Siemens RDE10, RDE10.1 Series Manual

Page 1
035
3
with 7-Day Time Switch and LCD
for heating systems
2-position control with ON/OFF output for heating Operating modes: normal operation and energy saving mode 7-day time switch and manual operation Mains-powered AC 230 V (RDE10) or battery-powered DC 3 V (RDE10.1)
RDE10...
Use
CE1N3035en
25.09.2003
The RDE10... is used for the control of the room temperature in heating systems.
Typical applications:
Apartments
Commercial spaces
Schools
For the control of the following pieces of equipment:
Thermic valves or zone valves
Gas or oil burners
Fans
Pumps
Siemens Building Technologies
HVAC Products
Page 2
Functions
Function diagram
The controller acquires the room temperature with its integrated sensor and maintains the setpoint by delivering control commands. The switching differential is 1 K.
ON
OFF
Q14
3030D01
W
T[°C]
T Room temperature
SD Switching differential
W Room temperature setpoint
Q14 Output signal for heating
Operating modes
Normal operation
Energy saving mode or OFF
7-day time switch
SD
The RDE10... provides normal operation and, optionally, energy saving mode or OFF. The difference between normal operation and energy saving mode is only the room temperature setpoint. The changeover between the operating modes can be made either automatically according to the 7-day time switch or manually with the operating mode selector.
When normal operation is activated, symbol “
can be readjusted by pressing buttons
,
When energy saving mode is activated, symbol “
point can be readjusted by pressing buttons
“ appears on the display. The setpoint
+
and -.
“ appears on the display. The set-
and
-
.
+
,
In energy saving mode, the unit can also be switched to “Off”. This is accomplished by
-
selecting a setpoint of 5 °C and then keeping button that case, symbol '
' does not appear.
depressed for 4 seconds. In
The changeover between the operating modes can take place either automatically (
) or manually ( , ), depending on the position of the operating mode selector.
When the operating mode selector is in position “
”, changeover will take place automatically according to the selected switching pattern. For every weekday, a specific switching pattern can be selected. Factory setting:
Day(s) Normal operation Energy saving mode Mo (1) – Fr (5) 6:00 – 8:00 h and
17:00 – 22:00 h
22:00 – 6:00 h and 08:00 – 17:00 h
Sa (6) – Su (7) 7:00 – 22:00 h 22:00 – 7:00 h
The current setpoint can be temporarily readjusted by pressing
buttons
+
and
-
. The setpoint will then be reset to its initial value the next time auto-
matic or manual changeover takes place.
When the operating mode selector is set to”
“ or “ “, the RDE10... will maintain
normal operation or energy saving mode respectively.
2/8
Siemens Building Technologies Room temperature controllers CE1N3035en HVAC Products 25.09.2003
Page 3
Display
The digital display shows the actual room temperature, the time of day, the weekday, the current switching pattern and the symbol of the operating mode currently active. The switching pattern shows normal operation as a double bar and energy saving mode as a single bar with a flashing time pointer. When the heating output is activated, the triangle symbol appears.
Backup
Type summary
Ordering
0 6 12 18 24
Automatic changeover according Normal operation Energy saving mode to the switching pattern
0 6 12 18 24
0 6 12 18 24
In the event of a power failure, the setpoints and the information required for operating mode changeover are retained for 3 minutes. This is enough to cope with power fail­ures of short duration (with RDE10) or when changing the batteries (with RDE10.1).
Type reference Features
RDE10
RDE10.1
Mains-powered AC 230 V
Battery-powered DC 3 V
When ordering, please give name and type references, e.g. room temperature con- troller RDE10. Valve actuators are to be ordered as separate items.
Equipment combinations
Accessories
Type of unit Type reference Data sheet Motoric on/off actuator Thermal actuator (for radiator valve) Thermal actuator (for small valve 2,5 mm)
SFA21... STA21... STP21...
4863 4893 4878
. . .
Description Type reference
Adapter plate 120 x 120 mm for 4“ x 4“ conduit boxes ARG70 Adapter plate 96 x 120 mm for 2“ x 4“ conduit boxes ARG70.1 Adapter plate for surface wiring 112x130 mm ARG70.2
. . . . . .
3/8
Siemens Building Technologies Room temperature controllers CE1N3035en HVAC Products 25.09.2003
Page 4
Mechanical design
The unit consists of two parts:
A plastic housing with digital display, which accommodates the electronics, the
operating elements and the built-in room temperatures sensor
A mounting base
The housing engages in the mounting base and snaps on. The base carries the screw terminals.
3035Z01
Legend
1 Display of the room temperature in °C or setpoints 2 Current time of day using the format 00:00 ... 23:59 3 Current weekday from 1 (Monday) to 7 (Sunday) 4 Current switching pattern with flashing time pointer
symbol when actual room temperature is displayed
5 6
Normal operation
Energy saving mode 7 8 9
symbol in automatic mode or when selecting the switching pattern
heating on
symbol indicating that batteries need to be replaced
(only with battery-powered versions) 10 Buttons for adjusting the setpoints, the time of day and the switching times 11 Operating mode selector 12 Setting the weekday 13 Setting the time of day 14 Selecting and leaving the setting mode for the switching pattern 15 Setpoint adjustment for energy saving mode 16 Setpoint adjustment for normal operation 17 Button for confirming the switching pattern settings 18 Battery compartment (only with battery-powered versions)
4/8
Siemens Building Technologies Room temperature controllers CE1N3035en HVAC Products 25.09.2003
Page 5
Notes
Mounting, installa­tions and commis­sioning
Maintenance
Sensor calibration
Change of batteries (only with battery­powered versions)
Reset
The room temperature controller should be mounted in a location where the air tem­perature can be measured as accurately as possible without getting adversely affected by direct solar radiation or other heat or refrigeration sources.
