Siemens QAA70 User Manual

QAA70 Room Unit
Basic Documentation
Edition 2.1 SW-Version 1.20 or higher CE1P1638E
17.04.2000
Siemens Building Technologies
Landis & Staefa Division
2/20 Siemens Building Technologies CE1P1638E
Landis & Staefa Division 17.04.2000
Contents
1 Summary.........................................................................................................5
1.1 Brief description...............................................................................................5
1.2 Functions.........................................................................................................5
1.3 Product range..................................................................................................5
1.4 Field of use......................................................................................................5
1.4.1 Target market..................................................................................................5
1.4.2 Types of houses and buildings........................................................................6
1.4.3 Types of heating plants ...................................................................................6
1.5 Product liability ................................................................................................6
2 Handling ..........................................................................................................6
2.1 Engineering and mounting...............................................................................6
2.2 Electrical installation........................................................................................7
2.2.1 Regulations for installation ..............................................................................7
2.2.2 Connection diagrams.......................................................................................7
2.3 Commissioning................................................................................................8
2.4 Display and operating elements......................................................................8
2.4.1 Operating elements.........................................................................................8
2.4.2 Display.............................................................................................................8
2.5 Operation.........................................................................................................9
2.5.1 Selecting the operating mode..........................................................................9
2.5.2 Info button........................................................................................................9
2.5.3 Temperature readjustments ..........................................................................10
2.5.4 Presence button ............................................................................................10
3 Parameter settings for the end-user..............................................................11
3.1 General..........................................................................................................11
3.2 Setting the temperatures...............................................................................11
3.3 Heating program............................................................................................12
3.4 Setting the time of day...................................................................................12
3.5 Actual values.................................................................................................12
3.6 Holiday function.............................................................................................13
3.7 Retrieving the default values.........................................................................13
3.8 Default values................................................................................................13
3.9 Status displays ..............................................................................................14
4 Operation by the heating engineer................................................................14
4.1 Activating the service and parameter setting level........................................14
4.2 Settings..........................................................................................................14
4.3 Leaving the service and parameter setting level...........................................15
3/20
Siemens Building Technologies Room Unit QAA70 CE1P1638E Landis & Staefa Division Contents 17.04.2000
5 Example of plant............................................................................................16
6 Technical data................................................................................................17
7 Dimensions....................................................................................................18
4/20 Siemens Building Technologies Room Unit QAA70 CE1P1638E
Landis & Staefa Division Contents 17.04.2000
1 Summary
1.1 Brief description
The QAA70 is a digital, multi-functional room unit designed to enhance room comfort and the functions of the following types of heating controllers and boiler management units:
RVP digital of the D-series
RVP54...
ALBATROS controllers type RVA...
LGM11...
The room unit enables all key functions to be controlled from the living room.
1.2 Functions
Ergonomic and function-specific operating levels and clear assignment of the basic functions:
Operating mode, setpoint readjustment and presence button are directly accessible
Various actual values can be called up with the Info button
Additional functions can be parameterized after opening the cover
Specific service level with protected access
Every setting or change is shown on the display and thus acknowledged
Heating program with up to three heating periods per day (can be individually
selected)
Holiday program
Possibility of resetting the heating program to the default values
Programming lock (protection against tampering)
Additional connection facility for:
One remote temperature sensor, or for
Changing the operating mode via the telephone network using an external switch,
or for
Changing the operating mode via a window switch
Minimum backup of 12 hours; individually programmed values remain stored in non-
volatile memory
Elegant housing made of recyclable plastic
1.3 Product range
Room unit QAA70
Remote room temperature sensor QAW44…
1.4 Field of use
1.4.1 Target market
The QAA70 room unit has been designed for the OEM market. It is delivered directly to the boiler manufacturer and is conceived to enhance the functions and the operation of boiler temperature controllers.
5/20
Siemens Building Technologies Room Unit QAA70 CE1P1638E Landis & Staefa Division Summary 17.04.2000
1.4.2 Types of houses and buildings
The room unit is suited for the following types of houses and buildings, depending on the type of controller with which it is used:
Single- and two-family houses
Smaller multi-family houses
Holiday houses and villas
Small commercial buildings
1.4.3 Types of heating plants
Suitable for all standard heating systems, such as radiators, convectors, underfloor and ceiling heating systems. Especially suited for heating plants that use a pump heating circuit.
1.5 Product liability
The room unit may only be used in building services plant and applications as indi­cated above
When using the unit, all requirements specified in “Technical data” must be ob­served
Local regulations for electrical installations must be complied with
2 Handling
2.1 Engineering and mounting
The QAA70 room unit should be mounted in the main living room
The unit should be sited such that its sensor can acquire the room temperature as
accurately as possible. This means that it should not be exposed direct solar radia­tion nor should it be affected by heat or refrigeration sources
Mounting height is about 1.5 m above the floor
The room unit fits on most commercially available recessed conduit boxes or can be
mounted directly on the wall