Siemens RVS43.143, RVS63.243, RVS63.283, AVS75.390, AVS37.294 User Guide

...
5 (1)

 

RVS43..

 

RVS63..

 

AVS75..

Albatros2

AVS37..

QAA75..

Boiler controllers

QAA78..

User manual

QAA55..

Edition 2.0 Controller series B CE1U2354en

11. May 2007

Building Technologies

HVAC Products

2/156

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

 

11. May 2007

Table of contents

 

1

Summary .........................................................................................................

9

 

1.1

Type summary...............................................................................................

10

 

2

Safety notes...................................................................................................

11

 

2.1

Product liability ..............................................................................................

11

 

3

Mounting and installation...............................................................................

12

 

3.1

Regulations....................................................................................................

12

 

3.2

Basic units RVS… .........................................................................................

12

 

 

Planning.........................................................................................................

12

 

 

Mounting method...........................................................................................

13

 

 

Dimensions and drilling plan..........................................................................

13

 

3.2.1

Connection terminals of RVS43.143 .............................................................

14

 

3.2.2

Connection terminals of RVS63.243 .............................................................

14

 

3.2.3

Connection terminals of RVS63.283 .............................................................

15

 

 

Terminal markings .........................................................................................

16

 

3.3

Extension module AVS75.390.......................................................................

18

 

 

Dimensions and drilling plan..........................................................................

18

 

3.3.1

Connection terminals of AVS75.390..............................................................

18

 

 

Terminal markings .........................................................................................

19

 

 

Assignment of terminals ................................................................................

19

 

3.4

Operator unit AVS37.294 ..............................................................................

20

 

 

Mounting method...........................................................................................

20

 

 

Connections...................................................................................................

20

 

 

Dimensions....................................................................................................

20

 

3.5

Operator unit AVS37.390 ..............................................................................

21

 

 

Connections...................................................................................................

21

 

 

Dimensions....................................................................................................

21

 

3.6

Room unit QAA55… ......................................................................................

22

 

 

Planning.........................................................................................................

22

 

 

Mounting method...........................................................................................

22

 

 

Connections...................................................................................................

22

 

 

Dimensions and drilling plan..........................................................................

22

 

3.7

Room unit QAA75… ......................................................................................

23

 

 

Planning.........................................................................................................

23

 

 

Mounting method...........................................................................................

23

 

 

Connections...................................................................................................

23

 

 

Dimensions and drilling plan..........................................................................

24

 

3.8

Wireless components ....................................................................................

25

 

3.8.1

Radio module AVS71.390 .............................................................................

25

 

 

Planning.........................................................................................................

25

 

 

Mounting method...........................................................................................

25

 

 

Connection ....................................................................................................

25

 

 

Radio connection...........................................................................................

25

 

 

Dimensions and drilling plan..........................................................................

25

 

3.8.2

Room unit QAA78.610...................................................................................

26

 

 

 

3/156

 

 

 

 

Siemens Switzerland Ltd.

User manual

 

CE1U2354en

HVAC Products

Summary

 

11. May 2007

 

 

Planning .........................................................................................................

26

 

 

Mounting with base ........................................................................................

26

 

 

Connection / power supply.............................................................................

27

 

 

Radio connection ...........................................................................................

27

 

 

Dimensions and drilling plan ..........................................................................

28

 

3.8.3

Wireless outside sensor AVS13.399..............................................................

29

 

 

Mounting method ...........................................................................................

29

 

 

Radio connection ...........................................................................................

30

 

 

Dimensions and drilling plan ..........................................................................

30

 

3.8.4

Radio repeater AVS14.390 ............................................................................

31

 

 

Mounting method ...........................................................................................

31

 

 

Connections ...................................................................................................

31

 

 

Radio connection ...........................................................................................

31

 

 

Dimensions and drilling plan ..........................................................................

31

 

3.8.5

Checking the wireless components ...............................................................

32

 

3.9

Power supply AVS16.290 ..............................................................................

32

 

 

Mounting notes ..............................................................................................

32

 

 

Mounting method ...........................................................................................

32

 

 

Connections ...................................................................................................

32

 

4

Commissioning ..............................................................................................

34

 

4.1

Basic units......................................................................................................

34

 

5

Handling.........................................................................................................

35

 

5.1

QAA75.. / QAA78… / AVS37.........................................................................

35

 

5.1.1

Operation .......................................................................................................

35

 

 

Operating elements........................................................................................

35

 

 

Display choices ..............................................................................................

36

 

 

Selecting heating mode .................................................................................

36

 

 

Selecting DHW heating mode........................................................................

37

 

 

Adjusting the room temperature setpoint .......................................................

37

 

 

Occupancy button ..........................................................................................

37

 

 

Displaying information....................................................................................

37

 

5.1.2

Programming .................................................................................................

40

 

 

Setting principle .............................................................................................

40

 

 

Example: “Setting the time of day“.................................................................

40

 

5.1.3

User levels .....................................................................................................

41

 

 

Setting structure “Enduser“ ............................................................................

42

 

 

Setting structure ”Heating engineer“ ..............................................................

42

 

5.1.4

Overview of settings.......................................................................................

