Siemens Schweiz AG User ManualCE1U2354en
HVAC Products 23. August 2007
1 Summary
The present User Manual describes the products listed in the following table and covers
handling and configuration of the controls for readers ranging from end users to heating
engineers.
Type reference
(ASN)
RVS43.143 B Basic unit boiler
RVS63.243 B Basic unit boiler
RVS63.283 B Basic unit boiler
AVS75.390 B Extension module
AVS37.294 B operator unit
AVS37.390 A Operator unit basic
QAA75.610 B Room unit, wired
QAA75.611 B Room unit with backlight, wired
QAA78.610 B Room unit, wireless
QAA55.110 A Room unit basic
AVS16.290 A Power section
AVS71.390 A Radio module
AVS14.390 A Radio repeater
AVS13.399 A Wireless outside sensor
The following products are described in separate pieces of documentation:
QAC34 Outside sensor NTC 1 kΩ
QAD36 Strap-on temperature sensor NTC 10 kΩ
QAZ36 Immersion temperature sensor NTC 10 kΩ
Series Name
9/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Type summary 23. August 2007
Wired
1.1 Type summary
1.1.1 Topology
Mobile, SMS, Pager, Fax,
WEB,
Remote
Wireless
Room
Unit
wired
BSB-W
HMI
Basic Unit
HMI
(RU)
wired
RVSxx
LPB
Basic Unit
RVS...
Service Unit
(RU)
wired
Extension
mod. AVS75…
(max. 2)
Service Tool
ACS700
OCI700
Telephone
Network
Telephone
SMS
OCI611
BSB :
Boiler System Bus
LPB : Local Process Bus
Mobile, SMS, Pager, Fax,
WEB,
Remote
Room
Unit
wireless
BSB-W
RF
Toutside
BSB-RF
RF
module
RF
Repeater
Basic Unit
RVSxx
LPB
Basic Unit
RVS...
HMI
(RU)
wireless
Service Unit
(RU)
wireless
Extension
mod. AVS75…
(max. 2)
Service Tool
ACS700
OCI700
Telephone
Network
Telephone
SMS
OCI611
BSB :
Boiler System Bus
LPB : Local Process Bus
10/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Type summary 23. August 2007
Operation with room
unit
Operating options
Wired Wireless
Operation with “basic”
operator unit
(optionally with additional
room unit)
Operation with “clear-text”
operator unit
(optionally with additional room
unit)
B
A
D
T
B
A
E1
EB
C
T
2359Z66
B
A
D
B
A
B
F
E1
E
C
2359Z67
A
A Basic unit RVS…
B Power section AVS16…
C Room unit QAA75… / 78… / QAA55..
D Outside sensor AVS13…
E Operator unit AVS37.294 (clear-text)
E1 Operator unit AVS37.390 (basic)
F Radio module AVS71…
A
11/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Type summary 23. August 2007
2 Safety notes
2.1 Product liability
• The products may only be used in building services plant and applications as
described above
• When using the products, all requirements specified in the chapters on "Handling"
and "Technical data" must be satisfied
• Local regulations (for installation, etc.) must be complied with
• Do not open the units. If not observed, warranty becomes void.
12/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Product liability 23. August 2007
Electrical installation
Engineering
Mounting location
3 Mounting and installation
3.1 Regulations
• Prior to installing the controller, the power supply must be turned off
• The connections for mains and low-voltage are separated
• The wiring must be made in compliance with the requirements of safety class II. This
means that sensor and mains cables may not be run in the same duct
3.2 Basic units RVS…
• Air circulation around the controller must be ensured, allowing the unit to emit the
heat produced by it.
A clearance of at least 10 mm must be provided for the controller's cooling slots
which are situated a the top and bottom of the housing.
The space should not be accessible and no objects should be placed there. If the
controller is enclosed in another (insulating) casing, a clearance of up to 100 mm
must be observed around the cooling slots
• The controller is designed conforming to the directives for safety class II mounted in
compliance with these regulations.
• Power to the controller may only be supplied when completely fitted. If this is not
observed, there is a risk of electric shock hazard near the terminals and through the
cooling slots.
• The controller may not be exposed to dripping water.
• Permissible ambient temperature when mounted and when ready to
operate: 0..50°C.
