Siemens QMX3.P37, QMX3.P34, QMX3.P02, QMX3.P74, QMX3.P30 Technical Principles

...
Page 1
s Infrastructure & Cities
QMX3.P37 QMX3.P34 / P74 QMX3.P02 QMX3.P70 QMX3.P30
Technical principles
CM2N1602en_01
2013-07-04
Building Technologies
Page 2
2 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Contents 2013-07-04
Contents
1
About this document .............................................................................. 4
1.1 Revision history ......................................................................................... 4
1.2 Before you start ......................................................................................... 4
1.2.1 Trademarks ............................................................................................... 4
1.2.2 Copyright ................................................................................................... 4
1.2.3 Quality assurance ..................................................................................... 4
1.2.4 Use of documents/ Request to the reader ................................................ 4
1.3 Abbreviations and naming conventions .................................................... 5
1.3.1 Abbreviations ............................................................................................ 5
1.3.2 Naming convention ................................................................................... 5
1.4 Reference documents ............................................................................... 5
2 Devices ..................................................................................................... 6
2.1 Type summary ........................................................................................... 6
2.2 Equipment combinations ........................................................................... 6
2.3 Variant and device parts ............................................................................ 7
2.4 Service and connection elements ............................................................. 8
2.5 Dimensions................................................................................................ 9
2.6 Environmental compatibility, disposal ..................................................... 10
3 Safety and EMC optimization ............................................................... 10
3.1 Notes on safety ....................................................................................... 10
3.2 Device-specific regulations ..................................................................... 10
3.3 Notes on EMC optimization..................................................................... 11
4 Mounting and electrical installation .................................................... 12
5 Functionality / Use ................................................................................ 15
5.1 Basics ...................................................................................................... 15
5.1.1 System environment ............................................................................... 15
5.1.2 Engineering and commissioning documentation .................................... 15
5.2 Overview ................................................................................................. 16
5.3 Use .......................................................................................................... 17
5.4 Display elements and buttons ................................................................. 18
5.5 Functions ................................................................................................. 19
5.5.1 Measuring................................................................................................ 19
5.5.2 Control and operation .............................................................................. 20
5.6 Application examples .............................................................................. 23
5.6.1 Room temperature control and operation via QMX3 .............................. 23
5.6.2 Presence dependent room climate control with operation of all disciplines24
5.6.3 Room temperature, humidity and air quality control ............................... 25
Page 3
3 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Contents 2013-07-04
6
GAMMA building management system .............................................. 26
6.1 Engineering ............................................................................................. 26
6.2 Commissioning........................................................................................ 26
6.3 KNX S-Mode communication objects ..................................................... 27
6.4 KNX S-Mode Parameter description ....................................................... 31
6.4.1 Room temperature sensor ...................................................................... 31
6.4.2 Room temperature control ...................................................................... 31
6.4.3 Room relative humidity sensor ................................................................ 32
6.4.4 Room relative humidity control ................................................................ 32
6.4.5 Room air quality sensor .......................................................................... 33
6.4.6 Room air quality control .......................................................................... 33
6.4.7 Device display parameters ...................................................................... 33
6.4.8 HVAC operation and display ................................................................... 34
6.4.9 Operation and display: Relative humidity visualization ........................... 34
6.4.10 Display on QMX3.P70 Air quality indication LED .................................... 34
6.4.11 Operation and display: air quality............................................................ 34
6.4.12 Operation of light, shading and scenes .................................................. 35
6.5 Examples for the functionality of touch keys and display elements ........ 36
7 Synco building automation and control system ................................ 38
7.1 Engineering ............................................................................................. 38
7.2 Commissioning........................................................................................ 38
7.3 Parameter description ............................................................................. 40
7.3.1 Communication ....................................................................................... 40
7.3.2 Universal temperature sensor ................................................................. 40
7.3.3 Room humidity sensor ............................................................................ 40
7.3.4 Room air quality sensor .......................................................................... 40
Page 4
4/40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies About this document 2013-07-04
1 About this document
1.1 Revision history
Revision
Date
Changes
Section
Pages
_01
July 2013
First edition
1.2 Before you start
1.2.1 Trademarks
The trademarks used in this document and their lawful owners are listed in the table below.. The use of trademarks is subject to international and domestic provisions of the law.
Trademark(s)
Legal owner
KNX® KNX Association, B - 1831 Brussels-Diegem Belgium
http://www.knx.org/
All product names listed in the table are registered (®) or not registered (™) trademarks of the owner listed in the table. These trademarks will not be indicated elsewhere in the text (e.g. by use of symbols such as ® and ™) due to the reference in this Section and to facilitate the reading of the text,
1.2.2 Copyright
This document may be duplicated and distributed only with the express permission of Siemens, and may be passed only to authorized persons or companies with the required technical knowledge.
1.2.3 Quality assurance
These documents were prepared with great care.
• The contents of all documents are checked at regular intervals.
• All necessary corrections are included in subsequent versions.
• Documents are automatically amended as a consequence of modifications and
corrections to the products described.
Please make sure that you are aware of the latest document revision date.
If you find any lack of clarity while using this document, or if you have any criticisms or suggestions, please contact your local POC at the nearest branch office. Addresses for Siemens RCs are available at www.siemens.com/sbt
1.2.4 Use of documents/ Request to the reader
Before using our products, it is important that you read the documents supplied with or ordered at the same time as the products (equipment, applications, tools etc.) carefully and in full.
We assume that persons using our products and documents are authorized and trained appropriately and have the technical knowledge required to use our products as intended.
Page 5
5/40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies About this document 2013-07-04
For more details on the products and applications, please refer to:
• On the internet: "Technical product data and descriptions" at
www.siemens.com/gamma-td
• On the intranet (for Siemens employees only) at
http://step.bt.siemens.com/portal/index.html
• At your next Siemens branch office www.siemens.com/sbt
or at your system
suppliers.
• From the support team in the headquarters fieldsupport-
[email protected] if no local POC is available.
Siemens assumes no liability to the extent allowed under the law for any losses resulting from a failure to comply with the aforementioned points or for the improper compliance of the same.
1.3 Abbreviations and naming conventions
1.3.1 Abbreviations
Abbr.
Description
ACS790
Engineering Tool for Synco devices (KNX LTE-Mode)
ETS
Engineering Tool Software (KNX S-Mode) http://www.knx.org/
KNX LTE-Mode
Communication with KNX LTE-Mode (Logical Tag Extended Mode)
KNX S-Mode
Communication with KNX
1.3.2 Naming convention
The term "room operator unit" in this document always refers to all types: QMX3.P02. P30. P34, P70 und P74.
1.4 Reference documents
The following documents are available at http://www.siemens.com/bt/download
[1] Data sheet N1602 [2] Mounting instructions M1692 [3] Word template for labels (QMX3.P02, P37) M1602.1 [4] KNX bus (CE1N3127
)
[5] KNX Standard, Volume 3: System Specifications, Part 7, Chapter 2: Data
Point Types (http://www.knx.org/
)
[6] Service- and Operating software ACS790 (CE1N5649
)
Page 6
6 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Devices 2013-07-04
2 Devices
2.1 Type summary
Product number Stock number
Features
Temperature
sensor
Sensor for
humidity and CO
2
Air quality indicator
with LED
Segmented backlit
display and
touchkeys
Parameterizable
touchkeys with
LED display
Window for labels
Sensors
QMX3.P30
S55624-H103
X
QMX3.P70
S55624-H104
X X X
Room operator units
QMX3.P02
S55624-H107
X X X
QMX3.P34
S55624-H105
X X
QMX3.P74
S55624-H106
X X X
QMX3.P37
S55624-H108
X X X X
2.2 Equipment combinations
The room operator units are KNX certified and can be connected to all suitable KNX devices, if the appropriate communication objects are available in the application.
Use in the following BAC systems:
• GAMMA Building Management Systems / third-party devices (KNX S-Mode)
• Building automation and control systems with KNX S-mode
Integration of third-party devices and free configuration.
• Synco700 KNX LTE can only use the sensor information of types QMX3.P30 and QMX3.P70.
• Desigo TRA The devices can be used with all series room automation stations.
Page 7
7 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Devices 2013-07-04
2.3 Variant and device parts
2602J01
B
C
A
• The devices are designed for wall-mounting (A). A conduit box is optional. – Conduit box: Keep in mind the dimensions of the conduit box! – Cable conduits on the wall: Keep a distance of 30 mm (from above) /
20 mm (from below) to the base plate (B), so that the device (C) can be snapped onto the base plate.