43

 

5.1.5

AVS37.390Operation .....................................................................................

62

 

 

Operating elements........................................................................................

62

 

 

Display choices ..............................................................................................

62

 

 

Selecting the operating mode ........................................................................

62

 

 

Adjusting the room temperature setpoint .......................................................

63

 

 

Adjusting the nominal DHW setpoint .............................................................

63

 

 

Displaying information....................................................................................

63

 

 

Setting principle .............................................................................................

64

 

 

Example: “Setting the time of day“.................................................................

64

 

5.1.6

User levels .....................................................................................................

65

 

5.1.7

Overview of settings.......................................................................................

66

4/156

 

 

 

 

 

 

 

Siemens Switzerland Ltd.

User manual

 

CE1U2354en

HVAC Products

Summary

 

11. May 2007

 

5.2

QAA55... ........................................................................................................

67

 

5.2.1

Operation.......................................................................................................

67

 

 

Operating elements .......................................................................................

67

 

 

Display choices..............................................................................................

67

 

5.2.2

Programming .................................................................................................

67

 

6

The settings in detail......................................................................................

68

 

6.1

Time of day and date.....................................................................................

68

 

6.2

Operator section ............................................................................................

68

 

 

Operation and display....................................................................................

68

 

 

Heating circuit assignment ............................................................................

69

 

 

Room sensor .................................................................................................

70

 

 

Device data....................................................................................................

70

 

6.3

Radio .............................................................................................................

70

 

 

Binding...........................................................................................................

70

 

 

Device list radio .............................................................................................

71

 

6.4

Time programs ..............................................................................................

71

 

 

Switching points.............................................................................................

71

 

 

Standard program..........................................................................................

72

 

6.5

Holidays.........................................................................................................

72

 

6.6

Heating circuits ..............................................................................................

72

 

 

Operating mode.............................................................................................

72

 

 

Setpoints........................................................................................................

72

 

 

Heating curve ................................................................................................

73

 

 

ECO functions ...............................................................................................

74

 

 

Flow temperature setpoint limitations ............................................................

75

 

 

Room influence..............................................................................................

75

 

 

Room temp limitation.....................................................................................

76

 

 

Boost heating.................................................................................................

77

 

 

Quick setback ................................................................................................

77

 

 

Optimum start / stop control ..........................................................................

78

 

 

Increase of Reduced setpoint........................................................................

79

 

 

Overtemperature protection pump heating circuit .........................................

79

 

 

Mixing valve control .......................................................................................

79

 

 

Floor curing function ......................................................................................

80

 

 

Excess heat draw ..........................................................................................

81

 

 

Buffer storage tank / primary controller .........................................................

81

 

 

Speed-controlled pump .................................................................................

81

 

 

Remote ..........................................................................................................

82

 

6.7

DHW ..............................................................................................................

82

 

 

Setpoints........................................................................................................

82

 

 

Priority ...........................................................................................................

82

 

 

Legionella function.........................................................................................

83

 

 

Circulating pump............................................................................................

83

 

6.8

Pump H1/H2/H3 ............................................................................................

84

 

 

Pump H1/H2/H3 ............................................................................................

84

 

6.9

Swimming pool ..............................................................................................

84

 

 

Setpoints........................................................................................................

84

 

 

Priority ...........................................................................................................

84

 

 

Plant hydraulics .............................................................................................

85

 

6.10

Primary controller / system pump ..................................................................

85

 

 

 

5/156

 

 

 

 

Siemens Switzerland Ltd.

User manual

 

CE1U2354en

HVAC Products

Summary

 

11. May 2007

 

 

Primary controller / system pump ..................................................................

85

 

6.11

Boiler..............................................................................................................

85

 

 

Operating mode .............................................................................................

85

 

 

Setpoints ........................................................................................................

85

 

 

Minimum limitation of the return temperature ................................................

86

 

 

Output data ....................................................................................................

86

 

 

2 x 1 cascade.................................................................................................

86

 

6.12

Cascade.........................................................................................................

87

 

 

Control ...........................................................................................................

87

 

 

Boiler sequence .............................................................................................

87

 

 

Minimum limitation of the return temperature ................................................

88

 

6.13

Solar...............................................................................................................

89

 

 

Charging controller (dT) .................................................................................

89

 

 

Priority............................................................................................................

89

 

 

Start function..................................................................................................

90

 

 

Frost protection for the collector ....................................................................

91

 

 

Overtemperature protection for the collector .................................................

91

 

 

Medium’s evaporation temperature ...............................................................

91

 

 

Speed control.................................................................................................

92

 

 

Yield measurement ........................................................................................

92

 

6.14

Solid fuel boiler ..............................................................................................

92

 

 

Operating mode .............................................................................................

92

 

 

Setpoints ........................................................................................................

92

 

 

Boiler / burner control.....................................................................................

92

 

6.15

Buffer storage tank.........................................................................................

93

 

 

Automatic locks..............................................................................................

93

 

 

Overtemperature protection ...........................................................................

93

 

 

Recooling .......................................................................................................

93

 

 

Plant hydraulics..............................................................................................

94

 

 

Return diversion.............................................................................................

