WIRING CONFIGURATIONS FOR THE OCC AND ACM ................................. 20
2
Page 3
INTRODUCTION
The Model RCM-1 Riser Control module from
Siemens Building Technologies, Inc.provides
control and supervision of global paging risers
in MXL voice networks. The RCM-1 is a doublewidth card and has 4 ports (See Figure 1) with
the following inputs and outputs:
PORTSTYLEFUNCTION
A
B
C
D
6Audio signal input
4/7Audio signal input/output
4Audio signal output
6Audio signal output
The RCM-1 supervises Port B for open and
short circuits, reports by exception to the MXL,
and isolates the fault.
must be used for transient protection (UL 1459).
Refer to LLM-1 Installation Instructions, P/N 315-
093530.
Modes of Operation
The RCM-1 can operate in the following modes:
Local ModeThe audio from the local MXL
(ACM) will be switched to local
speaker zones (OCCs). The
A D and B C
Global Mode 1The audio output from the local
C and D
B
Global Mode 2The audio from the local
A B, C and D
For additional information on the MXL/MXLV
System, refer to the MXL/MXLV Manual, P/N
315-092036.
global audio riser will be
switched to Port C, the Style 4
output riser.
MXL is disconnected. The
audio from the global riser is
connected to the local speaker
zones and to Port C, the Style
4 output riser.
system is connected to both
the local speaker outputs and
the global risers.
Figure 1
RCM-1 Ports
Only one RCM-1 may be connected to the
MXL. The module communicates with the MXL
using the RS-485 MNET. If the RCM-1 detects
that supervision is lost with the MXL, it will
automatically switch to Local Mode.
If any copper wire pair leaves the building
(Campus Configuration) the LLM-1 module
Diagnostic LEDs
The RCM-1 has two yellow diagnostic LEDs and
six green diagnostic LEDs along its top edge.
Their functions are described in Table 1 (Refer to
Figure 2 for their location).
ELECTRICAL RATINGS
tnerruCeludoMCDV5evitcAAm08
tnerruCeludoMCDV42evitcAAm081
tnerruCeludoMCDV42ybdnatSAm002
3
Page 4
TABLE 1
RCM-1 DIAGNOSTIC LEDS
LEDCOLORFUNCTION
Any Trouble
XMIT Enable
XMIT A
XMIT B
XMIT F
LM1
GM1
GM2
YellowLights when the RCM-1 cannot communicate with the MXL.
YellowLights whenever the RCM-1 transmits a message to the MXL.
GreenLights when the RCM-1 transmits voice using the copper
wire RECV connections.
GreenLights when the RCM-1 transmits voice using the copper
wire XMIT connections.
GreenLights when the RCM-1 transmits voice using any of the fiber
optic ports.
GreenLights when the RCM-1 is in local mode.
Flashes when there is no valid carrier on the riser.
GreenLights when the RCM-1 is in global mode 1.
Flashes when there is no valid carrier on the riser.
GreenLights when the RCM-1 is in global mode 2.
Flashes when there is no valid carrier on the riser.
Figure 2
RCM-1 Module Board
4
Page 5
Note:
Polarity must be observed
with all riser connections.
Odd pins are hi side while
even pins are lo side. See
the separate wiring
connections for the ACM/
TBM and the OCC shown
in Figure 12.
NOT USED
PORT C: Copper Interface, Transmit, Style 4 (CT4)
NOT USED
PORT B: Copper Interface, Receive, Style 4 (BR4)
PORT B: Copper Interface, Transmit, Style 4 (BT4)
NOT USED
PORT B: Copper Interface, Receive, Style 7 (BR7)
PORT B: Copper Interface, Transmit, Style 7 (BT7)
PORT B: Fiber Interface, Style 4 (BF4)
PORT B: Fiber Interface, Style 7 (BF7)
PORT C: Fiber Interface, Style 4 (CF4)
NOT USED
PORT D: Copper Connection To The OCC
PORT D: Copper Connection To The OCC
PORT A: Copper Connection To The ACM
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
RCM-1
CABLE TO
MMB OR PSR
P/N 555-190967
OMM-1
OMM-2
or
Figure 3
Description of the RCM-1 Terminals
The RCM-1 can be connected in many different ways. Table 2 describes the various applications. The
block diagrams below show the possible configurations.