• The base plate (B) has screw holes for all common flush-mount boxes. The screw head height must not exceed 3 mm.
• The device (C) incorporates a KNX plug, and, depending on the type, sensor element, keys, LCD panel, window for the label. The cable can be pushed into channels on the rear.
• A KNX plug is enclosed with the devices
Page 8
8 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Devices 2013-07-04
2.4 Service and connection elements
+
–
–
+
–
+
R1 QMX3... Room operator unit
N1 Controller, actor
= Twisted pair
Service LED (red)
Programming pin
The service element functions are described Commissioning, sections 6.2 and 7.2.
The devices are supplied with peel-off adhesive address labels containing the unique KNX ID as alphanumeric and barcode display.
KNX I D 00FD00086255 Hex
AQR2570NF
The address label can peeled off the device during mounting and stuck to a floor plan or similar. The floor plan thus contains the assignment of KNX IDs and physical installation location. This greatly simplifies the following steps. In addition, the procedure serves as the basis for the recommended engineering and commissioning process. If the adhesive labels are lost, all information is still available in printed form on the housing.
Connection
Service LED (red) and
programming pin
Adhesive address
labels
Simplifying engineerin
g
and commissioning
Page 9
9 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Devices 2013-07-04
2.5 Dimensions
133.4
115
88.4
18
1602M01
_
01
80.5
7
8
.
5
60
28.2
26.5
26
13.1
56.5
17.5
28.2
3.5
1602M02
Page 10
10 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Safety and EMC optimization 2013-07-04
2.6 Environmental compatibility, disposal
This device was developed and manufactured with environmentally compatible materials and procedures complying with all relevant environmental standards.
Note the following to dispose of the product following its useful life or in case of replacement:
• Do not dispose of the device as part of standard household garbage, but as special waste from plastic and steel, ferrite-magnet components. This applies in particular to the PCB.
• For this reason, dispose of the components compatible with current environmental, recycling, and disposal technologies.
Observe all local, applicable laws.
• The aim is to reuse as much of the basic materials as possible at the lowest possible environmental impact. To this end, note any material and disposal notes in individual components.
The product environmental declaration CM2E1602
contains data on
environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal)
3 Safety and EMC optimization
3.1 Notes on safety
This section explains general and system-specific regulations for mains and operating voltages. It includes important information for your safety and the safety of the entire plant.
Please comply with the following general regulations during engineering and execution:
• Electrical and mains power ordinances for the given country.
• Other applicable, national regulations.
• Building installation regulations for the given country.
• Regulations of the utility company.
• Diagrams, cable lists, dispositions, specifications, and orders by the customer or
authorized engineering office.
• Third-party regulations, e.g. by the general contractor or building owner.
The electrical safety for building automation and control systems by Siemens is essentially based on safely separating low voltage from mains voltage.
3.2 Device-specific regulations
Note permissible line lengths and topologies when planning and installing controllers and field devices featuring KNX bus connection. Make sure the bus supply complies with the KNX standard.
Do not open the device.
The device is maintenance free. Only the manufacturer can maintain the device.
General notes
Environmental
declaration
Please comply
with these notes
General
regulations
Safety
KNX bus supply
Warning, maintenance
Page 11
11 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Safety and EMC optimization 2013-07-04
3.3 Notes on EMC optimization
When setting up cable ducts, separate strongly interfering cables from susceptible entities.
• Interfering cables: Motor cables especially from motors supplied by inverters, energy-supplying cables.
• Susceptible entities: Control cables, low voltage cables, interface cables, LAN cables, digital and analog signal cables.
• Both types of cables may be in the same cable duct, but in separate compartments.
• If no three-sided, closed duct with separating wall is available, the interfering cables must be separated by at least 150 mm from the others or placed in separate ducts.
• Crossings of strongly interfering cables with possibly susceptible entities must be at a right angle.
• In exceptional cases, signal and interfering power cables may be run in parallel, resulting in a high interference risk.
We recommend to generally use unscreened cables. Comply with the manufacturer's installation recommendations for selecting unscreened cables. In general, unshielded twisted pair cables have sufficient EMC properties for technical building applications (including data applications) and do not require consideration of coupling to surrounding earth.
Setting up
cable ducts
Cable types
Separate cables
Unscreened cables
Page 12
12 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Mounting and electrical installation 2013-07-04
4 Mounting and electrical installation
Comply with the following notes as well as the mounting instructions [2] to mount the room sensor.
Note the permissible ambient temperature and humidity. See data sheet [1] for environmental conditions.
• The devices are suitable for wall mounting.
• Recommended height: 1.50 m above floor.
• Do not mount the devices in recesses, shelves, behind curtains or doors, or
above or near heat sources.
• Avoid direct solar radiation and drafts.
• Seal the conduit box or the installation tube, as air currents can affect sensor
readings.
• Adhere to allowed ambient conditions.
• Mounting instructions M1602 are enclosed with the devices.
2602J02
*
)
ServiceLED (red)
Programming pin
*) The installing tube must be sealed or cold or warm air may enter the device and
cause faulty temperature readings by the internal sensor.
Ambient conditions
Location (sensors,
room operator units)
Mounting instructions
Mounting over a
conduit box:
Page 13
13 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Mounting and electrical installation 2013-07-04
Wall mounting
Remove the breakout on the housing before putting the cable into the gaining channel.
4-wire cables (daisy chain wiring)
Remove the cable coating, as it will not fit in the gaining channel.
Cable ducts on the wall
30 mm
Keep a distance of 30 mm (from above) / 20 mm (from below) to the base plate, so that the device can be snapped onto the base plate.
Dismounting / service:
Page 14
14 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Mounting and electrical installation 2013-07-04
M
ax
. 6
5
9
.2
±
0
.1
5
1
6
0
2
z11
0
54 ± 0.15
Sample icons are available in the label template M1602.1
Information. e.g. on room operator unit location or on room type (free text)
• Follow the KNX regulations
• For KNX wiring (topology, allowed cables and cable length), see the document
KNX bus [4].
• Use the correct cables for the KNX bus
• Do not interchange the wires of the KNX cable.
– The red terminal is for KNX + – The gray terminal is for KNX –
• Observe all local installation regulations.
STOP
Caution!
• The devices are not protected against accidental connection to AC 230 V.
Information in topology and addressing in KNX networks is available in document KNX bus [4]. The following information requires electrical installation as per the KNX-TP1 standard.
Labels for QMX3.P02,
QMX3.P37
Insert label
Remove label
Installation
Bus cabling
1602Z106
1602J109
1602J110
1602Z107
Page 15
15 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Functionality / Use 2013-07-04
5 Functionality / Use
5.1 Basics
5.1.1 System environment
For engineering and commissioning, sound knowledge of KNX networks as well as sufficient knowledge of working with ETS or ACS790 depending on system environment is a prerequisite.
System environments and associated tools:
System / Network environment
Engineering and commissioning tool(s)
KNX LTE-Mode
ACS790
KNX S-Mode
ETS Version 3f or 4 and later
If ETS3 is used, make sure to install first ETS3 patch (additional software column SW) for ETS3.0f
www.siemens.com/hvac-td
For ETS4, make sure the latest version is installed or at least
version 4.1.2.
• For ACS: An interface converter, e.g. OCI700 (part of service tool OCI700.1) is required to connect a PC with USB interface to a KNX network.
• For ETS: An IP-interface, e.g. N148/22 (5WG1 148-1AB22), is required to access a KNX network via internet protocol (IP).
• The room operator units QMX3... are supplied with the physical address 0.2.255 (default address).
5.1.2 Engineering and commissioning documentation
We recommend documenting and storing all planning data and settings to ensure easy reuse even after an extended period of time or change of responsibilities. Clear documentation is required especially in case of calculated or customized settings. In KNX S-Mode systems, ETS for example can be used for this purpose.
Prerequisites
Engineering and commissioning
documentation
Page 16
16 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Functionality / Use 2013-07-04
5.2 Overview
Product number
Function
Temperature
sensor
Sensor for
humidity and CO
2
Air quality indicator
with LED
Display and
operation with
touchkeys
Operation of light,
shading and
scenes
Sensors
QMX3.P30 X
QMX3.P70 X X X
Room operator units
QMX3.P02 X X
QMX3.P34
X X
QMX3.P74 X X X
QMX3.P37 X X X
Page 17
17 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Functionality / Use 2013-07-04
5.3 Use
Six complementary device types are available which can control HVAC and electric applications.
