Siemens RAB10 Series, RAB10.1U, RAB10.1UW Technical Instructions

Page 1
RAB10 Series
Technical Instructions
Two-pipe Fan Coil Room
Thermostat with Manual Changeover
Document No. 155-524P25
ET RAB-1
March 2, 2007
Description
Features
Application
Product Numbers
Two-wire, gas diaphragm-based fan coil room thermostat with heating or cooling sequence for two-pi pe fan coil app licat io ns .
Manual, three-speed fan switch
Dual setpoint tem peratur e sc ale
Fan release function
Two-point control algorithm (On/Off)
24 to 120 Vac, 277 Vac operating voltage
Manual changeover switch
Two mounting styles: electrical wall box or drywall
Wall plate adapter (ARG70) included with electrical wall box mount styles
Typically used in commerc ial, high-ris e and light indus t r ial build in gs in conj uncti on w ith:
Zone valves
Thermal valves
Fans
See Table 1.
Technical Design
The RAB10... fan coil room thermostat is based on a two-wire, gas diaphragm technology.
Operation
Heating Mode Cooling Mode
When the heating mode is manually selected, and the room temperature falls below the selected setpoint, the heating contact is closed.
When the cooling mode is manually selected, and the room temperature rises over the selected setpoint, the cooling contact is closed.
Siemens Industry, Inc.
Page 2
Technical Instructions RAB10 Series Two-pipe Fan Coil Room Thermostat Document Number 155-524P25 March 2, 2007
Operation, Continued
Fan Speed
Fan Release Setting
Ventilation
Changeover
Adjustments
The fan control speed can be controlled two ways:
Manually, using the three-speed fan switch on the thermostat cover for continuous operation.
Automatically, by switching to the selected fan speed using the thermostat for controlled operation. Prior to commissioning, the jumper position corresponding to the thermostat function must be selected.
There are two jumper position choices on the printed circuit board:
Jumper SR1
Jumper SR2
When the ventilation function is selected (RAB10.1..), the heating and cooling contacts are always open and the fan works at the selected speed.
The control algorithm can be selected with a switch located on the front of the controller (change over switch).
The required temperature can be selected by a rotating setpoint adjuster at the front of the thermostat.
High and low setpoint limit stops can be engaged to limit temperature range.
Mounting Style Product Number Description
(Low), (Medium), (High).
Selected fan speed as continuous operation Auto Fan is switched at the same time as the valve
Table 1. Product Numbers.
Electrical Wall Box
(with wall box
adapter)
Drywall RAB10.1U 2-pipe; manual changeover; degrees
Accessory
ARG70 Wall Box Adapter
Warning/Caution Notations
WARNING:
CAUTION:
RAB10.1UW 2-pipe; manual changeover; degrees
Fahrenheit and Celsius; fan only function
Fahrenheit and Celsius; fan only function
Personal injury, or loss of life may occur if you do not perform a procedure as specified.
Equipment damage, or loss of data may occur if you do not follow a procedure as specified.
Page 2 Siemens Industry, Inc.
Page 3
RAB10 Series Two-pipe Fan Coil Room Thermostat Technical Instructions
Operation
Screw terminals for wires of 2 × 16 AWG or 1 × 14 AWG
Material Plastic
Conforms to CE requirements
Document Number 155-524P25 March 2, 2007
Specifications
Operating voltage 24 to 120 Vac, 277 Vac Frequency 50/60 Hz Setpoint adjustment range 50°F to 85°F (10°C to 30°C) Setpoint limit stops Adjustable Switching differential (SD) 1.8°F (1°C), fixed Switch rating 6A RES, 3.5A FLA, 12A LRA Switch action Single-Pole, Double-Throw (SPDT ) Selector switch Off/Low/Medium/High Weight 5 oz. (0.14 kg) Dimensions 3.80 × 4.45 × 1.68 inches
(96.4 × 113.1 × 42.8 mm) Color Ivory white with gray selector knobs
Ambient Conditions
Wiring
Housing
Agency Certification
Temperature 32°F to 122°F (0°C to 50°C) Relative humidity <95%
Transport/Storage
Temperature –4°F to 122°F (–20°C to 50°C) Relative humidity <95%
Minimum 20 AWG
Enclosure rating NEMA1 Bellows Environmentally-friendly gas
UL listed to 893 (E35918) cUL listed to Canadian standard C22.2 No. 24-93
Table 2. Control Valves.