94

 

 

Partial charging ..............................................................................................

95

 

 

Full charging ..................................................................................................

95

 

6.16

DHW storage tank..........................................................................................

96

 

 

Charging control.............................................................................................

96

 

 

Overtemperature protection ...........................................................................

96

 

 

Recooling .......................................................................................................

96

 

 

Electric immersion heater ..............................................................................

96

 

 

Plant hydraulics..............................................................................................

98

 

 

Speed-controlled pump..................................................................................

98

 

6.17

Instantaneous DHW heater............................................................................

98

 

 

Setpoints ........................................................................................................

98

 

 

Mixing valve control .......................................................................................

98

 

6.18

Configuration..................................................................................................

99

 

 

Heating circuits 1 and 2 .................................................................................

99

 

 

DHW sensor B3 .............................................................................................

99

 

 

DHW controlling element Q3 .........................................................................

99

 

 

Separate circuit ..............................................................................................

99

 

 

Boiler............................................................................................................

100

 

 

Solar.............................................................................................................

103

 

 

Output relay QX ...........................................................................................

104

 

 

Input sensor BX ...........................................................................................

107

 

 

Input H1/H3..................................................................................................

107

 

 

Input EX2 .....................................................................................................

110

6/156

 

 

 

 

 

 

 

Siemens Switzerland Ltd.

User manual

 

CE1U2354en

HVAC Products

Summary

 

11. May 2007

 

 

Mixing valve groups basic unit.....................................................................

111

 

 

Extension module ........................................................................................

112

 

 

QX extension module ..................................................................................

113

 

 

BX extension module...................................................................................

114

 

 

H2 extension module...................................................................................

114

 

 

10V output UX .............................................................................................

114

 

 

Types of sensors/readjustments..................................................................

115

 

 

Building and room model.............................................................................

115

 

 

Frost protection for the plant........................................................................

115

 

 

External requirements .................................................................................

116

 

 

sensor state .................................................................................................

116

 

 

Parameter reset...........................................................................................

116

 

 

Plant diagram ..............................................................................................

117

 

 

Device data..................................................................................................

119

 

6.19

LPB system .................................................................................................

120

 

 

Address / power supply ...............................................................................

120

 

 

Central functions..........................................................................................

120

 

 

Clock............................................................................................................

121

 

6.20

Errors...........................................................................................................

122

 

6.21

Maintenance / service..................................................................................

122

 

 

Maintenance functions.................................................................................

122

 

 

Chimney sweep ...........................................................................................

123

 

 

Economy mode............................................................................................

123

 

 

Manual operation.........................................................................................

123

 

 

Simulations ..................................................................................................

124

 

 

Telephone customer service .......................................................................

124

 

6.22

Input / output test.........................................................................................

125

 

6.23

State ............................................................................................................

125

 

 

Messages ....................................................................................................

125

 

6.24

Diagnostics of heat source ..........................................................................

128

 

6.25

Diagnostics consumers ...............................................................................

128

 

6.26

List of displays .............................................................................................

129

 

6.26.1

Error code....................................................................................................

129

 

6.26.2

Maintenance code .......................................................................................

130

 

6.26.3

Special operation code ................................................................................

130

 

7

Plant diagrams.............................................................................................

131

 

7.1

Basic diagrams ............................................................................................

131

 

7.1.1

Basic diagram RVS43.143 ..........................................................................

131

 

7.1.2

Basic diagram RVS63.243 ..........................................................................

132

 

7.1.3

Basic diagram RVS63.283 ..........................................................................

132

 

7.2

Versions of heat sources .............................................................................

133

 

7.3

Extra functions in general ............................................................................

134

 

 

Solar ............................................................................................................

134

 

 

Boiler ...........................................................................................................

136

 

 

Storage tank temperature............................................................................

137

 

 

Heating circuit..............................................................................................

137

 

 

Heat converter .............................................................................................

138

 

 

Swimming pool ............................................................................................

138

 

 

Pressureless header....................................................................................

138

 

 

 

7/156

 

 

 

 

Siemens Switzerland Ltd.

User manual

 

CE1U2354en

HVAC Products

Summary

 

11. May 2007

 

Extra functions .............................................................................................

139

7.4

Extra functions with AVS75.390...................................................................

140

 

Legend mains voltage..................................................................................

142

 

Legend low-voltage......................................................................................

143

8

Technical data..............................................................................................

144

8.1Basic units RVS…........................................................................................144

8.2

Extension module AVS75.390 .....................................................................

145

8.3

Operator unit and room units AVS37...

/ QAA7x… / QAA55.. .....................146

8.4

Power supply AVS16.290 ............................................................................

147

8.5

Radio module AVS71.390............................................................................

147

8.6

Wireless outside sensor AVS13.399............................................................

148

8.7

Radio repeater AVS14.390 ..........................................................................

149

8.8

Sensor characteristics..................................................................................

150

8.8.1

NTC 1 k........................................................................................................

150

8.8.2

NTC 10 k......................................................................................................

151

8.8.3

PT1000 ........................................................................................................

151

9

Revision history............................................................................................