TABLE 2
RCM-1 APPLICATIONS
Application No.
(See Corresponding Diagram)
1Typical Style 4 installation
2Style 4 installation with a Style 4 output only extension
3Typical Style 7 installation
4Style 7 installation with a Style 4 extension
5Style 4 installation with fiber optic transmission
6Style 4 fiber optic with a Style 4 fiber optic output only extension
7Style 7 fiber connections with a Style 4 output only fiber extension
8Combination wire and fiber installation
Configuration
9Style 4 Repeater Installation
5
Page 6
Application 1
Typical Style 4 Installation
RCM-1 Nos. 4, 5, and 6 have local ACMs, but cannot
output to the global bus — they can only receive.
Application 2
Style 4 with a Style 4 Output Only Extension
Application 3
Typical Style 7 Installation
6
Page 7
Application 4
Style 7 with a PORT C Extension
Application 5
Style 4 Fiber Optic Installation
7
Page 8
Application 6
Style 4 Fiber Optic with a PORT C Fiber Optic Extension
Style 7 Fiber Optic with a PORT C Fiber Optic Extension
Application 7
8
Page 9
Application 8
Combination Wire and Fiber Installation
Application 9
Style 4 Repeater Installation
INSTALLATION
Remove all system power before
installation, first battery and then AC.
(To power up, connect the
AC first, then the battery.)
The RCM-1 has two configuration dipswitches,
S1 and S2. Set the dipswitches before install-ing the RCM-1 into the OMM-1/2. (See NOTE
following Table 4 for the operation of
dipswitches.)
The RCM-1 takes up one of the 255 possible
network addresses. Use switch S1 to set the
MXL network address. Set this switch according
to the address where the RCM-1 is installed in
the MXL’s network map. Refer to the AccuLINK
(CSG-M) configuration printout for the address of
the module. See Table 3 for settings.
In addition to S1 which is used to set the network
address, the RCM-1 has a second bank of
dipswitches, S2, which must be correctly configured for the RCM-1 to operate properly. Refer to
Table 4 for a description of the functions for each
of the switches in S2.
XXXOXXXX
LAGELLI
LAGELLI
LAGELLI
LAGELLI
LAGELLI
LAG
LAGELLI
LAGELLI
10
Page 11
TABLE 4
S2 SETTINGS
(0 = OFF, 1 = ON)
Switch No.FunctionDescription
1 - 3Copper Riser Modes
Location SW1 SW2 SW3
A111No copper connection
B011Normal connections on both R and T (Style 4 and 7)
C101EOL Tx, connections on T terminals only (Style 4 and 7)
D001EOL Rx, connections on the R terminals only (Style 4 and 7)
E110EOL Rx4, connections on Style 4 R terminals; connections on
the Style 7 R and T terminals (Style 7 only)
F010EOL Rx7, connections on Style 7 R terminals; connections on
the Style 4 R and T terminals (Style 7 only)
G100First and only RCM-1 in a PORT C Style 4 extension
H000First RCM-1 in a PORT C Style 4 extension with
other RCM-1s connected to PORT C
4Copper RepeaterRepeater enabled when off, disabled when on
NOTE: To open a dipswitch, press down on the side of the dipswitch marked OPEN.
To close a dipswitch, press down on the side of the dipswitch opposite the side marked OPEN.
Toopen a slide switch, push the slide to the side opposite the side marked ON.
To close a slide switch, push the slide to the side marked ON.
Use switch S2 to set the correct module configuration for the application you have selected. Refer
to Table 4 and Application Diagrams 1-8 to
determine the setting for your application.
After setting the switches, install the RCM-1 into
the OMM card cage according to the following
instructions. Make sure that the module is in the
card guides and the card edge is firmly seated in
At all times handle all plug-in cards with
extreme care. When inserting or removing a
card, be sure the position of the card is kept
at right angles to the OMM board. Otherwise, the plug-in card can damage or
displace other components.
the connectors on the OMM.
