Siemens 3RA62, RA2 User Manual

SIRIUS Innovations Supplement 2011
6
Combination Starters & Starters for Group Installation
SIRIUS 3RA2 Motor Starters
6/2
General data
6/13 AC 50/60 Hz 110/120 V 6/15 24 V DC
3RA22 Reversing Starters
6/17 AC 50/60 Hz 110/120 V 6/19 24 V DC 6/21
Accessories
6/31
3RV29 Infeed System for
Motor Starters
For Operation in the Control Cabinet
SIRIUS 3RA6 Compact Starters
6/32
General data
3RA61, 3RA62 Compact Starters
6/40
3RA61 direct-on-line starters
6/41
3RA62 reversing starters
3RA64, 3RA65 Compact Starters for
IO-Link
6/42
3RA64 direct-on-line starters
6/43
3RA65 reversing starters
6/44
Accessories
6/50
Add-On Modules for AS-Interface
6/52
Infeed Systems for 3RA6
Technical Information
can be found at
www.siemens.com/industrial-controls/
support
under Product List:
- Technical specifications
under Entry List:
- Updates
- Download
- FAQ
- Manuals
- Characteristics
- Certificates
SIRIUS Motor Starters
© Siemens AG 2011
Combination Starters & Starters for Group Installation
SIRIUS 3RA2 Motor Starters
General data
6/2
SIRIUS Innovations Supplement 2011
6
Overview
3RA2 motor starters
The 3RA2 fuseless motor starters consist of the 3RV2 motor starter protector and the 3RT2 electromechanical contactor. The devices are electrically and mechanically connected using pre­assembled assembly kits (link modules, wiring kits and standard mounting rail or
busbar adapters).
Around 500 preassembled 3RA2 combinations of these innova­tive 3RT2 controls and 3RV2 protection equipment can be ordered for direct-on-line and reversing starting of standard in­duction motors up to 32 A (approx. 20 HP/460 V).
In the 3RA2 motor starter, the 3RV2 motor starter protector is responsible for overload and short-circuit protection. Back-up protective devices, such as melting fuses or limiters, are super­fluous here, as the motor starter protector is capable of with­standing short-circuits up to 65 kA at 480 V and 30 kA at 600 V. See the the actual SCCR ratings by device listed on the selection pages of this chapter.
The 3RT2 contactor is particularly suitable for extremely complex switching tasks requiring the greatest endurance.
The 3RA2 motor starters are available with setting ranges from
0.14 to 32 A in sizes S00 and S0:
The size of the 3RA2 motor starters is based on the size of the contactor:
1)
The combination of an S00 motor starter protector with an S0 contactor is possible only for screw connection versions.
Operating conditions 3RA2 motor starters are climate-proof. They are intended for use
in enclosed rooms in which no severe operating conditions (such as dust, caustic vapors, hazardous gases) prevail. Suit­able covers must be provided for installation in dusty and damp locations.
Tripping times All 3RA2 motor starters described here are designed for normal
starting, in other words for overload tripping times of less than 10 s (CLASS 10). At rated-load operating temperature the trip­ping times are shorter, depending on the particular equipment and the setting range. The exact values can be derived from the tripping characteristics of the motor starter protectors.
Connection methods For all 3RA2 starters up to 32 A, spring-type connection is avail-
able as well as screw connection. To connect two devices with spring-type connection there are plug-in connection modules for sizes S00 and S0 which enable very quick mounting of the start­ers and a vibration-resistant assembly.
To connect a motor starter protector with screw connection to a contactor with spring-type connection there are special hybrid connection modules for S00 and S0.
While starters can be assembled with either spring-type or screw connection, the pre-assembled versions offered in this chapter are with screw terminals only. For spring-type versions, simply order the components listed on the spring-type terminal pages and assemble these starters quickly and efficiently with­out the use of any tools.
Size Width Max. rated current
I
n max
For induction motors up to
mm A HP
S00 45 16 10
S0 45 32 20
Size of 3RA2 S00 S0
Size of 3RV2 motor starter protector S00 S001), S0
Size of 3RT2 contactor S00 S0
Screw terminals
Spring-type terminals
These terminals are indicated in the corresponding tables by the symbols shown on orange backgrounds.
© Siemens AG 2011
Combination Starters & Starters for Group Installation
SIRIUS 3RA2 Motor Starters
General data
6/3
SIRIUS Innovations Supplement 2011
6
3RA2 complete units
The 3RA2 fuseless motor starters can be ordered as preassem­bled complete units for direct-on-line starting (3RA21) or for reversing duty (3RA22) with screw connection.
Control supply voltages of AC 50/60 Hz 110/120 V and 24 V DC are available to choose from.
A distinction is also drawn between whether the starter is mounted on a 35 mm standard mounting rail, on a flat surface using screws, or on a 60 mm busbar system.
Accessories
As the 3RA2 fuseless motor starters are constructed from 3RV2 motor starter protectors and 3RT2 contactors, the same acces­sories - such as auxiliary switches, undervoltage releases or door-coupling rotary operating mechanisms - can be used for the 3RA2 fuseless motor starters as for these motor starter pro­tectors and contactors.
In particular, certain accessories have been optimized for the fuseless motor starters. They include the top-connected, trans­verse auxiliary switch on the motor starter protector, which is available with 1 CO contact or 1 NO contact + 1 NC contact. Special auxiliary switch blocks that can be snapped on from below are available for the contactor. These two accessories enable the fuseless motor starters to be wired simply without having to route cables through the device.
Incoming energy supply
On the whole four different infeed possibilities are available (see
"3RV29 Infeed System for Motor Starters" on page 6/31)
.
Customer assembly of fuseless motor starters
While the preassembled 3RA2 can be ordered up to 32 A, com­binations in customer assembly without link modules are also possible up to 40 A (approx. 25 HP/460 V).
Thanks to the SIRIUS modular system, the standard devices can be optimally combined in terms of both technical specifications and dimensions.
The fuseless motor starters can also be assembled easily by the customer. It is simply necessary to assemble the standard 3RV2 motor starter protector, the 3RT2 contactor and the appropriate assembly kit.
For single devices and assembly kits see "Selection and order­ing data" for 3RA21 direct-on-line starters and 3RA22 reversing starters.
For assembly kits for direct-on-line starting or reversing duty for mounting on standard mounting rails or busbars see "Selection and ordering data" for "Accessories".
For reversing starters size S0 it is imperative to use a standard mounting rail adapter in order to ensure the necessary mechan­ical strength. A standard mounting rail adapter is not necessary if a busbar adapter is used.
The 3RA1 fuseless motor starters can be used for the fuseless motor starters between 32 A and 100 A.
The SENTRON 3VL circuit breakers and the SIRIUS 3RT contac­tors are available for rated currents >100 A.
Special equipment for customer assembly can be ordered if other rated control supply voltages are required. Assembly kits can be used to facilitate assembly.
Customers can also assemble tested combinations of motor starter protectors with solid-state controls (soft starters, solid­state contactors) and motor starters with additional monitoring and control devices (3RR monitoring relays, SIMOCODE 3UF).
For the electrical and mechanical connection of protection equipment and controls there are preassambled assembly kits (link modules, wiring kits and standard mounting rail or busbar adapters).
The following types of configuration are possible:
• Direct-on-line/reversing starting (see preassembled 3RA2 combinations)
• Wye-delta starting (only customer assembly with link module)
• Solid-state/soft starting (only customer assembly with link module)
© Siemens AG 2011
Combination Starters & Starters for Group Installation
SIRIUS 3RA2 Motor Starters
General data
6/4
SIRIUS Innovations Supplement 2011
6
Communications integration using IO-Link Motor starters can also be assembled with IO-Link for connec-
tion to the higher-level control system. For each starter this requires a communication-capable contactor onto which a 3RA27 11 function module is plugged (various versions for direct-on-line, reversing and wye-delta starts). The design of the SIRIUS motor starters permits a group of up to 4 SIRIUS controls to be conveniently connected through a standardized IO-Link to a control system, reducing wiring time considerably compared to the conventional parallel wiring method. The electrical con­nection is made using only a single cable with three conductors.
The function modules perform not only the communication (con­tactor operation and feedback, ready signal) but also the elec­trical interlocking (for reversing and wye-delta starters) and the timing relay function (wye-delta reversing time).