Part Number Description Technical
Instructions
SFA71U 24V NC SFA11U 120V NC
155-521
SFA208V/25 208V NC SFA277V/25 277V NC FTA71 24V NC 155-109 599 Series Zone
Valves
Siemens Industry, Inc. Page 3
Two-way
Three-way
155-320P25
Page 4
Technical Instructions RAB10 Series Two-pipe Fan Coil Room Thermostat Document Number 155-524P25 March 2, 2007
Mounting
Locate the unit where the air temperature can be sensed as accurately as possible.
Do not mount in direct sunlight or near other heat or refrigeration sources.
Mounting height is approximately 60 inches (1.5 m) above the floor.
The unit can be fitted to most commercially available recessed conduit boxes or
directly on the wall.
Figure 1. Recommended Mounting Locations.
(Dimensions in Inches)
WARNING:
1. This unit can be installed by authorized pers onn el on l y.
2. The unit must be de-energized and the operating voltage checked before opening.
Setpoint Limit Stops Adjustment
Installation
Required Tools
An ARG70 wall plate adapter (provided with electrical wall box mount models) must be used to mount to a 2 × 4-inch or 4 × 4-inch electrical wall box.
An ARG70 wall plate adapter must be used to meet UL and cUL requirements.
The thermostat must be mounted on a flat wall.
All local electrical regulations must be complied with.
If there are radiator valves in the room, set them to their fully open position.
To set limit stops, remove gray tabs located on the setpoint knob and position high and low stops around the perimeter of knob as required. Each position on the setpoint dial is
1.8°F. See Figure 2.
Small, flat-blade screwdriver
1/4-inch drill bit
Drill motor
Small mallet
Pencil
Page 4 Siemens Industry, Inc.
Page 5
RAB10 Series Two-pipe Fan Coil Room Thermostat Technical Instructions Document Number 155-524P25 March 2, 2007
Drywall Mounting
1. Loosen the two screws at the bottom of thermostat.
2. Lift the bottom of the thermostat cover from the thermostat base and push up to
remove cover.
3. Remove sub-base from back of thermostat.
4. Using the sub-base (packed with thermostat) as a template, mark the hole locations
with a pencil.
5. Drill two 1/4-inch diameter holes for plastic wall anchors (provided).
6. Using a mallet, tap in the plastic wall anchors flush wit h wa ll.
7. Pull the wiring through the opening in the upper portion of the sub-base.
8. Level mounting plate.
9. Using the two wood screws provided, fasten sub-base to wall. Thermostat is not
position sensitive.
10. Pull the wiring through the sub-base.
11. Position thermostat housing over the two mounting lugs located at the top of the
sub-base, and press down on cover until bottom lugs snap in place.
12. Terminate wires per wiring instructions on the inside of thermostat cover.
Optional: To set limit stops, remove gray tabs located on the setpoint knob and position high and low stops around perimeter of knob as required.
Figure 2. Setpoint Limit Stops.
13. Place all thermostat switches in the “down” position to allow cover switch sliders to
fit over the switches.
14. Insert the top of the thermostat cover into the slots located on the top of the
thermostat and press down.
15. Tighten the two screws at the bottom of the thermostat.
16. Return selector switches to the normal position. Adjust setpoint dial to desired
setting.
The installation is now complete.