155

8/156

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Summary

11. May 2007

1 Summary

This User manual describes the products listed in the following table and covers handling and configuration of the controls for readers ranging from endusers to heating engineers.

Type reference

Series

Name

(ASN)

 

 

RVS43.143

A

Basic unit boiler

RVS63.243

B

Basic unit boiler

RVS63.283

B

Basic unit boiler

AVS75.390

B

Extension module

AVS37.294

B

Operator unit

AVS37.390

A

Operator unit basic

QAA75.610

B

Room unit, wired

QAA75.611

B

Room unit with backlight, wired

QAA78.610

B

Room unit, wireless

QAA55.110

A

Room unit basic

AVS16.290

A

Power section

AVS71.390

A

Radio module

AVS14.390

A

Radio repeater

AVS13.399

A

Wireless outside sensor

The following products are described in separate pieces of documentation:

QAC34

Outside sensor NTC 1 kΩ

QAD36

Strap-on temperature sensor NTC 10 kΩ

QAZ36

Immersion temperature sensor NTC 10 kΩ

 

 

9/156

 

 

 

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Summary

11. May 2007

1.1 Type summary

Operation with room unit

Operation with operator unit “basic”

(optionally with additional room unit)

Operation with operator unit “clear-text”

(optionally with additional room unit)

Wired

 

RF

 

 

 

B

 

 

B

 

 

 

 

 

 

 

A

 

 

A

 

 

 

 

 

 

 

D

 

 

 

 

 

T

 

T

D

F

 

 

 

 

 

 

 

 

 

 

B

E1

C

B

E1

C

 

 

 

 

A

 

 

A

 

 

 

 

 

 

 

 

 

2359Z66

 

 

2359Z67

B

E

 

B

E

 

 

 

 

 

A

 

 

A

 

 

 

 

 

 

 

ABasic unit RVS…

BPower section AVS16…

CRoom unit QAA75… / 78…

DOutside sensor AVS13…

EOperator unit AVS37.294 (clear-text) E1 Operator unit AVS37.390 (basic)

FRadio module AVS71…

10/156

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Summary

11. May 2007

2 Safety notes

2.1 Product liability

The products may only be used in building services plant and applications as described in this document

When using the products, all requirements specified in chapters "Handling" and "Technical data" must be satisfied

The local regulations (for installation, etc.) must be complied with

Do not open the units. If not observed, warranty becomes void.

 

 

11/156

 

 

 

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Safety notes

11. May 2007

3 Mounting and installation

3.1 Regulations

Electrical installation • Prior to installing the units, power must be turned off

The connections for mains and low-voltage are separated

For wiring, the requirements of safety class II must be satisfied. Sensor and power cables must not be run in the same cable duct

3.2 Basic units RVS…

Planning

Air circulation around the controller must be ensured, allowing the unit to emit the heat produced by it.

A clearance of at least 10 mm must be provided for the unit's cooling slots at the top and bottom of the housing.

That space should not be accessible and no objects should be placed there. If the controller is enclosed in another (insulating) casing, a clearance of up to 100 mm must be observed around the cooling slots

The controller is designed conforming to the directives for safety class II devices mounted in compliance with these regulations

Power to the controller may only be supplied when completely fitted. If this is not observed, there is a risk of electric shock hazard near the terminals and through the cooling slots

The controller must not be exposed to dripping water.

Permissible ambient temperature when mounted and when ready to operate: 0...50 °C

Power cables must be clearly segregated from low-voltage cables (sensors) observing a distance of at least 100 mm

Mounting location

• Boiler

 

• Control panel

 

• Housing for wall mounting

12/156

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Mounting and installation

11. May 2007

Mounting method

Screwed

2359Z09

Dimensions and drilling plan

L

L1

B

B1

2358M01

On DIN rail

 

 

 

 

 

 

 

 

 

 

 

 

A2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B2

 

 

 

2359Z11

B1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A: Mounting

/ B: Removal

 

 

 

 

 

 

Note:

To mount the controller on a DIN rail, a mounting clip is required!

Dimensions in mm

 

L

B

H

L1

B1

RVS63…

280.7

120.7

51.7

270

110

RVS43…

180.7

120.7

51.7

170

110

Total height required

2359Z10

Dimension X:

 

Connectors with tongues minimum 70 mm

Connector without tongues minimum 60 mm

x

 

 

13/156

 

 

 

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Mounting and installation

11. May 2007

Siemens RVS43.143, RVS63.243, RVS63.283, AVS75.390, AVS37.294 User Guide

3.2.1Connection terminals of RVS43.143

 

 

 

U

 

 

 

 

T

 

 

 

S

 

 

 

R

Q

 

 

 

P

N

 

 

L

 

 

 

 

QX1

 

 

N

Y2

 

 

 

N Y1

Q2

 

 

N

Q3

 

 

N

SK2 SK1

4 S3 T2 T1 N

 

 

L1

S3 L1 N

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

050110A

RVS43.143/109

000020

S050110000020

 

1PRVS13.143/109

 

2354Z08

M BX2

M BX1

M B1

M H1

M B9

M B3

- -

M B2

- G+

CL-

CL+

CLCL+

MB DB

X50

X60

X30

BSB

 

