Siemens RDF210, RDF210.2, RDF210.2/IR, RDF210/IR User Manual

Page 1
058
3
RDF210, RDF210.2, RDF210/IR, RDF210.2/IR
Room Temperature Controllers with LCD
with 7-day time program
for use with compressors in DX type equipment
RDF210…
N3058en
10.01.2006
Output for on / off valve actuator or 1-stage compressor Operating modes: Normal operation, Auto Timer (energy saving) and Standby 3-speed fan control: Automatic or manual 8 programmable timers Adjustable commissioning and control parameters Optional display of room temperature or setpoint Minimum and maximum setpoint limitation Operating voltage AC 230 V
Additional features of RDF210
Automatic heating / cooling changeover Input for heating / cooling changeover or return air temperature sensor
Additional features of RDF210.2 Manual heating / cooling changeover
Optional
Infrared remote control (RDF210/IR, RDF210.2/IR)
Building Technologies
HVAC Products
Page 2
Use
Functions
For controlling the room temperature in individual rooms and zones that are
heated or cooled with 2-pipe fan coil units
cooled with a single compressor in DX type equipment
The controller controls
a 3-speed fan
either a valve actuator in a 2-pipe system, or
a 1-stage compressor in DX type equipment
Suitable for use in systems with
automatic heating / cooling changeover (RDF210)
continuous heating or cooling mode (RDF210)
manual heating / cooling changeover (RDF2110.2)
Changeover between heating and cooling mode is either automatic by a QAH11.1
changeover cable temperature sensor or manually
Maintenance of room temperature either with integrated temperature sensor or ex­ternal room / return air temperature sensor (only with RDF210)
Selection of operating mode with the operating mode button
AUTO
or on the
controller
8 programmable timers for changing over between Normal operation and Energy Saving mode
3-speed fan control (automatic or manual)
Output for 2-position (on / off) valve actuator or 1-stage compressor
Optional with infrared remote control (only with RDF210…/IR)
Controller
Temperature control
Display
The controller acquires the room temperature via its built-in sensor and maintains the setpoint by delivering 2-position valve control commands or compressor output com­mands. With the RDF210, an external room temperature sensor (QAA32) or external return air temperature sensor (QAH11.1) can be used instead. The switching differential is 2 K in heating mode and 1 K in cooling mode (adjustable via parameters P08 and P09).
The display shows the acquired room / return air temperature or the setpoint of the current operating mode. This can be selected via parameter P18. Factory setting is display of the current room temperature.
The heating
and cooling symbols on the display show the status of the fan coil. This means that the symbols are also shown while the controller operates in the neutral zone.
If required, room temperature and setpoint can also be displayed in °F in place of °C by changing parameter P17.
2/15
Building Technologies Room Temperature Controllers N3058en HVAC Products 10.01.2006
Page 3
Operating modes
Y
Y
The following operating modes are available:
Normal operation
Tip!
Auto Timer mode
Energy Saving mode
Standby
Avoiding damage due to moisture
In Normal operation, the controller maintains the setpoint, which can be adjusted via the
buttons. The fan can be set to automatic or manual fan speed: Low, medium or high. The setpoint setting range can be limited to a minimum (P05) and maximum (P06). This helps prevent the waste of energy, thus saving costs.
In Auto Timer mode
AUTO
, the controller will automatically change over between Normal
operation and Energy Saving mode according to the 8 preprogrammed timers. The
AUTO
display shows the Auto Timer mode symbol currently maintained, either Normal operation
and the symbol of the operating mode
or Energy Saving mode
. The setpoints of Energy Saving mode can be adjusted via control parameters P01 and P02. The default fan speed in Auto Timer mode is automatic fan.
When the controller is in Standby mode
, the relevant setpoints of heating or cooling are maintained. These setpoints can be adjusted via control parameters P03 and P04. Factory setting of both setpoints is OFF, which means that the controller is not acti­vated when in Standby mode.
To avoid damage due to moisture in very warm and humid climatic zones resulting from lack of air circulation in Energy Saving mode, the fan can be kept running all the time (e.g. in apartments or shops during unoccupied periods), when setting parameter P20 “ON in dead zone”. In this case, the fan keeps running at minimum fan speed 1.
Control sequences
Water-based fan coil application
Compressor based application
ON
OFF
Used in conjunction with a valve, either for heating / cooling with changeover, heating only or cooling only.
