1/4 Op erati n g I n struc t ions CB1B1425en_01 / 2014-11-2 6 Siemens Building Technolog ies
s
Operating Instructions
The RDE100. 1R FS consists of a wireless ro om thermo stat RDE100.1RF an d an RCR100RF receiver.
The units allo w you to set the ideal room temperatur e at the tim e y ou w ant.
There a re sever al switching patterns available that can b e set to meet y our individual needs .
RDE100.1RF
1 Display
Indicates that batteri es
need to be replaced
Time of day
Frost protection (heating)
active
Morning: 12-hour format
Afternoon: 12- hour f ormat
Auto Timer mode Confirm ation
View and set Aut o Timer
Room temperature in
degrees Fahren h eit
Comfort mode
Room temperature in
degrees Cels ius
Economy mode Button lock activ ated
Escape
Room t emperature,
setpoint, etc.
External input enabl ed
Display of zon e
(default = 1)
Permanent set p oint sett ing Heating On
W eek d a y an d time of d a y
setting
Weekday 1 = Monday
Weekday 7 = Sunday
Holiday mode sett ing Timer b ar
Current room temperature
2 Change operating mode
3 Set
4 Ok
5 Decrease value
6 Increase value
7 Battery holder
RCR100RF
8 Indication of data transmission and operating state (LED)
9 Initializati on of w ir ele ss c ommunication w ith t ransmitter
(LEARN button)
Do you want to set the time of day and the weekday?
Set
Ok
+
–
Mode
Proceed as follow s:
· Press Set and select
· Press Ok and the time of day flashes for setting
· Press + or – to adjust the time of day
· Press Ok to confirm
· The weekday flashes; press + or – to select the desired day
· Press Ok to save the setting
· Press Mode t o exit or wait for the program to exit automatically

2/4 Op erati n g I n struc t ions CB1B1425en_01 / 2014-11-2 6 Siemens Building Technolog ies
Are your rooms too warm/too cold?
+
–
Ok
Set
Mode
Press + or – t o increase or dec rease th e
room t emperatu r e s et poin t i n in c rem ent s of
0.5 °C/1 °F. Proc eed as f oll ows:
· Press + or – to change the setpoint
temporarily.
This readjust m ent is reset as soon as
the operating mode changes
· Press Ok, Set or Mode to save the
setting or w ait for the progr am to exit
automatically
· T o loc k the setpo ints, use param eter s
P06 and P08
Do you want to change the operating
mode?
mode
!
Th e thermostat p rovides Comfort, Ec onomy
and autom atic mode. Changeover b etween
the operatin g m odes c an b e made m anu all y
by pressing Mode.
Comf ort mode i s the permanent (24 h)
selection of Comfort. Select this operating
m ode to m ai n tain C omfor t tem perat ure
permanently without any time switch. It is
used during occup anc y peri ods, for example.
Economy mode is the permanent (24 h)
selecti on of Economy. Select t his oper ating
m ode to maintain the Economy temperatu re
perman ent ly w ith out any time switch.
It is used during non-occ upancy periods
(e.g. at night).
In Auto Timer m ode, the operating
m odes (Comfort , Economy ) are changed
autom atically accordi n g to t he time switch
setti ng s.
Note:
Frost pr otection is a function alw ays activ e
in the backgr oun d. As soon the room
temperat ure falls below 5 ºC, the unit
autom atic al ly activates heat ing
.
Do you want to set permanent temperature
setpoints?
Set
Ok
+
–
Mode
!
· Press Set and select
· Press Ok to confirm
· Press Mode to select the oper ating
mode (C omfor t or Economy)
· Press + or – to adjust the set p oint
permanently
· Press Ok to confirm
· Press Mode to exit or wait for a timeout
to exit automatically
Note:
This permanent set point is used during Aut o Timer
mode.
Energy saving tips without loss of
comfort
· Select Auto Tim er mode for the h eati ng perio d , and
set the tim e swit ch according to you r normal h abits at
home
· Select Economy or Holiday mode f or longer periods
of non-occu p anc y an d t he sum mer period
Do you want to set your Holiday mode?
Set
Ok
+
–
Mode
!
Use the H o liday mode to s et th e thermostat
to a constant room temp erature w h ile
absent.
· Press Set and s elect
· Press Ok to confirm
· Press + or – to adjust the temperature
setpoint
· Press Ok to confirm
· Press + or – to set the number of days
for holidays (0 = Holiday mode Off)
· Press Ok to save the setting
· W hen Holiday mode is activated, the
remaining days are dis play ed
Note:
If you press Mode while Holida y mode is active,
the functi on is turned off and symbol
disappears.
If the Comfort and Economy setpoints are both
locked, the lowest lock ed setpoint is the Holiday
mode set point. You can adjust the setpoint from
5 ºC up to the lowest locked setpoint.
Do you want to enter your own time switch?
Option 1: Time switch with individual day settings
(P11=0)
Set
Ok
+
–
Mode
You can se lect Comf ort or Eco nomy mode in
steps of 15 minut es thr oughout t he day. The
0:00 to 24:00 h our time bar allows you to set
the operating m ode for the selec ted day( s) .
Ex ample:
Visible bars: Control to Comfort temperature
Invisible bar s: Control to Econom y
temperature
When Auto Timer m ode is en abled,
changeover b etween the operating m odes is
automatic after t he sett ings ar e saved.
Proceed as f ollows:
1) Press S et and sel ect
.
2) Press Ok to confirm.
3) Time switch f or Mon (1) is d is play ed.
4) Press + or – to select the weekday,
from Mon (1) to Sun (7).
5) Press Ok to confirm the selection and
initiate time programming.
During programming:
6) Press Mode to sel ect t h e operating mode
(Comfort or Econom y) or
7) Press + or – t o set the time in steps of 15
min u tes f or the selected mode.
8) Press Ok to save the tim e switch.
9) Repeat steps 4-8 for all rem aini ng d ays ( if
required) or
10) Press Mode or wait for the program to exit
automatically.