6.3.4 Room air quality sensor .......................................................................... 46
3 / 46
Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_05
Building Technologies Contents 2018-09-14
0 About this document
Revision
Date
Changes
Section
Pages
• Communication objects
5.3 — 26
_03
2016-03-15
• Corrections/additions for V6.0
All
—
• Deleted section 5.1
_01
2013-07
First edition
—
—
Trademark(s)
Legal owner
KNX®
KNX Association, B - 1831 Brussels-Diegem Belgium
http://www.knx.org/
Trademarks
Copyright
Quality assurance
0.1 Revision history
_05 2018-09-14 • Corrections/additions for V6.1
_04 2017-03-10 • Corrections/additions for V6.1
• Added QMX3.P40
_02 2015-04 • Corrections for V5.1
0.2 Before you start
The trademarks used in this document and their lawful owners are listed in the
table below.. The use of trademarks is subject to international and domestic
provisions of the law.
All product names listed in the table are registered (®) or not registered (™)
trademarks of the owner listed in the table. These trademarks will not be indicated
elsewhere in the text (e.g. by use of symbols such as ® and ™) due to the
reference in this Section and to facilitate the reading of the text,
All
All —
5.3 —
This
document may be duplicated and distributed only with the express permission
of Siemens, and may be passed only to authorized persons or companies with the
required technical knowledge.
These documents were prepared with great care.
• The contents of all documents are checked at regular intervals.
• All necessary corrections are included in subsequent versions.
• Documents are automatically amended as a consequence of modifications and
corrections to the products described.
Please make sure that you are aware of the latest document revision date.
If you find any lack of clarity while using this document, or if you have any
criticisms or suggestions, please contact your local POC at the nearest branch
office. Addresses for Siemens RCs are available at www.siemens.com/sbt
4 / 46
Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_05
Building Technologies About this document 2018-09-14
Before using our products, it is important that you read the documents supplied
Abbr.
Description
ACS790
Engineering Tool for Synco devices
ETS
Engineering Tool Software http://www.knx.org/
KNX/ACS
Communication with KNX, configuration with ACS
KNX/ETS
Communication with KNX, configuration with ETS
Use of documents /
Request to the reader
Abbreviations
Naming convention
with or ordered at the same time as the products (equipment, applications, tools
etc.) carefully and in full.
We assume that persons using our products and documents are authorized and
trained appropriately and have the technical knowledge required to use our
products as intended.
For more details on the products and applications, please refer to:
• On the internet: "Technical product data and descriptions" at
www.siemens.com/gamma-td
• On the intranet (for Siemens employees only) at
http://step.bt.siemens.com/portal/index.html
• At your next Siemens branch office www.siemens.com/sbt or at your system
suppliers.
• From the support team in the headquarters fieldsupport-
zug.ch.sbt@siemens.com if no local POC is available.
Siemens assumes no liability to the extent allowed under the law for any losses
resulting from a failure to comply with the aforementioned points or for the
improper compliance of the same.
0.3 Abbreviations and naming conventions
T
he term "room operator unit" in this document always refers to all types:
QMX3.P02. P30. P34, P70 und P74.
0.4 Reference documents
The following documents are available at www.siemens.com/gamma-td
[1] Data sheet N1602
[2] Mounting instructions M1692
[3] Word template for labels (QMX3.P02, P37) M1602.1
[4] KNX Standard, Volume 3: System Specifications, Part 7, Chapter 2: Data
oint Types (http://www.knx.org/
P
[5] Service- and Operating software ACS790 (Data sheet N5649)
)
Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_05
Building Technologies About this document 2018-09-14
5 / 46
1 Devices
Temperature sensor Sensor for humidity
Sensor for CO
Air quality indicator
with LED Segmented backlit
display and touchkeys «Green leaf» LED Parameterizable touch-keys with LED display
dow for labels
1.1 Type summary
Product number Stock number Features
Sensors QMX3.P30
S55624-H103
2
X
Win
QMX3.P40
QMX3.P70
Room operator units QMX3.P02
QMX3.P34
QMX3.P74
QMX3.P37
Accessories QMX3.MP1
S55624-H11 6
S55624-H104
S55624-H107
S55624-H105
S55624-H106
S55624-H108
S55624-H11 0 Base plate for conduit box / cavity wall box for 68 mm
X X
X X X X
X X X
X X X
X X X X X X
X X X X X
diameter hole
20 pcs. per package
1.2 Equipment combinations
The room operator units are KNX certified and can be connected to all suitable
KNX devices, if the appropriate communication objects are available in the
application.