Communication information and control supply voltages are passed on through ribbon cables so that the complete control current wiring on the starter is no longer needed.
The monitoring and maintenance of a plant is made consider­ably easier by transmitting diverse diagnostics data from the function modules (e. g. missing main and auxiliary voltage, local disconnection…) through IO-Link to the higher-level control sys­tem. Also, starters equipped for IO-Link can be conveniently controlled from the control cabinet door using the optional oper­ator panel.
More information:
• For IO-Link see Chapter 2 "Industrial Communication"
• For 3RA27 function modules see Chapter 3 "Controls – Contactors and Contactor Assemblies" --> "Function Modules".
Communications integration through AS-Interface Connection of the motor starters to the higher-level control sys-
tem is possible not only through IO-Link but also through AS-Interface. The AS-Interface connection is recommended wherever motor starters are used in distributed applications. This solution also requires a communication-capable contactor and a corresponding 3RA27 12 function module (various ver­sions for direct-on-line, reversing and wye-delta starts). The devices are implemented in A/B technology, making it easy to connect up to 62 starters to an AS-i master (regardless of whether they are direct-on-line, reversing or wye-delta starters).
This results in a significant reduction of wiring compared to the conventional parallel wiring method. The electrical connection is made using standard cables.
The function modules perform not only the communication (con­tactor operation and feedback, ready signal) but also the elec­trical interlocking (for reversing and wye-delta starters) and the timing relay function (wye-delta reversing time).
Communication information and control supply voltages are passed on through ribbon cables so that the complete control current wiring on the starter is no longer needed.
More information:
• For AS-Interface see Chapter 2 "Industrial Communication"
• For 3RA27 function modules see Chapter 3 "Controls – Contactors and Contactor Assemblies" --> "Function Modules".
Contactors with communication interface
For assembling motor starters with communications integration (AS-i/IO-Link) you need contactors with a communications inter­face. These contactors are not included as standard in the preassembled 3RA2 motor starters. A motor starter with com­munications interface must be assembled by the customer from individual devices.
Complete integration in the automation landscape
As the result of the communication connection through IO-Link or AS-i, the SIRIUS motor starters are fully integrated in the auto­mation landscape and can draw on all the advantages of TIA (e. g. integration in the TIA Maintenance Station).
Mounting
3RA2 fuseless motor starters are available:
• For mounting onto standard mounting rails TH 35 according to EN 60715 (depth 15 mm)
• For mounting onto busbar adapters (busbar center-to-center clearance 60 mm, bar thickness 5 to 10 mm)
The fuseless motor starters are also suitable for screw fixing us­ing two 3RV29 28-0B push-in lugs.
The 3RA2 fuseless motor starters can also be configured with the 3RV29 infeed system
(see Chapter 5 "Protection Equipment"
--> "SIRIUS 3RV2 Motor Starter Protectors up to 40 A"
Benefits
The 3RA2 fuseless motor starters offer a number of advantages:
• Minimum planning and assembly work and far less wiring with the preassembled complete units (only one order number 3RA2)
• Plug-in connectors from the motor starter protector to all types of SIRIUS controls, for quicker and error-free assembly of starters with screw and spring-type connection
• High planning reliability through consistent combination tests for fuseless (400 V according to IEC) and fused configuration (400 V, 500 V and 690 V according to IEC)
• Comprehensive approvals for use world-wide (please ask for details of availability)
• Uniform accessories for the two sizes S00 and S0
• Spring-type connection possible throughout: Enhanced operational reliability (vibration-resistant wiring) and less wiring work thanks to plug-in connections
• Power loss 5 to 10 % smaller than for legacy 3RA1 devices, hence lower power consumption
• Connection of starters to the control system through standard­ized system connection (IO-Link and AS-i), for fast integration in TIA and less wiring work. Requires communication contac­tor versions which are not offered in pre-assembled 3RA2 starters.
© Siemens AG 2011
Combination Starters & Starters for Group Installation
SIRIUS 3RA2 Motor Starters
General data
6/5
SIRIUS Innovations Supplement 2011
6
Direct-on-line starting • For standard rail mounting or screw fixing • Sizes S00 and S0
Left: 3RA21 motor starter with screw connection Center: 3RA21 motor starter with spring-type connection Right: Motor starter protector combination with screw connection, with contactor with spring-type connection
Left: Motor starter protector combination with solid-state switching device with screw connection Right: Motor starter protector combination with soft starter with spring-type connection
NSB0_02089
2 push-in lugs
3RV29 28-0B (only for screw mounting)
2 push-in lugs
3RV29 28-0B (only for screw mounting)
Motor starter protector
Size S00/S0 Spring-type terminals
Contactor
Size S00/S0 Spring-type terminals
Link module
3RA29 11-2AA00 for S00 3RA29 21-2AA00 for S0
Motor starter protector
Size S00/S0 Screw terminals
Contactor
Size S00/S0 Spring-type terminals
Link module
3RA29 11-2FA00 for S00 3RA29 21-2FA00 for S0
2 push-in lugs
3RV29 28-0B (only for screw mounting)
Motor starter protector
Size S00/S0 Screw terminals
Contactor
Size S00/S0 Screw terminals
Link module
3RA19 21-1DA00 (for S00) 3RA29 21-1AA00 (for S0, AC contactor) 3RA29 21-1BA00 (for S0, DC contactor)
NSB0_02090
2 push-in lugs
3RV29 28-0B (only for screw mounting)
Motor starter protector
Size S00/S0 Screw terminals
Solid-state switching device
Link module
3RA29 21-1BA00
2 push-in lugs
3RV29 28-0B (only for screw mounting)
Motor starter protector
Size S00/S0 Screw terminals/ spring-type terminals
Soft starter
Size S00/S0 Screw terminals/ spring-type terminals
Link module
3RA29 21-1BA00 for S00/S0 and screw terminals 3RA29 11-2GA00 for S00 and spring-type terminals 3RA29 21-2GA00 for S0 and spring-type terminals
© Siemens AG 2011
Combination Starters & Starters for Group Installation
SIRIUS 3RA2 Motor Starters
General data
6/6
SIRIUS Innovations Supplement 2011
6
Direct-on-line starting • For 60 mm busbar systems • Sizes S00 and S0
Left: 3RA21 motor starter for direct-on-line starting with busbar adapters with screw connection Right: 3RA21 motor starter for direct-on-line starting with busbar adapters with spring-type connection
NSB0_02091a
60 mm busbar adapter for screw terminals
8US12 51-5DS10 for S00 8US12 51-5NT10 for S0
Motor starter protector
Size S00/S0 Screw terminals
Link module
3RA19 21-1DA00 for S00 3RA29 21-1AA00 for S0, AC contactor 3RA29 21-1BA00 for S0, DC contactor
Contactor
Size S00/S0 Screw terminals
60 mm busbar adapter for spring-type terminals
8US12 51-5DT11 for S00 8US12 51-5NT11 for S0
Motor starter protector
Size S00/S0 Spring-type terminals
Link module
3RA29 11-2AA00 for S00 3RA29 21-2AA00 for S0
Contactor
Size S00/S0 Spring-type terminals
Additional 3RA29 11-1CA00 spacer for height compensation on AC contactors size S0 with spring-type terminals.