CAUTION
11
Page 12
The RCM-1 mounts in the OMM-1 or OMM-2
inside the MXL cabinet. Note that the RCM-1 is a
double-width card that requires the removal of the
middle card guides on the OMM-1 and OMM-2
before the card can be installed. On early versions of the OMM-1 and OMM-2 this was not
possible. Make sure that the OMM-1 and OMM-2
assemblies have date codes later than 3/1/95.
If the OMM-1 or OMM-2 is already installed in
the MXL, follow these steps:
1. Unfasten the screws that secure the
OMM-1/2 and remove it from the MXL
cabinet.
2. Remove the screws on the rear of the
OMM-1/2 which secure the two middle card
guides and remove the guides.
CAUTION
INSERT THE RCM-1 MODULE IN THE
OMM-1/2 WITH THE ELECTRONIC
COMPONENTS FACING OUTWARD
TOWARDS THE OMM SCREW TERMINALS.
INSTALLATION IN ANY OTHER WAY WILL
CAUSE DAMAGE TO THE RCM-1.
Typical Style 4 Connections - Application 1
(See Figure 4)
This is the basic configuration of the RCM-1. It
allows multiple networked MXL voice systems to
be connected together to act as one large
integrated voice evacuation system.
3. Re-install the OMM-1/2 into the MXL
backbox.
4. Install the RCM-1 into the OMM-1/2.
Port B receive from transmit out on other RCMs.
Notes:
1. Use 18AWG minimum wire.
2. Limit the maximum resistance of loop total from the first RCM to
the last RCM to 100 ohms. Maximum line capacitance = 1µF.
3. The wiring is power limited to NFPA 70 per NEC 760.
4. Maximum voltage is 1.5V RMS.
5. Maximum current is 50mA.
6. Refer to Figure 12 for proper EOLR placement.
7. Refer to Wiring Specification for MXL, MXL-IQ and MXLV
Systems, P/N 315-092772 revision 6 or higher, for additional
wiring information.
8. Positive and negative ground fault detected at <50K ohms for
terminals 17-20.
SGNITTES2S
WSnoitpircseD
1gifnocreppoCffonoffo
2gifnocreppoCnoffoffo
3gifnocreppoCnonono
4retaeperreppo
Cnonono
5gifnocrebiFnonono
6gifnocrebiFnonono
77elytSnonono
noitacoL
B
C
Port B transmit pair to receive inputs on other RCMs.
noitacoL
noitacoL
D
NOT USED
No connection if first RCM.
No connection if last RCM.
NOT USED
To OCC-1, TB 2/TB4, 1
To OCC-1, TB 2/TB4, 2
To TBM-2, TB5, 1
To TBM-2, TB5, 4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
+
_
+
_
16
17
18
19
20
21
22
RCM-1
CABLE TO
MMB OR PSR
P/N 555-190967
OMM-1
OMM-2
or
Figure 4
Typical Style 4 Connections
12
Page 13
Typical Style 4 Connections with PORT C
Extension - Application 2 (See Figure 5)
The RCM-1 provides a Style 4 output which
can be used to connect to other systems which
require global paging capability. A Style 4
output only (PORT C) extension is also
supported.
Port C output connects port B receive input on other RCMs.
Port B receive from transmit out on other RCMs.
Port B transmit pair to receive inputs on other RCMs.
SGNITTES2S
WSnoitpircseD
1gifnocreppoCffonoffonoffo
2gifnocreppoCnoffoffonoffo
3gifn
4retaeperreppoCnonononono
5gifnocrebiFnonononono
6gifnocrebiFnonononono
77elytSnonononono
ocreppoCnonononoffo
noitacoL
B
noitacoL
C
D
No connection if first RCM.
No connection if last RCM.
noitacoL
noitacoL
G
H
To OCC-1, TB 2/TB4, 1
To OCC-1, TB 2/TB4, 2
Notes:
1. Use 18AWG minimum wire.
2. Limit the maximum resistance of loop total from the first RCM to
the last RCM to 100 ohms. Maximum line capacitance = 1µF.