Mounting height is about 1.5 m above the floor.
The unit can be fitted to a recessed conduit box.
Only authorized staff may open the controller.
Caution: AC 230 V!
The cables used must satisfy the insulation requirements with regard to mains
potential
When mounting the unit, fix the baseplate first. Then, make the electrical connections and fit and secure the cover (also refer to separate Mounting Instructions). The controller must be mounted on a flat wall and in compliance with local regulations. If there are thermostatic radiator valves in the reference room, they must be set to their fully open position.
The controller is maintenance-free.
If the temperature on the display does not agree with the room temperature effectively measured, the temperature sensor can be recalibrated. For that purpose, both buttons
+
and must be pressed simultaneously for 3 seconds. Then, the temperature
+
displayed can be changed by a maximum of +/- 3 K by pressing the
and - buttons.
Five seconds after the last push of a button, the controller will automatically return to the normal operational statuses.
If the battery symbol appears, the battery power is almost exhausted and the batteries should be replaced.
+
To reset, first press and hold the button
, then press the two buttons
-
simultane-
ously for 3 seconds. All individual settings will be reset to their standard values.
5/8
Siemens Building Technologies Room temperature controllers CE1N3035en HVAC Products 25.09.2003
Page 6
Technical data
Power supply
Control outputs
Functional data
Environmental conditions
Norms and standards
Operating voltage
RDE10 at L and N AC 230 V +10/-15 %
RDE10.1 DC 3 V (2 x 1.5 V AAA Alkaline - batteries)
Frequency (RDE10) 50 or 60 Hz Power consumption (RDE10) 4VA Battery life (RDE10.1) > 1 years (AAA Alkaline - batteries) Control output Q12 (N.C. contact)
Rating RDE10 (AC 230 V) max. 5 A Rating RDE10.1 (AC 24…250 V) max. 5(2) A
Control output Q14 (N.O. contact)
Rating RDE10 (AC 230 V) max. 5 A
Rating RDE10.1 (AC 24…250 V) max. 5(2) A Switching differential SD 1 K Setpoint setting range 5…35 °C (normal operation)
0 (OFF) and 5…35 °C (energy saving mode)
Factory setting normal operation 20 °C
Factory setting energy saving mode 8 °C Resolution of settings and displays
Setpoints 0.5 °C
Switching times 60 min
Actual value displays 0.5 °C
Time of day displays 1 min Operation to IEC 721-3-3
Climatic conditions class 3K5 Temperature 0…+50 °C Humidity <95 % r. h.
Transport to IEC 721-3-2
Climatic conditions class 2K3 Temperature -25…+60 °C Humidity <95 % r. h. Mechanical conditions class 2M2
Storage to IEC 721-3-1
Climatic conditions class 1K3 Temperature -25…+60 °C Humidity <95 % r. h.
conformity to EMC directive 89/336/EEC Low voltage directive 73/23/EEC and 93/68/EEC
N474
C-Tick conformity to
EMC emission standard
AS/NSZ 4251.1:1994
Product standards
Automatic electrical controls for EN 60 730 – 1 and household and similar use EN 60 730 – 2 - 9
Electromagnetic compatibility
Emissions EN 50 081-1 Immunity EN 50 082-1
Safety class II to EN 60730 Pollution class normal Degree of protection of housing IP30 to EN 60529
6/8
Siemens Building Technologies Room temperature controllers CE1N3035en HVAC Products 25.09.2003
Page 7
General
Connection diagram
Connection terminals for Use solid wires or prepared stranded wires.
2
2 x 1.5 mm
or 1 x 2.5 mm2 (min. 0.5 mm2) Weight 0.21 kg Colour of housing front white, NCS S 0502-G (RAL 9003)
L
L
N
Q12
Ln
Q11
Q14
Y1
N
RDE10
N1 Room temperature controller
Y1 Regulating unit
L, Ln Live, AC 230 V
N Neutral, AC 230 V
Lx Live, AC 24 ... 250 V
L
N1
N
Lx
Q11
3V
Q12
3031A01
Nx
Q14
RDE10.1
Q11, Q12 N.C. contact (for N.O. valves)
Q11, Q14 N.O. contact (for N.C. valves)
Nx Neutral, AC 24 ... 250 V
3031A02
N1
Y1
Application examples
T
M1
N1
2222S01
T
F1
T
F2
Y2
Room temperature controller with direct control of a gas-fired wall-hung boiler
T
N1
F2
F1
T T
Y2
M1
2222S02
Room temperature controller with direct control of a gas-fired floor-standing boiler
7/8
Siemens Building Technologies Room temperature controllers CE1N3035en HVAC Products 25.09.2003
Page 8
T
N1
Y1
M1
2222S03
Dimensions
Controller
Room temperature controller with direct control of a heating circuit pump (precontrol by manual mixing valve)
F1 Thermal reset limit thermostat
F2 Safety limit thermostat
M1 Circulating pump
119
N1 RDE10... room temperatures controller
Y1 3-port valve with manual adjustment
Y2 Magnetic valve
3035M01
Baseplate
96
23,8
4
28 28
3530
28
28
4
112,3
11,8
26
89,45
30
3035M02
8/8
Siemens Building Technologies Room temperature controllers CE1N3035en HVAC Products 25.09.2003
2003 Siemens Building Technologies AG Subject to alteration
Loading...