Siemens RCU50U, RCU50.2U Technical Instructions

s
2
.
RCU50U and RCU50.2U
Room Temperature Controllers for CAV Systems
Technical Instruction
Document No. 155-327P2
Rev. 1, March, 200
Description
Features
Application
RCU50U
The RCU microprocessor controlled CAV room controller is designed for air only, or air and water heating and/or cooling systems. Controllers have proportional response.
Modulating P-control
0 to 10 Vdc output for heating or cooling
Automatic heating/cooling changeover (RCU50U)
Manual heating/cooling changeover (RCU50.2U)
Operating modes: Normal, Energy Saving, Frost Protection and Standby (RCU50U)
Operating modes: Normal and OFF (RCU50.2U)
Active 0 to 10 Vdc input for set point shifting (RCU50U)
Operating mode changeover input for remote control (RCU50U)
Adjustable minimum limitation for cooling output (RCU50U)
Operating voltage 24 Vac
Controlling individual room temperature in HVAC installations that are heated or cooled Controlling these types of equipment:
Valve actuators
RCU50.2U
Air damper actuators
Product Numbers
Product Numbers Features
NOTE:
Table 1.
RCU50U Without operating mode selector
RCU50.2U With manual heating/cooling changeover switch
To order without logo, change suffix to "/U/NL".
Example:
Siemens Building Technologies, Inc.
RCU50/U/NL.
Technical Instructions RCU50U and RCU50.2U Room Temperature Controllers
r
l
0
Document Number 155-327P25 for CAV Systems Rev. 1, March, 2002
Ordering
The temperature sensor, changeover mounting kit, and valve and damper actuators must be ordered separately.
Table 2. Equipment Combinations.
Function
Heating-Cooling with Minimum Limitation Cooling
Product Numbe
Description Technical Instructions
QAH11.1 Temperature sensor 155-329P25
GDE16… 44 lb-in NSR Air damper actuator
155-187P25
GLB16… 88 lb-in NSR Air damper actuator SSB61U Valve actuator 155-192P25
SSC61U
Valve actuator 155-313P25 SSC61.5U SQS65U
Valve actuator 155-190P25 SQS65.5U
The controller measures the room temperature with its integrated sensor and maintains the set point by delivering 0 to10 Vdc control commands. The RCU50U and RCU50.2U provide P-control. With the RCU50U, the proportional band can be 2°F or 7°F (1°C or 4°C) in heating mode and 1°F or 3.5°F (0.5°C or 2°C) in cooling mode (selectable with DIP Switch No. 4). With the RCU50.2U, the proportional band is fixed, 7°F (4°C) in heating mode and 3.5°F (2°C) in cooling mode.
RCU50U – When in the heating mode, on increase in temperature, the output signa goes down (Reverse Acting - R.A.) from 10 to 0 volts. When in cooling mode, on increase in temperature, the output signal goes up (Direct Acting - D.A.) from 0 to 1 volts.
RCU50.2U – The output signal can be reversed 0 to 10 or 10 to 0 volts via the DIP switch.
Y10 [%] Y10 [%]
100
c/o
100
T Room temperature Y10 Output percentage W Room temperature set point XpH Proportional band heating
TH0577R1
0
XpKXpH
W
VR
T [˚F]
XpK Proportional band cooling VR 0 to 100% minimum limitation of cooling output c/o Changeover
Figure 1. RCU50U Function Diagram.
Heating-Cooling
Y10 [%]
100
0
TH0578R1
Figure 2. RCU50.2U Function Diagram. Minimum Limitation of
Cooling Signal
RCU50U
Using the potentiometer located on the circuit board, the cooling signal output can be limited to a minimum value of between 0 and 100%. This can be used to ensure a minimum supply air volume. When used in connection with a VAV controller, this setting must be taken into account. To set minimum limitation, use a screwdriver to adjust the potentiometer (see Figure 3). Values on the scale are percentage of full operation.