1)
1)
© Siemens AG 2011
Combination Starters & Starters for Group Installation
SIRIUS 3RA2 Motor Starters
General data
6/7
SIRIUS Innovations Supplement 2011
6
Reversing duty • For standard rail mounting or screw fixing • Size S00
Left: 3RA22 motor starter with screw connection, push-in lugs, 2 contactors for reversing duty and 3RA29 13-2AA1 wiring kit for connecting the contactors (incl. mechanical interlocking and connecting clips) Right: 3RA22 motor starter with spring-type connection, push-in lugs, 2 contactors for reversing duty and 3RA29 13-2AA2 wiring kit (incl. mechanical interlocking and connecting clips)
NSB0_02092a
1
3
4
1
2
3
4
2
2 push-in lugs
3RV29 28-0B (only for screw mounting)
Motor starter protector
Size S00 Screw terminals
Link module
3RA19 21-1DA00 for S00
2 contactors
Size S00 Screw terminals
2 push-in lugs
3RV29 28-0B (only for screw mounting)
Motor starter protector
Size S00 Spring-type terminals
Link module
3RA29 11-2AA00 for S00
2 contactors
Size S00 Spring-type terminals
Wiring kit
3RA29 13-2AA1
Upper wiring module
Lower wiring module
2 connecting clips
Mechanical interlock (can be removed if necessary)
Wiring kit
3RA29 13-2AA2
Upper wiring module
Lower wiring module
2 connecting clips
Mechanical interlock (can be removed if necessary)
3
4
1
2
3
4
1
2
© Siemens AG 2011
Combination Starters & Starters for Group Installation
SIRIUS 3RA2 Motor Starters
General data
6/8
SIRIUS Innovations Supplement 2011
6
Reversing duty • For standard rail mounting • Size S0
3RA22 motor starter for reversing duty and standard rail mounting in size S0 (the version with screw connection is shown in the picture)
NSB0_02093b
3
4
1
2
Motor starter protector
Size S0 Screw terminals/ spring-type terminals
2 standard mounting rail adapters
3RA29 22-1AA00 with 2 connecting wedges 8US19 98-1AA00
2 contactors
Size S0 Screw terminals/ spring-type terminals
Wiring kit
For screw terminals: 3RA29 23-2AA1 For spring-type terminals: 3RA29 23-2AA2
Upper wiring module
Lower wiring module
2 connecting clips
Mechanical interlock (can be removed if necessary)
RH assembly kit for reversing duty and standard rail mounting in size S0
For screw terminals: 3RA29 23-1BB1 For spring-type terminals: 3RA29 23-1BB2
1)
Comprising: 1 wiring kit 2 standard mounting rail adapters 2 connecting wedges
Link module
For screw terminals: 3RA29 21-1AA00 (AC) 3RA29 21-1BA00 (DC) For spring-type terminals: 3RA29 21-2AA00
Additional 3RA29 11-1CA00 spacer for height compensation on AC contactors size S0 with spring-type terminals
3
4
1
2
1)
Also includes 3RA29 11-1CA00 spacer for height compensation on AC contactors size S0 with spring-type terminals.
2)
2)
© Siemens AG 2011
Combination Starters & Starters for Group Installation
SIRIUS 3RA2 Motor Starters
General data
6/9
SIRIUS Innovations Supplement 2011
6
Reversing duty • For 60 mm busbar systems • Sizes S00 and S0
3RA22 motor starter for reversing duty and 60 mm standard mounting rail in size S00/S0 (the version with screw connection is shown in the picture)
NSB0_02094b
3
4
1
2
Motor starter protector
Size S00/S0 Screw terminals/ spring-type terminals
2 contactors
Size S00/S0 Screw terminals/ spring-type terminals
Wiring kit
Screw connection: 3RA29 13-2AA1 for S00 3RA29 23-2AA1 for S0 Spring-type connection: 3RA29 13-2AA2 for S00 3RA29 23-2AA2 for S0
Upper wiring module
Lower wiring module
2 connecting clips
Mechanical interlock (can be removed if necessary)
3
4
1
2
RS assembly kit for reversing duty and busbar mounting
Screw connection: 3RA29 13-1DB1 for S00 3RA29 23-1DB1 for S0
For spring-type connection: 3RA29 13-1DB2 for S00 3RA29 23-1DB2 for S0
Comprising: 1 wiring kit 1 busbar adapter 1 device holder 2 connecting wedges
Link module
For screw terminals: 3RA19 21-1DA00 for S00 3RA29 21-1AA00 for S0, AC contactor 3RA29 21-1BA00 for S0, DC contactor For spring-type terminals: 3RA29 11-2AA00 for S00 3RA29 21-2AA00 for S0
Additional 3RA29 11-1CA00 spacer for height compensation on AC contactors size S0 with spring-type terminals.
60 mm busbar adapter
For screw terminals: 8US12 51-5DS10 for S00 8US12 51-5NT10 for S0 For spring-type terminals: 8US12 51-5DT11 for S00 8US12 51-5NT11 for S0
2 connecting wedges
8US19 98-1AA00
60 mm device holder
8US12 51-5AS10
Also includes 3RA29 11-1CA00 spacer for height compensation on AC contactors size S0 with spring-type terminals.
1)
1)
2)
2)
© Siemens AG 2011
Combination Starters & Starters for Group Installation
SIRIUS 3RA2 Motor Starters
General data
6/10
SIRIUS Innovations Supplement 2011
6
Order No. scheme
Note:
The Order No. scheme is presented here merely for information purposes and for better understanding of the logic behind the order numbers.
For your orders, please use the order numbers quote in the catalog in the Selection and ordering data.
Technical specifications
Digit of the Order No. 1st -
3rd
4th 5th 6th 7th 8th 9th 10th 11th 12th 13th 14th 15th 16th
@@@ @ @ @ 0 @ @ @ @ @ @ @ @ @
SIRIUS starters 3 R A
SIRIUS 2nd generation 2
Type of starter (direct-on-line starter = 1, reversing starter = 2)
@
Size (S00 = 1, S0 = 2) @
Setting range for overload release @ @
Design type and connection method @
Rated power at 460 V AC @ @
Integrated auxiliary switches of the contactor @
Operating range / solenoid coil circuit (contactor) @
Rated control supply voltage (contactor) @ @
Example
3 R A 2 1 1 0 0 B A 1 5 1 A K 6
Direct-on-line starters/ reversing starters
Size Connection methods Mounting Control voltage Width W Height H Depth D
mm mm mm
Mounting dimensions
Direct-on-line starters 3RA21.
S00 3RA21 1.
Screw terminals Standard mounting rails AC/DC 45 167 97
Busbar adapters AC/DC
45 200 155
Spring-type terminals Standard mounting rails AC/DC
45 198 97
Busbar adapters AC/DC
45 260 155 S0 3RA21 2.
Screw terminals Standard mounting rails AC
45 193 97
DC
45 193 107
Busbar adapters AC
45 260 155
DC
45 260 165
Spring-type terminals Standard mounting rails AC/DC
45 243 107
Busbar adapters AC/DC
45 260 165
Reversing starters 3RA22.
S00 3RA22 1.
Screw terminals Standard mounting rails AC/DC
90 170 97
Busbar adapters AC/DC
90 200 155
Spring-type terminals Standard mounting rails AC/DC
90 204 97
Busbar adapters AC/DC
90 260 155 S0 3RA22 2.
Screw terminals Standard mounting rail
adapters
AC
90 265 120.3
DC
90 265 130
Busbar adapters AC
90 260 155
DC
90 260 165
Spring-type terminals Standard mounting rail
adapters
AC/DC
90 270 131
Busbar adapters AC/DC
90 260 165
W
H
D
Type
3RA2. 1 3RA2. 2
Size
S00 S0
Number of poles
3 3
Mechanics and environment
Permissible ambient temperature
• During operation °C -20 ... +60
• Storage and transport °C
-55 ... +80
Weight kg 0.6 ... 1.5 0.8 ... 2.3
Permissible mounting positions
Important: Acc. to DIN 43602 start command "I" at the right or top
Shock resistance (sine-wave pulse)
Acc. to IEC 60086 Part 2-27
g
Up to 6 Up to 6
Degree of protection Acc. to IEC 60947-1
IP20
90°
90°
NSB00369
22,5°
22,5°
© Siemens AG 2011
Combination Starters & Starters for Group Installation
SIRIUS 3RA2 Motor Starters
General data
6/11
SIRIUS Innovations Supplement 2011
6
More information
Type 3RA2. 1 3RA2. 2
Size S00 S0 Number of poles
3 3
General data
Standards IEC 60947-1, EN 60947-1
IEC 60947-2, EN 60947-2 IEC 60947-4-1, EN 60947-4-1
Max. rated current I
n max
(= max. rated operational current Ie) A 16 32
Permissible ambient temperature °C
-20 ... +60 for operation
°C
-55 ... +80 during storage/transport
Rated operational voltage U
e
V 690
Rated frequency Hz
50/60
Rated insulation voltage U
i
(pollution degree 3) V 690
Rated impulse withstand voltage U
imp
kV 6
Trip class (CLASS) Acc. to IEC 60947-4-1,
EN 60947-4-1
10
Rated short-circuit current I
q
at AC 50/60 Hz 400 V
acc. to IEC 60947-4-1, EN 60947-4-1
kA 153
Power loss P
v max
of all main
current paths
Dependent on the rated current
I
n
(upper setting range)
Up to 1.25 A W
2
--
1.6 ... 6.3 A W
2.3 --
8 ... 12 A W
3.5 --
16 A W
4.3 --
5 ... 6.3 A W
-- 2.3
8 ... 12 A W
-- 3.5
16 ... 32 A W
-- 4.3
Power consumption of the solenoid coils for contactors
as a function of the standard output
P of the motor
(when coil is cold and
U
s
50 Hz)
• AC operation
- Closing Up to 4 kW VA 27 --
5.5 ... 7.5 kW VA
37 --
Up to 5.5 kW VA
-- 65
7.5 ... 15 kW VA
-- 77
P.f.