• Room temperature, humidity, and CO
2
content of the room are controlled
according to the demand and to energy efficiency criteria.
• Four freely parameterizable pairs of touchkeys can be configured for light switching, dimming, blinds, scenes, sending values, etc.
The sensors in the room operator unit measure: – Room temperature. – Relative room humidity. – CO
2
concentration in rooms with varying occupancy due to time or number of people such as in museums, movie theaters, offices, meeting rooms, class rooms, auditoriums, hospitals, living spaces.
The room operator units control and operate: – Room temperature (via PID controller) – Humidity (via threshold value) – Air quality (via threshold value) – Fan stages (independent of temperature, air quality and humidity control
functions)
– Room operating modes – Input of the occupancy state
as well as – Switching of electrical equipment – Switching and dimming of lights – Control of shading / blinds – Selecting and saving of scenes
The room operator units with display show the following information about the room: – Present room temperature, outdoor temperature. – Present room humidity, outdoor humidity . – Present room air quality . – State of window contacts – Device mode (e.g. heating, cooling).
Details
Page 18
18 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Functionality / Use 2013-07-04
5.4 Display elements and buttons
Button
Button
1
2
3
4
5
6
7
8
• An arrow indicates that an element can be operated
• Temperature display in °C or °F / humidity in % r.H. /
air quality in text, symbol, or ppm of CO2
• Toggling (key 1) between indoor and outdoor measurement (temperature, humidity, CO2)
• Indication that a window is open (connected window switch is active)
• Display of the plant state (Heating or Cooling / inactive)
Note: No manual switchover!
• Display of the relative or absolute setpoint for temperature
• Adjusting the setpoint using keys 2 and 6
• Display of the present fan speed (when automatic)
• Adjusting the fan speed using key 3 (or keys 3 and 7 if operation of room
operating mode is disabled)
• Display of the room operating mode (when automatic)
• Adjusting the room operating mode using key 7
• Navigation: toggle the display / setpoint setting between temperature /
humidity / CO
2
, using key 4. The black bar points to the displayed
information.
• Operation of the occupancy state (presence switch, Comfort extension)
• Activate the Comfort extension using key 8 (only available if enabled)
• Engineering functions (press keys 1 and 8 simultaneously during 5 s)
– Programming mode (key 2), same function as programming pin – Connection test (Key 3) – Reset device to factory settings (key 4) Note: This operation is irreversible!
A
B
Page 19
19 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Functionality / Use 2013-07-04
5.5 Functions
The room operator units with control functions can be integrated in a KNX network. The control functions for room temperature and ventilation allow for immediate control of suitable actuators to control heating, cooling, and ventilation.
5.5.1 Measuring
The room operator units measure the room temperature via an integrated sensing element. The room temperature can be transmitted to other bus members and serves in KNX S-Mode as control variable of the integrated room temperature controller.
The room operator units acquire the relative humidity in the room with the aid of a humidity sensing element integrated in the front module. The relative room humidity can be transmitted to other bus members and serves in KNX S-Mode as control variable of the integrated ventilation controller.
The room operator units determine the CO
2
concentration via infrared absorption measurement (NDIR). The sensor provides exact measurements at all times and does not require maintenance or recalibration thanks to an integrated, stable reference light source. The CO
2
concentration can be transmitted to other bus members and serves in KNX S-Mode as control variable of the integrated ventilation controller.
The background-lit symbol informs on the current level of CO2 in the room. The colors green / orange / red of the background lighting indicate good / moderte /
poor air quality. The display can be switched on or off by another bus member, e.g.
switch or timer.
Temperature (All Types)
Relative humidity (QMX3.P70, QMX3.P74)
CO
2
concentration
(QMX3.P70, QMX3.P74)
Air quality indication
(QMX3.P70)
Page 20
20 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Functionality / Use 2013-07-04
5.5.2 Control and operation
Product number
Control and operation
PID control temperature
Threshold value switch
humidity and CO
2
Operation of light, shading
and scenes
Manual switching of
ventilation
Room operating mode
Presence function
Only operation and display
Sensors
QMX3.P30 X X
QMX3.P70 X X
Room operator units
QMX3.P02 X X X
QMX3.P34 X X X X X X
QMX3.P74 X X X X X X
QMX3.P37 X X X X X X X
The room operator units can be connected via bus to suitable KNX S-Mode heating, ventilating, and air conditioning actuators via integrated control functions for room temperature, humidity, and air quality.
A proven PID controller for heating and cooling is provided to control the room temperature. The controller supplies a continuous or a pulse-width-modulated PID signal for one heating and one cooling actuator. The room temperature setpoints for the two operating modes heating and cooling as well as a blocking object can be set using the touchkeys and the display, or received from the bus. Changeover to the operating mode Heating/Cooling is automatic. Preset control parameters, adjusted to the building type, are available for selection.
The integrated room humidity controller and room air quality controller can be used for ventilation control. For both controllers, the setpoints can be adjusted using touchkeys and display, or they can receive up to three switching point values via the bus. When the respective switching point is exceeded, up to three control signals and one quasi-continuous signal to control the ventilation actuators are transmitted to
Control functions
(KNX S-Mode all types
Page 21
21 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Functionality / Use 2013-07-04
other bus members. In addition, a signal with the max. control value from both controllers is available. The setpoint (from local operation or received vi a bus) directly influences the first threshold value (see description in sections 6.4.4 and 6.4.6).
Room temperature controller, humidity threshold value, and air quality threshold switching can be activated or deactivated. As a result, simple sensor function or room operation is possible also.
Manual room fan control can be enabled, offering three different types for selection such as single stage, 3 stages, or continuous from 0 to 100 percent. The 9 display bars change after 10% (display: 10% one bar, …100% 9 bars). For manual operation, a bar is added on each button press, corresponding to a change of +/­11%. This function can be activated or deactivated. Fan control is independent of the room temperature. When the operating mode is Auto, the bus command is executed.
The room operating modes can be controlled from Auto to Comfort, Pre-Comfort, Economy, and Protection. This function can be activated or deactivated.
The presence button allows for manual changeover between Comfort and Pre­Comfort. This function can be activated or deactivated. When activated, the Comfort extension is not available (key 8, see section 5.4).
When the presence function is deactivated, Comfort can be extended. Extensions are set between 5 and 120 minutes in ETS. This function can be activated or deactivated (key 8, see section 5.4.
The following table provides information on assessing room air quality based on the determined CO
2
concentration.
[ppm]
Typical CO2 concentration
<400
Outside air
700
City air
1000
Comfort limit
1500
Ventilation strongly recommended
2000
Inacceptable indoor air quality
4000
Bedroom at poor ventilation
5000
Max. concentration for workspaces (MAC value)
40000
Exhaled air
CO
2
concentration measurements are influenced by air pressure and temperature. The lower the air pressure, the lower the measured value. Temperature influence is corrected automatically. The sensor allows for correcting the determined measured value to the prevailing average air pressure at the mounting location. To do this, altitude [m above sea level] must be set. The correction has the following effect on an uncorrected measured value of 1000 ppm at normal conditions (0 m altitude, 25 °C):
Altitude [m]
0
500
1000
1500
2000
2500
3000
CO2 [ppm]
1000
1095
1201
1317
1445
1586
1740
Fan control (QMX3.P34, P74 and P37)
Room operating modes (QMX3.P34, P74 and P37)
Presence button (QMX3.P34, P74 and P37)
Comfort extension (QMX3.P34, P74 and P37)
Air quality measurement and assessment
(QMX3.P70, QMX3.P74)
Page 22
22 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Functionality / Use 2013-07-04
• Function: The sensor determines the CO2 concentration via infrared absorption measurement (NDIR). The sensor is maintenance free in normal environments, thanks to the built-in self-correcting ABC (Automatic Baseline Correction) algorithm. This algorithm keeps track of the sensor’s lowest reading within 8 days and corrects for any drift detected. The sensor also contains self­diagnostics to assure proper operation during lifetime.
• Use: Normal environments, such as offices, class rooms, hotel rooms, or other non-permanently occupied areas, typically reach at least once a week the CO
2
concentration of fresh air of 400 ppm. However, exposure to a lowest CO
2
concentration other than fresh air, or incorrect altitude parameter setting, might result in reduced accuracy and incorrect operation.
• Rough handling during transport, storage or mounting might adversely affect accuracy during the first days of operation.
• The specified accuracy is reached after 25 days of continuous operation.