Used in conjunction with a 1-stage compressor for cooling only or heating only.
Heating mode Cooling mode
11
3058D01
1
0
½ SDH
T[°C] Room temperature SDH Switching differential “Heating”
W Room temperature setpoint SDC Switching differential “Cooling”
Y11 Control output “Valve” or “Compressor”
w
T[°C]
½ SDH
11
1
0
½ SDC
3058D02
w
T[°C]
½ SDC
The valve or compressor receives the OPEN command via control output Y11 when
1. the acquired room temperature lies by half the switching differential below the set-
point (heating mode) or above the setpoint (cooling mode), and
2. control output Y11 was not energized for more than the “Minimum output off time”
(factory setting 1 minute, adjustable via parameter P16)
The valve or compressor receives the CLOSE command via control output Y11 when
1. the acquired room temperature lies by half the switching differential above the set-
point (heating mode) or below the setpoint (cooling mode), and
3/15
Building Technologies Room Temperature Controllers N3058en HVAC Products 10.01.2006
Page 4
2. control output Y11 was energized for more than the “Minimum output on time”; (factory setting 1 minute, adjustable by parameter P15)
Note: Control output Y12 delivers a control command which is inverted to the control command at output Y11 and which can be used for normally open valves.
Heating / cooling mode
Minimum output on time / off time Y11
Fan operation
With the RDF210, the changeover between cooling and heating takes place either automatically via a heating / cooling changeover sensor or a remote changeover
switch. If the controller was set to ”Cooling only” or ”Heating only”, changeover will not
be possible (parameter P22, factory setting ”Cooling only”).
With the RDF210.2, when pressing the heating / cooling changeover button
, the
controller will change from heating to cooling, or vice versa.
The minimum output on time and off time of Y11 can be adjusted from 1…10 minutes via parameters P15 and P16. Factory setting is 1 minute. In this case, any readjustment of the setpoint or of heating / cooling mode changeover will be used immediately for computing the output status and output Y11 may not hold the minimum on / off time of 1 minute. If parameter P15 or P16 is set to a level above 1 minute, the minimum on / off time of Y11 will be maintained as set, even if the setpoint or changeover mode has been read­justed.
The fan operates either in automatic mode or at the selected speed when using manual mode. In automatic mode, the fan speed depends on the setpoint and the current room temperature. When the room temperature reaches the setpoint, the control valve will close and the fan switch off: Temperature-dependent fan control (see diagram below). The individual switching differentials of the fan speeds can be adjusted via control pa­rameters P08 – P13.
Heating mode Cooling mode
Valve
Valve
Y11Y11
3058D03
Q3
Q2
Q1
Fan
SDH
SDHSDH2SDH3
W
Temp
Q3
Q2
Q1
Temp
Fan
W
SDC
Temp
Temp
SDC3SDC2SDC
Ventilation always on
If desired, fan control can be set to ”Temperature-independent”, which means that ven­tilation is always on, even within the dead zone, using at least fan speed 1. This can be selected individually for Normal operation using parameter P21 and for Energy Saving mode using parameter P20 (also refer to “Avoiding damage due to moisture”).
Dwelling time
In automatic mode, a dwelling time of 2 minutes (factory setting) is active. The fan maintains that speed for at least 2 minutes before it switches to the next speed. This dwelling time can be adjusted from 1…5 minutes using parameter P14.
4/15
Building Technologies Room Temperature Controllers N3058en HVAC Products 10.01.2006
Page 5
Fan start
Fan in Auto Timer mode
Auto Timer
Whenever the fan starts from standstill, it starts with speed 3 for 1 second in order to guarantee a safe fan motor start (to overcome inertia and friction)
In Auto Timer mode, the default fan mode is automatic. The fan mode can be changed to manual fan speed. With each changeover from Normal operation to Energy Saving mode, or vice versa, the fan will return to default mode automatic.
The controller provides an Auto Timer mode with 8 programmable timers. In this mode, the controller will automatically change over between Normal operation and Energy Saving mode according to the preprogrammed timers.
Setting the timers
Auto Timer during Normal operation Auto Timer during Energy Saving mode
1
AUTO
o
C
1
AUTO
o
C
Each timer has a Normal operation start time and a Normal operation end time which can be applied to several weekdays. To adjust the time schedule, keep the
button depressed for 3 seconds to go to the programmable timer setting mode. This mode is indicated by displaying Ax (x= auto timer 1...8) and the time xx:xx flash­ing.