0.8 0.82
- Closed Up to 4 kW VA
4.2 --
5.5 ... 7.5 kW VA
5.7 --
Up to 5.5 kW VA
-- 8.5
7.5 ... 15 kW VA
-- 9.8
P.f.
0.25 0.25
• DC operation Closing = Closed
W
4 5.9
Solenoid coil operating range for contactors
0.8 ... 1.1 x U
s
Lower limit at 55 °C 0.8 x U
s
--
At 60 °C
0.85 x U
s
--
Endurance of the motor starter protector
• Mechanical endurance Operating cycles 100 000
• Electrical endurance Operating cycles
100000
• Max. switching frequency per hour (motor starts) 1/h
15
Endurance of contactor
• Mechanical endurance Operating cycles 30 million 10 million
• Electrical endurance Operating cycles
See endurance characteristic curves of the contactors --> Chapter 3 "Controls – Contactors and Contactor Assemblies"
Shock resistance (sine-wave pulse)
Acc. to IEC 60086 Part 2-27 g
Up to 6 Up to 6
Degree of protection Acc. to IEC 60947-1
IP20
Touch protection Acc. to EN 50274
Finger-safe
Phase failure sensitivity of the motor starter protector
Acc. to IEC 60947-1, EN 60947-1
Yes
Isolating features of the motor starter protector
Acc. to IEC 60947-2, EN 60947-2
Yes
Main control and EMER­GENCY-STOP switch charac­teristics of the motor starter protector and accessories
Acc. to IEC 60204-1, EN 60204-1
Yes (with overvoltage releases of category "1" under conditions of proper use)
Protective separation between main and auxiliary circuits
Acc. to EN 60947-1, Appendix N
V
Up to 400
Mirror contacts for contactors
Yes Yes, from main contact to auxiliary
NC contact
© Siemens AG 2011
Combination Starters & Starters for Group Installation
SIRIUS 3RA2 Motor Starters
General data
6/12
SIRIUS Innovations Supplement 2011
6
1)
If two different conductor cross-sections are connected to one clamping point, both cross-sections must lie in the range specified. If identical cross­sections are used, this restriction does not apply.
Type SIRIUS 3RA2 Motor Starters
Connection type
Screw terminals Spring-type terminals
Conductor cross-sections for main conductors Size S00
Motor starter protectors, contactors Motor starter protectors, contactors
Terminal screw
M3, Pozidriv size 2 --
Operating devices mm
! 5 ... 6 3.0 x 0.5 and 3.5 x 0.5
Prescribed tightening torque Nm
0.8 ... 1.2 --
Conductor cross-sections (min./max.),
1 or 2 conductors can be connected
• Solid and stranded mm22 x (0.5 … 1.5)1) only for contactors,
mm22 x (0.75 ... 2.5)1), 2 x (0.5 ... 4) mm
2
max. 2 x 4
• Finely stranded without end sleeve mm2-- 2 x (0.5 ... 2.5)
• Finely stranded with end sleeves (DIN 46 228 T1) mm22 x (0.5 ... 1.5)1). 2 x (0.5 ... 2.5)
mm
2
2 x (0.75 ... 2.5)1)
• AWG cables, solid or stranded AWG 2 x (20 … 16)1) only for contactors,
AWG 2 x (18 ... 14)1), 2 x (20 ... 12) AWG
2 x 12
Max. external diameter of the conductor insulation mm -- 3.6
Conductor cross-sections for main conductors Size S0
Motor starter protectors, contactors Motor starter protectors, contactors
Terminal screw
M4, Pozidriv size 2 --
Operating devices mm
! 5 ... 6 3.0 x 0.5 and 3.5 x 0.5
Prescribed tightening torque Nm
2.0 ... 2.5 --
Conductor cross-sections (min./max.),
1 or 2 conductors can be connected
• Solid and stranded mm22 x (1.0 ... 2.5)1), 2 x (1.0 ... 10)
mm
2
2 x (2.5 ... 10)1)
• Finely stranded without end sleeve mm2-- 2 x (1.0 ... 6.0)
• Finely stranded with end sleeves (DIN 46 228 T1) mm22 x (1.0 ... 2.5)1), 2 x (1.0 ... 6.0)
mm
2
2 x (2.5 ... 6)1)
mm2max. 1 x 10
• AWG cables, solid or stranded AWG 2 x (16 ... 12)1), 2 x (18 ... 8)
AWG
2 x (14 ... 8)1)
Max. external diameter of the conductor insulation mm -- 3.6
Conductor cross-sections for auxiliary conductors, Size S00/S0
Contactors (basic unit), motor starter protectors (accessories), contactors (mountable accessories), overload relays
Contactors S00 Contactors S0,
motor starter protec­tors (accessories), contactors (accessories), overload relays
Terminal screw
M3, Pozidriv size 2 --
Operating devices mm
! 5 ... 6 3.0 x 0.5 and 3.5 x 0.5
Prescribed tightening torque Nm
0.8 ... 1.2 --
Conductor cross-sections (min./max.),
1 or 2 conductors can be connected
• Solid and stranded mm22 x (0.5 ... 1.5)1), 2 x (0.5 ... 4) 2 x (0.5 ... 2.5)
mm
2
2 x (0.75 ... 2.5)1),
mm2max. 2 x 4 only for contactors S00
• Finely stranded without end sleeve mm2-- 2 x (0.5 ... 2.5) 2 x (0.5 ... 1.5)
• Finely stranded with end sleeve mm22 x (0.5 ... 1.5)1), 2 x (0.5 ... 2.5) 2 x (0.5 ... 1.5)
mm
2
2 x (0.75 ... 2.5)1)
• AWG cables, solid or stranded AWG 2 x (20 ... 16)1), 2 x (20 ... 12) 2 x (20 ... 14)
AWG
2 x (18 ... 14)1),
AWG 2 x 12 only for contactors S00
Max. external diameter of the conductor insulation mm -- 3.6 3.6
© Siemens AG 2011
Combination Starters & Starters for Group Installation
SIRIUS 3RA2 Motor Starters
3RA21 direct-on-line starters
50/60 Hz 110/120 V AC
6/13
SIRIUS Innovations Supplement 2011
Illustrations are approximate
6
Selection and ordering data
Rated control supply voltage 50/60 Hz 110/120 V AC With screw connections
• The motor starter protector and contactor are mechanically and electrically connected by means of the link module.
• Auxiliary switches
1)
on the motor starter protector and the con-
tactor can be easily fitted due to the modular system.
• Integrated auxiliary switches:
- Contactor size S00: 1 NO;
- Contactor size S0: 1 NO + 1 NC
Combination Starter, UL508 Type F
All size S00 and S0 devices can be applied as Combination Starters with the addition of either of these line side connectors: 3RV29 28-1H, 3RV29 25-5EB or 3RV29 28-1K.
1)
For auxiliary switches see Accessories page 6/21.
2)
Selection depends on the motor full load amps. HP ratings for reference only.
3)
Used only for mounting starter on 8US Fast Bus busbar systems.
3RA21 10
3RA21 20 3RA21 10 3RA21 20
Direct-on-line starting
Size UL Data FLA setting
range inverse­time delayed overload release
Consisting of the following single devices
Assembled starter Weight
approx.
