Siemens RDF301,RDF 301.50 Operating Instructions Manual

CE1B3171en / 26 Nov 2009 Subject to change Siemens Building Technologies
s
Operating Instructions
RDF301, RDF301.50
RDF301 / RDF301.50 – the room thermostat with KNX communications allows you to set the ideal room temperature. The thermostat provides Comfort, Energy Saving, and Protection mode and can operate in Auto timer mode using a time schedule provided via bus.
The fan operates either in Auto mode or at a speed selected in Manual mode.
You can either take advantage of the thermostat's factory settings or adjust it as needed.
Display
Protection mode
Auto Timer mode
Comfort mode
Energy Saving mode
Measured room temperature, setpoints and parameters
Current time of day or additional user information
Actual room temperature
Outdoor temperature
Fault indicator *
Condensation in the room *
Cooling demand / mode
Heating demand / mode
Electrical heater active
Extended Comfort mode *
Automatic fan
Low fan speed
Medium fan speed
High fan speed
Buttons are locked
Weekday 1…7 (1 = Monday / 7 = Sunday)
Operation and settings
Operating mode button
** **
Notes:
– The thermos tat goes back to Auto
Timer mode if a time schedule via bus changes the operating mode.
– User operations are ignored if a
time schedule via bus sets the operating mode to protection. When you press a button, "OFF" flashes on the LCD.
– Auto mode is not available if the-
re is no time schedule via bus.
Colder / Warmer
Fan mode button
– Automatic fan (
)
– Manual fan (
)
4 buttons for switching groups
(control of KNX actuators, RDF301.50 only) * – Switch lights etc. – Dim lights – Open / close blinds – Scenes (recall / save)
* Needs to be configured by your HVAC installer ** Needs to be enabled via parameter P02
Change room temperature
+ / –
Press + or to increase or decrease the current room temperature setpoint for Comfort mode. The thermostat changes to Comfort
.
The setting range is 5...40 °C, unless limited by parameters P09 and P10.
Adjust fan speed / fan mode
Press the button until you reach the desired fan mode.
In Auto mode, the thermostat automatically selects the fan speed based on set­point and actual room temperature. The fan continues to run at low speed (factory setting) after the room temperature reaches the setpoint .
In manual mode, the fan always runs at the speed that you select: Low fan speed Medium fan speed High fan speed
For a single-speed fan, you can change the mode between and .
Change thermostat operating
Press operating mode button
to change the operating mode display.
In protection mode, the plant stops operating. However, if the room temperature drops below 8 °C, heating is switched on to protect the room against frost. Your HVAC installer can change the frost protection limit and set a heat pro­tection limit as needed:
Changes made by installer: Frost protection: ........... ˚C
Heat protection: ........... ˚C
In Comfort mode, the thermostat maintains the room temperature on the setpoint which can be readjusted using the + and – buttons.
In Energy Saving mode, the room temperature is maintained at a lower or higher setpoint, thus saving energy and money. Adjust parameters P11 and P12 to change the preselected setpoints. The thermostat can be set to Energy Saving mode either by pressing the ope­rating mode button if enabled (P02 = 2), or via an external signal (switch or KNX bus command) such as window contact, keycard or presence detector.
In Auto timer mode, the thermostat automatically switches between Comfort and Energy Saving mode according to the time schedule via KNX bus.
Change from heating to cooling mode
/
Changeover between cooling and heating is either automatic using a heating / cooling changeover sensor or a remote changeover switch or via instruction from the central management station via KNX bus, or manual by pressing operating mode button
. No changeover is possible if the thermostat is configured for
cooling only or heating only, (see parameter P01).
Display for automatic changeover or heating only / cooling only:
Heating valve is open Cooling valve is open
Display for manual changeover:
Thermostat is in heating mode Thermostat is in cooling mode
CE1B3171en / 26 Nov 2009 Subject to change Siemens Building Technologies
Temporary timer to extend the Comfort mode
When Energy Saving operating mode is active, press operating mode button
to temporarily return to Comfort mode.
symbol appears. Press opera-
ting mode button
again to stop the timer. You can only extend Comfort mode if parameter P02 = 1. Duration * : P68 = 0...360 min, factory setting = 0 min.
Operate switching groups
Use buttons I, II, III and IV to operate KNX actuators *. The following functions are available: – Switching: Toggle on/off with 1 button or on/off with 2 buttons
(I + II or III+IV). "ON" or "OFF" is displayed.
Dim lights with 2 buttons (I+II or III+IV):
On/off with a short pulse (<0.5 s); "ON" or "OFF" is displayed.