Page 2
Siemens Building Technologies, Inc.
c/o
Y10 [%]
100
T Room temperature Y10 Output percentage W Room temperature set point XpH Proportional band heating XpK Proportional band cooling c/o Changeover
XpH
0
XpK
W
T [˚F]
RCU50U and RCU50.2U Room Temperature Controllers Technical Instructions
c
For VAV Systems Document Number 155-327P25 Rev. 1, March, 2002
Minimum Limitation of Cooling Signal, Continued
Figure 3. Potentiometer Location (RCU50U).
Inversion of Output Signal
RCU50.2U
Set Point Shifting
RCU50U
With the RCU50.2U, the output signal can be inverted with the help of DIP Switch No. 1. If set to ON, 0V corresponds to 0% travel and 10V to 100% travel. In position OFF, 0V corresponds to 100% travel and 10V to 0% travel.
Signal Input 1 and 2 is used for outside temperature compensation. Using a 0 to 10 Vd signal, the set point can be shifted by ±22.5°F at 72°F set point. The neutral position is at 5 Vdc and means no set point shift.
Q(%)
heating cooling
100
W Original set point W1 Highest set point at 10V input W2 Lowest set point at 0V input set point shift
72ºF
0
Set Point Shift (K)
TH0621R1
Figure 4. Set Point Shifting (RCU50U). Automatic Changeover
RCU50U
The water temperature measured by the changeover sensor (QAH11.1) is used by the controller to switch from heating to cooling mode, or vice versa. When the water
W2 W1
22.5ºF
0
22.5ºF 1
W
22.5ºF 22.5ºF
5
(72ºF)
10
T [ºF]
Input Voltage (V)
(V) Input voltage
temperature is above 82°F (28°C), the controller switches to heating mode; below 61°F (16°C) it switches to cooling mode.
CM
HM
TH0579R1
Siemens Building Technologies, Inc.
M
61
(16)82(28)
Figure 5. Automatic Changeover Mode.
˚
(˚C)
CM Cooling mode HM Heating mode M Operating mode T
Water temperature
W
T
W
F
Page 3
Technical Instructions RCU50U and RCU50.2U Room Temperature Controllers
o
Document Number 155-327P25 for CAV Systems Rev. 1, March, 2002
Set Point Limit Stops
The room temperature set point can be limited in increments of 2°F (1°C) by using the minimum and maximum set point limit stops. This prevents arbitrary set point readjustments.
To set limit stops, remove the set point knob by pulling it straight off the shaft. Reposition gray tabs for high and low stops in the holes around the perimeter of knob as required. See Figure 6.
65
7
0
2
0
60
15
55
10
50
L
a
n
d
i
s
&
75
20
18
22
6
2
5
1
24
14
26
12
1
0
8
S
t
a
e
80
28
30
85ºF
30
f
a
Operating Modes
Normal Mode
Frost Protection Mode (RCU50U)
Energy Saving Mode
Operating Mode Changeover Switch
(RCU50U)
TH0625R1
Figure 6. Set Point Limit Stops.
When dry contact (D1 and Ground) is open, the set point knob setting takes over control and normal mode is initiated.
Frost protection mode can be initiated by activating the external operating mode changeover switch, if DIP Switch No. 1 is set to OFF.
If the room temperature falls below 46°F (8°C), the controller will automatically switch t frost protection mode. In that case, the heating valve opens and the room temperature is maintained at a set point of 46°F (8°C). The set point adjusted by the user will be ignored.
Energy saving mode can be initiated by activating the external operating mode changeover switch, if DIP Switch No. 1 is set to ON.
In energy saving mode, the heating set point is 61°F (16°C) and the cooling set point is 82°F (28°C), independent of the position of the set point knob.
A changeover switch can be connected to status input D1–GND. When the switch closes its contact (caused by an open window, for instance), the operating mode changes from normal operation or standby to energy saving mode (if DIP Switch No. 1 is set to ON), or from normal operation or energy saving mode to standby (if DIP Switch No. 1 is set to OFF).
The operating action of the switch (N.C. or N.O.) can be selected.
Mechanical Design
The unit consists of two parts:
Plastic housing which accommodates the electronics, the operating elements and the built-in room temperature sensor.
Controller base.
The housing snaps into the top and bottom of the mounting base.
Page 4
Siemens Building Technologies, Inc.
Loading...
+ 7 hidden pages