Single-phase HP ratings
Three-phase2) HP ratings
SCCR at 480 V
Motor starter protector
+ Contactor + Link
module + Busbar adapter
3)
Screw terminals
115 V 230 V 200 V 230 V 460 V 575 V Order No.
kA A kg
Selection depends on motor full load amps
3RV20 3RT20 3RA
S00 -- -- -- -- -- -- 65 0.14…0.2 11-0BA10 15-1AK61 1921-1DA00
+ 8US1251­5DS10
3RA21 10-0B@15-1AK6 0.575
-- -- -- -- -- -- 65 0.18…0.25 11-0CA10
3RA21 10-0C@15-1AK6 0.575
-- -- -- -- -- -- 65 0.22…0.32 11-0DA10
3RA21 10-0D@15-1AK6 0.575
-- -- -- -- -- -- 65 0.28…0.4 11-0EA10
3RA21 10-0E@15-1AK6 0.575
-- -- -- -- -- -- 65 0.35…0.5 11-0FA10
3RA21 10-0F@15-1AK6 0.575
-- -- -- -- -- -- 65 0.45…0.63 11-0GA10
3RA21 10-0G@15-1AK6 0.575
-- -- -- -- -- -- 65 0.55…0.8 11-0HA10
3RA21 10-0H@15-1AK6 0.575
-- -- -- -- -- 1/2 65 0.7… 1 11-0JA10
3RA21 10-0J@15-1AK6 0.575
-- -- -- -- 1/2 1/2 65 0.9… 1.25 11-0KA10
3RA21 10-0K@15-1AK6 0.575
-- 1/10 -- -- 3/4 3/4 65 1.1… 1.6 11-1AA10
3RA21 10-1A@15-1AK6 0.575
-- 1/8 -- -- 3/4 1 65 1.4… 2 11-1BA10
3RA21 10-1B@15-1AK6 0.575
-- 1/6 1/2 1/2 1 1 1/2 65 1.8… 2.5 11-1CA10
3RA21 10-1C@15-1AK6 0.575
1/10 1/4 1/2 3/4 1 1/2 2 65 2.2… 3.2 11-1DA10
3RA21 10-1D@15-1AK6 0.575
1/8 1/3 3/4 3/4 2 3 65 2.8… 4 11-1EA10
3RA21 10-1E@15-1AK6 0.575
1/6 1/2 1 1 3 3 65 3.5… 5 11-1FA10
3RA21 10-1F@15-1AK6 0.575
1/4 1/2 1 1 1/2 3 5 65 4.5… 6.3 11-1GA10
3RA21 10-1G@15-1AK6 0.575
1/3 1 2 2 5 5 65 5.5… 8 11-1HA10 16-1AK61
3RA21 10-1H@16-1AK6 0.575
1/2 1 1/2 2 3 5 7 1/2 65 7… 10 11-1JA10
3RA21 10-1J@16-1AK6 0.575
1/2 2 3 3 7 1/2 10 65 9… 12 11-1KA10 17-1AK61
3RA21 10-1K@17-1AK6 0.575
1 2 3 5 10 -- 65 11… 16 11-4AA10 18-1AK61
3RA21 10-4A@18-1AK6 0.575
S0 1/6 1/2 1 1 3 3 65 3.5… 5 11-1FA10 24-1AK60 2921-1AA00
+ 8US1251­5NT10
3RA21 20-1F@24-0AK6 0.761
1/4 1/2 1 1 1/2 3 5 65 4.5… 6.3 11-1GA10
3RA21 20-1G@24-0AK6 0.761
1/3 1 2 2 5 5 65 5.5… 8 11-1HA10
3RA21 20-1H@24-0AK6 0.761
1/2 1 1/2 2 3 5 7 1/2 65 7… 10 11-1JA10
3RA21 20-1J@24-0AK6 0.761
1/2 2 3 3 7 1/2 10 65 9… 12.5 11-1KA10
3RA21 20-1K@24-0AK6 0.761
1 2 3 5 10 -- 65 11… 16 21-4AA10 26-1AK60
3RA21 20-4A@26-0AK6 0.761
1 1/2 3 5 5 10 -- 65 14… 20 21-4BA10
3RA21 20-4B@26-0AK6 0.761
1 1/2 3 5 7 1/2 15 -- 50 17… 22 21-4CA10 27-1AK60
3RA21 20-4C@27-0AK6 0.761
2 3 5 7 1/2 15 -- 50 20… 25 21-4DA10
3RA21 20-4D@27-0AK6 0.761
2 5 7 1/2 10 20 -- 50 27… 32 21-4EA10
3RA21 20-4E@27-0AK6 0.761
Add. weight
Order No. supplement for mounting onto standard mounting rail or screw fixing A
Screw fixing with 1 push-in lug each per motor starter is possible
(see "Accessories for Direct-On-Line and Reversing Starters").
Order No. supplement for mounting onto 60 mm busbar for size S00 1 D 0.263 With busbar adapter for size S0 2 D 0.295
© Siemens AG 2011
Combination Starters & Starters for Group Installation
SIRIUS 3RA2 Motor Starters
3RA21 direct-on-line starters 50/60 Hz 110/120 V AC
6/14
SIRIUS Innovations Supplement 2011
Illustrations are approximate
6
Rated control supply voltage 50/60 Hz 110/120 V AC With spring-type connection
• These starters can be assembled in the field without tools by simply snapping the components together. Follow the simple component selection system to form a starter.
• Auxiliary switches
1)
on the motor starter protector and the con-
tactor can be easily fitted due to the modular system.
• Integrated auxiliary switches:
- Contactor size S00: 1 NO;
- Contactor size S0: 1 NO + 1 NC
Combination Starter, UL508 Type F
All size S00 and S0 devices can be applied as Combination Starters with the addition of either of these line side connectors: 3RV29 28-1H, 3RV29 25-5EB or 3RV29 28-1K.
1)
For auxiliary switches see Accessories page 6/21.
2)
Selection depends on motor full load amps. HP ratings for reference only.
3)
Use only for mounting starter on 8US Fast Bus busbar systems.
4)
Mounting on standard mounting rails with adapter (3RA29 22-1AA00) is possible for feeder-orientated assembly, in which case the contactor must be screwed onto the adapter.
5)
For the AC version size S0 with spring loaded terminals, a 3RA29 11­1CA00 spacer is required for height compensation of the contactor.
3RA21 10
3RA21 20 3RA21 10 3RA21 20
Direct-on-line starting
Size UL Data FLA setting
range inverse­time delayed overload release
Consisting of the following single devices Not available
pre-assembled
Weight
approx.
Single-phase HP ratings
Three-phase2) HP ratings
SCCR at 480 V
Motor starter protector
+ Contactor + Link module + Busbar
adapter
3)