For each auto timer, proceed as follows:
1. The
and symbols are displayed. Press or to adjust the Normal opera-
tion start time and confirm by pressing
.
2. The
and symbols are displayed. Press or to adjust the Normal operation
end time or Energy Saving start time respectively and confirm by pressing
.
3. Symbol the next day. Confirm setting for actual timer by pressing
1
will flash. Press or to select or deselect each day and advance to
and advance to t
he
next timer.
5/15
Building Technologies Room Temperature Controllers N3058en HVAC Products 10.01.2006
Page 6
View the timers
Default timer setting
The controller will leave the programmable timer setting mode if no button is pressed within 20 seconds. All changes made after the last press of
button will not be
saved. Press the
button to sequentially review the 8 timers.
Timers A1…A4 have the following default setting:
Reload default timer setting
Overlapping of timer sequences
Day/s
Time when controller is in Normal operation
Mo (1) – Fr (5) 06:30 – 08:30 (A1) 17:30 – 22:30 (A2)
Sa (6) 08:00 – 23:00 (A3) Su (7) 08:00 – 22:30 (A4)
- During the remaining time, controller is in Energy Saving mode
- Timers A5…A8 are free, no default setting
The setting of these timers can be changed to suit individual needs. The default setting can be reloaded any time:
1. Set the controller to Standby .
2. Press and simultaneously for 3 seconds. Release them and, within 2 seconds,
press 2 times
.
Then, the display will show “8888“ during the reloading process.
In case 2, or when several timer sequences overlap, the resulting output is the OR combination of the normal operating mode time of all timers.
22:00
20:00
A1=09:00-22:00
12:00
09:00
7day-time clock
Setting the time clock
Power failure
A2=12:00-20:00
Resul t in g output = 09 : 0 0­22:00
3058D04
The 7day-time clock supports the 12-hour and 24-hour format. The format is chosen during setting of the time clock as follows:
1. Keep the
button depressed until the time digits start to flash and then press or
to set the time of day. If the current time is the 24-hour format and you wish to
change to the 12-hour format, press
passing 23:59 or press passing 00:00.
Vice versa back to the 24-hour format.
2. Confirm the time of day by pressing
3. Press
or to set the current weekday.
4. Confirm the current weekday by pressing
and the weekday indicator starts to flash.
.
In case of a power failure, the clock will stop, but its last running time will be stored. This time information will be reloaded and start running after a power up. The clock will flash to indicate that there was a power failure until the time will be confirmed by press­ing
or readjusted by folowing the above procedure.
6/15
Building Technologies Room Temperature Controllers N3058en HVAC Products 10.01.2006
Page 7
External sensor input B1-M
Automatic heating / cooling changeover
Remote heating / cooling changeover
With the RDF210, a return air / external room temperature sensor or heating / cooling changeover sensor can be connected to terminal B1-M. The function of this sensor input is determined by parameter P22.
Sensor input B1-M is not galvanically separated from the AC 230 V mains supply. Therefore, only a cable temperature sensor and wiring with sufficient insulation must be used.
When P22 is set to “Automatic H/C changeover”, the sensor input acts to ensure auto­matic heating / cooling changeover. The water temperature acquired by the changeover sensor (QAH11.1 + ARG86.3) is used to switch from heating to cooling mode, or vice versa. When the water temperature lies above 28 °C (parameter P24), the controller switches to heating mode; below 16 °C (parameter P23), it switches to cooling mode. If, immediately after switching on, the water temperature lies between the 2 changeover points, the controller will start in heating mode. The water temperature is acquired at 30-second intervals and the operating state is updated.
Automatic H/C changeover
M
CM
HM
M Operating mode CM Cooling mode T
16 28
Water temperature HM Heating mode
w
3021D03
TW [°C]
The QAH11.1 cable temperature sensor for automatic heating / cooling changeover can be replaced by an external switch (suited for mains voltage) for manual remote change­over:
External room or return air temperature sensor
Summary B1-M and P22
Contact open Æ heating mode
Contact closed Æ cooling mode
T °C
B1
M
T
QAH11.1
B1
M
3058Z03
With parameter P99 (diagnostic value), automatic heating / cooling changeover can be checked.