• Power cables must be clearly segregated from low-voltage cables (sensors)
observing a distance of at least 100 mm
• Boiler
• Control panel
• Housing for wall mounting
13/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Regulations 23. August 2007
Mounting method
Screwed
On DIN rail
Dimensions and drilling plan
BL1B1
A2
A1
2359Z09
L
B1
A: Mounting / B: Removal
Note:
To mount the controller on a DIN rail, a mounting clip
is required!
B2
Dimensions in mm
2359Z11
Total height required
RVS63…
RVS43…
2359Z10
x
2358M01
L B H L1 B1
281 121 52 270 110
181 121 52 170 110
Dimension X:
Connectors with tongues minimum 70 mm
Connector without tongues minimum 60 mm
14/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Basic units RVS… 23. August 2007
3.2.1 Connection terminals of RVS43.143
050110A
000020RVS43.143/109
S05011000002 0
1PRVS13.143/109
2354Z08
3.2.2 Connection terminals of RVS63.243
Z
UU
U
061107B
000020RVS63.243/10 9
S061107000020
1PRVS63.243/109
T
SRQ
PLN
2354Z06
15/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Basic units RVS… 23. August 2007
3.2.3 Connection terminals of RVS63.283
061107B
000020RVS63.283/10 9
S061107000020
1PRVS63.283/109
2354Z07
16/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Basic units RVS… 23. August 2007
Terminal markings
Mains voltage
Use Slot Connector type
L Live AC 230 V basic unit N L AGP4S.05A/109
Protective earth
N Neutral conductor
L1 Live AC 230 V burner
S3 Output burner fault
L1 Phase burner P AGP8S.07A/109
Protective earth
N Neutral conductor
T1 Phase 1st burner stage
T2 1st burner stage on
S3 Input burner fault
4 Input 1st burner stage operating hours
SK1 Safety loop Q AGP8S.02E/109
SK2 Safety loop
N Neutral conductor R AGP8S.03A/109
Protective earth
Q3 DHW charging pump / diverting valve
N Neutral conductor S AGP8S.03B/109
Protective earth
Q2
Y1
1st heating circuit pump
1st heating circuit mixing valve opening
N Neutral conductor
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Basic units RVS… 23. August 2007
Low voltage
Use Slot Connector type
BSB Service tool OCI700 - LPB Service tool OCI700 - X60 Radio module AVS71.390 - X50 Extension module AVS75.390 X30 Operator unit / boiler control panel -
DB LPB data
MB LPB ground
CL+ BSB data
AVS82.490/109
AVS82.491/109
AGP4S.02H/109
AGP4S.02A/109
CL- BSB ground b
CL+ Room unit 2 data
AGP4S.02A/109
CL- Room unit 2 ground b
CL+ Room unit 1 data
AGP4S.02A/109
CL- Room unit 1 ground b AGP4S.03D/109
G+ Room unit power supply 12 V
B2 Boiler sensor
AGP4S.02B/109
M Ground f
B3 DHW sensor top
AGP4S.02C/109
M Ground h
B9 Outside sensor
AGP4S.02D/109
M Ground k
H1 Digital / DC 0...10 V input
AGP4S.02F/109
M Ground n
B1 Flow temperature sensor HK1
AGP4S.02G/109
M Ground p
BX1 Multifunctional sensor input 1 AGP4S.02F/109
M Ground n
BX2 Multifunctional sensor input 2 AGP4S.02F/109
M Ground n
B12 Flow temperature sensor HK2
AGP4S.02G/109
M Ground p
H3 Digital / DC 0...10 V input
AGP4S.02F/109
M Ground n
BX3 Multifunctional sensor input 3
AGP4S.02F/109
M Ground n
BX4 Multifunctional sensor input 4
AGP4S.02F/109
M Ground n
UX DC 0…10 V output n AGP4S.02F/109
M Ground
18/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Basic units RVS… 23. August 2007
Dimensions and drilling plan
Connections
3.3 Extension module AVS75.390
For planning, mounting location and mounting method, refer to the information given for
the basic modules.
L
Dimensions in mm
BL1B1
2358M01
AVS75.390
The AVS75.390 extension module is connected to terminal
the
AVS83.490/109 connecting cable. The connectors are coded.