3. The wiring is power limited to NFPA 70 per NEC 760.
4. Maximum voltage is 1.5V RMS.
5. Maximum current is 50mA.
6. Refer to Figure 12 for proper EOLR placement.
7. Refer to Wiring Specification for MXL, MXL-IQ and MXLV
Systems, P/N 315-092772 revision 6 or higher, for additional
wiring information.
8. Positive and negative ground fault detected at <50K ohms for
terminals 17-20.
NOT USED
NOT USED
noitacoL
NOT USED
To TBM-2, TB5, 1
To TBM-2, TB5, 4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
RCM-1
CABLE TO
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
+
_
+
_
16
17
18
19
20
21
22
MMB OR PSR
P/N 555-190967
OMM-1
or
OMM-2
Typical Style 4 Connections with PORT C Extension
Figure 5
13
Page 14
Typical Style 7 Connections - Application 3
(See Figure 6)
The RCM-1 provides a Style 7 output which can
be used to connect to other systems which
require global paging capability.
Port B Style 4 receive from transmit out on other RCMs.
No connection if first RCM.
Port B Style 4 transmit pair to receive inputs on other RCMs.
No connection if last RCM.
Port B Style 7 receive from transmit out on other RCMs.
No connection if first RCM.
Port B Style 7 transmit pair to receive inputs on other RCMs.
No connection if last RCM.
To OCC-1, TB 2/TB4, 1
To OCC-1, TB 2/TB4, 2
NOT USED
NOT USED
NOT USED
To TBM-2, TB5, 1
To TBM-2, TB5, 4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
RCM-1
CABLE TO
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
+
_
+
_
16
17
18
19
20
21
22
MMB OR PSR
P/N 555-190967
OMM-1
or
OMM-2
SGNITTES2S
WSnoitpircseD
1gifnocreppoCffononoffo
2gifnocreppoCnoffonono
3gifnocreppoCnonoffoffo
4retaeperreppoCnononono
5gifnocrebiFnononono
6gifnocrebiFnononono
77elytSffoffoffono
noitacoL
B
noitacoL
C
Notes:
1. Use 18AWG minimum wire.
noitacoL
E
noitacoL
F
2. Limit the maximum resistance of loop total from the first RCM to
3. The wiring is power limited to NFPA 70 per NEC 760.
4. Maximum voltage is 1.5V RMS.
5. Maximum current is 50mA.
6. Refer to Figure 12 for proper EOLR placement.
7. Refer to Wiring Specification for MXL, MXL-IQ and MXLV
8. Positive and negative ground fault detected at <50K ohms for
Figure 6
Typical Style 7 Connections
14
the last RCM to 100 ohms. Maximum line capacitance = 1µF.
Systems, P/N 315-092772 revision 6 or higher, for additional
wiring information.
terminals 17-20.
Page 15
Style 7 Connections with PORT C
Extension - Application 4 (See Figure 7)
The RCM-1 provides a Style 7 output which
can be used to connect to other systems which
require global paging capability. A Style 4
output only (PORT C) extension is also
supported.
Notes:
1. Use 18AWG minimum wire.
2. Limit the maximum resistance of loop total from the first RCM to
the last RCM to 100 ohms. Maximum line capacitance = 1µF.
3. The wiring is power limited to NFPA 70 per NEC 760.
4. Maximum voltage is 1.5V RMS.
5. Maximum current is 50mA.
6. Refer to Figure 12 for proper EOLR placement.
7. Refer to Wiring Specification for MXL, MXL-IQ and MXLV
Systems, P/N 315-092772 revision 6 or higher, for additional
wiring information.
8. Positive and negative ground fault detected at <50K ohms for
terminals 17-20.
NOT USED
Port C output connects to riser B Style 4 receive input on other RCMs.
NOT USED
Port B Style 4 receive from transmit out on other RCMs.
No connection if first RCM.
Port B Style 4 transmit pair to receive inputs on other RCMs.
No connection if last RCM.
NOT USED
Port B Style 7 receive from transmit out on other RCMs.
No connection if first RCM.
Port B Style 7 transmit pair to receive inputs on other RCMs.
No connection if last RCM.