LPB

n

n

p

n

k

h

 

f

 

 

b

 

 

b

a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G+ CLCL+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b

 

 

 

 

 

 

 

 

 

 

3.2.2Connection terminals of RVS63.243

 

 

 

Z

 

 

 

U

 

 

 

U

 

 

 

 

 

 

U

 

 

 

 

 

 

T

 

 

 

 

 

S

 

 

 

 

R

 

Q

 

 

 

 

 

 

 

 

 

P

 

 

 

N

 

 

 

L

 

 

 

 

 

 

 

 

 

QX4

QX4 FX4

EX2

 

QX3

 

 

N

QX2

 

 

N

 

QX1

 

 

 

 

N

Y2

 

 

 

 

N

Y1

Q2

 

 

 

 

N

Q3

 

 

 

N

SK2

SK1

4

S3

T2

T1

N

 

 

 

 

L1

S3

L1

N

 

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- - - - - - -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RVS63.243/109

061107B

000020

S061107000020

 

1PRVS63.243/109

 

2354Z06

M UX

M BX4

M BX3

M H3

- -

M BX2

M BX1

M B1

M H1

M B9

M B3

- -

M B2

- G+

CLCL+

CLCL+

CLCL+

MB DB

X50

X60

X30

BSB

LPB

n

n

n

n

 

n

n

p

n

k

h

 

f

 

b

b

b

a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G+ CLCL+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b

 

 

 

 

 

 

 

 

14/156

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Mounting and installation

11. May 2007

3.2.3Connection terminals of RVS63.283

 

Z

 

 

 

U

 

 

 

U

 

 

 

 

T

 

 

S

 

 

 

 

 

U

 

 

 

 

 

 

T

 

 

 

 

S

 

 

 

 

R

 

Q

 

 

 

 

 

 

 

 

 

P

 

 

 

N

 

L

 

QX4

QX4 FX4 EX2

QX3

 

 

N

QX2

 

 

N

Y6

 

 

 

N Y5

Q6

 

 

N

QX1

 

 

 

 

N

Y2

 

 

 

 

N

Y1

Q2

 

 

 

N

Q3

 

 

 

N

SK2

SK1

4

S3

T2

T1

N

 

 

 

 

L1

S3

L1

N

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

061107B

RVS63.283/109

000020

S061107000020

 

1PRVS63.283/109

 

2354Z07

M UX

M BX4

 

M BX3

M H2

 

M B12

 

M BX2

 

M BX1

 

M B1

 

M H1

 

M B9

 

M B3

- -

M B2

 

- G+

 

CL-

CL+

 

CLCL+

 

CLCL+

 

MB DB

 

X50

 

X60

 

X30

 

BSB

 

LPB

n

n

 

n

n

 

p

 

n

 

n

 

p

 

n

 

k

 

h

 

f

 

 

 

b

 

 

b

 

b

 

a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G+ CLCL+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15/156

 

 

 

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Mounting and installation

11. May 2007

Terminal markings

Mains voltage

Use

Space

Connector type

 

L

Live AC 230 V basic unit

N

 

 

 

 

L

AGP4S.05A/109

 

 

 

 

 

 

 

 

 

 

 

Protective earth

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

Neutral conductor

 

 

 

 

 

 

 

 

L1

Live AC 230 V burner

 

 

 

 

 

 

 

 

S3

Output burner fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L1

Live burner

P

AGP8S.07A/109

 

 

 

 

 

 

 

Protective earth

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

Neutral conductor

 

 

 

 

 

 

 

 

T1

Phase 1st burner stage

 

 

 

 

 

 

 

 

T2

1st burner stage on

 

 

 

 

 

 

 

 

S3

Input burner fault

 

 

 

 

 

 

 

4

 

 

Input 1st burner stage hours run

 

 

 

 

 

 

 

 

SK1

Safety loop

Q

AGP8S.02E/109

 

SK2

Safety loop

 

 

 

 

 

 

 

 

N

Neutral conductor

R

AGP8S.03A/109

 

 

 

 

 

 

 

Protective earth

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q3

DHW charging pump / diverting valve

 

 

 

 

 

 

 

 

N

Neutral conductor

S

AGP8S.03B/109

 

 

 

 

 

 

 

Protective earth

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q2

1st heating circuit pump

 

 

 

 

 

 

 

 

Y1

1st heating circuit mixing valve opening

T

AGP8S.04B/109

 

N

Neutral conductor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protective earth

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y2

1st heating circuit mixing valve closing

 

 

 

 

 

 

 

 

N

Neutral conductor

U

AGP8S.03C/109

 

 

 

 

 

 

 

Protective earth

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

QX1

1st multifunctional output

 

 

 

 

 

 

 

 

N

Nullleiter

S

AGP8S.03B/109

 

 

 

 

 

 

 

Protective earth

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q6

2nd heating circuit pump

 

 

 

 

 

 

 

 

Y5

2nd heating circuit mixing valve opening

T

AGP8S.04B/109

 

N

Neutral conductor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protective earth

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y6

2nd heating circuit mixing valve closing

 

 

 

 

 

 