Siemens Industry, Inc. Page 5
Page 6
Technical Instructions RAB10 Series Two-pipe Fan Coil Room Thermostat Document Number 155-524P25 March 2, 2007
4 × 4-inch Electrical Wall Box Mounting
An ARG70 wall plate adapter is required to mount an RAB… thermostat to a 4 × 4-inch electrical wall box. The ARG70 wall plat e ada pter is include d with elec tric a l wal l box mount models.
1. Loosen the two screws at the bottom of thermostat.
2. Lift the bottom of the thermostat cover from the thermostat base and push up to remove cover.
3. Using the four screws provided, fasten wall box adapter (3) to plaster ring (2), supplied by others.
4. Pull wires through plaster ring (2).
5. Flex adapter mask (4) and snap in place inside wall box adapter (3).
6. Fasten sub-base (5), included with thermostat, to wall box adapter assembly (3) and (4) with the two screws provided.
7. Follow Drywall Mounting Steps 7 through 16.
The installation is now complete.
Figure 3. 4 × 4-inch Electrical Wall Box Installation.
1 Electrical wall box 2 Plaster ring
5 Sub-base 6 Thermostat base
3 Wall box adapter *
7 Thermostat cover
4 Adapter mask *
* Included with ARG70
Page 6 Siemens Industry, Inc.
Page 7
RAB10 Series Two-pipe Fan Coil Room Thermostat Technical Instructions Document Number 155-524P25 March 2, 2007
2 × 4-inch Electrical Wall Box Mounting
An ARG70 wall plate adapter is required to mount an RAB… thermostat to a 2 × 4-inch electrical wall box. The ARG70 wall plate ada pter is inc lude d with electr ica l wal l box mount models.
1. Loosen the two screws at the bottom of thermostat.
2. Lift the bottom of the thermostat cover from the thermostat base and push up to
remove cover.
3. Using the two screws provided, fasten wall box adapter (3) to plaster ring (2),
supplied by others.
4. Pull wires through plaster ring (2).
5. Flex adapter mask (4) and snap in place inside wall box adapter (3).
6. Fasten sub-base (5), included with thermostat, to wall box adapter assembly (3)
and (4) with the two screws provided.
7. Follow Drywall Mounting Steps 7 through 16. The installation is now complete.
Figure 4. 2 × 4-inch Electrical Wall Box Installation.
1 Electrical wall box
5 Sub-base 3 Wall box adapter * 4 Adapter mask *
6 Thermostat base
7 Thermostat cover
* Included with ARG70
Siemens Industry, Inc. Page 7
Page 8
Technical Instructions RAB10 Series Two-pipe Fan Coil Room Thermostat
W/Y Control output actuator
cooling
Document Number 155-524P25 March 2, 2007
Maintenance
Diagrams
The room thermostat is completely maintenance-free. If inoperable, replace entire unit.
WARNING:
High voltage. Disconnect power before servicing. Metal part is not grounded.
L Operating voltage M1 3-speed fan N Neutral N1 Room thermostat G1 Control output fan speed I
(Low)
G2 Control output fan speed II
(Medium)
G3 Control output fan speed III
(High)
ZV Zone valve or thermal valve
Figure 5. Wiring.
T Room temperature SD Switching differential SP Room temperature
setpoint
W Valve output signal
heating
Y Valve output signal
Page 8 Siemens Industry, Inc.
Heating Mode Cooling Mode
Figure 6. Operating.
Page 9
RAB10 Series Two-pipe Fan Coil Room Thermostat Technical Instructions
Siemens Indus try, Inc.
+ 1 847-215-1000
Your feedback is important to us. If you have
Document No. 155-524P25
Figure 9. ARG70.
Document Number 155-524P25 March 2, 2007
Dimensions
Dimensions in inches (millimeters)
Figure 7. RAB10… Unit.
Figure 8. Base Plate.
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners. © 2007 Siemens Industry, Inc.
Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089
comments about this document, please send them to SBT_technical.editor.us.sbt@siemens.com
Printed in the USA
Page 9
Loading...