Spring-type terminals
115 V 230 V 200 V 230 V 460 V 575 V Order No.
kA A kg
Selection depends on motor full load amps
3RV20 3RT20 3RA 8US12
S00 -- -- -- -- -- -- 65 0.14…0.2 11-0BA20 15-2AK61 2911-2AA00 51-5DT11 0.641
-- -- -- -- -- -- 65 0.18…0.25 11-0CA20 0.641
-- -- -- -- -- -- 65 0.22…0.32 11-0DA20 0.641
-- -- -- -- -- -- 65 0.28…0.4 11-0EA20 0.641
-- -- -- -- -- -- 65 0.35…0.5 11-0FA20 0.641
-- -- -- -- -- -- 65 0.45…0.63 11-0GA20 0.641
-- -- -- -- -- -- 65 0.55…0.8 11-0HA20 0.641
-- -- -- -- -- 1/2 65 0.7… 1 11-0JA20 0.641
-- -- -- -- 1/2 1/2 65 0.9… 1.25 11-0KA20 0.641
-- 1/10 -- -- 3/4 3/4 65 1.1… 1.6 11-1AA20 0.641
-- 1/8 -- -- 3/4 1 65 1.4… 2 11-1BA20 0.641
-- 1/6 1/2 1/2 1 1 1/2 65 1.8… 2.5 11-1CA20 0.641 1/10 1/4 1/2 3/4 1 1/2 2 65 2.2… 3.2 11-1DA20 0.641 1/8 1/3 3/4 3/4 2 3 65 2.8… 4 11-1EA20 0.641 1/6 1/2 1 1 3 3 65 3.5… 5 11-1FA20 0.641
1/4 1/2 1 1 1/2 3 5 65 4.5… 6.3 11-1GA20 0.641 1/3 1 2 2 5 5 65 5.5… 8 11-1HA20 16-2AK61 0.641 1/2 1 1/2 2 3 5 7 1/2 65 7… 10 11-1JA20 0.641 1/2 2 3 3 7 1/2 10 65 9… 12 11-1KA20 17-1AK61 0.641 1 2 3 5 10 -- 65 11… 16 11-4AA20 18-2AK61 0.641
S0 1/6 1/2 1 1 3 3 65 3.5… 5 11-1FA20 24-2AK60 2921-2AA00
4)
+2911-1CA00
5)
51-5NT11 0.925 1/4 1/2 1 1 1/2 3 5 65 4.5… 6.3 11-1GA20 0.925 1/3 1 2 2 5 5 65 5.5… 8 11-1HA20 0.925 1/2 1 1/2 2 3 5 7 1/2 65 7… 10 11-1JA20 0.925 1/2 2 3 3 7 1/2 10 65 9… 12.5 11-1KA20 0.925
1 2 3 5 10 -- 65 11… 16 21-4AA20 26-2AK60 0.925 1 1/2 3 5 5 10 -- 65 14… 20 21-4BA20 0.925 1 1/2 3 5 7 1/2 15 -- 50 17… 22 21-4CA20 27-2AK60 0.925 2 3 5 7 1/2 15 -- 50 20… 25 21-4DA20 0.925 2 5 7 1/2 10 20 -- 50 27… 32 21-4EA20 0.925
Screw fixing with 1 push-in lug each per motor starter is possible
(see "Accessories for Direct-On-Line and Reversing Starters").
© Siemens AG 2011
Combination Starters & Starters for Group Installation
SIRIUS 3RA2 Motor Starters
3RA21 direct-on-line starters
24 V DC
6/15
SIRIUS Innovations Supplement 2011
Illustrations are approximate
6
Rated control supply voltage 24 V DC With screw connections
• The motor starter protector and contactor are mechanically and electrically connected by means of the link module.
• Auxiliary switches
1)
on the motor starter protector and the con-
tactor can be easily fitted due to the modular system.
• Integrated auxiliary switches:
- Contactor size S00: 1 NO;
- Contactor size S0: 1 NO + 1 NC
Combination Starter, UL508 Type F
All size S00 and S0 devices can be applied as Combination Starters with the addition of either of these line side connectors: 3RV29 28-1H, 3RV29 25-5EB or 3RV29 28-1K.
1)
For auxiliary switches see Accessories page 6/21.
2)
Selection depends on the concrete motor full load amps. HP ratings for reference only.
3)
Use only for mounting starter on 8US Fast Bus busbar systems.
3RA21 10
3RA21 20 3RA21 10 3RA21 20
Direct-on-line starting
Size UL Data FLA setting
range inverse­time delayed overload release
Consisting of the following single devices
Assembled starter Weight
approx.
Single-phase HP ratings
Three-phase2) HP ratings
SCCR at 480 V
Motor starter protector
+ Contactor + Link
module + Busbar adapter
3)
Screw terminals
115 V 230 V 200 V 230 V 460 V 575 V Order No.
kA A kg
Selection depends on motor full load amps
3RV20 3RT20 3RA
S00 -- -- -- -- -- -- 65 0.14…0.2 11-0BA10 15-1BB41 1921-1DA00
+ 8US1251­5DS10
3RA21 10-0B@15-1BB4 0.630
-- -- -- -- -- -- 65 0.18…0.25 11-0CA10
3RA21 10-0C@15-1BB4 0.630
-- -- -- -- -- -- 65 0.22…0.32 11-0DA10
3RA21 10-0D@15-1BB4 0.630
-- -- -- -- -- -- 65 0.28…0.4 11-0EA10
3RA21 10-0E@15-1BB4 0.630
-- -- -- -- -- -- 65 0.35…0.5 11-0FA10
3RA21 10-0F@15-1BB4 0.630
-- -- -- -- -- -- 65 0.45…0.63 11-0GA10
3RA21 10-0G@15-1BB4 0.630
-- -- -- -- -- -- 65 0.55…0.8 11-0HA10
3RA21 10-0H@15-1BB4 0.630
-- -- -- -- -- 1/2 65 0.7… 1 11-0JA10
3RA21 10-0J@15-1BB4 0.630
-- -- -- -- 1/2 1/2 65 0.9… 1.25 11-0KA10
3RA21 10-0K@15-1BB4 0.630
-- 1/10 -- -- 3/4 3/4 65 1.1… 1.6 11-1AA10
3RA21 10-1A@15-1BB4 0.630
-- 1/8 -- -- 3/4 1 65
1.4… 2
11-1BA10
3RA21 10-1B@15-1BB4 0.630
-- 1/6 1/2 1/2 1 1 1/2 65 1.8… 2.5 11-1CA10
3RA21 10-1C@15-1BB4 0.630
1/10 1/4 1/2 3/4 1 1/2 2 65 2.2… 3.2 11-1DA10
3RA21 10-1D@15-1BB4 0.630
1/8 1/3 3/4 3/4 2 3 65 2.8… 4 11-1EA10
3RA21 10-1E@15-1BB4 0.630
1/6 1/2 1 1 3 3 65 3.5… 5 11-1FA10
3RA21 10-1F@15-1BB4 0.630
1/4 1/2 1 1 1/2 3 5 65 4.5… 6.3 11-1GA10
3RA21 10-1G@15-1BB4 0.630 1/3 1 2 2 5 5 65 5.5… 8 11-1HA10 16-1BB41 3RA21 10-1H@16-1BB4 0.630 1/2 1 1/2 2 3 5 7 1/2 65 7… 10 11-1JA10
3RA21 10-1J@16-1BB4 0.630 1/2 2 3 3 7 1/2 10 65 9… 12 11-1KA10 17-1BB41
3RA21 10-1K@17-1BB4 0.630 1 2 3 5 10 -- 65 11… 16 11-4AA10 18-1BB41
3RA21 10-4A@18-1BB4 0.630
S0 1/6 1/2 1 1 3 3 65 3.5… 5 11-1FA10 24-1BB40 2921-1BA00
+ 8US1251­5NT10
3RA21 20-1F@24-0BB4 0.948 1/4 1/2 1 1 1/2 3 5 65 4.5… 6.3 11-1GA10
3RA21 20-1G@24-0BB4 0.948 1/3 1 2 2 5 5 65 5.5… 8 11-1HA10
3RA21 20-1H@24-0BB4 0.948 1/2 1 1/2 2 3 5 7 1/2 65 7… 10 11-1JA10
3RA21 20-1J@24-0BB4 0.948 1/2 2 3 3 7 1/2 10 65 9… 12.5 11-1KA10
3RA21 20-1K@24-0BB4 0.948 1 2 3 5 10 -- 65 11… 16 21-4AA10 26-1BB40
3RA21 20-4A@26-0BB4 0.948 1 1/2 3 5 5 10 -- 65 14… 20 21-4BA10
3RA21 20-4B@26-0BB4 0.948 1 1/2 3 5 7 1/2 15 -- 50 17… 22 21-4CA10 27-1BB40
3RA21 20-4C@27-0BB4 0.948 2 3 5 7 1/2 15 -- 50 20… 25 21-4DA10
3RA21 20-4D@27-0BB4 0.948 2 5 7 1/2 10 20 -- 50 27… 32 21-4EA10
3RA21 20-4E@27-0BB4 0.948
Add. weight
Order No. supplement for mounting onto standard mounting rail or screw fixing A
Screw fixing with 1 push-in lug each per motor starter is possible
(see "Accessories for Direct-On-Line and Reversing Starters").
Order No. supplement for mounting onto 60 mm busbar for size S00 1 D 0.263 With busbar adapter for size S0 2 D 0.301
© Siemens AG 2011
Combination Starters & Starters for Group Installation
SIRIUS 3RA2 Motor Starters
3RA21 direct-on-line starters 24 V DC
6/16
SIRIUS Innovations Supplement 2011
Illustrations are approximate
6
Rated control supply voltage 24 V DC With spring-type connection
• These starters can be assembled in the field without tools by simply snapping the components together. Follow the simple component selection system to form a starter.