When parameter P22 is set to “Cooling only” or “Heating only”, sensor input B1-M can be used to connect an external room temperature (QAA32) or a return air temperature sensor (QAH11.1). Changeover is automatic if a sensor is detected at the sensor input. With parameter P98 (diagnostic value), the sensor status can be checked.
The following table summarizes the relation between parameter P22, external sensor B1-M and variables which the controller uses for maintaining the temperature:
Parameter P22
Heating only
Cooling only
Automatic H/C change­over
Variables: The controller….
No sensor at
B1-M
is in H/C mode Heating
controls according Internal sensor
is in H/C mode Cooling
controls according to Internal sensor
is in H/C mode Heating
controls according to
Internal sensor Internal sensor
QAH11.1/QAA32 at
B1-M
Heating
Sensor at B1
Cooling
Sensor at B1
depending on the tempera-
ture from sensor B1-M
7/15
Building Technologies Room Temperature Controllers N3058en HVAC Products 10.01.2006
Page 8
Error handling
Temperature out of range
External sensor failure
Infrared remote control
When the room temperature is out of the measuring range, which means above 49 °C or below 0 °°C, the display shows the limiting temperature in flashing figures, e.g. “0 °C” or “49 °C”. If the current setpoint is not OFF (see parameters 1-4) and the controller is in heating mode, and the temperature is below 0 °C, output Y11 will be energized. In all other cases, output Y11 will be deenergized. When the temperature returns to the measuring range, the controller will resume Normal operation.
In case of an external sensor failure (short-circuit or open-circuit), the controller will immediately switch back to the internal sensor to ensure control.
Should both the external and internal sensor fail, the display will flash “Err” to call the user‘s attention.
The RDF210/IR and RDF210.2/IR have an infrared receiver built in. Together with the IRA210 infrared remote control, the following operations can be performed from a re­mote location:
Selection of operating mode: Standby, Normal operation or Auto Timer
Adjustment of setpoint in Normal operation
Selection of fan mode: Automatic or manual fan speed
Using parameter P25, infrared remote control can be disabled.
Control parameters
Parameter settings
With the RDF210 and RDF210.2, a number of control parameters can be readjusted to optimize the control performance. These parameters can also be set during operation without opening the unit. In the event of a power failure, all control parameter settings will be maintained.
The parameters can be changed as follows:
1. Set the controller to Standby
2. Press buttons
and simultaneously for 3 seconds. Release them and,
within 2 seconds, press button
.
again for 3 seconds. Then, the display will
show “P01“.
3. Select the required parameter by repeatedly pressing buttons
P25
+-
+
4. By pressing buttons
+-+
P01 P02 P22 P98
--
3057z03
-
and simultaneously, the current value of the selected
+
P99
and :
-
parameter appears, which can be changed by repeatedly pressing buttons or
.
5. By pressing buttons
and simultaneously again or 5 seconds after the last
press of a button, the last parameter will be displayed again.
6. If you wish to display and change additional parameters, repeat steps 3 through 5.
7. 10 seconds after the last display or setting, all changes will be stored and the controller returns to Standby.
Note:
8/15
Building Technologies Room Temperature Controllers N3058en HVAC Products 10.01.2006
Parameters not used by the RDF210.2 are not available and cannot be displayed.
Page 9
Parameter reset
The factory setting of the control parameters can be reloaded as follows:
1. Set the controller to Standby
2. Press buttons
and simultaneously for 3 seconds. Release them and,
within 2 seconds, press operating mode selector button
.
2 times.
Then, the display will show “888“ during the reloading process.