Use in the following BAC systems:
• GAMMA Building Management Systems / third-party devices
• Building automation and control systems with ETS configuration
Integration of third-party devices and free configuration.
• Synco700 (with ACS configuration) can only use the sensor information of types
QMX3.P30, QMX3.P40 and QMX3.P70.
6 / 46
Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_05
Building Technologies Devices 2018-09-14
1.3 Variant and device parts
1602J01_01
B
C
A
B2
B1
Note
• T
he devices are designed for wall-mounting (A). A conduit box is optional.
– Conduit box: Keep in mind the dimensions of the conduit box!
– Cable conduits on the wall: Keep a distance of 30 mm (from above) /
20 mm (from below) to the base plate (B), so that the device (C) c
napped onto the base plate.
s
• The base plate (B) has screw holes for all common flush-mount boxes.
The screw head height must not exceed 3 mm.
• The device (C) incorporates a KNX / PL-Link plug, a tool plug, and, depending
on the type, sensor element, keys, LCD panel, window for the label.
The cable can be pushed into channels on the rear.
• A KNX plug is enclosed with the devices
an be
The optional metal-reinforced base plate QMX3.MP1(B1) serves for two purposes:
• It is more rigid so that it does not bend when fixed in the middle with two screws
only (directly over a conduit box or a cavity wall box).
• It has a removable gray foam plate (B2) for mounting on a 68 mm diameter
cavity wall box. The plate compensates for the jutting edge of the box (s
m
ounting, page 13).
Q
MX3.MP1 is supplied in boxes with 20 pcs.
ee
7 / 46
Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_05
Building Technologies Devices 2018-09-14
1.4 Service and connection elements
Connection
Service LED (red) and
programming pin
Adhesive address
labels
Simplifying engineering
and commissioning
R1 QMX3... Room operator unit
N1 Controller, actor
Twisted pair
Service LED (red)
Pr
ogramming pin
The s
ervice element functions are described Commissioning, sections 5.2 and 6.2.
The dev
ices are supplied with peel-off adhesive address labels containing the
unique KNX ID as alphanumeric and barcode display.
The addr
ess label can peeled off the device during mounting and stuck to a floor
plan or similar. The floor plan thus contains the assignment of KNX IDs and
physical installation location. This greatly simplifies the following steps. In addition,
the procedure serves as the basis for the recommended engineering and
commissioning process. If the adhesive labels are lost, all information is still
available in printed form on the housing.
8 / 46
Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_05
Building Technologies Devices 2018-09-14
1.5 Dimensions
133.4
115
88.4
18
1602M01_01
80.5
78
.5
60
28.2
26.5
26
13.1
56.5
17.5
28.2
3.5
1602M02
Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_05
Building Technologies Devices 2018-09-14
9 / 46
1.6 Environmental compatibility, disposal
Note
1.6.1 General notes
This device was developed and manufactured with environmentally compatible
materials and procedures complying with all relevant environmental standards.
Note the following to dispose of the product following its useful life or in case of
replacement:
• Do not dispose of the device as part of standard household garbage, but as
special waste from plastic and steel, ferrite-magnet components.
This applies in particular to the PCB.
• For this reason, dispose of the components compatible with current
environmental, recycling, and disposal technologies.
Observe all local, applicable laws.
• The aim is to reuse as much of the basic materials as possible at the lowest
possible environmental impact. To this end, note any material and disposal
notes in individual components.
1.6.2 Environmental declaration
The product environmental declaration CM2E1602contains data on
environmentally compatible product design and assessments (RoHS compliance,
materials composition, packaging, environmental benefit, disposal)
1.6.3 Notes on FCC rules
This device complies with Part 15 of the FCC Rules. Operation is subject to the
following two conditions: (1) this device may not cause harmful interference, and
(2)this device must accept any interference received, including interference that
may cause undesired operation.
10 / 46
Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_05
Building Technologies Devices 2018-09-14
Please comply
with these notes
General
regulations
Safety
KNX bus supply
Maintenance
Setting up
cable ducts
Cable types
Separate cables
Unscreened cables
2 Safety and EMC optimization
2.1 Notes on safety
This section explains general and system-specific regulations for mains and
operating voltages. It includes important information for your safety and the safety
of the entire plant.
lease comply with the following general regulations during engineering and
P
execution:
• Electrical and mains power ordinances for the given country.
