens RDF300…/RDF340 / RDF400… / RDF 600... Flush-mounted Room thermostats CE1N3076en Building Technologies 2018-12-27
Applications
The thermostat supports the following applications, which can be configured by DIP switches on the inner side of the thermostat’s front. Depending on the type, on/off or modulating control outputs are available.
Applications for fan coil systems
Application and output signal, DIP switches, diagram
· 2-pipe fan coil unit
ON/OFF
(heat ing or cooling)
ON
1 2
RDF300...
RDF400...
RDF600...
· 2-pipe fan coil unit ON/OFF
(heat ing or cooling)
with electrical heater
ON
1 2
RDF300...
RDF400...
RDF600...
· 2-pipe fan coil unit
modulating, DC 0…10 V
(heat ing or cooling)
ON
1 2
RDF340
· 2-pipe fan coil unit
modulating, DC 0…10 V
(heat ing or cooling)
with electrical heater
ON
1 2
RDF340
3076D20
(B1)
M1
V1
T
B2
T
T
(B1)
V1
M1
3171D21
T
B2
E1
T
(B1)
T
(B1)
· 2-pipe fan coil unit
modulating, 3-position
(heat ing or cooling)
ON
1 2
RDF300...
RDF400...
RDF600...
· 4-pipe fan coil unit ON/OFF
(heat ing and cooling)
ON
1 2
RDF300...
RDF400...
RDF600...
ON
1 2
RDF340
3076D20
(B1)
M1
V1
T
B2
T
T
(B1)
T
V2
V1
M1
3076D22
(B1)
T
(B1)
V1 Heating or h eating/cooling valve actuator M1 3-speed or single-speed fan V2 Cooling val ve actuator B1 Return air temperatur e sensor or
external room temperature sensor (optional)
E1 Electric al heater B2 Changeover sens or (optional)
4/14
Siemens RDF300…/RDF340 / RDF400… / RDF 600... Flush-mounted Room thermostats CE1N3076en Building Technologies 2018-12-27
Applications for Universal systems
Application and output signal, DIP switches, diagram
· Chilled / heated ceiling
ON/OFF
(heat ing or cooling)
ON
1 2
RDF300...
RDF400...
RDF600...
· Chilled / heated ceiling
ON/OFF (heating or cooling)
with electrical heater
ON
1 2
RDF300...
RDF400...
RDF600...
· Chilled / heated ceiling
modulating, DC 0…10 V
(heat ing or cooling)
ON
1 2
RDF340
· Chilled / heated ceiling
modulating, DC 0…10 V
(heat ing or cooling)
with electrical heater
ON
1 2
RDF340
3
191S1
1
N1T
B1
T
B2
T
D3
V1
3
191S1
2
N1T
E1
B1
T
B2
T
D3
V1
· Chilled / heated ceiling
modulating, 3-position
(heat ing or cooling)
ON
1 2
RDF300...
RDF400...
RDF600...
· Chilled ceiling and radiator
ON/OFF
(heat ing and cooling)
ON
1 2
RDF300...
RDF400...
RDF600...
ON
1 2
RDF340
3191S11
N1T
B1
T
B2
T
D3
V1
3191S13
N1T
B1
T
D3
V2
V1
V1 Heating or heating / cooling valve actuator B1 Return air temperature sensor or external room
temperature sensor (optional)
V2 Cooling val ve actuator B2 Changeover sensor (optional)
E1 Electrical heater D3 Dewpoint sensor
5/14
Siemens RDF300…/RDF340 / RDF400… / RDF 600... Flush-mounted Room thermostats CE1N3076en Building Technologies 2018-12-27
Applications for heat pump systems
Application and output signal, DIP switches, diagram
· 1-stage compressor ON/OFF
(heat ing or cooling)
ON
1 2
RDF300...
RDF400...
RDF600...
· 1-stage compressor ON/OFF
(heat ing or cooling)
with electrical heater
ON
1 2
RDF300...
RDF400...
RDF600...
3181S31
N1
T
B1
T
D3
3181S32
N1T
E1
B1
T
D3
· 1-stage compressor ON/OFF
(heat ing and cooling)
ON
1 2
RDF300...
RDF400...
RDF600...
3181S35
N1
T
B1
T
D3
N1 Thermostat
Terminal Y10/Y11: Heating (H&C) or Heating/Cooling
Terminal Y20/Y21: Cooling (H&C)
B1 Return air temperature sensor or external room
temperature sensor (optional)
E1 Electrical heater D3 Dewpoint sensor