 

 

N

Neutral conductor

U

AGP8S.03C/109

 

 

 

 

 

 

 

Protective earth

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

QX2

2nd multifunctional output

 

 

 

 

 

 

 

 

N

Neutral conductor

U

AGP8S.03C/109

 

 

 

 

 

 

 

Protective earth

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

QX3

3rd multifunctional output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EX2

Multifunctional input

Z

AGP8S.04C/109

 

FX4

Phase 4th Multifunctional output

 

 

 

 

 

 

 

 

(T6)

(phase 2nd burner stage)

 

 

 

 

 

 

 

 

 

 

4th Multifunctional output off

 

 

 

 

 

 

 

 

QX4

 

 

 

 

 

 

 

 

(T7)

(2nd burner stage off)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

QX4

4th Multifunctional output on

 

 

 

 

 

 

 

 

(T8)

(2nd burner stage on)

 

 

 

 

 

 

 

16/156

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Mounting and installation

11. May 2007

Low-voltage

 

Use

Space

Connector type

 

BSB

Service tool OCI700

-

-

 

LPB

Local Process Bus

-

-

 

system

 

 

 

 

X60

Radio module AVS71.390

-

-

 

X50

Extension module AVS75.390

-

AVS82.490/109

 

X30

Operator unit / boiler control panel

-

AVS82.491/109

 

DB

LPB data

 

AGP4S.02H/109

 

MB

LPB ground

 

 

 

CL+

BSB data

 

AGP4S.02A/109

 

CL-

BSB ground

b

 

 

CL+

Room unit 2 data

 

AGP4S.02A/109

 

CL-

Room unit 2 ground

b

 

 

CL+

Room unit 1 data

 

AGP4S.02A/109

 

CL-

Room unit 1 ground

b

AGP4S.03D/109

 

G+

Room unit power supply 12 V

 

 

 

B2

Boiler sensor

 

AGP4S.02B/109

 

M

Ground

f

 

 

B3

DHW sensor top

 

AGP4S.02C/109

 

M

Ground

h

 

 

B9

Outside sensor

 

AGP4S.02D/109

 

M

Ground

k

 

 

H1

Digital / DC 0...10 V input

 

AGP4S.02F/109

 

M

Ground

n

 

 

B1

Flow temperature sensor HK1

 

AGP4S.02G/109

 

M

Ground

p

 

 

BX1

Multifunctional sensor input 1

 

AGP4S.02F/109

 

M

Ground

n

 

 

BX2

Multifunctional sensor input 2

 

AGP4S.02F/109

 

M

Ground

n

 

 

B12

Flow temperature sensor HK2

 

AGP4S.02G/109

 

M

Ground

p

 

 

H3

Digital / DC 0...10 V input

 

AGP4S.02F/109

 

M

Ground

n

 

 

BX3

Multifunctional sensor input 3

 

AGP4S.02F/109

 

M

Ground

n

 

 

BX4

Multifunctional sensor input 4

 

AGP4S.02F/109

 

M

Ground

n

 

 

UX

DC 0…10 V output

n

AGP4S.02F/109

 

M

Ground

 

 

 

 

17/156

 

 

 

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Mounting and installation

11. May 2007

3.3 Extension module AVS75.390

For planning, mounting location and mounting method, refer to the information given for the basic modules.

Dimensions and drilling plan

L

L1

Dimensions in mm

 

B

B1

 

 

 

 

 

 

 

 

 

 

 

2358M01

 

 

 

 

L

B

H

L1

B1

 

AVS75.390

108.7

120.9

51.7

98

110

Connections

The AVS75.390 extension module must be connected to terminal X50 of the basic unit

 

using the AVS83.490/109 connecting cable. The connectors are coded.

3.3.1Connection terminals of AVS75.390

 

 

 

 

S

 

 

 

 

T

 

 

N

 

 

 

L

 

 

 

 

 

 

- - -

QX23

 

 

N

QX22

 

 

 

N QX21

N

 

 

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

050110A

AVS75.390/109

000020

S050110000020

 

1PAVS75.390/109

 

2359Z49

11 2

21 2

=Module 1

=Module 2

M H2

M BX22

M BX21

-

-X50

- -

X30

n

n

n

 

 

 

 

18/156

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Mounting and installation

11. May 2007

Terminal markings

Mains voltage

 

 

 

 

 

Use

 

Space

 

Connector type

 

L

 

Live AC 230 V basic unit

 

N

 

 

 

 

 

L

 

AGP4S.03E/109

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protective earth

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

Neutral conductor

 

 

 

 

 

 

 

 

 

 

 

QX21

 

Assignment according to function

T

 

AGP8S.04B/109

 

N

 

Neutral conductor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protective earth

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

QX22

 

Assignment according to function

 

 

 

 

 

 

 

 

 

 

 

N

 

Neutral conductor

S

 

AGP8S.03B/109

 

 

 

 

 

 

Protective earth

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

QX23

 

Assignment according to function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low-voltage

 

 

 

Use

 

Space

 

Connector type

 

X30

 

Operator unit / boiler control panel

-

 

 

 

 

 

 

 

AVS82.491/109

 

X50

 

Basic unit

 

 

 

 

 

 

 

 

 

AVS82.490/109

 

BX21

 

Assignment according to function

 

 

 

 

 

 

 

 

 

AGP4S.02F/109

 

M

Ground

 

n

 

 

 

BX22

 

Assignment according to function

 

 

 

 

 

 

 

 

 

AGP4S.02F/109

 

M

Ground

 

n

 

 

 

H2

 

Digital / DC 0...10 V input

 

 

 

 

 

 

 

 

 

AGP4S.02F/109

 

M

Ground

 

n

 

 

Assignment of terminals

Using the 2 parameters

Function extension module 1 (operating line 6020)

Function extension module 2 (operating mode 6021) usage of the respective module will be defined.