• Other applicable, national regulations.
• Building installation regulations for the given country.
• Regulations of the utility company.
• Diagrams, cable lists, dispositions, specifications, and orders by the customer or
authorized engineering office.
• Third-party regulations, e.g. by the general contractor or building owner.
he electrical safety for building automation and control systems by Siemens is
T
essentially based on safely separating low voltage from mains voltage.
2.2 Device-specific regulations
Warning,
Note permissible line lengths and topologies when planning and installing
controllers and field devices featuring KNX bus connection. Make sure the bus
supply complies with the KNX standard.
Do not open the device.
The device is maintenance free. Only the manufacturer can repair the device.
2.3 Notes on EMC optimization
When setting up cable ducts, separate strongly interfering cables from susceptible
entities.
• Interfering cables: Motor cables especially from motors supplied by inverters,
energy-supplying cables.
• Susceptible entities: Control cables, low voltage cables, interface cables, LAN
cables, digital and analog signal cables.
oth types of cables may be in the same cable duct, but in separat
• B
c
ompartments.
• If no three-sided, closed duct with separating wall is available, the interferi
ables must be separated by at least 150 mm from the others or placed i
c
s
eparate ducts.
• Crossings of strongly interfering cables with possibly susceptible entities must
be at a right angle.
• In exceptional cases, signal and interfering power cables may be run in parallel,
resulting in a high interference risk.
e
ng
n
Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_05
Building Technologies Safety and EMC optimization 2018-09-14
W
e recommend to generally use unscreened cables. Comply with the
manufacturer's installation recommendations for selecting unscreened cables. In
general, unshielded twisted pair cables have sufficient EMC properties for
technical building applications (including data applications) and do not require
consideration of coupling to surrounding earth.
11 / 46
3 Mounting and electrical installation
Service LED (red) Tool plug Programming pin
2602J02
*
)
Ambient conditions
Location (sensors,
room operator units)
Mounting instructions
Mounting over a
conduit box
1602J108
Comply with the following notes as well as the mounting instructions [2] to mount
the room sensor.
Note the permissible ambient temperature and humidity. See data sheet [1] for
environmental conditions.
he devices are suitable for wall mounting.
• T
• Recommended height: 1.50 m above floor.
• Do not mount the devices in recesses, shelves, behind curtains or doors, or
above or near heat sources.
• Avoid direct solar radiation and drafts.
• Seal the conduit box or the installation tube, as air currents can affect sensor
readings.
• Adhere to allowed ambient conditions.
• Moun
ting instructions M1602 are enclosed with the devices.
12 / 46
Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_05
Building Technologies Mounting and electrical installation 2018-09-14
he installing tube must be sealed or cold or warm air may enter the device and
*) T
cause faulty temperature readings by the internal sensor.
se a metal-reinforced base plate QMX3.MP1 instead oft he standard base plate
Monting over a cavity
wall box
1
1
223
U
delivered with the room operator unit.
he installing tube must be sealed or cold or warm air may enter the device and
T
cause faulty temperature readings by the internal sensor.
ixing the box on the cavity wall.
1 F
2 Fixing the QMX3.MP1 base plate on the box using 2 screws.
all mounting
W
4-wire cables
(daisy chain wiring)
3 The gray foam plate (removable) compensates for the jutting edge of the box so
that the plate is aligned with the wall.
Remove the breakout on the housing before putting the cable into the gaining channel.
Remove the cable coating, as it will not fit in
the gaining channel.
Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_05
Building Technologies Mounting and electrical installation 2018-09-14
13 / 46
Cable ducts on the wall
M
ax
. 6
5
9
.2
±
0
.1
5
1
6
0
2
z
11
0
54 ± 0.15
Dismounting / service:
Labels for QMX3.P02,
QMX3.P37
Insert label
1602Z106
1602J109
Keep a distance of 30 mm (from above) /
20 mm (from below) to the base plate,
so that the device can be snapped onto the
base plate.
30 mm
ample icons are available in the label
S
template M1602.1 (Download from
www.siemens.com/gamma-td
)
Information. e.g. on room operator unit
location or on room type
(free text)