L B H L1 B1
108.7 120.9 51.7 98 110
X50 of the basic unit using
3.3.1 Connection terminals of AVS75.390
050110A
AVS75.390/109
S050110000020
1PAVS75.390/109
000020
1
2359Z49
2
12
1
2
= Module 1
= Module 2
19/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Extension module AVS75.390 23. August 2007
Terminal markings
Mains voltage
Low voltage
Assignment of terminals
Use Slot Connector type
L Live AC 230 V basic unit N L AGP4S.03E/109
Protective earth
N Neutral conductor
QX21 Assignment according to function T AGP8S.04B/109
N Neutral conductor
Protective earth
QX22 Assignment according to function
N Neutral conductor S AGP8S.03B/109
Protective earth
QX23 Assignment according to function
Use Space Connector type
X30 Operator unit / boiler control panel X50 Basic unit
AVS82.491/109
AVS82.490/109
BX21 Assignment according to function AGP4S.02F/109
M Ground n
BX22 Assignment according to function AGP4S.02F/109
M Ground n
H2 Digital / DC 0...10 V input AGP4S.02F/109
M Ground n
The two following parameters define the usage of the respective module:
• Function extension module 1 (operating line 6020)
• Function extension module 2 (operating line 6021)
.
20/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Extension module AVS75.390 23. August 2007
3.4 Operator unit AVS37.294
Mounting method
Installation
2358Z30
Removal
2358Z31
2358Z32
Connections
Ground
Panel cutout
The AVS37.294 operator unit must be connected to terminal X30 of the basic unit using
the AVS82.491/109 connecting cable. The connectors are coded.
27
17
2358M03
96
144
90
42.4
(144)
0.5...3.0
0
+0.8
92
(96)
+1
138
0
2358M05
21/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Operator unit AVS37.294 23. August 2007
Connections
Dimensions
3.5 Operator unit AVS37.390
The AVS37.390 operator unit must be connected to terminal X30 of the basic unit using
the AVS82.491/109 connecting cable. The connectors are coded.
2354M01
0,5
13
A
A Control panel, front
22/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Operator unit AVS37.390 23. August 2007
Engineering
Mounting method
3.6 Room unit QAA55…
@
The room unit should be located in the main living room while giving consideration to
the following points:
• The place of installation should be chosen so that the sensor can capture the room
temperature as accurately as possible without getting adversely affected by direct
solar radiation or other heat or refrigeration sources (about 1.5 meters above the floor)
• In the case of wall mounting, there must be sufficient clearance above the unit,
enabling it to be fitted and removed
When the unit is removed from its base, power is cut off so that the unit is out of
operation.
2284Z33a
2284Z34a
Connections
Dimensions and drilling plan
• The controller must not be exposed to dripping water
34
562
1
2284Z40
1 CL+ BSB data
2 CL- BSB ground
2282M02
1
6
9
9
96
7
4
4,2
56
12
56
60
2359Z27
60
23/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Room unit QAA55… 23. August 2007
Engineering
Mounting method
3.7 Room unit QAA75…
@
The room unit should be located in the main living room while giving consideration to
the following points:
• The place of installation should be chosen so that the sensor can capture the room
temperature as accurately as possible without getting adversely affected by direct
solar radiation or other heat or refrigeration sources (about 1.5 meters above the floor)
• In the case of wall mounting, there must be sufficient clearance above the unit,
enabling it to be fitted and removed
When the unit is removed from its base, power is cut off so that the unit is out of
operation.
Connections
2359Z25
2359Z20
2359Z26
2359Z24
Terminal Name QAA75.610 QAA75.611
1 CL+ BSB data BSB data
2 CL- BSB ground BSB ground
3 G+ Reserved Power supply DC 12 V
2359Z21
24/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Room unit QAA75… 23. August 2007
Dimensions and drilling plan
4,2
56
60
100
2359Z50
56
60
80
82
42
185
100
2359Z12
25/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Room unit QAA75… 23. August 2007
Engineering
Mounting method
3.8 Wireless components
The wireless components should be located such that transmission will be as
interference-free as possible. The following criteria must be observed:
• Not in the vicinity of electrical cables, strong magnetic fields or equipment like PCs,
TV sets, microwave ovens, etc.
