Operating Instructions RDF310.2/MM
RDF310.2/MM – the thermostat that allows you to set the ideal room tempe rature you want. The thermo stat provides both comfort mode and protection mode. The fan operates either in automatic mode or at the selected speed when using manual mode. You can either rely on the factory settings or make adjustments that suit your individual nee ds.
Are your rooms too warm or too cold?
Only applicable in Comfort mode. Pressing the +or – button to increase or decrease the current room temperature setpoint for
Comfort mode in increments of 1.0 °C. The setting range is from 5...40 °C, unless it is limited by parameters P05 and P06.
Do you want to set your controller to protection mode?
Press the button and the symbol shows, indicating that protection mode is selected. In protection mode
, the controller maintains the lower setpoint of heating for frost protection via parameter P03 or the higher setpoint of cooling for moldy resistance according to parameter P04.
Important:
If the setpoint of protection is set to OFF,the thermostat will not be activated in protection mode.
Risk of frost!
Do you want to change the fan mode?
AUTO
Press the button until you have selected the desired fan mode. In automatic mode, the fan speed is automatically selected by the controller and depends on
the setpoint and the actual room temperature. When the room temperature has reached the setpoint, the fan either remains in fan speed low (factory setting) or switches off (parameter P21).
In manual mode the fan operates independently and always runs at the same speed: Low, medium or high. The actual fan speed is indicated by the number of fan symbols.
Low fan speed Medium fan speed High fan speed
Do you want to change from heating to cooling mode?
/
When pressing the button, the controller changes from heating to cooling or vice versa. If the controller is commissioned cooling only or heating only, no changeover is possible
(please see parameter P22: factory setting manual H/C changeover)
Do you want to calibrate the displayed room temperature?
If the displayed room temperature does not match the actual temperature, the temperature sensor can be calibrated by modifying parameter P07.
Proceed as described under “Changing the control parameters” and follow steps 1 through 3 to select parameter P07.
In step 4, modify the displayed room temperature to match the actual temperature. Each pressing of the + or - button changes the temperature in increments of 0.5 °C and up to
a range of ±3 °C. In step 7, the calibration is automatically stored 10 seconds after the last readjustment.
Display
Operation and Settings
Low fan speed Medium fan speed
High fan speed
AUTO Auto Automatic fan
Cooling mode
Heating mode
Comfort mode
Protection mode
Measured room temperature, setpoints and parameters
Actual room temperature symbol
Heating/cooling changeover button
to change manually between heating and coo ling mode
Button for changing of fan operating and
protection mode
- Protection (
)
- Automatic fan speed
(AUTO
)
- Manual fan speed
(
)
Colder / Warmer
Setting the temperature setpoints
Selectable temperature unit
CB1B3066en / 2015-01-28 Subject to change Siemens Building Technologies
Changing the control parameters
To optimize the control performance, you can use local HMI to adjust a number of control parameters. Proceed as follows to change the control parameters (see the table of “Commissioning by qualified HVAC staff
” for factory settings):
+ / - + / -
+ / -
+ / -
1. Set the thermostat to protection mode .
2. Press and hold down the + and – buttons simultaneously for 3 seconds. Release them and,
within 2 seconds, press and hold down the + button for 3 seconds. The display shows P03.
3. Select the required parameter by pres sing the + or – button as follows:
4. Press the + and – buttons simultaneously. The current value of the selected parameter displays on the screen. Press the + or -.button to change the value.
5. You can either press the + and - buttons simultaneously to confirm the change, or wait
for 5 seconds to have the change saved automatically.
6. Repeat step 3 through 5 to change more parameters.
7. 10 seconds after the last display, all changes are saved and it returns to protection mode.
8. Press the
button to switch to Comfort mode .
Commissioning (by qualified HVAC staff)
Para-
meter
Description
Factory setting
Setting range
Adj.!
P03
Setpoint of heating in protection (Wheat
Stb
)
8 °C OFF, 5 °C…Wcool
Stb
P04
Setpoint of cooling in protection (Wcool
Stb
)
OFF OFF, Wheat
Stb
…40 °C
P05 Minimum setpoint limitation in Comfort mode (Wmin
Norm
) 5 °C 5 °C…Wmax
Norm
P06 Maximum setpoint limitation Comfort mode (Wm ax
Norm
) 35 °C Wmin
Norm
…40 °C P07 Sensor calibration 0 K -3…3 K P08 Switching differential heating SDH 1 K 0.5…4 K P09 Switching differential cooling SDC 1 K 0.5…4 K P14 Dwelling time of auto fan s peeds 2 min. 1…5 minutes P17 Selec tion of °C or °F °C °C or °F
P18 Display of room temperature or setpoint ON
OFF: Setpoint ON: Room temperature
P21 Fan control in normal operation (Comfort mode) ON
OFF in dead zone ON in dead zone
P22 Heating/cooling mode
3:Manual H/C
changeover
0: Heating only 1: Cooling only 3: Manual H/C changeover
! Please record all changes you make.