Siemens rdf600kn User Manual

s
Operating Instructions
RDF600KN
The fan operates either in Auto mode or at a speed selected in Manual mode.
You can either take advantage of the thermostat's factory settings or adjust it as needed.
Protection mode
Auto Timer mode
Comfort mode
Economy mode
Measured room temperature, setpoints and parameters
Current time of day or additional user information
Display
Actual room temperature
Outdoor temperature
Fault indicator *
Condensation in the room *
Cooling demand / mode Heating demand / mode Electric heater active
Extended Comfort mode *
Automatic fan
Low fan speed
Medium fan speed
High fan speed
Buttons are locked
Weekday 1…7 (1 = Monday / 7 = Sunday)
Operating mode button
** **
Notes:
– The thermostat goes back to Auto
Timer mode if a time schedule via bus changes the operating mode.
– User operations are ignored if a
time schedule via bus sets the operating mode to protection. When you press a button, "OFF"
Operation and settings
flashes on the LCD.
– Auto mode is not available if the-
re is no time schedule via bus.
Colder / Warmer
Fan mode button
– Automatic fan ( – Manual fan (
)
)
* Needs to be configured by your HVAC installer ** Needs to be enabled via parameter P02

Change room temperature

+ / –
Press + or to increase or decrease the current room temperature setpoint for Comfort mode. The thermostat changes to Comfort
The setting range is 5...40 °C, unless limited by parameters P09 and P10.

Adjust fan speed / fan mode

Press the button until you reach the desired fan mode.
In Auto mode, the thermostat automatically selects the fan speed based on set­point and actual room temperature. The fan is switched off (factory setting) after the room temperature reaches the setpoint .
In manual mode, the fan always runs at the speed that you select: Low fan speed Medium fan speed High fan speed
Single-speed fan: You can change the mode between and .

Change thermostat operating

Press operating mode button
In protection mode, the plant stops operating. However, if the room temperature drops below 8 °C, heating is switched on to protect the room against frost. Your HVAC installer can change the frost protection limit and set a heat pro­tection limit as needed:
Changes made by installer: Frost protection: ........... ˚C
Heat protection: ........... ˚C
In Comfort mode, the thermostat maintains the room temperature on the setpoint which can be readjusted using the + and – buttons.
In Economy mode, the room temperature is maintained at a lower or higher setpoint, thus saving energy and money. Adjust parameters P11 and P12 to change the preselected setpoints. The thermostat can be set to Economy mode either by pressing the operating mode button if enabled (P02 = 2), or via an external signal (switch or KNX bus command) such as window contact, keycard or presence detector.
In Auto timer mode, the thermostat automatically switches between Comfort and Economy mode according to the time schedule via KNX bus.
to change the operating mode display.

Change from heating to cooling mode

/
Display for automatic changeover or heating only / cooling only:
Changeover between cooling and heating is either automatic using a heating / cooling changeover sensor or a remote changeover switch or via instruction from the central management station via KNX bus, or manual by pressing operating mode button
cooling only or heating only, (see parameter P01).
. No changeover is possible if the thermostat is configured for
Heating valve is open Cooling valve is open
Display for manual changeover:
Thermostat is in heating mode Thermostat is in cooling mode
.
CE1B3171.1en / 2012-08-29 Subject to change Siemens Building Technologies

Temporary timer to extend the Comfort mode

When Economy mode is active, press operating mode button
rarily return to Comfort mode. button
again to stop the timer.
symbol appears. Press operating mode
You can only extend Comfort mode if parameter P02 = 1. Duration * : P68 = 0...360 min, factory setting = 0 min.
to tempo-

Button lock

for 3 seconds to lock or unlock the buttons if
Press operating mode button
manual button lock is configured (parameter P14 = 2). The thermostat automatically locks the buttons 20 seconds after the last adjustment if "Auto lock" is configured (P14 = 1). The key symbol
indicates locked buttons.

Reminder to clean filters and for external faults

FIL *
AL1 * AL2 *
This message reminds you to clean your HVAC equipment filters. It is displayed after ………… “fan operating hours” and disappears when the thermostat is set to Protection (
).
These messages inform you on external faults *:
AL1 : ...……………………… AL2 : ...………………………………….