NOT USED
SGNITTES2S
WSnoitpircseD
1gifnocreppoCffononoffo
2gifnocreppoCnoffonoffo
3gifnocreppoCnononoffo
4retaeperreppoCnononono
5gifnocrebiFnononono
6gifnocrebiFnononono
77elytSffoffonono
noitacoL
B
noitacoL
C
noitacoL
E
noitacoL
F
To OCC-1, TB 2/TB4, 1
To OCC-1, TB 2/TB4, 2
To TBM-2, TB5, 1
To TBM-2, TB5, 4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
RCM-1
CABLE TO
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
+
_
+
_
16
17
18
19
20
21
22
MMB OR PSR
P/N 555-190967
OMM-1
or
OMM-2
Figure 7
Style 7 with Style 4 Extension
15
Page 16
Typical Style 4 Fiber Optic Connections
with Optional PORT C Extension Applications 5 and 6 (See Figure 8)
The RCM-1 provides a Style 4 Fiber Optic
output which can be used to connect to other
systems which only require global voice
output. A Style 4 Fiber Optic output only
(PORT C) extension is also supported.
To fiber optic module from Fiber Optic Model D2300CP.
To optional fiber module if a Style 4
output only extension is required.
(SEE APPLICATION 6)
To OCC-1, TB 2/TB4, 1
To OCC-1, TB 2/TB4, 2
NOT USED
NOT USED
NOT USED
To TBM-2, TB5, 1
To TBM-2, TB5, 4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
RCM-1
CABLE TO
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
+
_
+
_
16
17
18
19
20
21
22
MMB OR PSR
P/N 555-190967
OMM-1
or
OMM-2
SGNITTES2S
WSnoitpircseD
1gifnocreppoCno
2gifnocreppoCno
3gifnocreppoCno
4retaeperreppoCno
5gifnocrebiFffo
6gifnocrebiFno
77el
ytSno
sA
nwohS
Style 4 Fiber Optic Connection with Optional PORT C Extension
Notes:
1. Use 18AWG minimum wire.
2. Limit the maximum resistance of loop total from the first RCM to
the last RCM to 100 ohms. Maximum line capacitance = 1µF.
3. The wiring is power limited to NFPA 70 per NEC 760.
4. Maximum voltage is 1.5V RMS.
5. Maximum current is 50mA.
6. Refer to Figure 12 for proper EOLR placement.
7. Refer to Wiring Specification for MXL, MXL-IQ and MXLV
Systems, P/N 315-092772 revision 6 or higher, for additional
wiring information.
8. Positive and negative ground fault detected at <50K ohms for
terminals 1-6 and 17-20.
Figure 8
16
Page 17
Typical Style 7 Fiber Optic Connections
with Optional PORT C Extension Application 7 (See Figure 9)
The RCM-1 provides a Style 7 Fiber Optic
output which can be used to connect to other
systems which require global paging
capability. A Style 4 Fiber Optic output only
(PORT C) extension is also supported.
To fiber optic module from Fiber Optic Model D2300CP.
To fiber optic module from Fiber Optic Model D2300CP.
To optional fiber module if a Style 4
output only extension is required.
To OCC-1, TB 2/TB4, 1
To OCC-1, TB 2/TB4, 2
NOT USED
NOT USED
To TBM-2, TB5, 1
To TBM-2, TB5, 4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
RCM-1
CABLE TO
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
+
_
+
_
16
17
18
19
20
21
22
MMB OR PSR
P/N 555-190967
OMM-1
or
OMM-2
SGNITTES2S
WSnoitpircseD
1gifnocreppoCno
2gifnocreppoCno
3gifnocreppoCno
4retaeperreppoCno
5gifnocrebiFffo
6gifnocrebiFno
77el
ytSffo
sA
nwohS
Style 7 Fiber Optic Connection with Optional PORT C Extension
Notes:
1. Use 18AWG minimum wire.
2. Limit the maximum resistance of loop total from the first RCM to
the last RCM to 100 ohms. Maximum line capacitance = 1µF.
3. The wiring is power limited to NFPA 70 per NEC 760.
4. Maximum voltage is 1.5V RMS.
5. Maximum current is 50mA.
6. Refer to Figure 12 for proper EOLR placement.
7. Refer to Wiring Specification for MXL, MXL-IQ and MXLV
Systems, P/N 315-092772 revision 6 or higher, for additional
wiring information.