 

 

19/156

 

 

 

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Mounting and installation

11. May 2007

3.4 Operator unit AVS37.294

Mounting method

Installation

2358Z31

Removal

2358Z30

2358Z32

Connections

The AVS37.294 operator unit must be connected to terminal X30 of the basic unit using the AVS82.491/109 connecting cable. The connectors are coded.

Dimensions

 

27

 

 

 

 

17

 

 

2358M03

 

96

90

144

 

42.4

Panel cutout

(144)

 

0.5...3.0

 

 

+0.8

(96)

920

138+1

0

2358M05

20/156

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Mounting and installation

11. May 2007

3.5 Operator unit AVS37.390

Connections

The AVS37.390 operator unit must be connected to terminal X30 of the basic unit using the AVS82.491/109 connecting cable. The connectors are coded.

Dimensions

2354M01

0,5

A

13

A Control panel, front

 

 

21/156

 

 

 

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Mounting and installation

11. May 2007

3.6 Room unit QAA55…

Planning

@

The room unit should be located in the main living room while giving consideration to the following points:

The place of installation should be chosen so that the sensor can capture the room temperature as accurately as possible without getting adversely affected by direct solar radiation or other heat or refrigeration sources (about 1.5 meters above the floor)

In the case of wall mounting, there must be sufficient clearance above the unit, enabling it to be fitted and removed

When the unit is removed from its base, power is cut off so that the unit is out of operation.

Mounting method

2284Z33a

2284Z34a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• The controller must not be exposed to dripping water

Connections

 

4

3

 

 

 

 

6

5

2

1

Terminal

Designation

QAA55..

 

 

 

 

 

 

 

2284Z40

1

CL+

BSB data

 

 

 

2

CL-

BSB ground

 

 

 

 

Dimensions and drilling plan

96

 

2282M02

 

4,2

 

 

 

 

 

 

 

96

91

 

 

 

 

 

 

 

2 1

56

60

 

 

 

 

 

 

47

 

 

2359Z27

 

 

 

56

 

 

 

 

 

 

 

 

 

60

 

 

 

22/156

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Mounting and installation

11. May 2007

3.7 Room unit QAA75…

Planning

@

The room unit should be located in the main living room while giving consideration to the following points:

The place of installation should be chosen so that the sensor can capture the room temperature as accurately as possible without getting adversely affected by direct solar radiation or other heat or refrigeration sources (about 1.5 meters above the floor)

In the case of wall mounting, there must be sufficient clearance above the unit, enabling it to be fitted and removed

When the unit is removed from its base, power is cut off so that the unit is out of operation.

Mounting method

2359Z25

2359Z20

2359Z21

2359Z26 2359Z24

Connections

Terminal

Designation

QAA75.610

QAA75.611

1

CL+

BSB data

BSB data

2

CL-

BSB ground

BSB ground

3

G+

Reserved

Power supply DC 12 V

 

 

23/156

 

 

 

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Mounting and installation

11. May 2007

Dimensions and drilling plan

4,2

 

56

60

 

100

2359Z50

185

56

 

60

100

80

 

82

2359Z12

42

 

 

24/156

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Mounting and installation

11. May 2007

3.8 Wireless components

The wireless components should be located such that transmission will be as interference-free as possible. The following criteria must be observed:

Not in the vicinity of electrical cables, strong magnetic fields or equipment like PCs, TV sets, microwave ovens, etc.

Not near larger metal structures or constructional elements with fine metal meshes such as special glass or special concrete

The distance to the transmitter should not exceed 30 meters or 2 floors

3.8.1Radio module AVS71.390

The radio module extends the product range by introducing wireless communication. With this type of device, the system components, such as room units, transmit data with no need for laying cables.

Planning

Do not install the radio module inside metal casings (e.g. inside a boiler).

Mounting method

2359Z23

A LED

B Button

2359Z57

Connection

The prefabricated cable is to be connected to terminal X60 of the controller. Prior to connecting, the basic unit must be disconnected from power!

Radio connection

Establishment of the wireless connection is described in the following sections which cover the relevant radio-controlled units.

