Siemens QFM2100, QFM3101, QFM2101, QFM4101, QFM2160 Installation Instructions Manual

...
Installation Instructions
Document No. 129-413
Q-Series Relative Humidity (RH) and Relative Humidity & Temperature (RH/T) Duct Sensors
Relative Humidity (RH) and Relative Humidity & Temperature (RH/T) duct sensors monitor the relative humidity or the relative humidity and temperature in a duct, depending on the model.
Additional Reference Documents
Product Number Technical Instructions
QFM21… 155-748 QFM3160 155-749 QFM4160 155-750
October 13, 2004
Sensors are directly wired to the controller via twisted pair and/or three conductor cables (18 to 22 AWG). The number and type of cables required depends on the model selected. All field wiring is terminated in a terminal block on the sensor body.
Product Numbers
Table 1. Relative Humidity Only.
Product Number
QFM2100 ±5% QFM3100 QFM2101 ±5% QFM3101 ±2% QFM4101
Table 2. Relative Humidity and Temperature.
Product Number
QFM2160 ±5% QFM3160 ±2% QFM4160 QFM2171 ±5% QFM3171 ±2% QFM4171 QFM2110 QFM2120 QFM2140 T1 PTC QFM3110
Applies to humidity only
NOTE: Sensor tips on QFM31… and QFM41…
Humidity
Signal
0 to 10 Vdc
4 to 20 mA
Temperature
Signal
0 to 10 Vdc 0 to 10 Vdc
4 to 20 mA 4 to 20 mA
Pt 1K Ni 1K
Pt 1K
Humidity
0 to 10 Vdc
Accuracy
±2%
±2% Certified
Signal
models are field replaceable.
Accuracy
±2% Cert.
±2% Cert.
±5%
±2%
Required Tools
Phillips screwdrivers, #1 and #2
Wire cutters/strippers
Medium flat-blade screwdriver
Tape measure
Medium-duty electric drill
Marker or pencil
No. 26 (0.147-inch) drill bit
Small level
7/8-inch drill bit or hole saw
Two No. 8 × 1-inch sheet metal screws
Expected Installation Time
One hour
Prerequisites
Ensure that the appropriate field wiring is installed.
Appropriate wiring is one or more twisted pairs, or three conductor cables (plenum or non-plenum as required), within the maximum wiring run length for the individual equipment controller. The maximum recommended length is 750 feet (229 m).
Ensure that all wiring complies with National Electric Code (NEC) and local regulations.
Mounting Information
Locate the sensor:
In the center of a duct.
Away from fans, corners, heating and cooling
coils, and so on.
Where it receives adequate airflow for proper operation.
Item Number 129-413, Rev. 011 Page 1 of 3
Document No. 129-413 Installation Instructions October 13, 2004
Instructions
1. Drill a 7/8-inch diameter hole into the duct at the desired location of the sensor.
2. Decide if the sensor will be mounted directly to the duct or if the mounting flange will be used.
Sensor Mounting Bracket Installation
a. Use the bracket as a template, and drill
two holes with a No. 26 (0.147-inch) drill bit. See Figure 1(B).
b. Attach the sensor mounting bracket and
gasket to the duct using two No. 8 × 1­inch sheet metal screws. See Figure 1(C1).
c. Insert the sensor in the duct through the
bracket and tighten the mounting screw to set the insertion depth. See Figure 1(C2).
A
1
2
Direct installation:
a. Remove the sensor cover.
b. Use the base as a template, and drill four
holes with a No. 26 (0.147-inch) drill bit. See Figure 1(B).
c. Insert the probe through the gasket and
into the hole. Secure the head to the duct with four No. 8 × 1-inch sheet metal screws.
3. Attach conduit or plenum wire to the sensor base. See Figures 1 and 2.
4. If you are using conduit, pull the field wiring through the conduit and into the sensor base.
5. Connect the field wiring to the sensor terminal block on the base. See Figures 3 through 7 for wiring diagrams.
6. Reinstall the sensor cover. See Figure 1(C6).
The installation is now complete.
3
2
BC
Four holes required
if sensor base is
mounted directly onto
the duct
2.4 (80)
See Figure 2 for conduit or plenum cable
wiring instructions
4
5
2.4
(60)
max. 6.1
0.83
Two holes required
if flange is used to
mount the sensor
onto the duct
SEN0353R1
(21)
2.4
(60)
Figure 1. RH/T Duct Sensor Installation. Figure 2. Conduit or Plenum Cable Wiring Installation.
NOTE: Figure 2 shows how to connect the conduit or plenum cable to the sensor head.
(154) mm
1
6
3
2
1
.
Page 2 of 3
Loading...
+ 1 hidden pages