Siemens RDF302 Operating Instructions Manual

CE1B3079en / June 14, 2011 Subject to change Siemens Building Technologies
s
Operating Instructions
RDF302
RDF302 – the room thermostat with RS 485 communications, using Modbus protocol, allows you to set the ideal room temperature you want. The thermostat provides Comfort, Energy Saving, and Protection mode. The fan operates either in Auto mode or at a speed selected in Manual mode. You can either take advantage of the thermostat's factory settings or adjust it as needed.
Display
Protection mode Comfort mode Energy Saving mode
Measured room temperature, setpoints and parameters
Current time of day or additional user information
Actual room temperature
Outdoor temperature
Fault indicator *
Condensation in the room *
Cooling demand/mode Heating demand/mode Electrical heater active
Automatic fan
Low fan speed
Medium fan speed
High fan speed
Buttons are locked
Operation and settings
Operating mode button
- Protection
- Comfort
- Economy
**
or in a system with manual
changeover
:
- Protection
- Comfort heating
- Comfort cooling
Colder / Warmer
Fan mode button
– Automatic fan (
)
– Manual fan (
)
* Needs to be configured by your HVAC installer ** Needs to be enabled via parameter P02
Change room temperature
+/–
Press + or to increase or decrease the current room temperature setpoint for Comfort mode. The thermostat changes to Comfort
.
The setting range is 5...40 °C, unless limited by parameters P09 and P10.
Adjust fan speed/fan mode
Press the button until you reach the desired fan mode.
In Auto mode, the thermostat automatically selects the fan speed based on setpoint and actual room temperature. The fan continues to run at low speed (factory setting) after the room temperature reaches the setpoint.
In manual mode, the fan always runs at the speed that you select: Low fan speed Medium fan speed High fan speed For a single-speed fan, you can change the mode between
and .
Change thermostat operating
Press operating mode button
to change the operating mode display.
In protection mode, the plant stops operating. However, if the room temperature drops below 8 °C, heating is switched on to protect the room against frost. Your HVAC installer can change the frost protection limit and set a heat protection limit as needed:
Changes made by installer: Frost protection: ........... ˚C
Heat protection: ........... ˚C
In Comfort mode, the thermostat maintains the room temperature on the setpoint which can be readjusted using the + and – buttons.
In Energy Saving mode, the room temperature is maintained at a lower or higher setpoint, thus saving energy and money. Adjust parameters P11 and P12 to change the preselected setpoints. The thermostat can be set to Energy Saving mode either by pressing the operating mode button if enabled (P02 = 2), or via an external signal (switch or Modbus command) such as window contact, keycard or presence detector.
Change from heating to cooling mode
/
Changeover between cooling and heating is either automatic using a heating/cooling changeover sensor or a remote changeover switch or via instruction from the central management station via Modbus, or manual by pressing operating mode button
. No changeover is possible if the thermostat
is configured for cooling only or heating only (see parameter P01).
Display for automatic changeover or heating only/cooling only:
Heating valve is open Cooling valve is open
Display for manual changeover:
Thermostat is in heating mode Thermostat is in cooling mode
CE1B3079en / June 14, 2011 Subject to change Siemens Building Technologies
Button lock
Press operating mode button
for 5 seconds to lock or unlock the buttons if manual button lock is configured (parameter P14 = 2). The thermostat automatically locks the buttons 10 seconds after the last adjustment if "Auto lock" is configured (P14 = 1).
The key symbol
indicates locked buttons. Notes: The button lock cannot be released (unlocked) once the buttons were locked by the master through the Modbus command.
Reminder to clean filters and for external faults
FIL *
AL1 * AL2 *
This message reminds you to clean your HVAC equipment filters. It is displayed after ………… “fan operating hours” and disappears when the thermostat is set to Protection (
).
These messages inform you on external faults *:
AL1 : ...…………………………………. AL2 : ...………………………………….
Recalibrating the sensor
If the room temperature displayed by the thermostat does not agree with the temperature effectively measured (after min 1 hour of operation), the temperature sensor can be recalibrated through p arameter P05.
Note: energy saving mode
The energy saving setpoints are factory-set to 15 °C for heating and 30 °C for cooling. Use parameters P11 and P12 to adjust the values.
Important: You can set these setpoints to OFF; the thermostat then is inactive, i.e. no protective heating or cooling function.
Risk of frost!
Commissioning
You can adjust a number of different control parameters to adapt the thermostat to your system and optimize control performance. You can do this during operation either via the buttons on the thermostat or using a commissioning tool via Modbus.
Baud rate and parity
The Baud rate can be adjusted to 4800 bps, 9600 bps, 19200 bps (factory setting) or 38400 bps. The Parity can be s et to none, odd or even (factory setting). Your HVAC installer can set them through the additional parameters.
Important: Once you made any changes on the baud rate or parity, you must reset the power before the changes become effective.
* Needs to be configured by your HVAC installer
Control parameters
Proceed as follows to change the most important control parameters (your HVAC installer can set additional parameters):
+/–
1. Press the – and + buttons simultaneously at least 3 seconds. Release, and within 2 seconds, press + again for 3 seconds. "P01" is displayed.
2. Repeatedly press the + or – button to select the required parameter.
-
--
-
-
-
3. Press + and – simultaneously. The current value of the selected parameter begins to flash, allowing you to change the value by repeatedly pressing + or –.
4. The next parameter is displayed when you press + and – again simultaneously.
5. Repeat steps 2 to 4 to display and change additional parameters.
6. Press + or – until “End” is displayed, and then press + and – simultaneously to save the change and exit parameter entry mode.
Parameter Description
Factory setting Setting range Adjustment
P01 Control sequence
2-pipe: [0…3] 1 (Cooling only)
4-pipe: [2…4] 4 (Heating & Cooling)
0 = Heating only 1 = Cooling only 2 = Manual Heating or Cooling 3 = Auto Changeover 4 = Heating & cooling
P02 Mode selection by user via operating mode button 1 (Comfort, Protection)
1 = Comfort, Protection 2 = Comfort, Energy Saving,
Protection
P04 Selection of °C or °F °C
0 = °C 1 = °F
P05 Sensor calibration 0.0 °C
-3...3 °C
P06 Standard temperature display 0 (Room temperature)
0 = Room temperature 1 = Setpoint
P07 Additional user infor mation 0 (no display)
0 = No display 1 = Temperature in °C/°F 2 = Outside temperature
(via bus) 3 = Time of day (12 h, via bus) 4 = Time of day (24 h, via bus)
P08 Comfort basic setpoint 21 °C 5...40 °C
P09 Minimum setpoint limitation in Comfort (WminComf) 5 °C 5...40 °C
P10 Maximum setpoint limitation in Comfort (WmaxComf) 35 °C 5...40 °C
P11 Setpoint of heating in Energy Saving (WheatEco) 15 °C OFF, 5 °C…WcoolEco
P12 Setpoint of cooling in Energy Saving (WcoolEco) 30 °C OFF, WheatEco…40 °C
P13 *** Electrical heater in coo ling mode ON
OFF = disabled ON = enabled
P14
Button lock (Press operating mode button
for 5 seconds to lock
or unlock the buttons)
0 (Disabled)
0 = Disabled 1 = Auto lock 2 = Manual lock
*** Parameter P13 is only displayed for application "2-pipe with electric heater".
All temperature settings are in increments of 0.5 °C.
Please record all changes you make!