8 buttons (individual or button pairs) and related LEDs can be parameterized individually. See Section 4 for button labels. Common functions such as switching (On, Off, toggle) or sending of values (percentage), dimming, or blinds control, 8-bit scene control with/without memorize are supported.
Notes on CO2 sensor
Operation of light, shading and scenes
(QMX3.P37, QMX3.P02)
Page 23
23 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Functionality / Use 2013-07-04
5.6 Application examples
Below are a few typical application examples for the QMX3.P30, P34, P70 and P74 room operator units.
5.6.1 Room temperature control and operation via QMX3
Key (Possible combination of components)
1. Room operator unit QMX3.P34
2. Presence detector UP 258
3. Motoric valve actuator AP 562/02
4. Window contact S 290
This application is recommended for smaller offices with a single heater. The room operator unit measures and regulates room temperature and sends the regulation signal to the valve drive actuator via KNX bus.
In addition, window contacts and presence detectors influence the control behavior of the room operator unit and increase the room‘s energy efficiency. For example, if no one is in the room or if the window is open, the radiator valve closes and reduces the room temperature automatically. Up to 4 window contacts and presence detectors can be connected via KNX bus.
Page 24
24 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Functionality / Use 2013-07-04
5.6.2 Presence dependent room climate control with
operation of all disciplines
Key (Example of a possible combination of components)
1. Room operator unit QMX3.P37
2. Room sensor QMX3.P70
3. Room operator unit QMX3.P02
4. Presence detector UP 258
5. Switch actuator N 562/11 for fan
6. Shutter/blind actuators N 523/04
7. Universal dimmer N 528/31 with sub-module N 528/41
8. Thermal drive actuator N 605 for up to 6 rooms
9. Thermal valve actuator STA23 (for up to 4 rooms)
This application is especially suitable for rooms with several heaters, e.g. in offices, lecture halls or conference rooms.
The room operator unit (1) measures and controls the room temperature and sends the control signal to the thermal actuator (8) via KNX bus. Together with the integrated room temperature control, the sensor provides for a comfortable room climate.
The Room operator unit (2) measures the air quality (CO2) in the room, controls the ventilation as required and thus saves energy and costs. The buttons on the room operator unit (1 and 3) can be used to control shading, lighting and scenes for example.
Additional room operator units (1) can also be connected, e.g. in large rooms with several doors.
Page 25
25 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Functionality / Use 2013-07-04
5.6.3 Room temperature, humidity and air quality control
Key (Possible combination of components)
RMU7x0B Air handling controller
1. Room sensor QMX3.P70 Temperature sensor CO
2
sensor
Humidity sensor
2. Air handling controller RMU7x0B
The room operator unit (1) measures the room temperature, the room humidity, and the CO2 concentration, and passes these values on to the controller (2) via the KNX bus. The controller controls temperature, humidity and air quality of the corresponding room based on the measured values.
Page 26
26 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies GAMMA building management system 2013-07-04
6 GAMMA building management system
6.1 Engineering
The product data (*.vd5 or *.knxprod) must be downloaded from the website and imported in the ETS device catalog for KNX S-Mode engineering. The product data is available at www.siemens.com/hvac-td
or www.siemens.com/symaro
If ETS3 is used, make sure to install first ETS3 patch (additional software column SW) for ETS3.0f www.siemens.com/hvac-td
For ETS4, make sure the latest version is installed or at least version 4.1.2.
For a series of examples see section 6.5.
6.2 Commissioning
Prior to commissioning, all devices must be mounted as per the mounting instructions [2] and connected to the bus via bus connector as per to the bus topology (red to +, black to –). To check correct polarity of the wires for of a bus participant, press the programming pin if the bus is powered. If the service LED lights up, the polarity of the wires is correct
Pushbutton actuation
Meaning
Short (< 0.5 s) Switch over to programming mode or acknowledge
display of a connection test.
No functions are executed when the programming
button is pressed longer (> 0.5 s to 2 s).
Medium-long (>2 s and <20 s)
Special mode (connection test for Desigo TRA). This manufacturer-specific function can lock the device for programming mode for ca. 10 s. In this case, the
service LED briefly blinks.
Long (> 20 s)
STOP
Note!
Reset to factory settings.
This operation resets all user preference data and parameter settings to factory default.
This operation is irreversible.
LED indication
Meaning
Red
Device is in programming mode.
All other indication types do not apply to KNX S-Mode.
During parameterization using the commissioning software, the input objects are set to default values upon initial switch-on or following standard reset.
In the event of a bus voltage failure, the device detects the failure and saves the values received last to non-volatile memory. After bus power restoration, the saved status of all input objects is restored.
KNX product data
ETS version
Functionality of touch
keys and display
Commissioning
prerequisites
Pushbuttons
LED status indication
Switch-on response
Page 27
27 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies GAMMA building management system 2013-07-04
6.3 KNX S-Mode communication objects
The number and type of available group objects as well as adjustable parameters can vary depending on basic configuration. For detailed documentation on KNX S­Mode data point types, see [5].
Object No.
Communication objects available in ETS when function is enabled
Comm. enable
Read enable
Write enable
Transmit enable
Response update
Transmission
priority
Datapoint type
Number of Byte /
bit
QMX3.P30
QMX3.P70
QMX3.P34
QMX3.P74
QMX3.P37
QMX3.P02
Room Temperature Sensor
1 Room Temperature [°C] 1 1 0 1 0 normal 9.001 2 Byte X X X X X X
Room Temperature Control
2 Room temp. controller operating mode 1 1 1 0 1 normal 20.105 1 Byte X X X X X X 3 Enable room tem perature controller 1 1 1 0 1 normal 1.003 1 bit X X X X X X
4 Room temperature setpoint while cooling 1 1 1 0 1 normal 9.001 2 Byte X X X X X X 5 Room temperature setpoint while heating 1 1 1 0 1 normal 9.001 2 Byte X X X X X X 6 Control value cooling - cont. 1 1 0 1 0 normal 5.001 1 Byte X X X X X X 7 Control value heating - cont. 1 1 0 1 0 normal 5.001 1 Byte X X X X X X 8 Control value cooling - on/off 1 1 0 1 0 normal 1.001 1 bit X X X X X X
9 Control value heating - on/off 1 1 0 1 0 normal 1.001 1 bit X X X X X X
Room Temperature Setpoint
10 Room temperature: Setpoint absolute [°C] 1 1 1 0 1 normal 9.001 2 Byte X X X X X X 11 Room temperature: Setpoint relative [K] 1 0 1 0 1 normal 9.002 2 Byte X X X X X X 12 Room temperature: Setpoints set heating 1 1 1 0 1 normal 222.100 6 Byte X X X X X X 13 Room temperature: Setpoints set cooling 1 1 1 0 1 normal 222.100 6 Byte X X X X X X 14 Room operating mode: Time switch 1 1 1 0 1 normal 20.102 1 Byte X X X X X X 15 Room operating mode: Preselection 1 1 1 0 1 normal 20.102 1 Byte X X X X X X 16 Room operating mode: State 1 1 0 1 0 normal 20.102 1 Byte X X X X X X 17 Comfort mode: Timer button 1 0 1 0 0 norm al 1.017 1 bit X X X X X X 18 W indow State: Wind. 1 (1=open / 0=close) 1 1 1 0 1 normal 1.019 1 bit X X X X X X 19 W indow State: Wind. 2 (1=open / 0=close) 1 1 1 0 1 normal 1.019 1 bit X X X X X X 20 W indow State: Wind. 3 (1=open / 0=close) 1 1 1 0 1 normal 1.019 1 bit X X X X X X 21 W indow State: Wind. 4 (1=open / 0=close) 1 1 1 0 1 normal 1.019 1 bit X X X X X X 22 Presence State 1 1 1 0 1 normal 1.018 1 bit X X X X X X 23 Room temperature: Setpoint Heating [°C] 1 1 0 1 0 normal 9.001 2 Byte X X X X X X 24 Room temperature: Setpoint Cooling [°C] 1 1 0 1 0 normal 9.001 2 Byte X X X X X X