Control parameters of the RDF210 and RDF210.2
Para-
Meaning Setting range Factory
meter
P01 Setpoint of heating in Energy Saving mode (Wheat
P02 Setpoint of cooling in Energy Saving mode (Wcool P03
P04
Setpoint of heating in Standby Setpoint of cooling in Standby
(Wheat
(Wcool P05 Minimum setpoint limitation in Normal operation (Wmin P06 Maximum setpoint limitation in Normal operation (Wmax
) OFF, 5 °C…Wcool
Eco
) OFF, Wheat
Eco
OFF, 5 °C…Wcool
)
Stb
OFF, Wheat
)
Stb
) 5 °C…Wmax
Comf
) Wmin
Comf
…40 °C 35 °C
Comf
Eco
…40 °C
Eco
Stb
…40 °C OFF
Stb
Comf
P07 Sensor calibration -3…+3 K 0 K P08 Switching differential heating mode SDH 0.5…+4K 2 K P09 Switching differential cooling mode SDC 0.5…+4K 1 K P10 Switching differential fan speed 2 in heating mode SDH2 0.5…+4K 1 K P11 Switching differential fan speed 2 in cooling mode SDC2 0.5…+4K 1 K P12 Switching differential fan speed 3 in heating mode SDH3 0.5…+4K 1 K P13 Switching differential fan speed 3 in cooling mode SDC3 0.5…+4K 1 K P14 Dwelling time of auto fan speeds 1…5 minutes 2 min P15 Minimum output on time (Y11) 1…10 minutes 1 min P16 Minimum output off time (Y11) 1…10 minutes 1 min P17 Selection of °C or °F °C or °F °C
OFF: Setpoint
P18
Display of temperature or setpoint
ON: Room (or return air) temperature
P20 Fan control in Energy Saving mode
P21 Fan control in Normal operation
OFF in dead zone ON in dead zone OFF in dead zone ON in dead zone 0: Heating only
P22 Heating / cooling mode
1: Cooling only 2: Automatic H/C
changeover P23 Heating / cooling changeover switching point cooling 10…25 °C 16 °C P24 Heating / cooling changeover switching point heating 27…40 °C 28 °C
P25 Infrared receiver (only with RDF.../IR)
P98 Active temperature sensor
0: Disabled
1: Enabled
0: Internal sensor
1: External sensor
100 = input open Æ
mode
0…49 °C = cur. temp. value
P99
Value of current heating / cooling changeover temperature reading and indication of current mode
00 = input bridged Æ
mode OFF= not commissioned as automatic H/C changeover
1) Not available with RDF210.2
setting
16 °C
28 °C OFF
5 °C
ON
OFF
OFF
1: Cooling
1)
only
1)
1)
1
Diagnostic value
Diagnostic
1)
value
9/15
Building Technologies Room Temperature Controllers N3058en HVAC Products 10.01.2006
Page 10
Type summary
Type reference Features
Equipment combinations
RDF210
With input for automatic heating / cooling changeover or return air temperature sensor
RDF210.2
With manual heating / cooling changeover Without input for sensor (only available in AP)
RDF210/IR RDF210.2/IR
Same as RDF210 plus infrared remote control Same as RDF210.2 plus infrared remote control
(only available in AP)
Type of unit Type reference Data Sheet Infrared remote control Cable temperature sensor Room sensor Changeover mounting kit Electromotoric on / off valve and actuator Electromotoric on / off actuator Thermal actuator (for radiator valve) Thermal actuator (for small valves 2.5 mm) Zone valve actuators (only available in AP, UAE, SA and IN)
IRA210
QAH11.1
QAA32
ARG86.3
MVI…/MXI…
SFA21... STA21... STP21...
SUA…
­1840 1747 1840 4867 4863 4893 4878
4830
Accessories
Ordering
Description Type reference
Adapter plate 120 x 120 mm for 4“ x 4“ conduit boxes ARG70 Adapter plate 96 x 120 mm for 2“ x 4“ conduit boxes ARG70.1
Adapter plate for surface wiring 112 x 130 mm ARG70.2
When ordering, please give name and type reference: e.g. room temperature controller RDF210
The IRA210 infrared remote control is to be ordered as separate item The QAH11.1 can be used as a return air temperature or heating / cooling changeover
sensor. In case it is used as a changeover sensor, the ARG86.3 changeover sensor mounting kit is to be ordered as a separate item.
Valve actuators are to be ordered as separate items.
10/15
Building Technologies Room Temperature Controllers N3058en HVAC Products 10.01.2006
Page 11
Mechanical design
The controller consists of 2 parts:
Plastic housing which accommodates the electronics, the operating elements and the built-in room temperature sensor
Mounting base
The housing engages in the mounting base and snaps on. The base carries the screw terminals.
