CB1B1421en_01 / 2013-03-07 Subject to alteration Siemens Building Technologies
Are your rooms too warm/too cold?
+
–
Press + or – to increase or decrease the room
temperature setpoint in increments of 0.5 °C /
1 °F. Proceed as follows:
• Press + or – to adjust the setpoint
temporarily.
Press or to save the value or wait
for the program to exit automatically.
• To permanently modify the temperature
setpoints, use parameters P05 and P07.
To lock the setpoints, use parameters P06
and P08.
Does symbol appear on the display?
(Only with battery-powered version)
Symbol is displayed when the batteries are low.
Replace them with 2 new alkaline batteries type AAA.
Proceed as follows:
• Get 2 new alkaline batteries type AAA
• Remove the battery holder, then the batteries, insert
the new batteries and, within 1.5 minutes, replace the
battery holder
• Ensure the exhausted batteries are disposed of
correctly, in compliance with environmental
requirements
Do you want to lock the buttons?
Press and hold for at least 7 seconds to
activate a button lock. Repeat to unlock.
The unit operates normally when the buttons are
locked, but no changes are possible while the
buttons are locked.
Do you want to change parameters?
+
–
If you want to change control parameters,
proceed as follows:
• Press + and – simultaneously for 5 seconds
• Release them and parameter "P02" is
displayed on the bottom segment
• Press + or – to scroll to the parameter that
needs to be adjusted
• Press to select this parameter
• Press + or – to adjust the value
• Press to confirm the adjusted value
• Select and modify other parameters
• Press to exit the parameters without
saving or wait for the program to exit
automatically
Parameter list
Parameter
no.
Description Setting range (default)
P02 Selection of °C
or °F
1 = °C (default)
2 = °F
P03 Standard
temperature
display
1 = room temperature
(default)
2 = setpoint
P04 Temperature
sensor
calibration
-3…3 °C
Step 0.5 °C
(-6…6 °F, step 1 °F)
Default: 0 °C
P05 Comfort
setpoint
5…35 °C, step 0.5 °C
(41…95 °F, step 1 °F)
Default: 20 °C, 68 °F
P06 Comfort
setpoint lock
0 = OFF (default)
1 = ON –> locked according
to setting in P05
P07 Economy
setpoint
5…35 °C, step 0.5 °C
(41…95 °F, step 1 °F)
Default: 16 °C, 61 °F
P08 Economy
setpoint lock
0 = OFF (default)
1 = ON –> locked according
to setting in P07
P09 Buzzer 0 = OFF
1 = ON (default)
P10 Show frost
protection icon
0 = OFF (default)
1 = ON
P21 Button
scanning rate
for the
capacitive
buttons
Note: a shorter
scanning rate
means shorter
battery life.
0.2 = 0.25 s
0.5 = 0.5 s
1.0 = 1.0 s (default)
1.5 = 1.5 s
P22 Reload factory
settings
0 = OFF (default)
1 = reload
P23 Software
version
information
No adjustment possible