Room Relative Humidity Sensor
25 Room humidity [%r.h.] 1 1 0 1 0 normal 9.007 2 Byte X X X X X X
Room Relatvie Humitdity Control
26 Switching point r.h. - stage 1 1 1 1 0 1 normal 9.007 2 Byte X X X X X X 27 Switching point r.h. - stage 2 1 1 1 0 1 normal 9.007 2 Byte X X X X X X 28 Switching point r.h. - stage 3 1 1 1 0 1 normal 9.007 2 Byte X X X X X X
29 Control value r.h. cont. - m anual setp. 1 1 1 0 1 normal 5.001 1 Byte X X X X X X
30 Control value r.h. cont. - m anual mode 1 1 1 0 1 normal 1.003 1 bit X X X X X X
31 Enable room r.h. controller 1 1 1 0 1 normal 1.003 1 bit X X X X X X
32 Override room r.h. controller 1 1 1 0 1 normal 1.003 1 bit X X X X X X 33 Control value r.h. stage 1 - on/off 1 1 0 1 0 normal 1.001 1 bit X X X X X X 34 Control value r.h. stage 2 - on/off 1 1 0 1 0 normal 1.001 1 bit X X X X X X 35 Control value r.h. stage 3 - on/off 1 1 0 1 0 normal 1.001 1 bit X X X X X X 36 Control value r.h. - cont. 1 1 0 1 0 normal 5.001 1 Byte X X X X X X
Room Air Quality Sensor
38 CO2 concentration [ppm] 1 1 0 1 0 normal 9.008 2 Byte X X X X X X
Room Air Quality Control
39 Switching point CO2 stage 1 1 1 1 0 1 normal 9.008 2 Byte X X X X X X 40 Switching point CO2 stage 2 1 1 1 0 1 normal 9.008 2 Byte X X X X X X 41 Switching point CO2 stage 3 1 1 1 0 1 normal 9.008 2 Byte X X X X X X 42 Control value CO2 cont. - manual setp. 1 1 1 0 1 normal 5.001 1 Byte X X X X X X 43 Control value CO2 cont. - manual mode 1 1 1 0 1 normal 1.003 1 bit X X X X X X 44 Enable room air quality controller 1 1 1 0 1 normal 1.003 1 bit X X X X X X 45 Override room air quality controller 1 1 1 0 1 normal 1.003 1 bit X X X X X X 46 Control value CO2 stage 1 - on/off 1 1 0 1 0 normal 1.001 1 bit X X X X X X 47 Control value CO2 stage 2 - on/off 1 1 0 1 0 normal 1.001 1 bit X X X X X X 48 Control value CO2 stage 3 - on/off 1 1 0 1 0 normal 1.001 1 bit X X X X X X 49 Control value CO2 - cont. 1 1 0 1 0 normal 5.001 1 Byte X X X X X X 50 Control value CO2 / r.h. max. - cont. 1 1 0 1 0 normal 5.001 1 Byt e X X X X X X
Type
Page 28
28 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies GAMMA building management system 2013-07-04
Object No.
Communication objects available in ETS when function is enabled
Comm. enable
Read enable
Write enable
Transmit enable
Response update
Transmission
priority
Datapoint type
Number of Byte /
bit
QMX3.P30
QMX3.P70
QMX3.P34
QMX3.P74
QMX3.P37
QMX3.P02
QMX3.P70 Air Quality Indication LED
51 Air quality indication on/off 1 1 1 0 1 normal 1.003 1 bit X 52 Air quality indication level 1 0 1 0 1 normal 20.60209 1 Byte X
HMI: Temperature visualization
53 Outside temperature [°C] 1 0 1 0 1 normal 9.001 2 Byte X X X 54 Room temperature [°C] 1 0 1 0 1 normal 9.001 2 Byte X X X
HMI: Room Temperature Setpoint Setting
55 Room temperature: Setpoint absolute [°C] 1 1 1 1 1 normal 9.001 2 Byte X X X 56 Room temperature: Setpoint relative [K] 1 0 1 1 1 normal 9.002 2 Byte X X X 57 Room temperature: Current absolute [°C] 1 0 1 0 1 normal 9.001 2 B yte X X X
HMI: Room Operation Mode Setting
58 Room operating mode: Preselection 1 1 1 1 1 normal 20.102 1 Byte X X X 59 Room operating mode: State 1 0 1 0 1 normal 20.102 1 Byte X X X
HMI: Comfort Prolongation
60 Comfort mode: Timer button 1 0 0 1 0 normal 1.017 1 bit 61 Comfort mode: Timer state (invisible) 1 0 1 0 1 normal 1.011 1 bit
Display: WindowStatus
62 W indow State 1 0 1 0 1 normal 1.019 1 bit X X X
HMI: User Presence Switch
63 Presence Switch 1 1 1 1 1 normal 1.001 1 bit X X X 64 Presence State 1 0 1 0 0 normal 1.001 1 bit
HMI: Fan Speed Setting
65 Fan speed: Preselection [%] 1 1 1 1 1 normal 5.001 1 Byte X X X 66 Fan operation (0 = Auto / 1 = Manual) 1 1 1 1 1 normal 1.003 1 bit X X X 67 Fan speed: State [%] 1 0 1 0 1 normal 5.001 1 Byte X X X
HMI: Controller Mode visualization
68 Controller: Application Mode 1 0 1 0 1 normal 20.105 1 Byt e X X X
HMI: humidity visualization
69 Outside relative humidity [%rH] 1 0 1 0 1 normal 9.007 2 Byte X X X 70 Room relative humidity [%rH] 1 0 1 0 1 normal 9.007 2 Byte X X X
HMI: rel. humidity setpoint setting
71 Room relative humidity: Setpoint [%rH] 1 1 1 1 1 normal 9.007 2 Byte X X X
HMI: air quality visualization
73 Room air quality: CO2 concentr. [ppm] 1 0 1 0 1 normal 9.008 2 Byte X X X
HMI: air quality setpoint setting
74 Room air quality: Setpoint [ppm] 1 1 1 1 1 normal 9.008 2 Byte X X X
HVAC HMI Locking
75 HVAC operation: Lock 1 1 1 0 1 normal 1.011 1 bit X X X
Type
Page 29
29 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies GAMMA building management system 2013-07-04
Object No.
Communication objects available in ETS when function is enabled
Comm. enable
Read enable
Write enable
Transmit enable
Response update
Transmission
priority
Datapoint type
Number of Byte /
bit
QMX3.P30
QMX3.P70
QMX3.P34
QMX3.P74
QMX3.P37
QMX3.P02
Function Key Pair 1, Key 1
80 Button A1: switching on / off 1 0 1 1 0 normal 1.001 1 bit X X 81 Button A1: value 1 0 0 1 0 normal 5.001 1 Byte X X 82 Button A1: 2nd telegram; switching 1 0 1 1 0 normal 1.001 1 bit X X 83 Button A1: 2nd telegram; value 1 0 0 1 0 normal 5.001 1 Byte X X 84 Button A1: switching on/off 1 0 0 1 0 normal 1.001 1 bit X X 85 Button A1: dimm ing brighter/darker 1 0 0 1 0 normal 3.007 4 bit X X 86 Button A1: blind up / down 1 0 0 1 0 normal 1.008 1 bit X X 87 Button A1: slats stop / open / close 1 0 0 1 0 normal 1.007 1 bit X X 88 Button A1: 8-bit scene recall / save 1 0 0 1 0 normal 18.001 1 Byte X X 89 LED A1 on / off 1 1 1 0 1 normal 1.001 1 bit X X
Function Key Pair 1, Key 2
90 Button A2: switching on / off 1 0 1 1 0 normal 1.001 1 bit X X 91 Button A2: value 1 0 0 1 0 normal 5.001 1 Byte X X 92 Button A2: 2nd telegram; switching 1 0 1 1 0 normal 1.001 1 bit X X 93 Button A2: 2nd telegram; value 1 0 0 1 0 normal 5.001 1 Byte X X 94 Button A2: switching on/off 1 0 0 1 0 normal 1.001 1 bit X X 95 Button A2: dimm ing brighter/darker 1 0 0 1 0 normal 3.007 4 bit X X 96 Button A2: blind up / down 1 0 0 1 0 normal 1.008 1 bit X X 97 Button A2: slats stop / open / close 1 0 0 1 0 normal 1.007 1 bit X X 98 Button A2: 8-bit scene recall / save 1 0 0 1 0 normal 18.001 1 Byte X X 99 LED A2 on / off 1 1 1 0 1 normal 1.001 1 bit X X
Function Key Pair 2, Key 1
100 Button B1: switching on / off 1 0 1 1 0 normal 1.001 1 bit X X 101 Button B1: value 1 0 0 1 0 normal 5.001 1 Byte X X 102 Button B1: 2nd telegram; switching 1 0 1 1 0 normal 1.001 1 bit X X 103 Button B1: 2nd telegram; value 1 0 0 1 0 normal 5.001 1 Byte X X 104 Button B1: switching on/off 1 0 0 1 0 normal 1.001 1 bit X X 105 Button B1: dimming brighter/darker 1 0 0 1 0 normal 3.007 4 bit X X 106 Button B1: blind up / down 1 0 0 1 0 normal 1.008 1 bit X X 107 Button B1: slats stop / open / close 1 0 0 1 0 normal 1.007 1 bit X X 108 Button B1: 8-bit scene recall / save 1 0 0 1 0 normal 18.001 1 Byte X X 109 LED B1 on / off 1 1 1 0 1 normal 1.001 1 bit X X
Function Key Pair 2, Key 2
110 Button B2: switching on / off 1 0 1 1 0 normal 1.001 1 bit X X 111 Button B2: value 1 0 0 1 0 normal 5.001 1 Byte X X 112 Button B2: 2nd telegram; switching 1 0 1 1 0 normal 1.001 1 bit X
X 113 Button B2: 2nd telegram; value 1 0 0 1 0 normal 5.001 1 Byte X X 114 Button B2: switching on/off 1 0 0 1 0 normal 1.001 1 bit X X 115 Button B2: dimming brighter/darker 1 0 0 1 0 normal 3.007 4 bit X X 116 Button B2: blind up / down 1 0 0 1 0 normal 1.008 1 bit X X 117 Button B2: slats stop / open / close 1 0 0 1 0 normal 1.007 1 bit X X 118 Button B2: 8-bit scene recall / save 1 0 0 1 0 normal 18.001 1 Byte X X 119 LED B2 on / off 1 1 1 0 1 normal 1.001 1 bit X X
Type
Page 30
30 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies GAMMA building management system 2013-07-04
Object No.