• Auxiliary switches
1)
on the motor starter protector and the con-
tactor can be easily fitted due to the modular system.
• Integrated auxiliary switches:
- Contactor size S00: 1 NO;
- Contactor size S0: 1 NO + 1 NC
Combination Starter, UL508 Type F
All size S00 and S0 devices can be applied as Combination Starters with the addition of either of these line side connectors: 3RV29 28-1H, 3RV29 25-5EB or 3RV29 28-1K.
1)
For auxiliary switches see Accessories page 6/21.
2)
Selection depends on the motor full load amps. HP ratings for reference only.
3)
Used only for mounting starter on 8US Fast Bus busbar systems.
4)
Mounting on standard mounting rails or with screws (3RA29 22-1AA00) is possible for feeder-orientated assembly, in which case the contactor must be screwed onto the adapter.
3RA21 10
3RA21 20 3RA21 10 3RA21 20
Direct-on-line starting
Size UL Data FLA setting
range inverse­time delayed overload release
Consisting of the following single devices Not available
pre-assembled
Weight
approx.
Single-phase HP ratings
Three-phase2) HP ratings
SCCR at 480 V
Motor starter protector
+ Contactor + Link module + Busbar
adapter
3)
Spring-type terminals
115 V 230 V 200 V 230 V 460 V 575 V Order No.
kA A kg
Selection depends on motor full load amps
3RV20 3RT20 3RA 8US12
S00 -- -- -- -- -- -- 65 0.14…0.2 11-0BA20 15-2BB41 2911-2AA00 51-5DT11 0.641
-- -- -- -- -- -- 65 0.18…0.25 11-0CA20 0.641
-- -- -- -- -- -- 65 0.22…0.32 11-0DA20 0.641
-- -- -- -- -- -- 65 0.28…0.4 11-0EA20 0.641
-- -- -- -- -- -- 65 0.35…0.5 11-0FA20 0.641
-- -- -- -- -- -- 65 0.45…0.63 11-0GA20 0.641
-- -- -- -- -- -- 65 0.55…0.8 11-0HA20 0.641
-- -- -- -- -- 1/2 65 0.7… 1 11-0JA20 0.641
-- -- -- -- 1/2 1/2 65 0.9… 1.25 11-0KA20 0.641
-- 1/10 -- -- 3/4 3/4 65 1.1… 1.6 11-1AA20 0.641
-- 1/8 -- -- 3/4 1 65 1.4… 2 11-1BA20 0.641
-- 1/6 1/2 1/2 1 1 1/2 65 1.8… 2.5 11-1CA20 0.641 1/10 1/4 1/2 3/4 1 1/2 2 65 2.2… 3.2 11-1DA20 0.641 1/8 1/3 3/4 3/4 2 3 65 2.8… 4 11-1EA20 0.641 1/6 1/2 1 1 3 3 65 3.5… 5 11-1FA20 0.641
1/4 1/2 1 1 1/2 3 5 65 4.5… 6.3 11-1GA20 0.641 1/3 1 2 2 5 5 65 5.5… 8 11-1HA20 16-2BB41 0.641 1/2 1 1/2 2 3 5 7 1/2 65 7… 10 11-1JA20 0.641 1/2 2 3 3 7 1/2 10 65 9… 12 11-1KA20 17-2BB41 0.641 1 2 3 5 10 -- 65 11… 16 11-4AA20 18-2BB41 0.641
S0 1/6 1/2 1 1 3 3 65 3.5… 5 11-1FA20 24-2BB40 2921-2AA00 51-5NT11 0.925
1/4 1/2 1 1 1/2 3 5 65 4.5… 6.3 11-1GA20 0.925 1/3 1 2 2 5 5 65 5.5… 8 11-1HA20 0.925 1/2 1 1/2 2 3 5 7 1/2 65 7… 10 11-1JA20 0.925 1/2 2 3 3 7 1/2 10 65 9… 12.5 11-1KA20 0.925
1 2 3 5 10 -- 65 11… 16 21-4AA20 26-2BB40 0.925 1 1/2 3 5 5 10 -- 65 14… 20 21-4BA20 0.925 1 1/2 3 5 7 1/2 15 -- 50 17… 22 21-4CA20 27-2BB40 0.925 2 3 5 7 1/2 15 -- 50 20… 25 21-4DA20 0.925 2 5 7 1/2 10 20 -- 50 27… 32 21-4EA20 0.925
Screw fixing with 1 push-in lug each per motor starter is possible.
© Siemens AG 2011
Combination Starters & Starters for Group Installation
SIRIUS 3RA2 Motor Starters
3RA22 reversing starters
50/60 Hz 110/120 V AC
6/17
SIRIUS Innovations Supplement 2011
Illustrations are approximate
6
Selection and ordering data
1)
For push-in lugs and auxiliary switches see Accessories.
2)
Selection depends on the motor full load amps. HP ratings for reference only.
3)
According to ordering option: RH = assembly kit for reversing duty with standard rail mounting adapter in size S0. RS = assembly kit for reversing duty with 8US Fast Bus busbar mounting.
4)
With standard rail mounting or screw fixing, the 3RA29 13-2AA1 wiring kit is required for size S00.
3RA22 10 3RA22 20 3RA22 10 3RA22 20
Reversing duty
Rated control supply voltage 50/60 Hz 110/120 V AC With screw connections
• The motor starter protector and contactor are mechan­ically and electrically connected by means of the link module.
• Auxiliary switches
1)
on the motor starter protector and the contactor can be easily fitted due to the modular system.
• With the contactor S0, an integrated NO contact is available for free use.
Combination Starter, UL508 Type F
All size S00 and S0 devices can be applied as Combina­tion Starters with the addition of either of these line side connectors: 3RV29 28-1H, 3RV29 25-5EB or 3RV29 28-1K.
Size UL Data FLA setting
range inverse­time delayed overload release
Consisting of the following single devices Assembled starter Weight
approx.
Single-phase HP ratings
Three-phase2) HP ratings
SCCR at 480 V
Motor starter protector
+ 2 contac­tors
+ Link module + Assembly kit RH/RS
3)
