Siemens QFM3100, QFM2100, QFM2101, QFM3101, QFM4101 Installation Instructions Manual

...
Installation Instructions
QFM2100
±5%
QFM3100
±2%
QFM2101
±5%
QFM3101
±2%
QFM4101
±2% Certified
QFM2160
±5%
QFM3160
QFM3160D
QFM4160
±2% Cert.
QFM2171
±5%
QFM3171
QFM3171D
QFM4171
±2% Cert.
QFM2110
Pt 1K
QFM2120
Ni 1K
QFM3110
Pt 1K
±2%
QFM21…
155-748
QFM3160
155-749
QFM4160
155-750
Document No. 129-413
October 5, 2009
Relative Humidity & Temperature (RH/T) Duct Sensors
Product Descript ion
Relative Humidity (RH) and Relative Humidity & Temperature (RH/T) duct sensors monitor the relative humidity or the relative humidity and temperature in a duct, depending on the model.
Sensors are directly wired to the controller via twisted pair and/or three conductor cables (18 to 22 AWG). The number and type of cables required depends on the model selected. All field wiring is terminated in a terminal block on the sensor body.
Product Numbers
Table 1. Relative Humidity Only.
Product Number
Humidity
Signal
0 to 10 Vdc
4 to 20 mA
Accuracy
Additional Reference Document s
Product Number Technical Instructions
Required Tools
Phillips screwdrivers, No. 1 and No. 2
Wire cutters/strippers
Medium flat-blade screwdriver
Tape measure
Medium-duty electric drill
Marker or pencil
No. 26 (0.147-inch) drill bit
Small level
7/8-inch drill bit or hole saw
Two No. 8 × 1-inch sheet metal screws
Expected Installation Time
One hour
Table 2. Relative Humidity and Temperature.
Product Number
Applies to humidity only
Temperature
Signal
0 to 10 Vdc 0 to 10 Vdc
4 to 20 mA 4 to 20 mA
Ω Ω
Humidity
Signal
0 to 10 Vdc
Accuracy
±2%
±2%
±5%
NOTE: Sensor tips on QFM31… and QFM41…
models are field replaceable.
Item Number 129-413, Rev. CA Page 1 of 3
Prerequisites
Ensure that the appropriate field wiring is installed.
Appropriate wiring is one or more twisted pairs, or three conductor cables (plenum or non-plenum as required), within the maximum wiring run length for the individual equipment controller. The maximum recommended length is 750 feet (229 m).
Ensure that all wiring complies with National Electric Code (NEC) and local regulations.
Mounting Infor m a t ion
Locate the sensor:
In the center of a duct.
Away from fans, corners, heating and cooling
coils, and so on.
Where it receives adequate airflow for proper operation.
Document No. 129-413 Installation Instructions October 5, 2009
Instructions
1. Drill a 7/8-inch diameter hole into the duct at the desired location of the sensor.
2. Decide if the sensor will be mounted directly to the duct or if the mounting flange will be used.
Sensor Mounting Bracket Installation
a. Use the bracket as a template, and drill
two holes with a No. 26 (0.147-inch) drill bit. See Figure 1(B).
b. Attach the sensor mounting bracket and
gasket to the duct using two No. 8 × 1­inch sheet metal screws. See Figure 1(C1).
c. Insert the sensor in the duct through the
bracket and tighten the mounting screw to set the insertion depth. See Figure 1(C2).
Direct installation: a. Remove the sensor cover. b. Use the base as a template, and drill four
holes with a No. 26 (0.147-inch) drill bit. See Figure 1(B).
c. Insert the probe through the gasket and
into the hole. Secure the head to the duct with four No. 8 × 1-inch sheet metal screws.
3. Attach conduit or plenum wire to the sensor base. See Figures 1 and 2.
4. If you are using conduit, pull the field wiring through the conduit and into the sensor base.
5. Connect the field wiring to the sensor terminal block on the base. See Figures 3 through 7 for wiring diagrams.
6. Reinstall the sensor cover. See Figure 1(C6).
The installation is now complete.
Figure 1. RH/T Duct Sensor Installation. Figure 2. Conduit or Plenum Cable Wiring Installation.
NOTE: Figure 2 shows how to connect the conduit or plenum cable to the sensor head.
.
Page 2 of 3 Siemens Industry, Inc.
Loading...
+ 1 hidden pages