Siemens QMX2.P33, QMX2.P43 User Manual

2017-07-
Wall-mounted sensors and room operator units for KNX PL-Link
Communicative sensors and room operator units with KNX PL
-
Link (for Desigo™ T
o-
QMX2.P33 / QMX2.P43
tal Room Automation).
Room temperature and humidity measurement (depending on types)
LCD display of room temperature, operating modes, etc.
Operation with 8 push buttons
Interface KNX PL-Link (for TRA, with plug and play functionality)
Powered over KNX PL-Link
A6V10733768_en--_a Building Technologies
2
Siemens
A6V10733768_en
--
_a
Use
Functions
Measure and display the room temperature and humidity (depending on types)
Operate room functions such as fan control and room operating modes
Indicate open windows, room air quality, outdoor temperature, and outdoor humidity
Function of the display elements and push buttons
Elements Functions
/
15.5 °C ● Temperature display in °C or °F / humidity in % r.h.
/
/
25.0 °C ● Display of relative or absolute setpoint for
/ / / /
/ /
/
/ /
A visible arrow Indicates an operable element
/ air quality in text, symbol, or ppm of CO
Toggling (button 1) between indoor and outdoor measurement (temperature, humidity and CO)
Indicates that a window is open (connected window contact is active)
Display of plant state (heating or cooling / inactive) Note: No manual switchover
temperature
Adjust setpoint using buttons 2 and 6
Display of present fan speed (when automatic)
Adjust fan speed using button 3 (or buttons 3 and 7
if room operating mode operation is disabled)
Display of room operating modes (w hen automatic)
Adjust room operating mode us ing button 7
Navigation: Toggle display/setpoint setting between temperature/humidity/CO using button 4
Operation of occupancy state (presence switch,
Comfort extension)
Activate Comfort extension using button 8 (only available if enabled)
Engineering functions (press buttons 1 and 8 simultaneously for 5s
- Programming mode (button 2), s ame function as programming pin (service pin) on the rear of device)
- Connection test (button 3) (not supported by ETS and ACS)
- Reset device to factory settings (button 4) Note: This operation is irreversible!
Indicates that the room operator unit is locked by the system.
- Operation disabled
- Display in line 1 shows the temperature from bus
2017-07-28
3
Siemens
A6V10733768_en
--
_a
Mechanical design
1 Frame for panel mounting 4 KNX PL-Link bus connector
2 Base plate
With screw holes for all common conduit boxes in regions such as EU, UK, etc.
With guide channels for wir ing from center, up, or bottom
3 Room operator unit
5 Jack connector for tool connection
Type summary
Product number Stock number Feature
QMX2.P33 S55624-H 118 Yes No
QMX2.P43 S55624-H 117 Yes Yes
Equipment combinations
All controllers from Desigo TRA.
Product documentation
Topic Title Document ID:
Installation, cable length, topology Mounting instructions A6V10733759
CE declar ation A5W90002237
Product environmental declaration A5W90002450
All documents can be downloaded from http://siemens.com/bt/download.
Notes
The subsections include important information for sale or that is essential for engineering.
Temperature sensor Humidity sensor
2017-07-28
4
Siemens
A6V10733768_en
--
_a
Security
CAUTION
National safety regulations
Observe national provisions and comply with the appropriate safety regulations.
Engineering
Mounting
Failure to comply with national safety regulations may result in personal injury and property damage
The device offers plug & play functionality.
The device receives its power from the connected room automation station via the KNX
PL-Link interface, or from the jack connector.
Engineering and commissioning using the ABT (Automation Building Tool) tool and SSA (Setup & Service Assistant) tool.
The devices are suitable for wall mounting and panel mounting.
Recommended height: 1.50 m above the floor.
Do not mount the devices in recesses, shelves, behind curtains or doors, or above or
near heat sources.
Avoid direct solar radiation and drafts.
Seal the conduit box or the installation tube if any, as air currents can affect sensor
readings.
Adhere to allowed ambient conditions.
2017-07-28