Communication objects available in ETS when function is enabled
Comm. enable
Read enable
Write enable
Transmit enable
Response update
Transmission
priority
Datapoint type
Number of Byte /
bit
QMX3.P30
QMX3.P70
QMX3.P34
QMX3.P74
QMX3.P37
QMX3.P02
Function Key Pair 3, Key 1
120 Button C1: switching on / off 1 0 1 1 0 normal 1.001 1 bit X X 121 Button C1: value 1 0 0 1 0 normal 5.001 1 Byte X X 122 Button C1: 2nd telegram; switching 1 0 1 1 0 normal 1.001 1 bit X X 123 Button C1: 2nd telegram; value 1 0 0 1 0 normal 5.001 1 Byte X X 124 Button C1: switching on/off 1 0 0 1 0 normal 1.001 1 bit X X 125 Button C1: dimming brighter/darker 1 0 0 1 0 normal 3.007 4 bit X X 126 Button C1: blind up / down 1 0 0 1 0 normal 1.008 1 bit X X 127 Button C1: slats stop / open / close 1 0 0 1 0 normal 1.007 1 bit X X 128 Button C1: 8-bit scene recall / save 1 0 0 1 0 normal 18.001 1 Byte X X 129 LED C1 on / off 1 1 1 0 1 normal 1.001 1 bit X X
Function Key Pair 3, Key 2
130 Button C2: switching on / off 1 0 1 1 0 normal 1.001 1 bit X X 131 Button C2: value 1 0 0 1 0 normal 5.001 1 Byte X X 132 Button C2: 2nd telegram; switching 1 0 1 1 0 normal 1.001 1 bit X X 133 Button C2: 2nd telegram; value 1 0 0 1 0 normal 5.001 1 Byte X X 134 Button C2: switching on/off 1 0 0 1 0 normal 1.001 1 bit X X 135 Button C2: dimming brighter/darker 1 0 0 1 0 normal 3.007 4 bit X X 136 Button C2: blind up / down 1 0 0 1 0 normal 1.008 1 bit X X 137 Button C2: slats stop / open / close 1 0 0 1 0 normal 1.007 1 bit X X 138 Button C2: 8-bit scene recall / save 1 0 0 1 0 normal 18.001 1 Byte X X 139 LED C2 on / off 1 1 1 0 1 normal 1.001 1 bit X X
Function Key Pair 4, Key 1
140 Button D1: switching on / off 1 0 1 1 0 normal 1.001 1 bit X X 141 Button D1: value 1 0 0 1 0 normal 5.001 1 Byte X X 142 Button D1: 2nd telegram; switching 1 0 1 1 0 normal 1.001 1 bit X X 143 Button D1: 2nd telegram; value 1 0 0 1 0 normal 5.001 1 Byte X X 144 Button D1: switching on/off 1 0 0 1 0 normal 1.001 1 bit X X 145 Button D1: dimming brighter/darker 1 0 0 1 0 normal 3.007 4 bit X X 146 Button D1: blind up / down 1 0 0 1 0 normal 1.008 1 bit X X 147 Button D1: slats stop / open / close 1 0 0 1 0 normal 1.007 1 bit X X 148 Button D1: 8-bit scene recall / save 1 0 0 1 0 normal 18.001 1 Byte X X 149 LED D1 on / off 1 1 1 0 1 normal 1.001 1 bit X X
Function Key Pair 4, Key 2
150 Button D2: switching on / off 1 0 1 1 0 normal 1.001 1 bit X X 151 Button D2: value 1 0 0 1 0 normal 5.001 1 Byte X X 152 Button D2: 2nd telegram; switching 1 0 1 1 0 normal 1.001 1 bit X
X 153 Button D2: 2nd telegram; value 1 0 0 1 0 normal 5.001 1 Byte X X 154 Button D2: switching on/off 1 0 0 1 0 normal 1.001 1 bit X X 155 Button D2: dimming brighter/darker 1 0 0 1 0 normal 3.007 4 bit X X 156 Button D2: blind up / down 1 0 0 1 0 normal 1.008 1 bit X X 157 Button D2: slats stop / open / close 1 0 0 1 0 normal 1.007 1 bit X X 158 Button D2: 8-bit scene recall / save 1 0 0 1 0 normal 18.001 1 Byte X X 159 LED D2 on / off 1 1 1 0 1 normal 1.001 1 bit X X
Type
Page 31
31 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies GAMMA building management system 2013-07-04
6.4 KNX S-Mode Parameter description
Factory settings are boldfaced / in brackets
Designation Values Typ e
Communication objects available in ETS when function is enabled
Range (Default)
Unit
QMX3.P30
QMX3.P70
QMX3.P34
QMX3.P74
QMX3.P37
QMX3.P02
6.4.1 Room temperature sensor
Room temp.: Sensor correction
-5…+5 in0.1 steps (0K))
K
X X X X X
X
Room temp.: Send following change by
0.1…2.5 (0.1)
K
X X X X X
X
Room temp.: Send cyclically after
1…60 (2 min)
min
X X X X X
X
6.4.2 Room temperature control
Activate room temperature control
yes; no
X X X X X
X
Heating type Radiator heating slow
(Radiator heating fast) Floor heating slow
Floor heating fast
X X X X X
X
Cooling type
(Chilled ceiling) Floor cooling
X X X X X
X
Parameters heating / cooling type allow for adapting the controller to the type of heating / cooling. In addition, the controller features two control algorithms: one for continuous mode (0..100%) and one for PWM mode (On/Off). The mode is selected via parameter "Control value type". The control value type is identical for all operating modes. In continuous mode, the associated PWM output is "On" at continuous control value ≠ 0.
In PWM mode, cycle time and pulse width are adapted to the type of heating / cooling, the setpoint, and the measured room
temperature. The min. cycle time is 12 minutes, the min. pulse
width is 4 minutes. The continuous control value issues 0% or 100% in this operating mode.
Default heating setpoint
5…40 (21.0)
°C
X X X X X
X
Default cooling setpoint
5…40 (24.0)
°C
X X X X X
X
Control value type
(PWM) Continuous 0…100%
X X X X X
X
Send cyclically after Do not send cyclically
1;2;3...30;45;60
min
X X X X X
X
Protection heating setpoint
5…40 (12.0)
°C
X X X X X
X
Economy heating setpoint
5…40 (15.0)
°C
X X X X X
X
Comfort heating setpoint
5…40 (21.0)
°C
X X X X X
X
Comfort cooling setpoint
5…40 (24.0)
°C
X X X X X
X
Economy cooling setpoint
5…40 (28.0)
°C
X X X X X
X
Protection cooling setpoint
5…40 (35.0)
°C
X X X X X
X
Comfort extension time
5…120 (30)
min
X X X X X
X
Number of window status inputs
0…4
X X X X X
X
Page 32
32 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies GAMMA building management system 2013-07-04
Designation Values Type
Visible parameter name in ETS Range
(Default)
Unit
QMX3.P30
QMX3.P70
QMX3.P34
QMX3.P74
QMX3.P37
QMX3.P02
6.4.3 Room relative humidity sensor
Humidity: Send following change by
2; 3; 4; 5; 7; 10 (2%)
%r.h.