Note: Economy mode

Commissioning
You can adjust a number of different control parameters to adapt the thermostat to your system and optimize control performance. You can do this during operation either via the buttons on the thermostat or using a commissioning tool.

Control sequence

Recalibrating the sensor

* Needs to be configured by your HVAC installer
The Economy setpoints are factory-set to 15 °C for heating and 30 °C for cooling. Use parameters P11 and P12 to adjust the values. Important: You can set these setpoints to OFF; the thermostat then is inactive, i.e. no protective heating or cooling function. Risk of frost!
The thermostat can be used in systems either for heating only or cooling
only, manually selection of heating or cooling, or automatic heating / cooling changeover. Depending on the selected application, the relevant modes are
available and can be adjusted by commissioning parameter P01 if needed.
The factory setting for 2-pipe application is "Cooling only", and for 4 pipe application "Heating and Cooling"
If the room temperature displayed by the thermostat does not agree with the
erature effectively measured (after min 1 hour of operation), the tem-
temp perature sensor can be recalibrated. With parameter P05 the temperature can be adjusted by + or – 0.5 °C up to a maximum of + / - 3 °C.

Control parameters

Proceed as follows to change the most important control parameters: (Your HVAC installer can set additional parameters)
+ / – 1. Press the – and + buttons simultaneously at least 4 seconds.
Release, and within 2 seconds, press + again until "P01" is displayed.
2. Repeatedly press the + or – button to select the required parameter.
+
+-+
P01 P02 P08 P14
--
3171z99
-
3. Press + and – simultaneously. The current value of the selected parameter begins to flash, allowing you to change the value by repeatedly pressing + or –.
4. The next parameter is displayed when you press + and – again simultaneously.
5. Repeat steps 2 to 4 to display and change additional parameters,.
6. Press + or – until “End” is displayed, and then press + and – simultaneously to save the change and exit parameter entry mode.
15 minutes after the last display or setting, all changes are saved and the thermostat leaves parameter setting mode.
Para­meter
Description
P01 Control sequence
P02 Mode selection by user via operating mode button
P04 Selection of °C or °F 0 (°C) 0 = °C
P05 Sensor calibration 0.0 °C – 3 ... +3 °C P06 Standard temperature display 0 (Room temp.) 0 = Room temperature
P07 Additional user information 0 (no display) 0 = No display
P08 Comfort basic setpoint 21 °C 5 ... 40 °C P09 Minimum setpoint limitation in Comfort (WminComf) 5 °C 5 ... 40 °C P10 Maximum setpoint limitation in Comfort (WmaxComf) 35 °C 5 ... 40 °C P11 Setpoint of heating in Economy (WheatEco) 15 °C OFF, 5 °C…WcoolEco P12 Setpoint of cooling in Economy (WcoolEco) 30 °C OFF, WheatEco…40°C
P13 *** Electric heater in cooling mode ON OFF = disabled
P14 Button lock
(Press operating mode button
the buttons)
for 3 seconds to lock or unlock
** Without time schedule via KNX, Auto is equal to Comfort. *** P a ra me t er P1 3 is on ly di sp la ye d fo r a p pl i ca t io n "2 -p i pe w it h el he a te r ". All temperature settings in increments of 0.5 °C.
The control parameters displayed depend on the DIP switch settings made
+
P13
+-
End
-
Factory setting Setting range
2-pipe: [0…3] 1 (Cooling only)
4-pipe: [2…4] 4 (Heating&Cooling) 1 (Auto **, Protection)
0 (Disabled) 0 = Disabled
0 = Heating only 1 = Cooling only 2 = Manual H or C 3 = Auto Changeover 4 = Heating & cooling 1 = Auto **, Protection 2 = Auto **, Comfort, Economy,
Protection
1 = °F
1 = Setpoint
1 = Temp. in °C / °F 2 = Outside temperature (via bus) 3 = Time of day (12h, via bus) 4 = Time of day (24h, via bus)
ON = enabled
1 = Auto lock 2 = Manual lock
Please record all changes you make!
Adj
CE1B3171.1en / 2012-08-29 Subject to change Siemens Building Technologies