Setting and operating elements
Legend
3 1
AM
2
4
PM
AUTO
$
5
6
8 7
9 10 11
15
12
14
1 Display of the room temperature, setpoints and control parameters
2
Symbol used when displaying the current room temperature
3 Weekday 1..7 (1 = Monday / 7 = Sunday)
4 Current time of day
5 Standby / fan mode status
Standby mode
AUTO Auto fan active
fan speed low, medium, high
13
6
in cooling mode
in heating mode
AUTO
Auto Timer mode
7
Normal operation
Energy Saving mode
8 Buttons for adjusting the setpoints, control parameters and time of day
9 Button for changing fan operation and Standby (
)
AUTO
10 Button operating mode (
11 Button for setting time of day and weekday (
12 Manual heating / cooling changeover (
13 Auto timer program (
14 Confirmation (
)
): Normal operation / Auto Timer mode
)
) (only with RDF210.2)
AUTO
)
15 Infrared receiver (only with RDF210…/IR)
11/15
Building Technologies Room Temperature Controllers N3058en HVAC Products 10.01.2006
Page 12
Mounting and installation
Wiring
The room controller can be mounted on a wall or inside the fan coil unit. The mounting location on a wall should not be in niches or bookshelves, not behind curtains, above or near heat sources and not exposed to direct solar radiation. Mounting height is about
1.5 m above the floor.
The controller can be fitted on a recessed conduit box.
When using a heating / cooling changeover sensor, then, before fitting the sensor, thermal conductive paste must be applied to the location on the pipe where the sensor is placed.
Also refer to the Mounting Instructions B3058 enclosed with the controller.
Commissioning
Heating / cooling mode
Compressor-based application
Calibrating the sensor
Setpoint and range limitation
Diagnostic values
Wiring, fuse and earthing must be installed in compliance with local regulations. It must be made certain that safety extra low-voltage lines (SELV circuit) are clearly separated from AC 230 V mains voltage cable
The cables to the controller, external sensor, fan and valves carry AC 230 V mains voltage and must be appropriate sized
Only sensors and valves rated for AC 230 V may be used
The AC 230 V mains supply line must have an external fuse or circuit breaker with a
rated current of no more than 10 A
Maximum 10 changeover contact inputs B1-M can be connected in parallel if an external switch is used in place of a changeover sensor. The switch must be suited for AC 230 V. The cable length must not exceed 80 m overall
After applying power, the controller makes a reset during which all LCD segments flash, indicating that the reset has been correctly made. This takes about 3 seconds. Then, the controller is ready for commissioning by qualified HVAC staff. The control parame­ters of the controller can be set to ensure optimum performance of the whole system (also refer to “Setting the control parameters”).
Only with RDF210: Depending on the application, the heating / cooling mode must be set via parameter P22. Factory setting is “Cooling only”. When using the ”Auto­matic heating / cooling changeover” function, P22 must be set to “Automatic H/C changeover”. Note: When P22 is set to “Automatic H/C changeover”, the integrated sensor is used for acquiring the room temperature
If the controller is used in conjunction with a compressor, the minimum output on time (parameter P15) and off time (parameter P16) of Y11 must be adjusted in order not to harm the life time of the compressor
If the room temperature displayed by the controller dos not accord with the room temperature effectively measured, the temperature sensor can be recalibrated. In that case, parameter P07 must be changed
For comfort and energy saving reasons, it is suggested to review the setpoints and setpoint ranges (parameters P01…P06) and, if necessary, to change them accord­ingly
Only with RDF210: Parameters P98 and P99 are diagnostic values and help check the system. With P98, the status of the active temperature sensor is shown and, with P99, the status of the heating / cooling changeover sensor
12/15
Building Technologies Room Temperature Controllers N3058en HVAC Products 10.01.2006
Page 13
Technical data
Power supply
Outputs
Inputs
Operational data
Environmental conditions
Norms and standards
Operating voltage AC 230 V +10/-15 % Frequency 50/60 Hz Power consumption max. 8 VA Fan control Q1, Q2, Q3- N
Rating
Control output Y11-N (N.O.) / Y12-N (N.C.)