Dimensions and drilling plan

2354Z11

43

 

 

25/156

 

 

 

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Mounting and installation

11. May 2007

3.8.2Room unit QAA78.610

Planning

@

The room unit should be located in the main living room while giving consideration to the following points:

The place of installation should be chosen so that the sensor can capture the room temperature as accurately as possible without getting adversely affected by direct solar radiation or other heat or refrigeration sources (about 1.5 meters above the floor)

In the case of wall mounting, there must be sufficient clearance above the unit, enabling it to be fitted and removed

Mounting with base

2359Z26

2359Z25 2359Z20

2359Z21

2359Z22

26/156

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Mounting and installation

11. May 2007

Mounting without base

2359Z61

Connection / power supply

Radio connection

Establishment

The room unit is powered by three 1.5 V Alkali batteries type AA (LR06).

Make the radio connection in the vicinity of the radio module prior to mounting so that all system are within easy reach.

Prerequisite for the radio connection is that all components receive power, which means that the radio module must be correctly connected to the basic unit and the batteries must be correctly installed in the room unit.

1.Press the button on the installed radio module for at least 8 seconds until the LED on the radio module starts flashing at high frequency.

2.Press OK on the room unit to switch to programming.

3.Press the info button for at least 3 seconds and select operating level “Commissioning“ with the setting knob. Then, press OK.

4.Select operating page “Operator unit“ and press OK.

5.Select operating line “Used as“ (operating line 40) and make the appropriate selection. Then, press OK.

6.Select operating page “Radio“ and press OK.

7.Select setting line “Binding“ (line 120). Then, press OK.

8.Set the setting knob to “YES“ and press OK. Connection establishment is started.

9.The display shows the progress of connection establishment in %. This process can take 2 to 120 seconds.

10.The connection is established when “Device ready” appears and the LED on the radio module extinguishes

Testing

The test is made to check the quality of the radio link.

 

• The test can be aborted by pressing the ESC button.

While the radio link can be opened on the controller, the test should be made at the location where the room unit will be installed

On the room unit, as described above (points 2 through 4), select operating page “Radio“ and activate the test mode on setting line “Test mode“ (line 121).

 

 

27/156

 

 

 

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Mounting and installation

11. May 2007

Example of a display during the test:

The digits on the left shows telegrams that have been sent, the digits on the right telegrams that have been received. The test will be ended after 24 telegrams. The test is considered successful when at least 50 % of the telegrams sent have been received.

Operator section Testmode

If the test was not successful, some other mounting location is to be selected or the AVS14.390 radio repeater can be used.

2359Z140

Dimensions and drilling plan

185

39

11

9

 

67

 

 

100

82

2359Z12

42

 

 

4,2

56

60

80

2359Z50

100

28/156

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Mounting and installation

11. May 2007

3.8.3Wireless outside sensor AVS13.399

• The radio transmitter must be installed inside the building.

The radio transmitter’s mounting location should be chosen such that batteries can be easily changed.

Mounting method

Radio transmitter

Outside sensor

 

 

2359Z33

2359Z30

 

2359Z54

2359Z32

 

2359Z59

 

 

2359Z31

 

 

2359Z53

 

 

Battery

AAA

AAA

 

 

 

Battery transit

 

2359Z55

tab

 

 

Connections

The outside sensor is to be connected to the radio transmitter via a 2-core cable, the

 

connections are interchangeable.

 

The room unit is powered by 2 pieces 1.5 V Alkali batteries type AAA (LR03).

 

 

29/156

 

 

 

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Mounting and installation

11. May 2007

Radio connection

Establishment

Make the radio connection in the vicinity of the radio module prior to mounting so that all system are within easy reach.

Prerequisite for the radio connection is that all components receive power, which means that the radio module must be correctly connected to the basic unit and the

batteries must be correctly installed in the room unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Press the button on the radio module for at least 8

 

 

 

 

 

 

 

 

 

 

 

 

 

LED

 

 

seconds until the LED on the radio module starts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

flashing at high frequency.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AAA

 

 

 

 

 

AAA

 

 

2.

Press the button on the transmitter of the wireless

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

outside sensor for at least 8 seconds until that LED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

also starts flashing at high frequency.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2359Z58

3.

The connection is established when the LED on the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Button

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

radio module extinguishes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.Press the button on the transmitter of the wireless outside sensor briefly again until the LED extinguishes.

Testing

The test is made to check the quality of the radio link.

 

• The test can be aborted by pressing the ESC button.

While the radio link can be opened on the controller, the test should be made at the location where the room unit will be installed

1.Press button 3 on the transmitter of the wireless outside sensor for a maximum of 8 seconds until the LED starts flashing at low frequency.

2.When radio communication works, the LED on the radio module flashes briefly at 10-second intervals.

3.After the test, press the button on the transmitter of the wireless outside sensor again briefly until the LED extinguishes.

Dimensions and drilling plan

100

 

 

2359Z16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

91,6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90

 

 

32

79,8

 

49,7

 

4,2

 

 

5,5

3

 

 

2 1

56

60

4

6

5,5

 

 

 

 

 

 

 

 

2359Z27

 

 

Ø 14,1

 

56

 

 

24,5

25

 

 

 

 

 

60

 

 

 

49,5

1811M02

 

 

 

 

 

 

 

 

 

 

 

 

1811M01

30/156

Siemens Switzerland Ltd.

User manual

CE1U2354en

HVAC Products

Mounting and installation

11. May 2007