Screw terminals
115 V 230 V 200 V 230 V 460 V 575 V Order No.
kA A kg
Selection depends on motor full load amps
3RV20 3RT20 3RA
S00 -- -- -- -- -- -- 65 0.14…0.2 11-0BA10 15-1AK62 1921-1DA00
+ 2913-2AA1
4)
+ 2913-1DB1 (RS)
3RA22 10-0B@15-2AK6 0.824
-- -- -- -- -- -- 65 0.18…0.25 11-0CA10
3RA22 10-0C@15-2AK6 0.824
-- -- -- -- -- -- 65 0.22…0.32 11-0DA10
3RA22 10-0D@15-2AK6 0.824
-- -- -- -- -- -- 65 0.28…0.4 11-0EA10
3RA22 10-0E@15-2AK6 0.824
-- -- -- -- -- -- 65 0.35…0.5 11-0FA10
3RA22 10-0F@15-2AK6 0.824
-- -- -- -- -- -- 65 0.45…0.63 11-0GA10
3RA22 10-0G@15-2AK6 0.824
-- -- -- -- -- -- 65 0.55…0.8 11-0HA10
3RA22 10-0H@15-2AK6 0.824
-- -- -- -- -- 1/2 65 0.7… 1 11-0JA10
3RA22 10-0J@15-2AK6 0.824
-- -- -- -- 1/2 1/2 65 0.9… 1.25 11-0KA10
3RA22 10-0K@15-2AK6 0.824
-- 1/10 -- -- 3/4 3/4 65 1.1… 1.6 11-1AA10
3RA22 10-1A@15-2AK6 0.824
-- 1/8 -- -- 3/4 1 65 1.4… 2 11-1BA10
3RA22 10-1B@15-2AK6 0.824
-- 1/6 1/2 1/2 1 1 1/2 65 1.8… 2.5 11-1CA10
3RA22 10-1C@15-2AK6 0.824
1/10 1/4 1/2 3/4 1 1/2 2 65 2.2… 3.2 11-1DA10
3RA22 10-1D@15-2AK6 0.824
1/8 1/3 3/4 3/4 2 3 65 2.8… 4 11-1EA10
3RA22 10-1E@15-2AK6 0.824
1/6 1/2 1 1 3 3 65 3.5… 5 11-1FA10
3RA22 10-1F@15-2AK6 0.824
1/4 1/2 1 1 1/2 3 5 65 4.5… 6.3 11-1GA10
3RA22 10-1G@15-2AK6 0.824 1/3 1 2 2 5 5 65 5.5… 8 11-1HA10 16-1AK62 3RA22 10-1H@16-2AK6 0.824 1/2 1 1/2 2 3 5 7 1/2 65 7… 10 11-1JA10
3RA22 10-1J@16-2AK6 0.824 1/2 2 3 3 7 1/2 10 65 9… 12 11-1KA10 17-1AK62
3RA22 10-1K@17-2AK6 0.824 1 2 3 5 10 -- 65 11… 16 11-4AA10 18-1AK62
3RA22 10-4A@18-2AK6 0.824
S0 1/6 1/2 1 1 3 3 65 3.5… 5 11-1FA10 24-1AK60 2921-1AA00
+ 2923-1BB1 (RH) + 2923-1DB1 (RS)
3RA22 20-1F@24-0AK6 1.434 1/4 1/2 1 1 1/2 3 5 65 4.5… 6.3 11-1GA10
3RA22 20-1G@24-0AK6 1.434 1/3 1 2 2 5 5 65 5.5… 8 11-1HA10
3RA22 20-1H@24-0AK6 1.434 1/2 1 1/2 2 3 5 7 1/2 65 7… 10 11-1JA10
3RA22 20-1J@24-0AK6 1.434 1/2 2 3 3 7 1/2 10 65 9… 12.5 11-1KA10
3RA22 20-1K@24-0AK6 1.434 1 2 3 5 10 -- 65 11… 16 21-4AA10 26-1AK60
3RA22 20-4A@26-0AK6 1.434 1 1/2 3 5 5 10 -- 65 14… 20 21-4BA10
3RA22 20-4B@26-0AK6 1.434 1 1/2 3 5 7 1/2 15 -- 50 17… 22 21-4CA10 27-1AK60
3RA22 20-4C@27-0AK6 1.434 2 3 5 7 1/2 15 -- 50 20… 25 21-4DA10
3RA22 20-4D@27-0AK6 1.434 2 5 7 1/2 10 20 -- 50 27… 32 21-4EA10 3RA22 20-4E@27-0AK6 1.434
Add. weight
Order No. supplement for mounting onto standard mounting rail or screw fixing
• Without standard mounting rail adapter for size S00
4)
1 A
• With 2 standard mounting rail adapters for size S0 2 B Screw fixing with 2 push-in lugs each per motor starter is possible
Order No. supplement for mounting onto 60 mm busbar for size S00 1 D 0.486 With 8US Fast Bus busbar adapter for size S0 2 D 0.293
© Siemens AG 2011
Combination Starters & Starters for Group Installation
SIRIUS 3RA2 Motor Starters
3RA22 reversing starters 50/60 Hz 110/120 V AC
6/18
SIRIUS Innovations Supplement 2011
Illustrations are approximate
6
1)
For push-in lugs and auxiliary switches see Accessories.
2)
Selection depends on the motor full load amps. HP ratings for reference only.
3)
Code for abbreviations: RH = assembly kit for reversing duty and standard rail mounting adapter in size S0. RS = assembly kit for reversing duty and busbar mounting.
4)
With standard rail mounting or screw fixing, the 3RA29 13-2AA2 wiring kit and link module are required for size S00.
5)
The RH/RS assembly kits also include 3RA29 11-1CA00 spacer for height compensation on AC contactors size S0 with spring-type terminals.
3RA22 10 3RA22 20 3RA22 10 3RA22 20
Reversing duty
Rated control supply voltage 50/60 Hz 110/120 V AC With spring-type connection
• These starters can be assembled in the field without tools by simply snapping the components together. Follow the simple component selection system to form a starter.
• Auxiliary switches
1)
on the motor starter protector and the contactor can be easily fitted due to the modular system.
• With the contactor S0, an integrated NO contact is available for free use.
Combination Starter, UL508 Type F
All size S00 and S0 devices can be applied as Combina­tion Starters with the addition of either of these line side connectors: 3RV29 28-1H, 3RV29 25-5EB or 3RV29 28-1K.
Size UL Data FLA set-
ting range inverse­time delayed overload release
Consisting of the following single devices Not available
pre-assembled
Weight
approx.
Single-phase HP ratings
Three-phase2) HP ratings
SCCR at 480 V
Motor starter protector
+ 2 contac­tors
Standard rail or screw mounting + Link module + Assembly kit (RH)
3)
8US Busbar mounting system + Link module + Assembly kit (RS)
3)
Spring-type terminals
115 V 230 V 200 V 230 V 460 V 575 V Order No.
kA A kg
Selection depends on motor full load amps
3RV20 3RT20 3RA 3RA
S00 -- -- -- -- -- -- 65 0.14…0.2 11-0BA20 15-2AK62 2911-2AA00
+ 2913-2AA2
4)
2911-2AA00 + 2913-1DB2
5)
0.641
-- -- -- -- -- -- 65 0.18…0.25 11-0CA20 0.641
-- -- -- -- -- -- 65 0.22…0.32 11-0DA20 0.641
-- -- -- -- -- -- 65 0.28…0.4 11-0EA20 0.641
-- -- -- -- -- -- 65 0.35…0.5 11-0FA20 0.641
-- -- -- -- -- -- 65 0.45…0.63 11-0GA20 0.641
-- -- -- -- -- -- 65 0.55…0.8 11-0HA20 0.641
-- -- -- -- -- 1/2 65 0.7… 1 11-0JA20 0.641
-- -- -- -- 1/2 1/2 65 0.9… 1.25 11-0KA20 0.641
-- 1/10 -- -- 3/4 3/4 65 1.1… 1.6 11-1AA20 0.641
-- 1/8 -- -- 3/4 1 65 1.4… 2 11-1BA20 0.641
-- 1/6 1/2 1/2 1 1 1/2 65 1.8… 2.5 11-1CA20 0.641 1/10 1/4 1/2 3/4 1 1/2 2 65 2.2… 3.2 11-1DA20 0.641 1/8 1/3 3/4 3/4 2 3 65 2.8… 4 11-1EA20 0.641 1/6 1/2 1 1 3 3 65 3.5… 5 11-1FA20 0.641
1/4 1/2 1 1 1/2 3 5 65 4.5… 6.3 11-1GA20 0.641 1/3 1 2 2 5 5 65 5.5… 8 11-1HA20 16-2AK62 0.641 1/2 1 1/2 2 3 5 7 1/2 65 7… 10 11-1JA20 0.641 1/2 2 3 3 7 1/2 10 65 9… 12 11-1KA20 17-1AK62 0.641 1 2 3 5 10 -- 65 11… 16 11-4AA20 18-2AK62 0.641
S0 1/6 1/2 1 1 3 3 65 3.5… 5 11-1FA20 24-2AK60 2921-2AA00
+ 2923-1BB2
5)
2921-2AA00 + 2923-1DB2
5)
0.925 1/4 1/2 1 1 1/2 3 5 65 4.5… 6.3 11-1GA20 0.925 1/3 1 2 2 5 5 65 5.5… 8 11-1HA20 0.925 1/2 1 1/2 2 3 5 7 1/2 65 7… 10 11-1JA20 0.925 1/2 2 3 3 7 1/2 10 65 9… 12.5 11-1KA20 0.925
1 2 3 5 10 -- 65 11… 16 21-4AA20 26-2AK60 0.925 1 1/2 3 5 5 10 -- 65 14… 20 21-4BA20 0.925 1 1/2 3 5 7 1/2 15 -- 50 17… 22 21-4CA20 27-2AK60 0.925 2 3 5 7 1/2 15 -- 50 20… 25 21-4DA20 0.925 2 5 7 1/2 10 20 -- 50 27… 32 21-4EA20 0.925
Screw fixing with 2 push-in lugs each per motor starter is possible with RH configured starters.
(see "Accessories for Direct-On-Line and Reversing Starters").
© Siemens AG 2011