X X
Humidity: Send cyclically after
1; 2…45; 60 (15 min)
min
X X
6.4.4 Room relative humidity control
Default switching point stage 1 (%r.h.)
0…100 (40)
%r.h.
X X X X X
X
Default switching point stage 2 (%r.h.)
0…100 (70)
%r.h.
X X X X X
X
Default switching point stage 3 (%r.h.)
0…100 (90)
%r.h.
X X X X X
X
Hysteresis
2;3;4;5;7;10 (5%)
%r.h.
X X X X X
X
If room humidity exceeds a switching point r.h., the control value r.h. for the respective stage is switched on. Control value r.h. is switched off again when room humidity < switching point r.h. – hysteresis.
OFF
ON
Control value stage 1
OFF
ON
OFF
ON
[ppm CO2] [% r.H.]
1411D01en
Threshold
Stage 1
Threshold
Stage 2
Threshold
Stage 3
Hysteresis
Control value stage 2
Control value stage 3
Control value stage 0 (%)
0…100 (0)
%
X X X X X
X
Control value stage 1 (%) (>stage 0)
0…100 (35)
%
X X X X X
X
Control value stage 2 (%) (>stage 1)
0…100 (70)
%
X X X X X
X
Control value stage 3 (%) (>stage 2)
0…100 (100)
%
X X X X X
X
If room humidity exceeds switching point r.h., the control value
parameterized for this stage is issued. The control value again issues the next lower stage value when room humidity < switching point r.h. – hysteresis.
[ppm CO2] [% r.H.]
[%]
Control value – cont.
Control value stage 3
Hysteresis
1411D02en
Threshold
Stage 1
Threshold
Stage 2
Threshold
Stage 3
Control value stage 2
Control value stage 1
Control value stage 0
Stage when overridden
0;1;2;3 (3)
X X X X X
X
Send cyclically after
Do not send cyclically 1;2;3...30;45;60 (15 min)
min.
X X X X X
X
Page 33
33 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies GAMMA building management system 2013-07-04
Designation Values Type
Visible parameter name in ETS Range
(Default)
Unit
QMX3.P30
QMX3.P70
QMX3.P34
QMX3.P74
QMX3.P37
QMX3.P02
6.4.5 Room air quality sensor
CO2 concentr.: Send following change by 5;10;20…500;750;1000
(10ppm)
ppm
X X
CO2 concentr.: Sensor correction (ppm)
-500…+500 (0 ppm)
ppm
X X
CO2 concentr.: Send cyclically after 1;2;3…30;45;60 (15
min)
min
X X
CO2 concentr.: Altitude above sea level (m)
0…5000 (0 m)
min
X X
6.4.6 Room air quality control
Default switching point stage 1 (ppm)
400…2000 (800)
ppm
X X X X X
X
Default switching point stage 2 (ppm)
400…2000 (1000)
ppm
X X X X X
X
Default switching point stage 3 (ppm)
400…2000 (1500)
ppm
X X X X X
X
Hysteresis
50…500 (100)
ppm
X X X X X
X
If the CO2 concentration exceeds a switching point CO2, the control value CO
2
for the related stage is switched on. The control value CO2 is again switched off, if the CO2 concentration returns to < switching point CO
2
– hysteresis.
OFF
ON
Control value stage 1
OFF
ON
OFF
ON
[ppm CO2] [% r.H.]
1411D01en
Threshold
Stage 1
Threshold
Stage 2
Threshold
Stage 3
Hysteresis
Control value stage 2
Control value stage 3
Control value stage 0 (%)
0…100 (0)
%
X X X X X
X
Control value stage 1 (%) (>stage 0)
0…100 (35)
%
X X X X X
X
Control value stage 2 (%) (>stage 1)
0…100 (70)
%
X X X X X
X
Control value stage 3 (%) (>stage 2)
0…100 (100)
%
X X X X X
X
If the CO2 concentration exceeds a switching point CO2, the control value CO
2
for the related stage is switched on. The control value issues again the value of the next lower stage when CO
2
concentration < switching point CO2 – hysteresis.
[ppm CO2] [% r.H.]
[%]
Control value – cont.
Control value stage 3
Hysteresis
1411D02en
Threshold
Stage 1
Threshold
Stage 2
Threshold
Stage 3
Control value stage 2
Control value stage 1
Control value stage 0
Stage when overridden
0;1;2;3 (3)
X X X X X
X
Send cyclically after Do not send cyclically
1;2;3...30;45;60 (15 min)
min.
X X X X X
X
6.4.7 Device display parameters
Backlight Level
0; 10;…100 (60%)
%
X X X
Backlight idle time
3…20 (15 s)
s
X X X
Active unit set
°C; °F (°C)
X X X
Active audio feedback (buttons)
yes; no (yes)
X X X
LED Brightness
0…100 (100)
%
X
X
Display: Idle page
(HVAC operation and display)
Temperature
Relative humidity
Air quality
X X X
Time to return to idle page (s)
3…120 (15 s)
s
X X X
Page 34
34 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies GAMMA building management system 2013-07-04
Designation Values Typ e
Visible parameter name in ETS Range
(Default)
Unit
QMX3.P30
QMX3.P70
QMX3.P34
QMX3.P74
QMX3.P37
QMX3.P02
6.4.8 HVAC operation and display
Display Temperature visualization -----
(Room) Outside
Room and Outside
X X X
Room temperature setpoint type
Absolute; (Relative)
X X X
Lower limit temp.setp.abs.
5…21 (18)
°C
X X X
Upper limit temp. Setp. Abs.
21…40 (26)
°C
X X X
Temp.setp.op.in steps of
0.1; 0.2; 0.5; 1.0; 2.0 (0.1)
°C
X X X
Max. negative temp.shift
-10…0 (-3)
K
X X X
Max. positive temp.shift
0…+10 (+3)
K
X X X
Temperature shift in steps of
0.1; 0.2; 0.5; 1.0; 2.0 (0.5)
K
X X X
Operation Room Operating Mode
yes; (no)
X X X
Operation Room Occupancy Mode
(yes); no
X X X
Display Window state visualization
yes; (no)
X X X
Display Heating/Cooling indication
yes; (no)
X X X
Operation fan Speed
yes; (no)
X X X
Fan type
1-speed
(3-speed)
Variable speed
X X X
Minimum fan speed (variable speed)
0…100 (0%)
%
X X X
Maximum fan speed (variable speed)
100…0 (100%)
%
X X X
6.4.9 Operation and display: Relative humidity visualization
Display: Relative humidity visualization
(-----)
Room
Outside Room and Outside
X X X
Min. rel. humidity setp. (%r.h.)
0…99 (10%)
%r.h.
X X X
Max. rel. humidity setp. (%r.h.)
1…100 (95%
%r.h.