Rating
Changeover or external room temperature sensor B1-M
Temperature sensor Voltage against earth Cable length
Infrared receiver (only with RDF210…/IR)
Transmission distance Orientation angle
Switching differential, adjustable from 0.5...4K
Heating mode (factory setting) Cooling mode (factory setting)
Setpoint setting range
Normal operation
Energy Saving mode (only with RDF110)
Standby
Factory setting of setpoints
Normal operation
Energy Saving in heating / cooling mode
Standby (heating and cooling mode)
Built-in room temperature sensor
Measuring range Accuracy at 25 °C Temperature calibration range
Resolution of settings and display
Setpoints Current temperature value displayed
Operation
Climatic conditions Temperature Humidity
Transport
Climatic conditions Temperature Humidity Mechanical conditions
Storage
Climatic conditions Temperature Humidity
conformity to EMC directive Low voltage directive
N474
C-Tick conformity to
EMC emission standard
AC 230 V max. 4(2)A AC 230 V max. 4(2)A
QAH11.1, safety class II AC 230 V max. 80 m (min. 1.5 mm
2
)
7.5 m ± 30 °
2 K 1 K
5...40 °C off, 5...40 °C off, 5...40 °C
20 °C 16 °C / 28 °C OFF
0…49 °C < ± 0.5 K ± 3.0 K
0.5 °C
0.5 °C to IEC 721-3-3 class 3K5
0...+ 50 °C <95 % r.h. to IEC 721-3-2 class 2K3
25...+60 °C <95 % r.h. class 2M2 to IEC 721-3-1 class 1K3
25...+60 °C <95 % r.h.
89/336/EEC 73/23/EEC and 93/68/EEC
AS/NSZ 4251.1:1994
13/15
Building Technologies Room Temperature Controllers N3058en HVAC Products 10.01.2006
Page 14
General
Connection terminals
Product standards
Automatic electrical controls for household and similar use Special requirements for temperature-
EN 60 730 – 1
EN 60 730 – 2 - 9
dependent controls
Electromagnetic compatibility
Emissions Immunity
IEC/EN 61 000-6-3 IEC/EN 61 000-6-1
Devices of safety class II to EN 60 730 Pollution class normal Degree of protection of housing IP 30 to EN 60 529 Connection terminals solid wires or prepared
stranded wires 2 x 0.4-1.5 mm
2
mm
2
or 1 x 2.5
Weight 0.28 kg Color of housing front white, NCS S 0502-G (RAL
9003)
Connection diagrams
Application:
2-pipe fan coil units
Application:
Compressor in DX type equipment
AC 230 V
LB1*M
N Q1Q2Q3 Y11N
Y12
L, N Operating voltage AC 230 V B1* Changeover (QAH11.1+ ARG86.3) or
external room temperature sensor (QAH11.1 / QAA32)
M Measuring neutral for sensor
L
N
L
N
B1/B2
*
B1
I II III
4(2)A max.
B1/B2
*
I II III
4(2)A max.
QAH11.1 + ARG86.3
/ QAA32
M
QAH11.1 + (ARG86.3) / QAA32
Y12
M1
Y12
M1
10 A
L
N Q1Q2Q3 Y11 N
AC 230 V
10 A
LB1M
N Q1Q2Q3 Y11 N
AC 230 V
4(2)A max.
4(2)A max.
RDF210
*
N1
RDF210
*
N1
C1
Y1
Q1 Control output “Fan speed 1 AC 230 V Q2 Control output “Fan speed 2 AC 230 V
3058G01
Q3 Control output “Fan speed 3 AC 230 V Y11 Control output “Valve” AC 230 V (N.O.,
for normally closed valves) or output for compressor
Y12 Control output “Valve” AC 230 V (N.C.,
for normally open valves)
* Only with RDF210 or RDF210/IR
B1* Return air temperature sensor (QAH11.1) or external room temperature sensor (QAA32) B2* Changeover sensor (temperature sensor
QAH11.1 + changeover mounting kit
ARG86.3) M1 3-speed fan N1 Room temperature controller RDF210.. Y1 Zone valve
1 0 A 8 5
* Only with RDF210 or RDF210/IR
0 3
B1* Return air temperature sensor (QAH11.1) or external room temperature sensor (QAA32) B2* Changeover sensor (temperature sensor
QAH11.1 + changeover mounting kit
ARG86.3) M1 3-speed fan N1 Room temperature controller RDF210.. C1 Compressor
Only with RDF210 or RDF210/IR
2 0 A 8 5
0 3
Note: For compressor applications, RDF210 or RDF210/IR is recommended
14/15
Building Technologies Room Temperature Controllers N3058en HVAC Products 10.01.2006
Page 15
Dimensions
Controller
Mounting base
128
120.3
4 0 Z 8 5
30
102
0 3
28
28
4
120.3
21.85
34.15
2.5
30
94.85
2828
28.7
4
35
24.35
30
31.65
11.8
10.15
3058Z05
©2006 Siemens Switzerland Ltd. Subject to alteration
Building Technologies Room Temperature Controllers N3058en HVAC Products 10.01.2006
15/15
Loading...