CE1B3171en / 26 Nov 2009 Subject to change Siemens Building Technologies
Temporary timer to extend the Comfort mode
When Energy Saving operating mode is active, press operating mode button
to temporarily return to Comfort mode.
symbol appears. Press opera-
ting mode button
again to stop the timer.
You can only extend Comfort mode if parameter P02 = 1.
Duration * : P68 = 0...360 min, factory setting = 0 min.
Operate switching groups
Use buttons I, II, III and IV to operate KNX actuators *.
The following functions are available:
– Switching: Toggle on/off with 1 button or on/off with 2 buttons
(I + II or III+IV). "ON" or "OFF" is displayed.
– Dim lights with 2 buttons (I+II or III+IV):
On/off with a short pulse (<0.5 s); "ON" or "OFF" is displayed.
Brighter/darker with a long pulse (>1 s); "dI" is displayed.
– Operate blinds with 2 buttons (I+II or III+IV):
A long pulse (>1 s) starts the up/down motor; "UP" or "down" is displayed.
A short pulse (<0.5 s) stops the motor or slightly adjusts the position of
blinds; "ON" or "OFF" is displayed.
– Scene I, II, III, or IV: A scene can be used to recall certain states of all
actuators involved, as well as to save new states as needed. E.g. different
dimmed lights and blinds positions you consider adequate for certain
events / times.
A short pulse (<0.5 s) starts the scene. "CALL" is displayed.
A long pulse (>3 s) saves the actual position of all actuators involved as
adjusted previously; "SAVE" is displayed.
Button lock
Press operating mode button
for 5 seconds to lock or unlock the buttons if
manual button lock is configured (parameter P14 = 2).
The thermostat automatically locks the buttons 20 seconds after the last
adjustment if "Auto lock" is configured (P14 = 1).
The key symbol
indicates locked buttons.
Reminder to clean filters and for external faults
FIL *
AL1 *
AL2 *
This message reminds you to clean your HVAC equipment filters.
It is displayed after ………… “fan operating hours” and disappears when the
thermostat is set to Protection (
).
These messages inform you on external faults *:
AL1 : ...……………………… AL2 : ...………………………………….
Note: Energy saving mode
The energy saving setpoints are factory-set to 15 °C for heating and 30 °C for
cooling. Use parameters P11 and P12 to adjust the values.
Important: You can set these setpoints to OFF; the thermostat then is
inactive, i.e. no protective heating or cooling function.
Risk of frost!
* Needs to be configured by your HVAC installer
Commissioning
You can adjust a number of different control parameters to adapt the thermostat to your system and optimize control performance. You can do this during operation either via the buttons on the thermostat or using a commissioning tool.
Control parameters
Proceed as follows to change the most important control parameters:
(Your HVAC installer can set additional parameters)
+ / – 1. Press the – and + buttons simultaneously at least 3 seconds.
Release, and within 2 seconds, press + again for 3 seconds. "P01" is displayed.
2. Repeatedly press the + or – button to select the required parameter.
P01 P02 P08 P14
+-+
--
+
3171z99
End
-
+
P13
+-
3. Press + and – simultaneously. The current value of the selected parameter begins to flash, allowing you to change
the value by repeatedly pressing + or –.
4. The next parameter is displayed when you press + and – again simultaneously.
5. Repeat steps 2 to 4 to display and change additional parameters,.
6. Press + or – until “End” is displayed, and then press + and – simultaneously to save the change and exit parameter
entry mode.
Parameter
Description
Factory setting Setting range Adj
P01 Control sequence
2-pipe…: [0…3]
1 (Cooling only)
4-pipe:. [2…4]
4 (Heating&Cooling)
0 = Heating only
1 = Cooling only
2 = Manual H or C
3 = Auto Changeover
4 = Heating & cooling
P02 Mode selection by user via operating mode button
** Without time schedule via KNX, Auto is equal to Comfort.
1 (Auto **,
Protection)
1 = Auto **, Protection
2 = Auto **, Comfort, Energy
Saving, Protection
P04 Selection of °C or °F °C 0 = °C
1 = °F
P05 Sensor calibration 0.0 °C – 3 ... +3 °C
P06 Standard temperature display 0 (Room temp.) 0 = Room temperature
1 = Setpoint
P07 Additional user information 0 (no display) 0 = No display
1 = Temp. in °C / °F
2 = Outside temperature (via bus)
3 = Time of day (12h, via bus)
4 = Time of day (24h, via bus)
P08 Comfort basic setpoint 21 °C 5 ... 40 °C
P09 Minimum setpoint limitation in Comfort (WminComf) 5 °C 5 ... 40 °C
P10 Maximum setpoint limitation in Comfort (WmaxComf) 35 °C 5 ... 40 °C
P11 Setpoint of heating in Energy Saving (WheatEco) 15 °C OFF, 5 °C…WcoolEco
P12 Setpoint of cooling in Energy Saving (WcoolEco) 30 °C OFF, WheatEco…40°C
P13 *** Elec trical heater in cooling mode ON OFF = disabled
ON = enabled
P14 Button lock
(Press operating mode button
for 5 seconds to lock or unlock
the buttons)
0 (Disabled) 0 = Disabled
1 = Auto lock
2 = Manual lock
*** P ar am et er P1 3 i s o nl y d i s pl ay ed fo r a pp li ca ti on "2 -p i pe wi th el h e at er ".
All temperature settings in increments of 0.5 °C.
Please record all changes you make!