X X X
Rel. Hum. operation in steps of
1;2;5;10;20 (1%)
%
X X X
6.4.10 Display on QMX3.P70 Air quality indication LED
Change color green <--> yellow at (ppm)
400.2000 (1000)
ppm
X
Change color yellow <--> red at (ppm)
400…2000 (1500)
ppm
X
Bus influence
(No) Can be de-/activated via bus
X
6.4.11 Operation and display: air quality
Display: Air quality visualization
(-----) Room
X X X
Display: Air quality visualization Numeric value (ppm)
(Symbol)
Text
X X X
Change symbol '+++' <-> '++-' at ppm
400…2000 (1000)
ppm
X X X
Change symbol '++-' <-> '+- -' at ppm
400…2000 (1500)
ppm
X X X
Change text 'Good' <-> 'Okay' at ppm
400…2000 (1000)
ppm
X X X
Change text 'Okay' <-> 'Poor' at ppm
400…2000 (1500)
ppm
X X X
Min. air quality setpoint (ppm)
0…2000 (400)
ppm
X X X
Max. air quality setpoint (ppm)
0…2000 (2000)
ppm
X X X
Air qual. operation in steps of
1;2;5….50;100;200 (100)
ppm
X X X
Page 35
35 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies GAMMA building management system 2013-07-04
6.4.12 Operation of light, shading and scenes
Possible function assignment for buttons / button pairs (8 individual buttons or 4 pairs of buttons). Only QMX3.P02 and QMX3.P37
Individual buttons
LED response and parameterization
1-button switching/sending value
Edge Action rising edge [---, Off, On, At, Send
percentage value, Send 8-Bit value]
LED display [object-independent, status
object]
(Action falling edge [---, Off, On, At, Send
percentage value, Send 8-Bit value])
(Object independent) LED constant value [off, on (orientation light)]
Short button pressure
Action short button pressure [---, Off, On, At, Send percentage value, Send 8-Bit value]
( Status object) LED activation [Off/On, On/Off]
Long button pressure
Long button pressure via send 2nd object [No, Yes]
Action long button pressure[---, Off, On, At,
Send percentage value, Send 8-Bit value]
1-button dimming
LED display [object-independent, status object]
Action short/long button pressure [at/dim, On/brighter,
Off/darker]
(Object independent) LED constant
value [Off, On (orientation light)]
Long button pressure [0.5 - 6.0s] dimming value 0% or 100%
( status object) LED activation [Off/On, On/Off]
1-button solar protection / blinds control
No LED display
Action short/long button pressure [stop/up/up, stop/close/down]
Long button pressure [0.5 - 6.0s] move to end positions
Scene
Scene number [1…64]
Selection of predefined scene (short button pressure <0.5 s). LED On for 3 s
Release scene memory [Yes/Non] (long button pressure [1 - 6s])
Memorize changed scene (long button pressure >5 s).
LED flashes for 3 s. When off, user can
release button.
Combined / Button pairs
LED response and parameterization
2-button switching
LED display [object-independent, status object]
Action button pair [left Off, right On, right Off/left On] (Object independent) LED constant
value [Off, On (orientation light)]
(status object) LED activation [Off/On,
On/Off]
2-button dimming
LED A2 display [object-independent, status object]
Action button pair [left On/brighter, right Off/darker] (Object independent) LED constant
value [Off, On (orientation light)]
Long button pressure [0.5 - 6.0s] dimming value 0% or 100%
(status object) LED activation [Off/On, On/Off]
2-button solar protection / blinds control
No LED display
Action button pair [left: step up/drive up, right: close/down]
Long button pressure [0.5 - 6.0s] move to end positions
Page 36
36 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies GAMMA building management system 2013-07-04
6.5 Examples for the functionality of touch keys and display elements
In RTS, these functions are created as follows: In the device view,
• activate or deactivate functions
• modify the default values if required
The objects that are now visible, must be connected to group addresses.
Key 1 Toggle the display between outdoor and indoor temperature Keys 2 and 6 Room temperature setpoint adjustment (absolute) Keys 3, 4 and 5 No function Key 7 Toggle the room operating mode (in Auto mode, the present operating mode is
displayed)
Key 8 Presence key, or Comfort extension
Key 1 No function, as only room temperature is displayed Keys 2 and 6 Room temperature setpoint adjustment (relative) Keys 3 and 7 Manual adjustment of fan speed Key 4 Toggle the display pages between temperature, humidity, and CO
2
Keys 5 and 8 No function
Temperature and room
operating modes
Temperature, fan control and
navigation
Page 37
37 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies GAMMA building management system 2013-07-04
Key 1 No function, display of room air quality in text form
GOOD, OKAY, or POOR Keys 2, 3, 5, 6, 7 and 8 No function Key 4 Toggle the display pages between temperature, humidity, and CO
2
Key 1 Toggle the display between outdoor and indoor humidity Keys 2 and 6 Room humidity setpoint adjustment (absolute) Keys 3, 5 and 7 No function Key 4 Toggle the display pages between temperature and humidity Key 8 Presence key, or Comfort extension
Air quality, CO2
Humidity and presence
Page 38
38 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Synco building automation and control system 2013-07-04
7 Synco building automation and
control system
7.1 Engineering
Tool ACS790 is used for engineering in KNX LT E–Mode with devices from the Synco 700 range. This tool is documented in Service- and Operating software ACS790 [6].
For ACS790, version 8.23 must be installed at a minimum.
During room operator unit mounting, the address labels can be peeled off the devices and stuck to a floor plan or similar to show the KNX IDs and the physical location in one place.
After mounting/installation, the devices are detected after updating the ACS790 device list. The devices can be easily identified in the device list based on the collected KNX IDs, and the physical addresses can be assigned as planned. As a result, commissioning requires only very little effort.
7.2 Commissioning
Depending on the environment, both type and number of adjustable parameters will vary. Prior to commissioning, all devices must be mounted as per the mounting instructions [2] and connected to bus cabling. If available, pushbuttons and external temperature sensors must also be connected to the device. Bus cabling must be tested.
Pushbutton actuation
Meaning
Short (< 0.5 s) Switch over to programming mode or acknowledge
display of a connection test.
No functions are executed when the programming button is pressed longer (> 0.5 s to 2 s).
Medium-long (>2 s and
<20 s)
Special mode (connection test for Desigo TRA). This
manufacturer-specific function can lock the device for programming mode for ca. 10 s. In this case, the LED
status indication briefly blinks (orange).
Long (> 20 s)
Reset to factory settings.
LED indication
Meaning
Orange
Feedback on special mode.
Red
Device is in programming mode.
All other indication types are irrelevant for KNX LTE-Mode.
Room sensor QMX3, KNX LTE –Mode controllers, and operator units are connected to power. Update first the ACS790 device list, then open.
Variant 1 (recommended)
1. Select a room operator unit from the device list via the KNX ID (KNX-IDs must be collected during mounting).
2. Double-click this line to open the "Address assignment" dialog.
or
ACS790 version
Recommendation: Keep the adhesive
address labels
Commissioning
prerequisites
Pushbuttons
LED status indication
KNX LTE–Mode
commissioning
Page 39
39 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Synco building automation and control system 2013-07-04
Variant 2
1. Set addressing mode for the room operator unit (briefly press button on
device LED is red).
2. In the ACS790 device list, use "Addressing mode…" to select the
currently active device Enter a physical address in the "Address assignment" dialog  Click "Write".
Enter a physical address and short description for the selected room operator
unit.
Close the "Address assignment“ dialog by clicking "Write…“.
Repeat these steps for all room operator units to be commissioned.
Then: Continue parameterization in ACS790.
The sensor can be operated as both KNX S-Mode and KNX LTE-Mode system at the same time. To do this, commissioning for both KNX S-Mode and KN X LTE­Mode is required. All parameters exist only once, i.e. all parameters excepting zone settings apply to both operating modes and are overwritten by ETS and ACS. For this reason, do not use ETS to set sending intervals > 15 min. for the measured values.
Only the sensor values (T, R.F., CO
2
) of the QMX3... devices can be used with Synco. To activate them set the zones accordingly in ACS. ACS settings and ETS settings do not influence each other.
KNX multi-Mode
commissioning
Page 40
40 / 40
Siemens Wall-mounted sensors and room operator units for KNX S-Mode and KNX LTE-Mode CM2N1602en_01 Building Technologies Synco building automation and control system 2013-07-04
7.3 Parameter description
Factory settings are boldfaced.
7.3.1 Communication
Designation Values Description
Geographical zone (apartment)
---, 1...126
Geographical zone, apartment or room group
Geographical zone (room)
---, 1…63
Geographical zone, room
Geographical zone (subzone)
---, 1…15
Geographical zone, subzone
7.3.2 Universal temperature sensor
Designation Values Description
LTE transmission zone
---, 1…4095
Sending zone for KN X LTE-Mode
Sensor correction -5...+5K
in 0.1K steps
0K
Correction of universal temperature sensor value
7.3.3 Room humidity sensor
Designation Values Description
LTE transmission zone
---, 1…4095
Sending zone for KN X LT E-Mode
7.3.4 Room air quality sensor
Designation Values Description
LTE transmission zone
---, 1…4095
Sending zone for KN X LT E-Mode
Altitude above sea level [m]
0…3000 m
0 m
Entry of altitude above sea level at measuring location to correct CO2 measured value
Siemens Switzerland Ltd. Infrastructure & Cities Sector Building Technologies Division Gubelstrasse 22 6301 Zug Switzerland Tel. +41 41-724 24 24
www.siemens.com/sbt
© 2013 Siemens Switzerland Ltd.
Subject to change
Loading...