Brighter/darker with a long pulse (>1 s); "dI" is displayed. – Operate blinds with 2 buttons (I+II or III+IV): A long pulse (>1 s) starts the up/down motor; "UP" or "down" is displayed.
A short pulse (<0.5 s) stops the motor or slightly adjusts the position of
blinds; "ON" or "OFF" is displayed. – Scene I, II, III, or IV: A scene can be used to recall certain states of all
actuators involved, as well as to save new states as needed. E.g. different
dimmed lights and blinds positions you consider adequate for certain
events / times. A short pulse (<0.5 s) starts the scene. "CALL" is displayed. A long pulse (>3 s) saves the actual position of all actuators involved as
adjusted previously; "SAVE" is displayed.
Button lock
Press operating mode button
for 5 seconds to lock or unlock the buttons if manual button lock is configured (parameter P14 = 2). The thermostat automatically locks the buttons 20 seconds after the last adjustment if "Auto lock" is configured (P14 = 1). The key symbol
indicates locked buttons.
Reminder to clean filters and for external faults
FIL *
AL1 * AL2 *
This message reminds you to clean your HVAC equipment filters. It is displayed after ………… “fan operating hours” and disappears when the thermostat is set to Protection (
).
These messages inform you on external faults *:
AL1 : ...……………………… AL2 : ...………………………………….
Note: Energy saving mode
The energy saving setpoints are factory-set to 15 °C for heating and 30 °C for cooling. Use parameters P11 and P12 to adjust the values. Important: You can set these setpoints to OFF; the thermostat then is inactive, i.e. no protective heating or cooling function. Risk of frost!
* Needs to be configured by your HVAC installer
Commissioning
You can adjust a number of different control parameters to adapt the thermostat to your system and optimize control perfor­mance. You can do this during operation either via the buttons on the thermostat or using a commissioning tool.
Control parameters
Proceed as follows to change the most important control parameters: (Your HVAC installer can set additional parameters)
+ / – 1. Press the – and + buttons simultaneously at least 3 seconds.
Release, and within 2 seconds, press + again for 3 seconds. "P01" is displayed.
2. Repeatedly press the + or – button to select the required parameter.
P01 P02 P08 P14
+-+
--
+
3171z99
End
-
+
­P13
+-
3. Press + and – simultaneously. The current value of the selected parameter begins to flash, allowing you to change the value by repeatedly pressing + or –.
4. The next parameter is displayed when you press + and – again simultaneously.
5. Repeat steps 2 to 4 to display and change additional parameters,.
6. Press + or – until “End” is displayed, and then press + and – simultaneously to save the change and exit parameter entry mode.
Para­meter
Description
Factory setting Setting range Adj
P01 Control sequence
2-pipe…: [0…3] 1 (Cooling only)
4-pipe:. [2…4] 4 (Heating&Cooling)
0 = Heating only 1 = Cooling only 2 = Manual H or C 3 = Auto Changeover 4 = Heating & cooling
P02 Mode selection by user via operating mode button
** Without time schedule via KNX, Auto is equal to Comfort.
1 (Auto **, Protection)
1 = Auto **, Protection 2 = Auto **, Comfort, Energy
Saving, Protection
P04 Selection of °C or °F °C 0 = °C
1 = °F P05 Sensor calibration 0.0 °C – 3 ... +3 °C P06 Standard temperature display 0 (Room temp.) 0 = Room temperature
1 = Setpoint P07 Additional user information 0 (no display) 0 = No display
1 = Temp. in °C / °F
2 = Outside temperature (via bus)
3 = Time of day (12h, via bus)
4 = Time of day (24h, via bus) P08 Comfort basic setpoint 21 °C 5 ... 40 °C P09 Minimum setpoint limitation in Comfort (WminComf) 5 °C 5 ... 40 °C P10 Maximum setpoint limitation in Comfort (WmaxComf) 35 °C 5 ... 40 °C P11 Setpoint of heating in Energy Saving (WheatEco) 15 °C OFF, 5 °C…WcoolEco P12 Setpoint of cooling in Energy Saving (WcoolEco) 30 °C OFF, WheatEco…40°C
P13 *** Elec trical heater in cooling mode ON OFF = disabled
ON = enabled P14 Button lock
(Press operating mode button
for 5 seconds to lock or unlock
the buttons)
0 (Disabled) 0 = Disabled
1 = Auto lock
2 = Manual lock
*** P ar am et er P1 3 i s o nl y d i s pl ay ed fo r a pp li ca ti on "2 -p i pe wi th el h e at er ". All temperature settings in increments of 0.5 °C.
Please record all changes you make!
Loading...