8. Positive and negative ground fault detected at <50K ohms for
terminals 1-6 and 17-20.
Figure 9
17
Page 18
Combination Fiber and Wire Style 4
Connection - Application 8 (See Figure 10)
The RCM-1 can support a combination of fiber
optics and wire which can be used to connect
to other systems which require global paging
capability.
Port B receive from transmit out on other RCMs.
No connection if first RCM.
Port B transmit pair to receive inputs on other RCMs.
No connection if last RCM.
To fiber optic module from Fiber Optic Model D2300CP.
To OCC-1, TB 2/TB4, 1
To OCC-1, TB 2/TB4, 2
NOT USED
NOT USED
NOT USED
To TBM-2, TB5, 1
To TBM-2, TB5, 4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
RCM-1
CABLE TO
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
+
_
+
_
16
17
18
19
20
21
22
MMB OR PSR
P/N 555-190967
OMM-1
or
OMM-2
SGNITTES2S
WSnoitpircseD
1gifnocreppoCffonoffo
2gifnocreppoCnoffoffo
3gifnocreppoCnonono
4retaeperreppo
Cnonono
5gifnocrebiFffonono
6gifnocrebiFnonono
77elytSnonono
noitacoL
B
noitacoL
C
Combination Fiber and Wire Connection
Notes:
1. Use 18AWG minimum wire.
noitacoL
D
2. Limit the maximum resistance of loop total from the first RCM to
the last RCM to 100 ohms. Maximum line capacitance = 1µF.
3. The wiring is power limited to NFPA 70 per NEC 760.
4. Maximum voltage is 1.5V RMS.
5. Maximum current is 50mA.
6. Refer to Figure 12 for proper EOLR placement.
7. Refer to Wiring Specification for MXL, MXL-IQ and MXLV
Systems, P/N 315-092772 revision 6 or higher, for additional
wiring information.
8. Positive and negative ground fault detected at <50K ohms for
terminals 1-6 and 17-20.
Figure 10
18
Page 19
Style 4 Repeater Connection - Application 9
(See Figure 11)
The RCM-1 can be used as a repeater when the
required global riser exceeds 100 ohms. Do not
install more than two repeaters in any global
riser.
Port B receive from transmit out on
last RCM in the old global riser.
Port B transmit pair to receive inputs
on first RCM in the new global riser.
To OCC-1, TB 2/TB4, 1
To OCC-1, TB 2/TB4, 2
To TBM-2, TB5, 1
To TBM-2, TB5, 4
NOT USED
NOT USED
NOT USED
_
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
RCM-1
CABLE TO
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
+
_
+
16
17
18
19
20
21
22
MMB OR PSR
P/N 555-190967
OMM-1
or
OMM-2
SGNITTES2S
WSnoitpircseD
1gifnocreppoCffoffo
2gifnocreppoCnono
3gifnocreppoCnono
4retaeperreppoCnoffo
5gifnocreb
iFnono
6gifnocrebiFnono
77elytSnono
noitacoL
B
noitacoL
*B
*Refer to Application 9,
page 9, for Location B
and Location B*.
Riser Repeater
Notes:
1. Use 18AWG minimum wire.
2. Limit the maximum resistance of loop total from the first RCM to
the last RCM to 100 ohms. Maximum line capacitance = 1µF.
3. The wiring is power limited to NFPA 70 per NEC 760.
4. Maximum voltage is 1.5V RMS.
5. Maximum current is 50mA.
6. Refer to Figure 12 for proper EOLR placement.
7. Refer to Wiring Specification for MXL, MXL-IQ and MXLV
Systems, P/N 315-092772 revision 6 or higher, for additional
wiring information.
8. Positive and negative ground fault detected at <50K ohms for
terminals 17-20.
Figure 11
19
Page 20
RCM Style 4 connections to the OCC
RCM Style 6 connections to the OCC
RCM Style 4 connections to the ACM
RCM Style 6 connections to the ACM
Wiring Configurations for the OCC and ACM
P/N 315-093878-11
Figure 12
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.