• Not near larger metal structures or constructional elements with fine metal meshes
such as special glass or special concrete
• The distance to the transmitter should not exceed 30 meters or 2 floors
3.8.1 Radio module AVS71.390
The radio module extends the product range by introducing wireless communication.
With this type of device, the system components, such as room units, transmit data with
no need for laying cables.
Do not install the radio module inside metal casings (e.g. inside a boiler).
2359Z23
Terminals
Radio connection
Dimensions and drilling plan
LED
A
Button
B
2359Z57
The prefabricated cable is to be connected to terminal X60 of the controller.
Prior to connecting the module, the basic unit must be disconnected from power!
Establishment of the wireless connection is described in the following sections which
cover the relevant radio-controlled units.
2354Z11
43
26/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Wireless components 23. August 2007
Engineering
Mounting with base
3.8.2 Room unit QAA78.610
@
The room unit should be located in the main living room while giving consideration to
the following points:
• The place of installation should be chosen so that the sensor can capture the room
temperature as accurately as possible without getting adversely affected by direct
solar radiation or other heat or refrigeration sources (about 1.5 meters above the floor)
• In the case of wall mounting, there must be sufficient clearance above the unit,
enabling it to be fitted and removed
2359Z26
2359Z20
2359Z25
2359Z21
2359Z22
27/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Wireless components 23. August 2007
Mounting without base
Connection / power supply
Radio connection
Establishing the link
Testing
2359Z61
The room unit is powered by 3 pieces 1.5 V alkaline batteries type AA (LR06).
Make the radio connection in the vicinity of the radio module prior to mounting so that
all system are within easy reach.
Prerequisite for the radio connection is that all components receive power, which
means that the radio module must be correctly connected to the basic unit and the
batteries must be correctly installed in the room unit.
1. Press the button on the installed radio module for at least 8 seconds until the LED
on the radio module starts flashing at high frequency.
2. Press OK on the room unit to switch to programming.
3. Press the info button for at least 3 seconds and select operating level
“Commissioning“ with the setting knob. Then, press OK.
4. Select operating page “Operator unit“ and press OK.
5. Select operating line “Used as“ (operating line 40) and make the appropriate
selection. Then, press OK.
6. Select operating page “Radio“ and press OK.
7. Select setting line “Binding“ (line 120). Then, press OK.
8. Set the setting knob to “YES“ and press OK. Connection establishment is started.
9. The display shows the progress of connection establishment in %. This process can
take 2 to 120 seconds.
10. The connection is established when “Device ready” appears and the LED on the
radio module extinguishes
The test is made to check the quality of the radio link.
• The test can be aborted by pressing the ESC button.
• While the radio link can be opened on the controller, the test should be made at the
location where the room unit will be installed
On the room unit, as described above (points 2 through 4), select operating page
“Radio“ and activate the test mode on setting line “Test mode“ (line 121).
28/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Wireless components 23. August 2007
Dimensions and drilling plan
Example of a display during the test:
The digits on the left shows telegrams that have
been sent, the digits on the right telegrams that
have been received. The test will be ended
after 24 telegrams. The test is considered
successful when at least 50 % of the telegrams
Bedieneinheit
Testmode
sent have been received.
If the test was not successful, some other mounting location is to be selected or the
AVS14.390 radio repeater can be used.
9
185
11
39
67
4,2
2359Z50
100
82
42
2359Z12
56
60
80
100
29/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Wireless components 23. August 2007
Mounting method
3.8.3 Wireless outside sensor AVS13.399
• The radio transmitter must be installed inside the building.
• The radio transmitter’s mounting location should be chosen such that batteries
can be easily changed.
RF transmitter
2359Z30
2359Z33
Outside sensor
2359Z54
2359Z32
2359Z59
2359Z31
2359Z53
Battery
AAA
AAA
Battery transit
2359Z55
tab
Connections
The outside sensor is to be connected to the radio transmitter via a 2-core cable, the
connections are interchangeable.
The room unit is powered by two 1.5 V alkaline batteries type AAA (LR03).
30/180
Siemens Schweiz AG User ManualCE1U2354en
HVAC Products Wireless components 23. August 2007