Siemens RDF600 User Manual

yp
s

Operating Instructions

RDF600 – the room thermostat that allows you to set the ideal room temperature you want.
The thermostat provides Comfort mode, Economy mode and Protection.
The fan operates either in automatic mode or at the selected speed when using manual mode.
Protection
Comfort
Economy
Measured room temperature, setpoints and parameters
Symbol when actual room
Display
temperature is displayed
Current time of day or additional user information
Fault indicator *
Adjusting operating mode
- Protection ( )
- Comfort (
- Economy (
or in a system with manual changeover:
- Protection (
- Comfort heating (
- Comfort cooling (
Operation and settings
* if configured by your HVAC installer
CE1B3176.3en / 2012-08-29 Subject to change Siemens Building Technologies
) )*
)
)
)
Colder / Warmer
Adjusting fan mode
- Automatic fan ( )
- Manual fan
Condensation in the room*
Cooling demand / mode
Heating demand / mode Electric heater active
Automatic fan
Low fan speed
Medium fan speed
High fan speed
Ke
ad locked
( )

RDF600

Change room temperature

Press + or - to increase or decrease the current room temperature setpoint for
+ -
Comfort mode. The thermostat changes to Comfort The setting range is from 5...40 °C, unless limited by parameters P09 and P10.

Adjust fan speed / fan mode

Set the thermostat to Protection

Set the thermostat to Economy mode

 

Change from heating to cooling mode

Press the button until you reach the desired fan mode. In Auto mode, the fan speed is automatically selected by the thermostat and
depends on the setpoint and the actual room temperature. When the room temperature has reached the setpoint, the fan is switched off (factory setting)
In manual mode the fan operates independently and always runs at the same speed: Low, medium or high.
Low fan speed
Medium fan speed
High fan speed
For a single-speed fan, the mode can be changed between
Press the operating mode button several times until the display shows the
symbol to indicate that Protection is selected. In Protection
your HVAC installer has adjusted the factory settings.
Changes by installer Frost protection: ________ ˚C  Heat protection:
The thermostat can be set to Economy mode either via pressing the operating mode button
as window switch, key card switch etc. If the external contact is activated the thermostat changes from Comfort mode or Protection to Economy mode. Any operation by the user has no influence.
In Economy mode, the automatic fan control is active.
Note: If the thermostat is configured for manual heating / cooling changeover, the Economy mode can not be selected via operating mode button
The changeover between cooling and heating is done either automatically by a
/
heating / cooling changeover sensor or a remote changeover switch, or manually by pressing the operating mode button
cooling only or heating only, no changeover is possible (see parameter P01)
Display for automatic changeover or continuous heating/cooling: Heating valve is open
Cooling valve is open
Display for manual changeover: Thermostat is in heating mode
Thermostat is in cooling mode
, only frost protection is active (factory setting = 8˚C), unless
if enabled (see parameter P02), or via an external contact such
.
and .
________ ˚C
.
. If the thermostat is configured for

Button lock

Press operating mode button
for 3 seconds to lock or unlock the buttons if
manual button lock is configured (parameter P14 = 2). The thermostat automatically locks the buttons 30 seconds after the last adjustment if "Auto lock" is configured (P14 = 1). The key symbol
indicates locked buttons.

Reminder to clean filters

This message reminds you to clean the filter on your HVAC equipment.
FIL
It will appear after __________ "fan operating hours" and disappear when the thermostat is set to Protection (
).
This reminder must be configured by your HVAC installer.

External faults

This alarm message tells you an external alarm has occurred:
AL1
AL2
AL1 : ______________________
AL2 : ______________________
The alarms are configured by your HVAC installer
Commissioning (by qualifie
d HVAC installer) To adapt the thermostat to your system and optimize the control performance, a number of control parameters can be adjusted. This can also be made during operation without opening the thermostat.

Control sequence

The thermostat can be used in systems either for heating only or cooling only, manually selection of heating or cooling, or automatic heating / cooling changeover. Depending on the selected application, the relevant modes are
available and can be adjusted by commissioning parameter P01 if needed.
The factory setting for 2-pipe application is "Cooling only", and for 4 pipe application "Heating and Cooling"

Recalibrating the sensor

If the room temperature displayed by the thermostat does not agree with the temp
erature effectively measured (after min 1 hour of operation), the tem­perature sensor can be recalibrated. With parameter P05 the temperature can be adjusted by + or – 0.5 °C up to a maximum of + / - 3 °C.

Note: Economy mode

The Economy setpoints are factory-set to 15 °C for heating and 30 °C for cooling. Use parameters P11 and P12 to adjust the values.
Important: You can set these setpoints to OFF; the thermostat then is inactive, i.e. no protective heating or cooling function. Risk of frost!

Control parameters

Proceed as follows to change the most important control parameters: (Your HVAC installer can set additional parameters)
3057z03
P12
+-
P14
-
+
-
1. Set the thermostat to Protection
+ / -
2. Press - and + simultaneously for a minimum of 4 seconds.
+ / -
+ / -
+ / -
Release them and, within 2 seconds, press + again until "P01" is displayed.
3. Repeatedly press the + or – button to select the required parameter.
+
+-+
P01 P02 P08 P13
--
4. Press + and – simultaneously, the current value of the selected parameter starts to flash, allowing you to change the value by repeatedly pressing + or –.
5. The next parameter is displayed when you press + and – again simultaneously.
6. Repeat steps 3 to 5 to display and change additional parameters.
7. 15 seconds after the last display or setting, all changes are saved and the thermostat will leave parameter entry mode.
Para­meter
The control parameters displayed depend on the DIP switch settings made
Description
P01 Control sequence
P02 Mode selection by user via operating mode button 1 (Protection,
P04 Selection of °C or °F 0 (°C) 0 = °C
P05 Sensor calibration 0.0 K – 3 ... +3 K
P06 Standard temperature display 0 (Room temp.) 0 = Room temperature
P07 Additional user information 0 (no display) 0 = no display
P08 Comfort basic setpoint 21 °C 5 ... 40 °C
P09 Minimum setpoint limitation in Comfort (WminComf) 5 °C 5 ... 40 °C
P10 Maximum setpoint limitation in Comfort (WmaxCo mf) 35 °C 5 ... 40 °C
P11 Setpoint of heating in Economy mode (WheatEco) 15 °C OFF, 5 °C…WcoolEc o
P12 Setpoint of cooling in Economy mode (WcoolEco) 30 °C OFF, WheatEco…40°C
P13 Electric heater in cooling mode ON OFF = Disabled
Button lock
P14
(Press operating mode button
unlock the buttons)
for 3 seconds to lock or
Factory setting Setting range
2-pipe: [0…3] 1 (Cooling only)
4-pipe: [2…4] 4 (Heating & Cooling)
Comfort)
0 (Disabled) 0 = Disabled
0 = Heating only 1 = Cooling only 2 = Manual H or C 3 = Auto Changeover 4 = Heating & cooling
1 = Protection, Comfort, 2 = Protection, Comfort, Economy
1 = °F
1 = Setpoint
1 = Temp in °C / °F
ON = Enabled
1 = Auto lock 2 = Manual lock
Please record all changes you make! (All temperature settings can be made in increments of 0.5 K)
CE1B3176.3en / 2012-08-29 Subject to change Siemens Building Technologies
Loading...