Siemens RDD100.1RF, RDE-MZ6 Operating Instructions Manual

1/2 Operating Instructions CB1B1431en_01 / 2013-07-05 Siemens Building Technologies
s
Operating Instructions
RDD100.1RF
RDD100.1RF
1 Display
Indicates that batteries need to be replaced
Comfort mode
Economy mode
Frost protection (heating) active
Room temperature, setpoint, etc.
F
Room temperature in degrees Fahrenheit
C
Room temperature in degrees Celsius
Button lock activated
Display of zone (default = 1)
Heating On
Current room temperature
2 Change operating mode
3 Decrease value
4 Increase value
5 Battery holder
RDE-MZ26
To be purchased separately
Do you want to lock the buttons?
Press and hold for at least 7 seconds to activate a button lock. Repeat to unlock.
The unit operates normally when the buttons are locked, but no changes can be made.
Do you want to change the operating mode?
!
The room thermostat provides Comfort mode and Economy mode . Changeover between the operating modes can be
made manually by pressing
.
Comfort mode is a permanent (24 h) selection of Comfort. Select this mode when you want to maintain permanently the Comfort temperature. It is used during occupancy periods, for example.
Economy mode is a permanent (24 h) selection of Economy. Select this mode when you want to maintain permanently the Economy temperature. It is used during non-occupancy periods (e.g. at night).
Note:
Frost protection is a function always active in the background. As soon as the room temperature falls below 5 ºC, the unit
automatically activates heating
.
Energy saving tips without loss of comfort
Use Economy mode during longer periods of non-occupancy
2/2 Operating Instructions CB1B1431en_01 / 2013-07-05 Siemens Building Technologies
Are your rooms too warm/too cold?
+ –
Press
+ or to increase or decrease the room
temperature setpoint in increments of 0.5 °C/1 °F. Proceed as follows:
Press
+ or to change the setpoint temporarily.
Press
to save the setting or wait for the
program to exit automatically
To permanently change the temperature setpoints, use parameters P05 and P07. To lock the setpoints, use parameters P06 and P08
Does symbol appear on the display?
Symbol is displayed when the batteries are low. Replace them with 2 new alkaline batteries type AAA. Proceed as follows:
Get 2 new alkaline batteries type AAA
Remove the battery holder and then the batteries. Insert the
new batteries and, within 1.5 minutes, replace the battery holder
Ensure the exhausted batteries are disposed of correctly, in compliance with environmental requirements
Do you want to pair transmitter and receiver?
Please refer to the instructions that come with the RDE-MZ6.
Do you want to change parameters?
+ –
If you want to change control parameters, proceed as follows:
Press
+ and simultaneously for 5 seconds
Release them and parameter P02 is displayed
Press
+ or – to scroll to the parameter that needs
to be changed
Press
to select the parameter
Press
+ or – to change the value
Press
to confirm and save the changed value
Select and change other parameters
The program automatically returns to the normal
screen after a timeout
Parameter list
Parameter no.
Description Setting range (default)
P02 Selection of °C or °F 1 = °C (default)
2 = °F
P03 Standard temperature
display
1 = room temperature (default)
2 = setpoint
P04 Temperature sensor
calibration
-3…3 °C Step 0.5 °C (-6…6 °F, step 1 °F) Default: 0 °C
P05 Comfort setpoint 5…35 °C, step 0.5 °C
(41…95 °F, step 1 °F) Default: 20 °C, 68 °F
P06 Comfort setpoint lock 0 = OFF (default)
1 = ON locked according to setting in P05
P07 Economy setpoint 5…35 °C, step 0.5 °C
(41…95 °F, step 1 °F) Default: 16 °C, 61 °F
P08 Economy setpoint lock 0 = OFF (default)
1 = ON locked according to setting in P07
P09 Buzzer 0 = OFF
1 = ON (default)
P10 Show frost protection
icon
0 = OFF (default) 1 = ON and always on at 5 ºC
P19 Sequential number of
room unit
0 = no display of zone (RF off)
1 = zone number 1 (for standard RF) (default)
6 = zone number 6
P20 RF learn 0 = OFF (default)
1 = ON
P21 Scanning rate for the
capacitive buttons Note: Shorter
scanning rate means shorter battery life
0.2 = 0.25 s
0.5 = 0.5 s
1.0 = 1.0 s (default)
1.5 = 1.5 s
P22 Reload factory
settings
0 = OFF (default) 1 = reload
P23 Software version
information
No adjustment possible