Siemens RCC10U Technical Instructions

RCC10U
Technical Instructions
Document No. 155-712
Room Temperature Controller for Two-pipe Fan Coil Units
Siemens Industry, Inc.
Description
Room temperature controller for two-pipe fan coil units.
Features
Output for on/off valve actuator.
Output for three-speed fan.
Dual setpoint temperature scale.
Control depending on the room or return air temperature.
Automatic Heating/Cooling changeover.
Operating modes: Normal, Energy Saving, Freeze Protection and Off.
Operating mode changeover input for remote control.
Selectable control parameters.
Operating voltage 120 Vac.
Application
Typical use:
Controlling room temperature in individual rooms that are heated or cooled with two­pipe fan coil units.
Opening or closing a valve
Switching a three-speed fan.
Suitable for use in systems with:
Automatic Heating/Cooling changeover.
Heating only/Cooling only or Heating and Cooling applications.
Product Number
RCC10U With input for return air temperature sensor
Technical Instructions RCC10U Room Temperature Controller Document Number 155-712 for Two-pipe Fan Coil Units September 27, 2007
Page 2 Siemens Industry, Inc.
Accessories
ARG70 Adapter plate, for 2-inch × 4-inch or 4-inch × 4-inch electrical wall boxes QAH11.1 Changeover/remote sensor 141-570 Lockable Thermostat Guard
Ordering
The QAH11.1 temperature sensor (which can be used as a return air temperature or changeover sensor), and valves must be ordered separately. An ARG70 Wall Box Adapter (used to mask the drywall when mounting the controller to a 2-inch × 4-inch or 4-inch × 4-inch electrical wall box) must also be ordered separately.
Table 1. Equipment Combinations.
Product Number
Description
Technical Instructions
QAH11.1
Temperature Sensor
155-329P25
599 Series
Two-way and Three-way Zone Valves
155-320P25
SF Series
Zone Valve Actuator
155-321P25
Warning/Caution Notations
WARNING:
Personal injury, or loss of life may occur if you do not follow a procedure as specified.
CAUTION:
Equipment damage, or loss of data may occur if you do not follow a procedure as specified.
Functions
The controller measures the room temperature with its integrated sensor or external return air temperature sensor (QAH11.1)if usedand maintains the setpoint by delivering control commands to the two-position (on/off) valve.
The switching differential is adjustable; it can be 2°F (1°C) or 7°F (4°C) in Heating mode, or 1°F (0.5°C) or 3.5°F (2°C) in Cooling mode.
Fan Operation
The fan is switched to the selected speed via control output 11, 10 or 9 (Low, Medium or High).
When the Temperature-dependent fan control function is activated (can be selected with DIP Switch No. 1), the fan and valve are switched ON or OFF depending on the temperature.
It is switched OFF by:
Leaving the Heating or Cooling sequence, if the function Temperature-dependent fan control is activated.
Manually changing to Standby , if room conditions do not call for Freeze Protection mode.
Activating an external operating mode changeover switch, if installation conditions do not call for Energy Saving or Freeze Protection mode.
Turning the controller’s power supply OFF.
RCC10U Room Temperature Controller Technical Instructions for Two-pipe Fan Coil Units Document Number 155-712 September 27, 2007
Siemens Industry, Inc. Page 3
Heating/Cooling Mode
Output terminals 7 and 5 (neutral) command the control valve. Output terminals 7 and 5 are open (0 Vac) when:
1. The measured room temperature is at half the switching differential below the
setpoint (Heating mode), and
2. The valve has been fully closed for more than one minute.
Output terminals 7 and 5 are closed (120 Vac) when:
1. The measured room temperature is at half the switching differential above the
setpoint (Heating mode), and
2. The valve has been fully open for more than one minute.
NOTE: Output terminals 7 and 5 deliver a control command only for fail-safe open
(Normally Open) valve/actuator assemblies. Fail-safe closed (Normally
Closed) valve/actuator assemblies cannot be used with the RCC10U Controller.
Return Air Temperature
The RCC10U provides control based on either the measured room temperature or the fan coil unit’s return air temperature.
Changeover is automatic if a QAH11.1 cable temperature sensor is connected to the device. Place the sensor in the return air duct and terminate to the controller.
Order the QAH11.1 separately for return air sensing.
Automatic Heating/Cooling Changeover
CW = Chilled Water Cooling mode HW = Hot Water Heating mode M = Operating mode SDC = Switching differential, cooling SDH = Switching differential, heating T = Room temperature Tw = Water temperature W = Room temperature setpoint Y = Signal voltage
The controller uses the water temperature measured by the changeover sensor (QAH11.1) to switch from Heating to Cooling mode, or vice versa. When the water temperature is above 82°F (28°C), the controller switches to Heating mode; below 61°F (16°C) it switches to Cooling mode. If the water temperature is between the two changeover points immediately after switching on, the controller will start in the Heating mode. The water temperature is measured at one-minute intervals and the operational status is updated.
Heating Mode
Cooling Mode
Automatic Changeover
Figure 1. Switch Action for Output Teminals 7 and 5.
Remote Changeover
Heating/Cooling
An electric switch placed between input terminals 2 and 3 can facilitate remote changeover. Terminals 2 and 4 must be bridged. When the switch is closed, the Cooling mode is selected. When the switch is open, the Heating mode is selected. Up to ten thermostats can be connected in parallel.
Heating only
For heating only applications, input terminals 2 and 3 are open.
Cooling only
For cooling only applications, input terminals 2 and 3 must be bridged with wire.
Technical Instructions RCC10U Room Temperature Controller Document Number 155-712 for Two-pipe Fan Coil Units September 27, 2007
Page 4 Siemens Industry, Inc.
Purging Function
The changeover sensor initiates the change from Heating to Cooling mode even if the two-way valves are shut down for a long period of time. To ensure this function, the valves are opened for one minute at two-hour intervals.
After power is reset to the controller, the heating and cooling valve will open for one minute to flush pipes, for accurate remote changeover sensing. When this function is completed, the changeover sensor will select the correct mode.
Setpoint Limit Stops
The room temperature setpoint can be limited in increments of 2°F (1°C) by using the minimum and maximum setpoint limit stops. This prevents unauthorized setpoint adjustment.
To set limit stops, remove the setpoint knob by pulling straight off the shaft. Reposition gray tabs for high and low stops in the holes around the perimeter of knob as required. See Figure 2.
Figure 2. Setpoint Limit Stops.
Operating Modes
The following operating modes are available:
Normal Operating Mode
Heating or Cooling mode with automatic changeover and with manually selected fan speed: (Low), (Medium), (High). In Normal operation, the controller maintains
the adjusted setpoint.
Freeze Protection Mode
The Freeze Protection function is activated only when DIP Switch No. 4 is set to OFF. Freeze Protection mode can be activated by:
Manually switching to Standby .
Activating the external operating mode changeover switch, if DIP Switch No. 2 is set
to OFF.
If the room temperature falls below 46°F (8°C), the controller will automatically switch to Freeze Protection mode. In that case, the heating valve opens and the fan operates at the selected speed. If the Standby mode is selected, the fan will operate at low speed. The room temperature is maintained at a setpoint of 46°F (8°C) and the setpoint adjusted by the user will be ignored.
If Freeze Protection operation is locked (DIP Switch No. 4 in position ON), Standby is also locked, which means that the controller will switch to OFF instead of Standby.
Loading...
+ 9 hidden pages