Siemens QBM Series, QBM3100U025U, QBM3100U1, QBM3100U2.5, QBM3100U5 Installation Instructions Manual

...
Air Differential Pressure Sensors
The Siemens QBM Series Air Differential Pressure Sensors use a well-proven ceramic technology. They deliver temperature-compensated sensor signals for registering airflow in HVAC systems and for the measurement of differential pressures in environmental, laboratory and cleanroom applications.
Installation Instructions
Document No. 129-903
October 4, 2013
Expected Installation Time
30 minutes
Prerequisites
Even though the device is protected against electro­magnetic interference, installation and cabling must be carried out correctly to ensure interference immunity.
Product Numbers
Product Number Percent
Accuracy
QBM3100U025U +/- 0.25 QBM3100U1 1 QBM3100U2.5 2.5 QBM3100U5 5 QBM3100U10
+/-1% FS
Pressure
Range
Inches WC
(Water
Column)
10
Contents
Sensor
Conduit Adapter
Use shielded cables for the signal and control
lines with the connecting lead of the shield being kept as short as possible. The connection point of the shielding depends on the existing connection conditions.
Never route signal and control cables together with the trunk line or feeder cables of motors, cylinder coils, rectifiers, and so on. The cables must be routed in conductive and grounded cable conduits. This applies especially to long­distance cables, or environments where the cables are exposed to strong radio waves from broad casting stations.
CAUTION:
Prior to mounting or removing the
Do not mount sensors in locations
Warning/Caution Notations
WARNING:
CAUTION:
Personal injury/loss of life may occur if you do not follow the procedures as specified. Equipment damage/loss of data may occur if you do not follow the procedures as specified.
Significant thermal changes in the
sensor, verify that the system is depressurized.
subject to high pressure pulses.
sensor environment can lead to a zero shift. As a result, the measuring value displayed in a depressurized state will read zero. This kind of drift can be corrected by zero point reset.
Required Tools
Small, Phillips screwdriver
Small, flat-blade screwdriver
Adjustable wrench
Item Number 129-903, Rev. BA Page 1 of 2
Document No. 129-903
SSEN0024R2
Installation Instructions October 4, 2013
Installation
Recommended mounting positions:
Vertical, with the pressure connections facing downward, drain off possible condensed water (factory calibration).
Horizontal, with the cover facing downward.
Horizontal, with the cover facing upward.
NOTE: Mount the transmitter with a minimum 0.39
inches (10 mm) distance to magnetic material. If this is not possible there may be an error of up to -.004 inch WC for transmitters mounted on sheet steel.
Figure 1. Recommended Mounting Positions.
Wiring Diagram
Figure 3. Wiring Diagram, 4 to 20 mA.
Tubing Connections
ZP – Push Zero Point Reset
The installation position is variable by using the Zero Point Reset button. Pressure variations can be reset after installation.
Ensure the power supply is not interrupted when storing customer settings (ZP – reset).
Figure 4. High and Low Pressure Connections.
The installation is now complete.
Figure 2. ZP Push Zero Point Reset.
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners. © 2013 Siemens Industry, Inc.
Siemens Industry, Inc.
Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 USA +1-847-215-1000
Your feedback is important to us. If you have
comments about this document, please send them
to SBT_technical.editor.us.sbt@siemens.com
Document No. 129-903
Printed in the USA
Page 2 of 2
Loading...